XUA1 - AC Voltage and phase balance relay

Similar documents
XUA1 AC Voltage and phase balance relay. (August 1996) Manual XUA1 (Revision New)

XU2-AC AC voltage relay. (Februar 1997) Manual XU2-AC (Revision New)

XP2-R Power and reverse power relay. (January 2006) Manual XP2-R (Revision New)

XR1 Rotor Earth Fault Relay. (May 2007) Manual XR1 (Revision New)

XF2 Frequency Relay. Manual XF2 (Revision A)

XI1-I Time overcurrent relay. (Januar 2007) Manual XI1-I (Revision New)

XP2-R Power and Reverse Power Relay

XN2 - Mains decoupling relay

XR1 Rotor Earth Fault Relay. Manual XR1 (Revision C)

XN2 - Mains decoupling relay. Manual XN2 (Revision C)

XD1-T Transformer differential protection relay. Manual XD1-T (Revision A)

IRI1-ER - Stabilized Earth Fault Current Relay. Manual IRI1-ER (Revision A)

CM-MPS.11, CM-MPS-21, CM-MPS.31 and CM-MPS.41 Data sheet. UL 508, CAN/CSA C22.2 No.14 GL GOST CB scheme CCC

ABB NEW. Multifunctional three-phase monitoring relays. CM-MPS.23 and CM-MPS.43 Data sheet. Features J. Approvals. Marks.

ABB 1. Multifunctional three-phase monitoring relays. CM-MPS.11, CM-MPS-21, CM-MPS.31 and CM-MPS.41 Data sheet. Features. Approvals. Marks.

XD1-T - Transformer differential protection relay

IRI1-ER - Stabilized Earth Fault Current Relay

Three-phase monitoring relays

ABB NEW. Three-phase monitoring relays. CM-PVS.31 and CM-PVS.41 Data sheet. Features J. Approvals. Marks. Order data. Order data - Accessories

Measuring and monitoring relays CM-SRS.1 Current monitoring relays, single-phase AC/DC

AC/DC. Monitoring Technique. VARIMETER IMD Insulation monitor RN 5897/300

Multifunctional three-phase monitoring relays CM-MPS CM-MPS.23

ABB 1. Multifunctional three-phase monitoring relays. CM-MPN.52, CM-MPN.62 and CM-MPN.72 Data sheet. Features. Approvals. Marks.

Overcurrent Protection / 7SJ45

Three-phase monitoring relays CM-PVS.81

Voltage monitoring relays CM-ESS.1 for single-phase AC/DC voltages

RISH Ducer TV 808, 2 channels Isolating amplifier unipolar / bipolar

Current monitoring relays CM-SRS.2 for single-phase AC/DC currents

Type CP-S, CP-C & CP-A Switch mode

SIPROTEC easy 7SJ46 Numerical Overcurrent Protection Relay

Electronic timer CT-ERS ON-delayed with 2 c/o contacts Data sheet

High-set undervoltage stage with definitetime. or inverse definite minimum time (IDMT) characteristic. Low-set undervoltage stage with definitetime

Multifunctional three-phase monitoring relays CM-MPS CM-MPS.23 and CM-MPS.43

Electronic timer CT-AWS Impulse-OFF with 1 c/o contact Data sheet

Electronic timer CT-SDS.22 Star-delta change-over with 2 n/o contacts Data sheet

Voltage monitoring relay CM-EFS.2 For single-phase AC/DC voltages

Three-phase monitoring relays CM-PSS CM-PSS.31 and CM-PSS.41

02/11/2015

Three-phase monitoring relays CM-PVS CM-PVS.31, CM-PVS.41 and CM-PVS.81

Installation / Monitoring Technique

02/11/2015

Multifunctional three-phase monitoring relays CM-MPN CM-MPN.52, CM-MPN.62 and CM-MPN.72

MRS1 - Negative sequence relay. Manual MRS1 (Revision A)

Voltage monitoring relays CM-ESS.2 For single-phase AC/DC voltages

High-Tech Range. IRI1-ER- Stablized Earth Fault Current Relay. C&S Protection & Control Ltd.

Current monitoring relays CM-SRS.1 for single-phase AC/DC currents

EMD-FL-3V-400. Electronic monitoring relay for voltage monitoring in three-phase networks. INTERFACE Data sheet _en_03. 1 Description.

DATASHEET - ETR4-70-A. Delivery program. Timing relay, 2W, 0.05s-100h, multi-function, VAC/DC, potentiometer connection

QUINT-PS/ 3AC/24DC/10

QUINT-PS/ 3AC/24DC/40

22/10/2012

Electronic relays. Monitoring. Monitoring

Current monitoring relays CM-SRS.2 For single-phase AC/DC currents

EMD-FL-3V Phase Voltage Monitoring Relay INTERFACE. Data Sheet. Description

QUINT-PS-24DC/24DC/10

Electronic timer CT-SDS.22

Current monitoring relays CM-SRS.1 For single-phase AC/DC currents

DATASHEET - ETR4-51-A. Delivery program. Technical data General. Timing relay, star-delta, 50 ms, 1W, 3-60s, VAC/DC

PHOENIX CONTACT - 06/2008. Features. DANGER OF EXPLOSION! Only remove equipment when it is disconnected and not in the potentially explosive area.

Electronic timer CT-AHS.22 OFF-delayed with 2 c/o (SPDT) contacts

02/11/2015

Three-phase monitoring relay CM-PVE

QUINT-PS/ 1AC/24DC/20

08/07/2015

Three-phase monitoring relay

QUINT-PS AC/24DC/40

Voltage monitoring relays CM-ESS.M For single-phase AC/DC voltages

MINI-PS AC/24DC/1.3

Thermistor motor protection relays

02/11/2015

Installation- / Monitoring technique

Electronic timer CT-SDD.22


SINEAX I 503 / SINEAX U 504 Transducer for AC current or AC voltage

Electronic timer CT-MVS.23 Multifunctional with 2 c/o (SPDT) contacts

Electronic timer CT-EBE Flasher starting with OFF, 1 c/o (SPDT) contact

Three-phase monitoring relay CM-PFS

Electronic timer CT-WBS.22 Impulse generating and flashing with 2 c/o (SPDT) contacts

Three-phase monitoring relays Product group picture

Analog signal converters CC-E I/I

Temperature monitoring relays CM-TCS Monitoring relays for monitoring temperatures with a PT100 sensor (2- or 3-wire connection)

Three-phase monitoring relays CM-PFE and CM-PFE.2

Theta 60R. Technical Data Sheet. Special Features. Fig. 2 Theta R, 2 channel version, in housing S17 hole mounting brackets pulled out.

Three-phase monitoring relays Product group picture

Three-phase monitoring relays Table of contents

AC/DC. Monitoring Technique. VARIMETER IMD Insulation monitor RN 5897/020

Electronic timer CT-TGD.22

08/07/2015

PHOENIX CONTACT - 05/2008. DANGER OF EXPLOSION! Remove an item only when it is not connected to power or if it is located in the non-explosive area.

Current monitoring relays CM-SRS.M1 For single-phase AC/DC currents

Electronic timers CT-S range Selection and ordering details

Electronic timer CT-AHS.22 OFF-delayed with 2 c/o (SPDT) contacts

SINEAX TV 808, 2 channels Isolating Amplifier Unipolar/Bipolar

LINAX 4000L Continuous-line recorder

Fault indicator. Application. SPEF 3A2 C 1MRS MBG Issued: April 1999 Status: Updated Version: B/ Data subject to change without notice

02/11/2015

Protection and safety SQZ3 phase and sequence relay

MINI-PS AC/2X15DC/1

s s s 3-60 s min min 3-60 min h h 3-60 h V AC, 50/60 Hz

Electronic measuring and monitoring relays CM-range

Transcription:

XUA1 - AC Voltage and phase balance relay

Contents 1. Applications and features 2. Design 3. Function 3.1 Voltage supervision 3.2 Unbalanced voltage supervision 4. Operation and settings 4.1 Setting of DIP-switches 4.2 Setting of the tripping values 4.3 Communication via serial interface adapter XRS1 5. Relay case and technical data 5.1 Relay case 5.2 Technical data 1. Applications and features Relay XUA1 of the PROFESSIONAL LINE is a digital relay for voltage and phase balance supervision of 3-phase systems and provides protection for electrical power generators and general equipment against inadmissible undervoltage or overvoltage as well as voltage unbalance e.g. due to blown fuse or conductor break. When compared to conventional protection equipment all relays of the PROFESSIONAL LINE reflect the superiority of digital protection technique with the following features: High measuring accuracy by digital processing Fault indication via LEDs Extremely wide operating ranges of the supply voltage by universal wide range power supply unit Wide setting ranges very accurately graded Data exchange with process management system by serial interface adapter XRS1 which can be retrofitted RMS measurement Extremely short reaction times Adjustment of rated data Negative sequence measuring of voltage unbalance Compact design by SMD-technology In addition to this relay XUA1 has the following special features: Different switching hysteresis adjustable Measurement phase-to-neutral or phase-to-phase voltage possible Tripping times for supervision U</U>/U2s> adjustable 2 TB XUA1 08.96 E

2. Design 3 35-78 Hz; 60-400 V DIP - switch Auxiliary voltage supply The XUA1 can be supplied directly from the measuring quantity itself or by a secured aux. supply. Therefore a DC or AC voltage must be used. Unit XUA1 has an integrated wide range power supply. Voltages in the range from 19-55 V DC can be applied at connection terminals A1(L-) and A2(L+). Terminals A1/A3 are to be used for voltages from 50-750 V DC or from 36-520 V AC. Fig. 2.1: Connection three wire system 3/N 35-78 Hz; 60-400 V DIP - switch Y Contact Positions 14 12 11 24 22 21 U>/U< U2s> Under-/overvoltage in at least one phase or dead condition 14 12 11 24 22 21 Operation without fault U>/U< U2s> 14 12 11 24 22 21 Voltage unbalance tripping Fig. 2.2: Connection four wire system U>/U< U2s> Fig. 2.3: Contact positions of the output relays Analog inputs The analog voltage input signals are connected to the protection relay via terminals L1 - L3 and N. TB XUA1 08.96 E 3

3. Function 3.1 Voltage supervision Unit XUA1 has an independent overvoltage (U>) and undervoltage supervision (U<). The noise signals caused by inductive and capacitive coupling are supressed by an analog RC-filter circuit. The analog voltage signals are fed to the A/Dconverter of the microprocessor and transformed to digital signals through sample-and-hold circuits. The analog signals are sampled with a sampling frequency of 12 x fn, a sampling rate of 1.66 ms (1,39 ms) for every measuring quantity at 50 Hz (60 Hz). 3.2 Unbalanced voltage supervision The XUA1 detects unbalanced voltages in terms of value and phase position. Such unsymmetric conditions can occur due to break of a conductor, blown fuses or unbalanced loading of the three phases system. These conditions always result in displacement of the star point. The negative sequence voltage is measured by the XUA1 and so correct tripping after the adjusted tripping time is ensured. Measuring principle: A rotating three-phase system can be split according to the method of Symmetrical Components into a positive-sequence system, a negative-sequence system and a zero sequence system. The XUA1 calculates the negative-sequence system by rotating the voltage vector U 2 by 240 and the voltage vector U 3 by 120 and following addition of the voltage vectors. 4 TB XUA1 08.96 E

Fig. 3.1: Symmetrical three-phase system A rotating field is produced with opposite direction of rotating field. If the voltages of this negative-sequence system are added, the sum is zero in case of symmetrical voltages and angles. U 1 U' 1 U' 2 240 U' 2 U' 2 U' 3 U' 1 U 3 120 U' 3 U' 3 3xU 2 U Asymmetrical three-phase system Fig. 3.2: Asymmetrical three-phase system 2 Rotation of the voltage vectors for calculation of the negative sequence system Addition of the rotated voltage vectors In fig. 3.2 voltages of an asymmetrical system are shown. The XUA1 calculates the negative-sequence system by rotating and following addition of the voltage vectors. The adjusting pickup value related to the rated voltage Un. At phase loss (and correct phase angle) the asymmetrical voltage amounts to 33 % Un. TB XUA1 08.96 E 5

4. Operation and settings All operating elements needed for setting parameters are located on the front plate of unit XUA1 as well as all display elements. Because of this all adjustments of the unit can be made or changed without disconnecting the unit from the DIN-rail. LEDs LED "ON" is used for display of the readiness for operation (at applied auxiliary voltage Uv). LED U indicates undervoltage by flashing, at overvoltage the LED U is lit permanently. LED U2s> indicates tripping because of voltage unbalance. Test push button This push button is used for test tripping of the unit and when pressed for 5 s a check-up of the hardware takes place. Both output relays are tripped and all tripping LEDs light up. Fig. 4.1: Front plate For adjustment of the unit the transparent cover has to be opened as illistrated. Do not use force! The transparent cover has two inserts for labels. Fig. 4.2: How to open the transparent cover 6 TB XUA1 08.96 E

4.1 Setting of DIP-switches The DIP-switch block on the front plate of unit XUA1 is used for adjustment of the nominal values and setting of function parameters: DIP-switch OFF ON Functions 1* Un = 60 V Un = 110 V Setting of rated voltage 2* Un = 60 V Un = 230 V 3* Un = 60 V Un = 400 V 4 5 Y measurement phase-to-neutral/phase-to-phase voltage 6* 3 % 5 % Switching hysteresis for U</U> 7* 3 % 10 % 8 2 % 5 % Switching hysteresis for U2s Table 4.3: Function of DIP-switches * Only one of the DIP-switches 1-3 or 6-7 shall be in ON position at the same time. Rated voltage The required rated voltage Un (phase-to-phase voltage) can be set with the aid of DIP-switch 1-3 to 60, 110, 230 or 400 V AC. It has to be ensured that only one of the three DIP-switches is switched on. The following DIP-switch configurations are permissible for adjustment of the rated voltage are allowed: Measurement of phase-to-neutral / phase-to-phase voltage The phase-to-neutral (position "OFF") or phase-tophase voltage (position "ON") can be adjusted by means of switching over the DIP-switch 5. (See figure 2.1 and 2.2) Switching hysteresis for U</U> ON 1 2 3 ON 1 2 3 ON The switching hysteresis for U> and U< can be set with the aid of DIP-switches 6-7 to 3, 5 or 10 % of the tripping value. As for the rated voltage, it has to be ensured that only one of the two DIP-switches is switched on. 1 2 3 ON 1 2 3 Fig. 4.3: Adjustment of rated voltage Rated voltage chosen too low, does not cause destruction of the unit but leads to wrong measuring results which may lead to false trippings. Switching hysteresis for U2s The switching hysteresis for U2s (residual voltage) can be set with the aid of DIP-switch 8 to 2 or 5 % of the tripping value. TB XUA1 08.96 E 7

4.2 Setting of the tripping values The PROFESSIONAL LINE units have the unique possibility of high accuracy fine adjustments. For this, two potentiometers are used. The course setting potentiometer can be set in descrete steps of 10 %. A second fine adjustment potentiometer is then used for continuously variable setting of the final 0-10 %. Adding of the two values results in the precise tripping value. 4.3 Communication via serial interface adapter XRS1 Undervoltage trip element The undervoltage trip element can be set in the range from 75-100 % Un with the aid of potentiometer U</Un. Overvoltage trip element The overvoltage trip element can be set in the range from 100-125 % Un with the aid of potentiometer U>/Un. Asymmetry trip element The trip element can be set in the range from 0-60 % Un with the aid of the potentiometer illustrated in the following drawing. Example: A tripping value U2s> for 36 % Un is to be set. The set value of the right potentiometer is just added to the value of the coarse setting potentiometer. (The arrow of the coarse setting potentiometer must be inside the marked bar, otherwise no defined setting value). Fig. 4.5: Communication principle For communication of the units with a superior management system, the interface adapter XRS1 is available for data transmission, including operating software for our relays. This adapter can easily be retrofitted at the side of the relay. Screw terminals simplify its installation. Optical transmission of this adapter makes galvanic isolation of the relay possible. Aided by the software, actual measured values can be processed, relay parameters set and protection functions programmed at the output relays. Information about unit XRS1 in detail can be taken from the description of this unit. Fig. 4.4: Adjustment example Time delay The time delay tu and tu2s> can be adjusted continuously variable in the range from 0-10 s. 8 TB XUA1 08.96 E

5. Relay case and technical data 5.1 Relay case Relay XUA1 is designed to be fastened onto a DIN-rail acc. to DIN EN 50022, the same as all units of the PROFESSIONAL LINE. The front plate of the relay is protected with a sealable transparent cover (IP40). 110 75 65 Fig. 5.1: Dimensional drawing Connection terminals The connection of up to a maximum of 2 x 2.5 mm 2 cross-section conductors is possible. For this the transparent cover of the unit has to be removed (see para. 4). TB XUA1 08.96 E 9

5.2 Technical data Measuring input circuits Rated voltage Un: Rated frequency range: Power consumption in voltage circuit: Thermal capacity of the voltage circuit: 60, 110, 230, 400 V AC 35-78 Hz 1 VA/per phase at Un continuously 520 V AC Auxiliary voltage Rated auxiliary voltage Uv/ 36-520 V AC (f = 35-78 Hz) or 50-750 V DC / 4 W (terminals A1-A3) Power consumption: 19-55 V DC / 3 W (terminals A1(L-) - A2(L+)) Common data Dropout to pickup ratio: Resetting time from pickup: Returning time from trip: Minimum initialization time after supply voltage has applied: Minimum response time when supply voltage is available: depending on the adjusted hysteresis <70 ms 190-280 ms U</U> approx. 130 ms; U 2S approx. 290 ms U</U> 60-110 ms; U 2S 70-130 ms Output relay Number of relays: 2 Contacts: 1 changeover contact for each trip relay Maximum breaking capacity: ohmic 1250 VA/AC resp. 120 W/DC inductive 500 VA/AC resp. 75 W/DC Max. rated voltage: 250 V AC 220 V DC ohmic load Imax. = 0,2 A inductive load Imax. = 0,1 A at L/R 50 ms 24 V DC inductive load Imax. = 5 A Minimum load: 1 W / 1 VA at Umin 10 V Maximum rated current: 5 A Making current (16 ms): 20 A Contact life span: 10 5 operations at max. breaking capacity System data Design standard: VDE 0435 T303; IEC 0801 part 1-4, VDE 0160; IEC 255-4; BS 142; VDE 0871 Temperature range at storage and operation: - 25 C to + 70 C 10 TB XUA1 08.96 E

Constant climate class F acc. to DIN 40040 and DIN IEC 68, part 2-3: High voltage test acc. to VDE 0435, part 303 Voltage test: Surge voltage test: High frequency test: Electrostatic discharge (ESD) acc. to IEC 0801, part 2: Radiated electromagnetic field test acc. to IEC 0801, part 3: Electrical fast transient (burst) acc. to IEC 0801, part 4: Radio interference suppression test acc. to DIN 57871 and VDE 0871: more than 56 days at 40 C and 95 % relative humidity 2.5 kv (eff) /50 Hz; 1 min 5 kv; 1.2/50 µs, 0.5 J 2.5 kv / 1 MHz 8 kv 10 V/m 4 kv/2.5 khz, 15 ms limit value class A Repeat accuracy: 1 % Basic time delay accuracy: 0.5 % or ±25 ms Accuracy of the specific rated values: Un = 60 V U2s: 2 % U: 1.5 % U phase-to-neutral 2 % U phase-to-phase Un = 110 V / 230 V / 400 V 1 % Temperature effect: Frequency effect: 0.02 % per K 45-66 Hz no tolerance 35-45 Hz and 66-78 Hz 1 % Mechanical test Shock: class 1 acc. to DIN IEC 255-21-2 Vibration: class 1 acc. to DIN IEC 255-21-1 Degree of protection: Front plate: Weight: Mounting position: Relay case material: IP40 at closed front cover approx. 0.5 kg any self-extinguishing Parameter Setting range Graduation U< 75-100 % Un continuously variable U> 100-125 % Un continuously variable U2s> 0-60 % Un continuously variable tu/t U 0-10 s continuously variable Hysteresis U</U> 3, 5, 10 % Hysteresis U2s 2, 5 % Table 5.1: Setting ranges and graduation Technical data subject to change without notice! TB XUA1 08.96 E 11

Setting-list XUA1 Project: SEG job.-no.: Function group: = Location: + Relay code: - Relay functions: Date: Setting of parameters Function Unit Default settings Actual settings U< Undervoltage % Un 75 U> Overvoltage % Un 100 U2s> Voltage asymmetry % Un 0 tu Time delay for U< and U> s 0 tu2s> Time delay for tu2s> s 0 DIP-switch Function Default settings Actual settings 1* 60 V 2* Adjustment of rated voltage 60 V 3* 60 V 4 5 Measuring phase-to-neutral / phase-to-phase voltage Y 6* Hysteresis for U< and U> 3 % 7* Hysteresis for U< and U> 3 % 8 Hysteresis for U2s 2 % *Only one of the DIP-switches 1-3 or 6-7 shall be in ON -position at the same time. 12 TB XUA1 08.96 E

Woodward SEG GmbH & Co. KG Krefelder Weg 47 D 47906 Kempen (Germany) Postfach 10 07 55 (P.O.Box) D 47884 Kempen (Germany) Phone: +49 (0) 21 52 145 1 Internet Homepage http://www.woodward-seg.com Documentation http://doc.seg-pp.com Sales Phone: +49 (0) 21 52 145 635 Telefax: +49 (0) 21 52 145 354 e-mail: kemp.electronics@woodward.com Service Phone: +49 (0) 21 52 145 614 Telefax: +49 (0) 21 52 145 455 e-mail: kemp.pd@woodward.com