Fault Detection Using Hilbert Huang Transform

Similar documents
INTERNATIONAL JOURNAL OF PURE AND APPLIED RESEARCH IN ENGINEERING AND TECHNOLOGY

Detection of Power System Faults in the Presence of Linear Loads Using Stockwell Transform

Discrete Wavelet Transform and Support Vector Machines Algorithm for Classification of Fault Types on Transmission Line

[Nayak, 3(2): February, 2014] ISSN: Impact Factor: 1.852

TRANSIENT STABILITY ENHANCEMENT OF POWER SYSTEM USING INTELLIGENT TECHNIQUE

Fault Detection in Double Circuit Transmission Lines Using ANN

Application of Wavelet Transform in Power System Analysis and Protection

DETECTION AND CLASSIFICATION OF POWER QUALITY DISTURBANCES

Research Article International Journal of Emerging Research in Management &Technology ISSN: (Volume-6, Issue-6)

Wavelet Based Fault Detection, Classification in Transmission System with TCSC Controllers

Ultra Hight Voltge Transmission line Faults Identified and Analysis by using MATLAB Simulink

Distribution System Faults Classification And Location Based On Wavelet Transform

Fault Detection and Classification Using Discrete Wavelet Transform

Application of Hilbert-Huang Transform in the Field of Power Quality Events Analysis Manish Kumar Saini 1 and Komal Dhamija 2 1,2

A DWT Approach for Detection and Classification of Transmission Line Faults

Detection and Classification of One Conductor Open Faults in Parallel Transmission Line using Artificial Neural Network

Characterization of Voltage Sag due to Faults and Induction Motor Starting

Experimental Investigation of Power Quality Disturbances Associated with Grid Integrated Wind Energy System

SERIES (OPEN CONDUCTOR) FAULT DISTANCE LOCATION IN THREE PHASE TRANSMISSION LINE USING ARTIFICIAL NEURAL NETWORK

Characterization of Voltage Dips due to Faults and Induction Motor Starting

Keywords: Wavelet packet transform (WPT), Differential Protection, Inrush current, CT saturation.

Roberto Togneri (Signal Processing and Recognition Lab)

Power Quality Disturbaces Clasification And Automatic Detection Using Wavelet And ANN Techniques

A COMPARATIVE STUDY: FAULT DETECTION METHOD ON OVERHEAD TRANSMISSION LINE

An Enhanced Symmetrical Fault Detection during Power Swing/Angular Instability using Park s Transformation

A Novel Scheme of Transmission Line Faults Analysis and Detection by Using MATLAB Simulation

Improved first zone reach setting of artificial neural network-based directional relay for protection of double circuit transmission lines

Detection and Classification of Power Quality Event using Discrete Wavelet Transform and Support Vector Machine

Chapter -3 ANALYSIS OF HVDC SYSTEM MODEL. Basically the HVDC transmission consists in the basic case of two

Voltage Sag Source Location Using Artificial Neural Network

Fault Location Technique for UHV Lines Using Wavelet Transform

Detection of Power Quality Disturbances using Wavelet Transform

IDENTIFYING TYPES OF SIMULTANEOUS FAULT IN TRANSMISSION LINE USING DISCRETE WAVELET TRANSFORM AND FUZZY LOGIC ALGORITHM

SIGNAL PROCESSING OF POWER QUALITY DISTURBANCES

A Review on Protection Techniques used in HVDC Transmission Line

CLASSIFICATION OF POWER QUALITY DISTURBANCES USING WAVELET TRANSFORM AND S-TRANSFORM BASED ARTIFICIAL NEURAL NETWORK

CHAPTER 1 INTRODUCTION

An Ellipse Technique Based Relay For Extra High Voltage Transmission Lines Protection

Voltage sag assessment and Area of vulnerability due to balanced fault for 11 bus system

Fault Classification with Artificial Neural Networks based on the Application of Teager Energy Operator

Real-time Visualization, Monitoring and Controlling of Electrical Distribution System using MATLAB

Identification of Faults in HVDC System using Wavelet Analysis

Simulation Analysis of Three Phase & Line to Ground Fault of Induction Motor Using FFT

Classification of Voltage Sag Using Multi-resolution Analysis and Support Vector Machine

DIAGNOSIS OF ROLLING ELEMENT BEARING FAULT IN BEARING-GEARBOX UNION SYSTEM USING WAVELET PACKET CORRELATION ANALYSIS

DETECTION AND CLASSIFICATION OF POWER QUALITY DISTURBANCE WAVEFORM USING MRA BASED MODIFIED WAVELET TRANSFROM AND NEURAL NETWORKS

MITIGATION OF POWER QUALITY DISTURBANCES USING DISCRETE WAVELET TRANSFORMS AND ACTIVE POWER FILTERS

Assessment of Power Quality Events by Empirical Mode Decomposition based Neural Network

Wavelet Transform Based Islanding Characterization Method for Distributed Generation

Artificial Neural Network Based Fault Locator for Single Line to Ground Fault in Double Circuit Transmission Line

Comparison of Wavelet Transform and Fourier Transform based methods of Phasor Estimation for Numerical Relaying

ISSN: [Taywade* et al., 5(12): December, 2016] Impact Factor: 4.116

A Transient Current Based Wavelet-Fuzzy Approach for the Protection of Six-Terminal Transmission System

ADVANCED VECTOR SHIFT ALGORITHM FOR ISLANDING DETECTION

DIAGNOSIS OF GEARBOX FAULT USING ACOUSTIC SIGNAL

Research Article Analysis of Unsymmetrical Voltage Sag Propagation Trough Distribution Transformer

Review on Identification of Faults of Transmission and Distribution Lines

Power Quality Monitoring of a Power System using Wavelet Transform

A Novel Fuzzy Neural Network Based Distance Relaying Scheme

Adaptive Approach for Fault classification of Parallel Transmission Line

Detection and classification of faults on 220 KV transmission line using wavelet transform and neural network

AN ANN BASED FAULT DETECTION ON ALTERNATOR

A Single Monitor Method for Voltage Sag Source Location using Hilbert Huang Transform

AC : APPLICATIONS OF WAVELETS IN INDUCTION MACHINE FAULT DETECTION

HIGH IMPEDANCE FAULT DETECTION AND CLASSIFICATION OF A DISTRIBUTION SYSTEM G.Narasimharao

Keywords: Transformer, differential protection, fuzzy rules, inrush current. 1. Conventional Protection Scheme For Power Transformer

Inter-Turn Fault Detection in Power transformer Using Wavelets K. Ramesh 1, M.Sushama 2

Empirical Mode Decomposition: Theory & Applications

Online Diagnosis and Monitoring for Power Distribution System

ICA & Wavelet as a Method for Speech Signal Denoising

International Journal of Digital Application & Contemporary research Website: (Volume 2, Issue 6, January 2014)

Decriminition between Magnetising Inrush from Interturn Fault Current in Transformer: Hilbert Transform Approach

A NOVEL CLARKE WAVELET TRANSFORM METHOD TO CLASSIFY POWER SYSTEM DISTURBANCES

RESEARCH ON CLASSIFICATION OF VOLTAGE SAG SOURCES BASED ON RECORDED EVENTS

SVC Compensated Multi Terminal Transmission System Digital Protection Scheme using Wavelet Transform Approach

MATLAB/GUI Simulation Tool for Power System Fault Analysis with Neural Network Fault Classifier

Fault Localization using Wavelet Transforms in 132kV Transmission Lines

ANFIS Approach for Locating Faults in Underground Cables

New Windowing Technique Detection of Sags and Swells Based on Continuous S-Transform (CST)

Spectral analysis of voltages and currents during different modes of ferroresonance in switchgear

International Journal of Digital Application & Contemporary research Website: (Volume 2, Issue 10, May 2014)

KONKANI SPEECH RECOGNITION USING HILBERT-HUANG TRANSFORM

Wavelet Transform for Classification of Voltage Sag Causes using Probabilistic Neural Network

Selection of Mother Wavelet for Processing of Power Quality Disturbance Signals using Energy for Wavelet Packet Decomposition

DESIGN AND DEVELOPMENT OF SMES BASED DVR MODEL IN SIMULINK

Study and Simulation of Phasor Measurement Unit for Wide Area Measurement System

Detection of Fault in Fixed Series Compensated Transmission Line during Power Swing Using Wavelet Transform

PV Module fault detection & diagnosis

Classification of Signals with Voltage Disturbance by Means of Wavelet Transform and Intelligent Computational Techniques.

Protective Relaying of Power Systems Using Mathematical Morphology

ASSESSMENT OF POWER QUALITY EVENTS BY HILBERT TRANSFORM BASED NEURAL NETWORK. Shyama Sundar Padhi

Detection and Identification of PQ Disturbances Using S-Transform and Artificial Intelligent Technique

Accurate Hybrid Method for Rapid Fault Detection, Classification and Location in Transmission Lines using Wavelet Transform and ANNs

A Comparative Study of Wavelet Transform Technique & FFT in the Estimation of Power System Harmonics and Interharmonics

Increasing Dynamic Stability of the Network Using Unified Power Flow Controller (UPFC)

Artificial Neural Network based Fault Classifier and Distance

DISTRIBUTION LINE FAULT DETECTION AND INTIMATION USING GSM

FAULT DETECTION AND DIAGNOSIS OF HIGH SPEED SWITCHING DEVICES IN POWER INVERTER

International Journal for Research in Applied Science & Engineering Technology (IJRASET) Distance Protection Scheme for Transmission Lines

J. Electrical Systems 15-1 (2019): Regular Paper

Transcription:

International Journal of Research in Advent Technology, Vol.6, No.9, September 2018 E-ISSN: 2321-9637 Available online at www.ijrat.org Fault Detection Using Hilbert Huang Transform Balvinder Singh 1, Tanuj Manglani 2 1 M.Tech Scholar, 2 Professor, Department of Electrical Engineering Yagyavalkya Institute of Technology, Jaipur, India ballurajput124@gmail.com Abstract This paper accords a method based on the Hilbert Huang Transform (HHT) for detection of symmetrical faults on the transmission line. A test system comprising of a transmission line connected at both ends to AC sources is used for the proposed study. Current is recorded at both ends of the transmission line. Current is decomposed using the Hilbert Huang Transform. A fault index is proposed to diagnose the symmetrical fault involving all the 3 phases and ground. The threshold value of the proposed fault index is used for detection of the fault. It is established that the proposed effectively detects symmetrical fault involving the ground. Keywords Hilbert Huang Transform; power system fault; Transmission line. 1. INTRODUCTION The complicated nature of present power system network increases the significance of fault location methods which are considered one of the most interesting research projects in the recent years. The transmission line relaying is an extremely important device in safety operations of the power system. It must be done as fast and accurate as possible to turn off the faulted line in order to protect the system against the harmful fault effects. Conventional techniques such as fault impedance measurements in such difficult conditions represent a problem primarily due to big fault resistance. Measuring instruments and devices for fault location estimation are usually located in a main grid substation. Cost reduction of the fault location can be obtained with current and voltage measurements in combination with computer simulations and calculations and precise planning of the network. In this regard, signal processing techniques may play an important role for the detection of the faults using a threshold value which is used to actuate a relay to generate a command signal for outage of faulty section. The artificial intelligent technique may be utilized to classify and find the type of fault occurred in the network. An algorithm to detect and classify the fault and indicate the fault position in a transmission line with respect to a FACTS device placed in the midpoint of the transmission line has been proposed in [1]. In [2], two approaches are presented to detect short-circuit faults in power transmission lines. In [3], authors proposed a method for fault location on transmission lines, which is based on time to frequency domain transformation of transient signals of the fault instant measured at one end. Fast Fourier Transform (FFT) is used for determination of the fault location using the travelling wave theory of the transmission line. In [4], time domain relaying schemes for complete protection of parallel transmission lines using wavelet and artificial neural network (ANN) are presented. In [5], authors presented a new approach to classify fault types and predict the fault location in the high-voltage power transmission lines, by using Support Vector Machines (SVM) and Wavelet Transform (WT) of the measured oneterminal voltage and current transient signals. In [6], authors presented a statistical algorithm for classification of faults on power transmission lines. The proposed algorithm is based upon the wavelet transform of three phase currents measured at the sending end of a line. 2. TEST SYSTEM USED FOR STUDY Proposed test system consists of transmission line connected between two sources of alternating supply. Proposed test system modeled in MATLAB/Simulink environment is shown in Fig. 1.[7] Transmission line consists of 10 pi sections each of length 20 km. This will help to simulate symmetrical fault at different locations of line. There are two buses at the ends of line where AC generators are connected to transmission line. 2250

Fig. 1. 3. PROPOSED FAULT INDEX The current signal of phase-a is decomposed using Hilbert transform. Absolute value of output of the Hilbert Huang Transform based decomposition is obtained. The intrinsic mode functions at decomposition level 1 are calculated. The proposed fault index (FI) is calculated as below. C=IMF1.*IMF1 The peak values of the FI are used to detect and discriminate the symmetrical fault involving the ground. 4. SIMULATION RESULTS AND DISCUSSION The three-phase fault involving ground (LLLG) is simulated at 50% of line length from the AC source-1 end. The current recorded on bus-1 is decomposed Proposed test system used for the study of fault analysis. using the Hilbert transform. The absolute value of the output of Hilbert transform is decomposed using the empirical mode decomposition and IMFs are obtained at first and second decomposition levels. The proposed fault index is obtained from the IMF at first level of decomposition. The three phase currents on bus-1, current of phase-a, IMF at first level of decomposition, IMF at second level of decomposition are shown respectively in Fig. 2 (a), (b), (c), and (d). This can be observed from the Fig. 2 (c) that the values of IMF at first level of decomposition are nonzero at the time of fault occurrence indicating the presence of disturbances other than the fundamental frequency. The values of the IMF at first level of decomposition are zero before the fault occurrence. The low magnitude transients are obtained throughout the range after fault occurrence. The transient 2251

components are also observed in the values of IMF at second level of decomposition as shown in Fig. 2 (d). Hence, it is observed that significant disturbance components are present in the IMFs at the time of fault occurrence which will help to detect the LLLG fault. The fault index calculated on bus-1 during the event of three-phase involving the ground is shown in Fig. 3. It is noticed from this figure that the value of fault index is zero before the occurrence of the fault i.e. for initial 6 cycles. High magnitude peak having the value 34000 is observed at the time of fault occurrence indicating the presence of LLLG fault. Hence, the LLLG fault can be detected effectively using the proposed algorithm. The LLLG fault is also simulated at 10%, 20%, 30%, 40%, 50%, 60%, 70%, 80% and 90% of line length from the end of AC source-1 and peak values of the proposed fault index measured on bus-1 are provide in Tale I. The three phase fault involving ground (LLLG) fault is simulated at 50% of line length from the AC source-1 end. The current recorded on bus-2 is decomposed using the Hilbert transform. The absolute value of the output of Hilbert transform is decomposed using the empirical mode decomposition and IMFs at first and second decomposition levels are obtained. The proposed fault index is obtained from IMF at first level of decomposition. Three phase currents on bus-2, current of phase-a, IMF at first level of decomposition, IMF at second level of decomposition are shown respectively in Fig. 4 (a), (b), (c) and (d). This can be observed from the Fig. 4 (c) that the value of IMF at first level of decomposition are non-zero at the time of fault occurrence indicating the presence of disturbances other than the fundamental frequency. The values of this IMF are zero before the fault occurrence. The transient components are also observed in the values of IMF at second level of decomposition after fault occurrence as shown in Fig. 4 (d). Hence, it is observed that significant disturbance components are presented in the IMFs at the time of occurrence of LLLG fault which helps to detect the LLLG fault. Fig. 2 Fig. 3 Parameters on bus-1 during LLLG fault at 50% of line length (a) three phase currents (b) current of phase-a (c) intrinsic mode function-1 (d) intrinsic mode function-2 Fault index on bus-1 during LLLG fault at 50% of line length The fault index calculated on bus-2 during LLLG fault at middle of the line (50%) is shown in Fig. 5. It is observed from this figure that the value of fault index is zero before the occurrence of the fault i.e. for initial 6 cycles. High magnitude peak having the magnitude equal to 24000 is observed at the time of fault occurrence indicating the presence of fault. Hence, the LLLG fault can be detected effectively using the proposed algorithm on bus-2 of the transmission line. The three-phase fault involving ground is also simulated at 10%, 20%, 30%, 40%, 50%, 60%, 70%, 80% and 90% of line length from AC source-1 and peak values of the fault index measured on bus-2 are provide in the Tale I. 2252

ground at the locations 10%, 20%, 30%, 40%, 50%, 60%, 70%, 80% and 90% of line length from AC source-1 are provide in the Table I. The variations of fault indexes are plotted in the Figure 6. It is observed from the Fig. 6 that the peak values of the fault indexes calculated on buses at both ends of the transmission line are above the threshold value (TH2) of 20000. If the peak value of the fault index is below 20000 then there will be other types of the fault on the system or may be the healthy condition. The value of faulty fault index above 20000 indicates the presence of the three phase fault involving the ground. It is also observed that the values of the fault index on bus-1 are highest at 10% of the line length which is near the bus-1 end and it is minimum on the 90% of the line length. The reverse trend is observed with the fault index calculated on the bus-2 of the test system. It is maximum on the 90% of the line length which is near the bus-2 of the test system and minimum at the 10% of line length which is near the bus-2 of the test system. However, the value of proposed fault index during the LLLG fault significantly high compared to the corresponding values observed on the bus-1. Fig. 4 Parameters on bus-2 during LLLG fault at 50% of line length (a) three phase currents (b) current of phase-a (c) intrinsic mode function-1 (d) intrinsic mode function-2 Fig. 6 Variations of Fault index on buses 1 and 2 during LLLG fault Fig. 5 Fault index on bus-2 during LLLG fault at 50% of line length TABLE I PEAK VALUES OF THE FAULT INDICES DURING LLLG FAULT Line length from Peak value of Fault Index AC source-1 side Bus-1 Bus-2 10% 34500 23600 20% 34300 23800 30% 34200 23850 40% 34100 23900 50% 34000 24000 60% 33900 24100 70% 33800 24200 80% 33750 24250 90% 33900 24400 The peak values of the proposed fault index on the buses-1 and 2 during the three-phase fault involving 5. SIMULATION RESULTS AND DISCUSSION This presents detection of symmetrical fault with the involvement of ground. The study has been performed using a test system with two buses and one transmission line having the line length of 200 km and rated at 765 kv and 60 Hz. The currents are recorded at both the ends of the transmission line. The symmetrical fault is simulated at 10%, 20%, 30%, 40%, 50%, 60%, 70%, 80% and 90% of line length. The current of phase-a is decomposed using the Hilbert Huang transform. IMFs are obtained at first level of decomposition. The proposed fault index is calculated by multiplying the respective values of the IMFs at first level of decomposition. This fault index is calculated at both ends of the transmission line. The plots of values of the fault index at 50% of line length are provided. It is concluded that the fault index has zero values in the absence of the fault and 2253

non-zero values during the faulty events. The plots of variations of the fault indexes at different line lengths are also obtained. The threshold value is used to discriminate faulty event from the healthy condition. REFERENCES [1] A. M. El-Zonkoly, H. Desouki, Wavelet entropy based algorithm for fault detection and classification in FACTS compensated transmission line, Electrical Power and Energy Systems, Vol. 33, pp. 1368 1374, 2011. [2] Hassan Fathabadi, Two novel proposed discrete wavelet transform and filter based approaches for short-circuit faults detection in power transmission lines, Applied Soft Computing, Vol. 36, pp. 375 382, 2015. [3] Mehmet Salih Mamis, Müslüm Arkan, Cemal Keles, Transmission lines fault location using transient signal spectrum, Electrical Power and Energy Systems, Vol. 53, pp. 714 718, 2013. [4] Aleena Swetapadma, Anamika Yadav, Time domain complete protection scheme for parallel transmission lines, Ain Shams Engineering Journal, pp. 1-15, 2015. [5] Sami Ekici, Support Vector Machines for classification and locating faults on transmission lines, Applied Soft Computing, Vol.12, pp. 1650 1658, 2012. [6] J. Upendar, C.P. Gupta, G.K. Singh, Statistical decision-tree based fault classification scheme for protection of power transmission lines Electrical Power and Energy Systems, Vol. 36, pp. 1 12, 2012. [7] Bhuvnesh Rathore; Abdul Gafoor Shaik, Fault detection and classification on transmission line using wavelet based alienation algorithm, Innovative Smart Grid Technologies - Asia (ISGT ASIA), 2015 IEEE, Bangkok, Thailand, 3-6 Nov. 2015. 2254