Electronic fan speed regulators

Similar documents
RELIABLE SOLUTIONS in POWER ELECTRONICS VRST SERIES. Power Management Instruments ELECTRONIC STABILIZER FROM PMI & OES GROUP COMPANIES SUD

INSTRUCTION MANUAL. Power Factor Controller - 12 steps Model A12 NOKIAN CAPACITORS. Power Factor Controller A12

TIG 250 AC-DC. POWER SOURCE art

Electronically Commutated (EC) Motor Control with Solo, Select and Sync PWM Boards

Fan Coil Actuator FCA 2

Compliance with CE Marking, UL Standard and CSA Standard

Gutor PxW AC UPS Designed for North American Market

Sine Wave Power Inverter GD150/GD300 Series User s Manual

Installation and Operational Instructions for ROBA -switch Type 017._00.2

U S E R S M A N U A L

These true on-line inverters incorporate pulse width modulation (PWM) control combined with high frequency igbt power transistors.

Drives 101 Lesson 3. Parts of a Variable Frequency Drive (VFD)

VFSC9 ELECTRONIC SPEED CONTROLLER. Mounting and operating instructions

Operation Manual. Congratulations on purchasing your high quality AIMS Power pure sine inverter!

Operating Instructions

Process/Mini. English IMPORTANT NOTE. Installation and Operation Manual. General Purpose Light Curtain with 30 mm resolution

MINI MCR-SL-UI-f(-SP)

MTV-1-CP 230 VAC POTENTIOMETER WITH MIN & MAX SETTINGS, DRY CONTACT. Mounting and operating instructions

AEROCONNECT 1B NA C Control manual

CP-T range Product group picture

TS-700/1000 INVERTER Instruction Manual

Installation and Operational Instructions for ROBA -multiswitch Type 019._00.2

Siemens AG Allows easy and consistent configuration with one series of overload relays (for small to large loads)

Installation and Operating Instructions. Power IT Power Factor Controller RVC

Quick Reference Guide. DF5-... Frequency Inverters 02/02 AWB GB

IN ELECTRICAL ENGINEERING - I C M E T CRAIOVA

S11 Adjustable Speed Drive Engineering Specification

RMO500 M I C R O O H M M E T E R

Power Regenerative Converter, THYFREC CV240S

CONTROL MANUAL. Dry-Pic 09PE - 09VE

Ambient Conditions Storage Conditions Installation Minimum Clearances and Air Flow...2 3

MST-5. Varifan USER S MANUAL MST-5 5 STAGE THERMOSTAT. computer compatible ADJUST. 9 reduc. per day 8 7 F rel. rel. rel. rel.

! "! # $ % & ' ( ) " * % +, # # -. / ( ! " ! # $ % &

Orbital GFI Inverter Series

SUGGESTED SPECIFICATION for Series 300 Automatic Transfer Switches

IRT AT-Small. Technical Manual. quality IN MOTION. quality IN MOTION

CONTENTS XV300K GB r doc XV300K 2/13

theben Fan Coil Actuator FCA 1 Fan Coil Actuator FCA 1 FCA Version: Jan-08 (Subject to change) Page 1 of 77

ERV-M ELECTRONIC FAN SPEED CONTROLLER. Mounting and operating instructions

ELECTRONIC THERMOSTAT: T920

TOSHIBA International Corp

Installation and Operational Instructions for ROBA -switch Type 017._00.2

Type CP-S, CP-C & CP-A Switch mode

Quick Reference Guide. DF5-... Frequency Inverters 02/02 AWB GB. For Immediate Delivery call KMParts.com at (866)

Sensitivity range ( ) kω adjustable Delay time (0.5s or 7s) switch selectable Emptying or filling functions switch selectable

Temperature monitoring relays CM-TCS Monitoring relays for monitoring temperatures with a PT100 sensor (2- or 3-wire connection)

CP-T range Benefits and advantages

Power Quality Solutions

Control panel touch screen MOD. 80

Three-Phase Transformer Demagnetizer DEM60

Power supply CP-T 24/40.0 Primary switch mode power supply

Power supply CP-T 24/10.0 Primary switch mode power supply

EC centrifugal fan. backward curved, single inlet

Thyristorised Automatic Power Factor

6.9 Jump frequency - Avoiding frequency resonance

Digital flow transmitter for continuous flow measurement

Voltage Transient Emission Test

SPAC265-8W. AC-DC power supply module. Features. Description. Applications

QUICK GUIDE PUMP CONTROL. Frequency inverter for pump control and HVAC applications. Date Version 24/10/

1 SAFETY INSTALLATION OPERATION COMPONENTS FAULT DIAGNOSTICS FUNCTIONS TECHNICAL SPECIFICATIONS...

CROSS Chassis from 160 A to 450 A

DSA150 Series. xxx Series. 150 Watts. AC-DC Power Supplies. Models & Ratings. Mechanical Details 3.92 (99.8) 2.18 (55.5) 4.92 (125.

Technical Information

D SERIES EM16 IP 20 / NEMA 1 & IP 66 / NEMA 4X COMPACT VECTOR CONTROL DRIVE EM 16 COMPACT VECTOR CONTROL DRIVE

AHC-XP. Dewpoint-guided Power Controller for Glass and Handrail Heaters. Front view. Characteristics

QUINT-PS/ 1AC/24DC/20

Installation, Operation and Maintenance Instructions

PURE SINE WAVE INVERTERS WITH INTEGRATED BATTERY CHARGER FOR VEHICLES ECE R10-05 PURE SINE WAVE HIGH FREQUENCY INVERTERS FOR VEHICLES ECE R10-05

PURE SINE WAVE INVERTERS WITH INTEGRATED BATTERY CHARGER FOR VEHICLES ECE R10-05 PURE SINE WAVE HIGH FREQUENCY INVERTERS FOR VEHICLES

USE OF INVERTERS WITH COPELAND STREAM COMPRESSORS

EC centrifugal fan - RadiCal

QUICK GUIDE PUMP CONTROL. Frequency inverter for pump control and HVAC applications. Date Version 22/09/

High Frequency Sinewave Guardian TM Filter

P. O. BOX 269 HIGHLAND, ILLINOIS, U.S.A PHONE FAX

VF-nC1 Adjustable Speed Drive Engineering Specification

Sensitivity range ( ) kω adjustable Delay time (0.5s or 7s) switch selectable Emptying or filling functions switch selectable

Power supply CP-E 24/20.0

Commissioning and Maintenance of Power Factor Correction Systems

IRT Mini Evo. Technical Manual. quality IN MOTION. quality IN MOTION

Analogue temperature controllers

SR32 line regen Converters

Contents. English User Manual Regulators

QUINT-PS/ 3AC/24DC/10

Liquid level monitoring relay CM-ENS.2x

Power supply CP-T 24/20.0 Primary switch mode power supply

Brief description of KR 15 controllers

USER S MANUAL. Rail-mounted temperature transmitter ATL

StacoDVR-5 60kVA to 6000kVA

SPEED CONTROL OPTIONS

RADIOBAND 3G RB3 T868 RB3 R868 USER'S MANUAL

Nivotester FTR325. Technical Information. 1-channel switch amplifier for the microwave barrier Soliwave FDR50/FQR50

Power supply CP-T 48/5.0 Primary switch mode power supply

INSTALLATION INSTRUCTIONS FOR SYMCOM S MODEL 77C-LR-KW/HP ELECTRONIC OVERLOAD RELAY

Variable Frequency Drive Packages with Harmonic Mitigation. Low Harmonic Drive Packages Engineered by Rockwell Automation

8V General information. 2 Order data 8V

GESTRA Steam Systems LRS English. Installation & Operating Instructions Conductivity Switch LRS 1-50

Level Limit Switch nivotester FTL 325 P

Guidelines to Using a Three Phase Voltage Monitor

Installation and Operating Instructions for Phase Demodulator Type _.2

SECTION 16483D ADJUSTABLE FREQUENCY DRIVE - MICRODRIVE (MVX <10-HP)

Transcription:

Electronic fan speed regulators Purpose The fan speed controller maintains the condensing pressure for fan-type condensers or fluid outlet temperatures for dry coolers, within prefixed values, for any given load on the unit, reducing power consumption and noise levels of the fan motors. The fan speed controller automatically varies the fan motor speed by changing the input voltage to the motors controlled by discharge pressure which is sensed by a pressure sensor (for air cooled condensers) or by fluid outlet temperature which is sensed by a temperature sensor (for dry coolers). For condensers and dry coolers the fan regulation is a crucial issue. In fact those products are designed for max. conditions (max. thermal load and max. ambient temperature). Practically only for a very limited period of the year the max. ambient temperature is present and the max. load is required. Therefore it is possible to conclude that for the large part of the working time, the products are oversized. In order to reduce the oversized capacity the normal procedure is to limit the ventilation. There are several possible methods. Different regulating systems 1) STEP CONTROL ON-OFF controller. It is the most traditional one. The system is based on a simple pressure switch or thermostat that according to the effective capacity request is turning ON and OFF a certain number of fans. ADVANTAGES: The system is simple and cheap. On board installation already wired and tested. DISADVANTAGES: they are related to the low energy and noise reduction. In case of 40% of air quantity, 40% of the fans will run. That involve 60% of energy reduction and about only 3,5 db(a) noise reduction. The limited noise reduction can not be accepted in several conditions, specially wherever there is a prescription of very low noise during night operating, while during the day much higher noise is allowed. 2) ELECTRONIC COMMUTATION FANS EC FANS: the single fan is provided with an integrated regulation system which allows to modulate the rotation speed depending on the needs. The sound level under regulation is extremely quiet and no magnetic noise occurs. The fan can be controlled by a signal 0-10 VDC or by bus (RS 485). The fan is self pro ADVANTAGES: it is a very high efficiency and flexible regulation. 3) VARIABLE FAN SPEED Cut phase speed controller. In the last year it became the most popular fan speed controller of the market. It is a quality speed controller that is modulating the speed of all the fans together, by reducing the input fan voltage. ADVANTAGES: it has a high ratio between price and quality; this device allows a high energy saving and noise reduction. On board installation already wired and tested. In case of limited speed with about 40% of air quantity, all fans will be working at lower speed with: 6 poles 8 poles 8ps poles 12 poles Energy saving 75% 62% 72% 79% Noise reduction db(a) -11-12 -13-4 DISADVANTAGES: By reducing the fan speed, magnetic noise may occur. This effect can be in some condition very delicate. Noise picks instead can be avoided by the new LU-VE URT speed controller. In fact generally the noise level reduction in terms of db(a) is assured. Inverter speed controller. The system is quite sophisticate; it regulates all the fans together by changing the frequency.

ADVANTAGES: this device allows high energy saving and noise reduction (in term of energy saving we can have values align to other best performances, while noise reduction will suffer to reach the best possible efficiency). It is possible to eliminate some frequency particularly noisy, reducing almost to zero magnetic noise and noise picks. DISADVANTAGES: It is an expensive regulation. The eliminating of noisy frequency has normally to be done on job site by expert technicians. Normally screened cables are necessary and IP 55 versions are generally available for lower capacity compare other systems. Shorter fan life may occur due to microwave. High power units are generally IP 20 and it is always necessary to install them in an internal ventilated switch board. Therefore it is not possible to deliver big condensers or big dry coolers completely wired, but an important wiring has to be done on job site with screened cables. Transformer speed controller: it regulates all the fans together by changing the input voltage ADVANTAGES: it is a very high efficiency regulation that does not generate magnetic noise and noise picks and furthermore no electric disturb, therefore normal cables are enough. This device allows a high energy saving and noise reduction. On board installation already wired and tested. In case of limited speed with about 40% of air quantity, all fans will be working at lower speed with: This regulation is fully compliant with the new standard EN 61000-3-12: Electromagnetic compatibility (EMC). Limits for harmonic currents produced by equipment connected to public low-voltage system with input current > 16A and < 75A per phase. 6 poles 8 poles 8ps poles 12 poles Energy saving 80% 72% 76% 83% Noise reduction db(a) -23-20 -23-25 LU-VE Recommendations LU-VE can offer all the above mentioned solution; it is crucial to choose them properly, according to the effective request; we strongly invite to verify also the real installation condition of the condensers and dry coolers that are going to be selected. A speed controller guideline can be as follows: ON-OFF: select when low price solution is mandatory and the noise reduction during the night is not an important issue. The product is named QEP (for condensers) or QET (for dry coolers); the are special switch boards complete with pressure switch or thermostat. Cut Phase: it is the general solution. Of course the customer and the installer must be aware of the possible magnetic noise disturbs (not picks). In particular for low noise condensers and dry coolers (like 12 poles) we suggest to use this speed controller very carefully. The adding of noise filters (in order to reduce magnetic noise) is definitely not a good solution, because the real benefit is very limited. The products are named URT (for condenser, dry coolers and 0-10VdC signal input). Transformer: it is the real solution to be applied when low noise regulation and energy saving is required. In particular we suggest its use with 12 pole fans. The product is named RUS Electronic commutation fans: it is possible to select easily using the Refriger software. The product is named EC Fan

Ex: Energy consumption comparison per air quantity, among different types of regulation

What is a regulation system made of Basically, a regulation system is made up of three components: 1. Regulator: RUS, URT, FSC, SCU. 2. Sensor: SPR, STE 3. Switch Board: QE Accessories: SPR: pressure sensor, SPR 15: pressure sensor for refrigerant fluid R134a (0 15 bar) SPR 25: pressure sensor for refrigerant fluid R22, R404A, R407C, R507 (0 25 bar) STE: temperature sensor STE: temperature sensor (-10 +90 C) QE: switch-board

Features of LU-VE variable speed controllers FSC-SCU Single-phase fan speed controllers based on cut phase principle suitable for low and medium capacity units. URT Electronic fan speed controllers based on the cut phase principle suitable for effective and precise control o medium and high capacity units. They can be coupled with the QE control panel. URT is a series of electronic 3 phase voltage variators using the phase cut principle. A microcontroller carries out all the necessary regulating and control functions according to the multiple possible configuration modes (rte, rpr, rs) for every cut. The selected mode is programmed using a keypad and a 5 digit display which also permit reading the settings and the scale measured. RUS Electronic fan speed controllers using technology based on voltage steps for a regulation completely free from noise, electric and electromagnetic interference. They find their best application where a very precise noise control is needed in particular for high capacity units and can be coupled with the QE control panel. RUS is a steps speed controller, modulating the output voltage with autotransformers; the passage between the steps is realized by a set of electromechanical solid state power relays; each one is assisted by one solid state relay which open the load side circuit with zero cross mode i.e. when the voltage is zero and when the current is zero: in this way the relays change-over always happens in no load conditions and there is no sparking between the contacts, no overheating of the contacts, no generation of electromagnetic noise and on top of that the line current distortion, the motor noise level and the motor overheating are minimized. RUS is absolutely maintenance free. An electronic controller realizes all the control functions necessary to run the device and the following configuration modes can be selected by the keypad with display: Mode RTE: for dry coolers - RUS is modulating fan speed according to the selected Set point Mode RPR: for condensers - RUS is modulating fan speed according to the selected Set point Mode RS: RUS is modulating fan speed according to an external signal (0-10 VdC or 0-20 ma) Electricity supply: 400 VAC +/- 10% Three phases (230 VAC on request) 50 Hz (60 Hz on request)

Modifying the working configuration (common to RUS & URT) Access to this mode only when switching on: power supply from OFF to ON PROCEDURE 1 - Press the ENTER and - keys at the same time and connect the power supply to the regulator (from OFF to ON). Release the ENTER and - keys at the same time: the regulator switches on and the current configuration appears on the display. 2 - The CODE of the available configurations can be scrolled through the display using the + e - keys. 3 - Press the ENTER key when the default configuration required is found. 4 - The display begins to flash. 5 - To confirm the selection, press the ENTER + ESCAPE keys at the same time 6 - Update appears on the display and the preselected configuration is saved and immediately put into operation. 7 At this point the display shows the SP value. To exit without changing the current configuration, press ESCAPE : the word ESCAPE appears on the display.

Modifying Set Points (S1 S2) and night limit (Lh) 1 - Press the ENTER + ESCAPE keys at the same time 2 - ProGrA appears on the display, followed by S1 (for rte rpr) or Lh (in case of URT regulation rs) 3 - Select the parameter to be modified using the + key 4 - Then press the ENTER key 5 - The display begins to flash. 6 - Use the (+) and ( ) keys to reach the required value (the process is speeded up by pressing ENTER at the same time) 7 - Press the ENTER key : the display stops flashing To modify another parameter, begin again at point 2 above 8 - To confirm the selection, press the ENTER + ESCAPE keys at the same time: Update appears on the display and the preselected configuration is saved and immediately put into operation. To exit without changing the current configuration, press ESCAPE : the word ESCAPE appears on the display. Configuration of Jh & Jl (1-2-3) to eliminate sound peaks Option available only on URT controllers to avoid high level sound peaks. 1 - Press the ENTER + ESCAPE keys at the same time: ProGrA appears on the display, followed by S1 (for rte rpr) Lh (for rs) 2 - Select the Jh1 code with the + key 3 - Press ENTER: the display begins to flash and the regulator interrupts the settings and supplies the fan(s) to the value of the set voltage (default Jh1 = 100).

4 - Press the +/- keys to scroll through the regulation field and identify the high-level sound peak, selecting a position slightly above it. 5 - Press ENTER to confirm : the display stops flashing. 6 - Select the JL1 code using the + key. 7 - Press ENTER : the display begins to flash. 8 - Pressing -, select the value of the setting for Jh1: move down and identify the peak of the sound level. Select a position slightly under it. 9 - Press ENTER to confirm : the display stops flashing. For any other zones of high-level sound, proceed in the same manner using Jh/JL 2 e Jh/JL3 10 - To confirm the choice, press the ENTER and ESCAPE keys at the same time: Update appears on the display. To exit without changing the current configuration, pres the ESCAPE key: ESCAPE appears on the display. The regulator goes back to ACTIVE operation and the display shows the value of the input signal (in).

Troubleshooting PROBLEMS CAUSE CHECKS REQUIRED Ventilator won t run when power feeding the regulator. Loss of one or more phases in the RST supply (Red AC LINE ALARM ON). Check supply connections, blown fuses in the control box on the connection linking control box and regulator. Voltage available at RST and UVW posts in the regulator. Ventilators won t run. Disconnected ventilators. Check the wiring between UVW posts and motors. Contactors in the control box don t close. Overheating TK protection open. Voltage available at RST posts but not at UVW posts. Loss of control signal. Check the SPR pressure transducer, check the supply voltage, current flow or the DC voltage across the sensor. Check the STE temperature sensor with resistance readings. Setting of S2 remote control. S2 shall be open (OFF). Fuses blow. Interferences on the RST supply voltage or to the ventilators. Possible short circuits or large voltage variations. In case of unstable power lines use surge filters. Fuses improperly rated. Refer to the power drawn according the former table (installation instructions). Speed regulation worked properly but now ventilators supply is continuously at its max setting. Failure in the control signal. Check the sensor response. RUS 30: note: for a correct operation a minimum load of 0,5 A at 65 V is necessary.

Appendix A Codes Appendix B Visualization and messages Service digit It is a seven segments digit When no alarm, shows the step in use 0 to 8 (RUS) or the percentage voltage supply (URT); When there is an alarm, shows the alarm condition. Alarm conditions RL1 ON = ALARM relay is functioning

Notified alarms P One supply phase off or insufficient voltage t External thermal fan protection tripped u Prevailing input signal exceeding the low limit (under range), or transducer/signal not connected o Prevailing input signal exceeding upper limit (over range) or transducer/signal in short circuit F * Load side fuse blown A * Autotransformers overtemperature or high ambient temperature S * Missed opening of the Solid State Switch (Break of one or more phases during the commutation between two steps or fan not connected - min. load 0,5A - 65V) C * Missed activation of a step (Lack of one or more phases during the first step insert or fan not connected - min. load 0,5A - 65V) H * Missed opening of the relay during the changeover * only for RUS regulation