TECHNICAL SPECIFICATION

Similar documents
LIGHTNING ARRESTOR. September 2017 WEST BENGAL STATE ELECTRICITY TRANSMISSION COMPANY LIMITED

SPECIFICATION No SS-135/ kv METAL OXIDE SURGE ARRESTERS WITHOUT GAPS

POTENTIAL TRANSFORMER

Technical Specification For 33 KV, Single Phase, Dead Tank Type Out Door Current Transformer Of Different Ratio

36kV VOLTAGE TRANSFORMERS (OUTDOOR TYPE)

شركة كهرباء محافظة القدس المساهمة المحدودة JERUSALEM DISTRICT ELECTRICITY CO. LTD.

CAPACITOR VOLTAGE TRANSFORMER

1.0 mh, 3150 A LINE TRAP

COMBINED METERING TRANSFORMERS (OUT DOOR TYPE) FOR 11kV & 33kV SYSTEMS

Type DMX-N Surge Arresters Maximum System Voltage 2 to 36 kv

TECHNICAL SPECIFICATION OF ELECTRICAL MATERIALS CT & PT GROUP C

TECHNICAL SPECIFICATION FOR 11KV, 3C x95mm mm 2 AERIAL BUNCHED CABLES FOR OVERHEAD LINES (CROSSED LINKED POLYTHENE DRY GAS CURED)

TECHNICAL SPECIFICATION FOR 22 KV CURRENT TRANSFORMERS

GENERAL TECHNICAL SPECIFICATION (Turnkey Work)

1.1_KV PVC insulated PVC sheathed multicore Aluminium Cable (armoured & unarmoured)

MGVCL/MM/ /2082/11KV AB CABLE TECHNICAL SPECIFICATION FOR 11KV AERIAL BUNCHED CABLES FOR OVERHEAD LINES

Technical Specification. for 1.1 KV Copper Control Cable

S. C. Electric Cooperative s Specification for a Single-Phase, Single Bushing Overhead Distribution Transformer (Revised 10/2013)

SPECIFICATION FOR STEP UP TRANSFORMER 0.415/11Kv and (630KVA & 1000KVA)

50-SDMS-01 SPECIFICATIONS FOR

AMENDMENT NO. 1 SEPTEMBER IS (Part 1) : 2001/IEC (1991) SURGE ARRESTORS

TECHNICAL SPECIFICATION FOR G.I. WIRE AND G.I. STAY WIRE

GUJARAT ENERGY TRANSMISSION CORPORATION LTD. SARADAR PATEL VIDYUT BHAVAN, RACE COURSE, BARODA TECHNICAL SPECIFICATIONS

SPECIFICATION SS-140/9. 0.6/1 (1.2) kv CONTROL AND POWER UNDERGROUND CABLES WITH PVC OR XLPE INSULATION AND PVC JACKET

COOPER POWER. UltraSIL Polymer-Housed VariSTAR Type U2Surge Arrester for Systems through 275 kv IEC 10-kA; Line Discharge Class 2 SERIES

GTP NO-16 GUARANTEED TECHNICAL PARTICULARS FOR 33kV, 200A, 50 Hz AB SWITCH, 3 POLE, SINGLE BREAK TYPE

012: 2015 CEB SPECIFICATION GALVANIZED STEEL WIRE (EXCEPT SHIELDING WIRE FOR TOWER LINE APPLICATION)

GURANTEED TECHNICAL PARTICULARS OF BACK CLAMP FOR LT CROSS ARM

(TECHNICAL SPECIFICATIONS & GTP FORMATS) 11KV METERING UNITS

GENERAL TECHNICAL SPECIFICATION

EE 1402 HIGH VOLTAGE ENGINEERING

3. COMBINED TRANSFORMERS Oil-paper insulation

TECHNICAL DESCRIPTION TD-77A/3 170 KV COMPACT GAS INSULATED INTEGRATED SUBSTATION MODULES

51-SDMS-02 SPECIFICATIONS FOR DISTRIBUTION TRANSFORMERS UP TO 36KV 400/230 VOLTS

Energy Division. Bowthorpe LV/MV Surge Arresters

Title: Southern States Type SLS Smart Sectionalizer Solid Dielectric Three Phase Sectionalizer. Product Specification Guide TABLE OF CONTENTS

Secondary Arresters. Figure 1. Type L secondary surge arrester rated 175 Vac, 125 Vdc.

The NOVA Recloser shall be designed and tested in accordance with the following standards as applicable:

Insulation Co-ordination For HVDC Station

SPECIFICATION FOR 11 KV CLASS, 24/15.7, 30/19.7 & 45/29.5 AMPS SPECIAL DESIGN TRANSFORMERS.

TECHNICAL SPECIFICATION OF 11 KV AND 22 KV THREE PHASE FOUR WIRE, THREE

TECHNICAL SPECIFICATION OF 11 KV THREE PHASE FOUR WIRE, THREE CTs COMBINED METERING CTPT SET OF ACCURACY CLASS 0.5s

EARTHING TRANSFORMER

11-SDMS-03 REV. 02 SPECIFICATIONS FOR

VariSTAR Type AZL heavy-duty distribution-class MOV arrester

GUJARAT ENERGY TRANSMISSION CORPORATION LTD. TECHNICAL SPECIFICATIONS 400KV, 8800PF LINE CVT FOR EXISTING & NEW SUB- STATIONS

Effective February 2017 Supersedes January 2012 (CP1122)

TECHNICAL SPECIFICATIONS

SUPPLY OF CARRIER PROTECTION COUPLER TYPE NSD-50

PRESENTATION ON IS 1180 (Part 1): 2014 DISTRIBUTION TRANSFORMERS SHYAM KUMAR SCIENTIST B ELECTROTECHNICAL BUREAU OF INDIAN STANDARDS

Plant Client Contract Code Document ID Contract No. TECHNICAL SPECIFICATIONS DC SHUNT Rev 00 Page 1 of 2

APDRP SCHEME, WESCO. Technical Specification for Distribution Transformers ( 11/0.4KV ) PART 1: GENERAL

SPTS 1 - Ratings and General Requirements for Plant, Equipment and Apparatus for The ScottishPower System and Connection Points to it.

MAHARASHTRA STATE ELECTRICITY DISTRIBUTION COMPANY LTD. TECHNICAL SPECIFICATION FOR. 36 kv (PROTECTION CUM METERING) INSTRUMENT TRANSFORMERS

Maharashtra State Electricity Distribution Co. Ltd.

The RSM shall be extensively used in field & laboratory for verification of the accuracy of all types of single-phase energy meters.

DISTRIBUTION TRANSFORMER kv

LOCOMOTIVE ENGINEERING DEPTT.

TECHNICAL SPECIFICATION OF LT SHACKLE BOLT (G. I. BOLT) WITH NUT AND SPRING WASHER

Our experience. Our products

Maharashtra State Electricity Distribution Co. Ltd.

All the standards referred to the most current issue, including all amendment supplements. as of the date of the bid.

Single-Phase Mini Pad-Mounted Transformer Specification: Energy+ MPDL

MGM Transformer. Vacuum Pressure Impregnated (VPI) Dry-Type Substation Transformer Specification Guide

PROCEDURE FOR INSPECTION OF ELECTRICAL INSTALLATIONS ABOVE 250KVA

51-SDMS-04 SPECIFICATIONS FOR. DISTRIBUTION TRANSFORMERS UP TO 36 kv WITH ALUMINUM WINDINGS FOR DUAL SECONDARY 400/230 V AND 230/133 V

DISTRIBUTION TRANSFORMER 11 / kv

CONSULTANT PROCEDURES & DESIGN GUIDELINES Liquid-Filled Utility Transformers UNIVERSITY OF MISSOURI

Analysis of Major Changes to Arrester Standards IEC STEVE BREWER

7. INSPECTION AND TEST PROCEDURES

3EK8 distribution class surge arresters. Catalogue HP-AR Version siemens.com/arresters

ELECTRICAL NETWORKS SPECIFICATION TECHNICAL SPECIFICATION FOR A 230V/110V AND 400V/110V TRANSFORMER

SPECIFICATION FOR SAFETY POLE SIGNS & ACCESSORIES

TECHNICAL SPECIFICATION FOR SELF PROTECTED SINGLE PHASE DISTRIBUTION TRANSFORMERS ( SPECIFICATION NO: DIST/01-N/2004 )

MV ELECTRICAL TRANSMISSION DESIGN AND CONSTRUCTION STANDARD. PART 1: GENERAL 1.01 Transformer

CONDITIONS FOR A TENTATIVE APROVAL FOR CONNECTION OF TRANSFORMERS

SOUTHERN ELECTRICITY SUPPLY COMPANY OF ODISHA LIMITED (SOUTHCO UTILITY)

INTERNATIONAL STANDARD

SUGGESTED SPECIFICATION for Series 300 Automatic Transfer Switches

WESTERN UNDERGROUND COMMITTEE GUIDE 2.6 (2.6/00/0868)

The Variable Threshold Neutral Isolator (VTNI)

Substation Design Volume VII

Tab 8 Surge Arresters

66/ or 23.1 kv, 05, 10, 15 & 20 MVA POWER TRANSFORMER

400 kv EARTHING SWITCH

Transformers connected via a cable Overvoltage protection

User s Manual For CT Model IMB

شركة كهرباء محافظة القدس المساهمة المحدودة JERUSALEM DISTRICT ELECTRICITY CO. LTD.

NUCLEAR POWER CORPORATION OF INDIA LIMITED. (A Government of India Enterprise) TECHNICAL SPECIFICATION 220 KV CAPACITOR VOLTAGE TRANSFORMERS FOR

The power line carrier equipment will provide speech, telecontrol and teleprotection channels over 50 Hz, 132 KV transmission systems.

DATA SHEET FOR LIGHTING TRANSFORMER APPD. BY VDV PROJECT NO

Network Standard NETWORK. Document No Amendment No Approved By Approval Date Review Date NW000-S0142 : : : : : Head of AEP&S 08/06/ /06/2017

3EE2 Special-Purpose Surge Arresters for the Protection of Motors, Generators and Furnace Transformers

TS RES - OUTSTANDING ISSUES

220 kv INSTRUMENT TRANSFORMERS (with Tariff Metering)

TECHNICAL SPECIFICATION OF 630 KVA, 11/ KV DRY TYPE OUTDOOR TRANSFORMERS.

Business reform Action Plan Rec # 299 to 303 Certification of Electrical Installation by Electrical inspectorate

VI 3 - i TABLE OF CONTENTS

Eaton s Cooper Power Series DEADFRONT ARRESTERS

VBS TBS KTS BSS LFS UFS

Transcription:

TECHNICAL SPECIFICATION 1. SCOPE : TECHNICAL SPECIFICATION FOR LIGHTNING ARRESTORS 1.1. This Specification covers design, manufacture, testing at manufacturer's Works, packing, supply, delivery of 42 KV & 12 KV classes of gapless Lightning Arrestors complete with fittings and accessories. 1.2. These arrestors shall be of Heavy Duty, Station Class / Distribution Class and Gapless Zinc Oxide type. 1.3. Arrestors shall be hermetically sealed units suitable for outdoor installation on self-supporting base or structures. 2. STANDARD : Arrestors shall conform in general to IEC-99-4 document or its latest amendment and IS/IEC as follows: i) IEC-99-4 : Gapless Lightning Arrestor ii) IS 3070 P-III : Metal Oxide Surge Arrestors without gaps for AC Systems. IEC 99 P-III : Artificial Pollution Testing of Lightning Arrestor IEC 270 : Partial Discharge Measurement. v) IS 2071 : Methods of H V Testing vi) IS 6209 : Methods for Partial Discharge Measurement vii) IS 5621 : Hollow Insulators for use in electrical equipment 3. DEVIATION : Normally the offer should be as per Technical Specification without any deviation. But any deviation felt necessary to improve performance, efficiency and utility of equipment must be mentioned in the 'Deviation Schedule' with reasons duly supported by documentary evidences and advantages of such deviation. Such deviations suggested may or may not be accepted. But deviations not mentioned in Deviation Schedule will not be considered. 4. DUTY REQUIREMENT : The Surge Arrestors are being provided to protect the following equipment whose insulation levels are indicated in the table given below: Equipment to be protected Power Transformer Instrument Transformer CB/Isolator Phase to ground Across open poles L I for 42 KV system (KVp) +/-170 L I for 12 KV system KVp) +/-75 +/-170 +/-75 +/-170 +/-75 +/-195-4.1. The Lightning Arrestors shall be capable of discharging Lightning and switching surges and temporary power frequency over voltages.the Surge Arrestor shall be capable of discharging over voltages occurring during switching of unloaded transformers and long lines. 4.2. The Arrestors shall be capable of withstanding Maximum Continuous Operating Voltages (M.C.O.V).

4.3. The Arrestors supplied shall be suitable for heavily polluted atmosphere. 4.4. The reference current of the Arrestors shall be high enough to eliminate the influence of grading and stray capacitance on the measured reference voltages. 5. FITTINGS & ACCESSORIES : 5.1 Arrestor rating upto 42 KV shall be directly mounted on structure as there is no surge counter. 5.2 Each single pole arrestor shall be provided with suitable name plate, at the base with the following data : i) Name of device ii) Manufacturer's name and trade mark, type and identification Year of manufacture Voltage rating & frequency rating. v) Nominal discharge current vi) MCOV (Maximum Continuous Operating Voltage in KV). vii) Discharge class. v Energy Discharge capability (KJ/KV rating) ix) Purchase Order reference. x) Applicable Standard. xi) Pressure Relief rated current in KA rms (for arrestors fitted with Pressure Relief device) xii) Serial Number 5.3 Clamp type terminal connector shall be suitable for either ACSR DOG Conductor for 42 KV and WEASEL / RABBIT Conductor for 12 KV system voltage class L.A. having horizontal/ vertical take off. Detailed particulars have been indicated in the specification for Clamps and Connector in this bid document. 5.4 Two ground terminal connectors suitable for G.I strip of required size shall be provided on diagonally opposite sides. 5.5 Necessary hardware such as nuts, bolts, spring washers, etc. shall be supplied for different units. 5.9 12 KV Lightning Arrestor should be of Distribution Type and should have suitable Fault Indicator. 6 CONSTRUCTIONAL FEATURES : 6.1 The arrestor elements shall be designed in such a way as to obtain robust construction with excellent mechanical and electrical properties even after repeated operation. The lightning arrestors should be adequately designed to operate satisfactorily under temporary power frequency over voltage as given in Specific Technical Parameters, after discharging two shots of respective long duration surges. Uniform density of zinc oxide element shall be maintained to provide uniform current distribution. 6.2 The lightning Arrestors shall be of adequate Pressure Relief Class as per IEC-99-4, fitted with Pressure Relief Devices and Arc diverting ports to minimise possibilities of shattering of porcelain housing. 6.3 Sufficient creepage distance shall be provided to reduce excessive uneven voltages over the porcelain due to contamination, for which the arrestor shall not fail. 6.4 Seals shall be provided in such a way that these are always effectively maintained even when discharging the maximum rated lightning current.

6.5 Housing of Insulators shall be of Porcelain, glazed and completely vitrified and free from blow holes, micro-cracks or void. Porcelain, housing shall be so coordinated that external flashover will not occur due to application of any impulse or switching surge voltage up to the maximum design value for the arrestor. 6.6 The end fittings shall be made of non-magnetic and corrosion proof material. It is preferable that the LAs shall be hermetically sealed with inert gas (Nitrogen). 6.7 Arrestors shall be suitable for mounting on a support structure. 6.8 12 KV Class Distribution Type Lightning Arrestor should have provision for Fault Indicator/Disconnector. 7 APPLICATION : The lightning Arrestors are used for protection of incoming and outgoing line and also of the power transformers from lightning surge as well as from power frequency over voltage. 8 TENDER DRAWINGS, CATALOGUES: General outline drawing giving plan, elevation, side view and sectional view, top and bottom connection arrangement with pitch circle diameter and other dimensions of the complete assembly with surge counter and leakage current measuring meter where applicable, Size of terminals and lifting lugs, shipping weight etc are to be indicated. 9 CONTRACT DRAWINGS AND MANUALS : 9.1 In the event of placement of Order, six (6) copies of drawings and descriptive literatures shall be furnished to the Chief Engineer, P&CD, Vidyut Bhavan (4th floor), Salt Lake, Kolkata - 700 091 for approval : i) General Outline Drawing showing plan, elevation and end views with dimensions and showing full mounting details with weights. ii) Dimensional Drawing showing the Arrestor mounted on its base and where applicable with surge counter and leakage current measuring meter. Details of Bushing top terminals & terminal connectors. Shipping Dimensional Drawings with weights. v) Position of Centre of gravity and clearances with adjacent grounded metallic structures. vi) vii) v Diagram Plate showing electrical connections of the surge counter and leakage current measuring meter where applicable. Rating Plate. Complete foundation drawings for the structure of Lightning arrestor, where applicable. 9.2 Ten (10) sets of approved drawings and operation and maintenance manuals shall be submitted for our record and distribution to site. 10 TEST REPORTS AND TYPE TESTS : The Bidder should submit the Complete Test Reports (including Dynamic Short Circuit Test Report) & Reports of Type Tests as stipulated in latest relevant IS/IEC with complete Identification, Date & Sl.No., carried out within 5(Five) Years from Due Date of Tender, from CPRI/ NABL accredited/govt. Recognized Test House or Laboratory on Tendered Item of identical design, With Tender Documents failing which their offer may not be technically accepted.

11 TEST AT FACTORY AND TEST CERTIFICATES : i) Each LA. shall comply with the requirements of routine test as specified in the relevant IEC:99-4 & IS:3070 (Part - III). ii) Routine test at manufacturer's works shall be carried out in presence of representative of WBSEDCL. All routine & acceptance tests shall be carried out at the manufacturer's works on every lot offered for inspection as per relevant IEC & IS. Selection of samples for acceptance test as well as rejection and retesting shall be guided by relevant IEC & IS. Six (6) copies of Test Reports shall be submitted to the Chief Engineer (P&CD), Vidyut Bhavan (4 th floor), Salt Lake, Kolkata - 700 091 for approval. Adequate extra copies should also be submitted to Chief Engineer (P&CD) Vidyut Bhavan (4 th floor), Salt Lake, Kolkata - 700 091 for distribution to site. The Tenderer shall give at least 15 (fifteen) days advance notice intimating the actual date of inspection and details of all tests that are to be carried out. Relevant Type & Routine Tests Certificates obtained from the competent Authorities for all accessories/ bought out items shall have to be furnished. 12. TYPE TESTS after issuance of order : Besides submission of Type Test Report, carried out within five years as per Tender Specification, Type Test at the discretion of Ordering authority, shall have to be arranged by the successful contractor from any lot offered for inspection, sample chosen at random after successful Routine Test by our Inspection Team, as per relevant ISS from NABL accredited/govt. Recognized Test House or Laboratory in presence of WBSEDCL S representative. In case of failure of the materials after type test the WBSEDCL will have the right to reject the total supplied lot of the said materials and the party have to replace the complete lot of materials at his own cost including transportation of materials at site. However the necessary cost of the Type Test charges will be reimbursed to the party on production of necessary supporting documents. 13. Documents to be submitted at the time of physical delivery at consignee stores : The following documents to be submitted by the vendors to the consignee Stores at the time of despatch to stores by the vendors:- a) Copy of Purchase Order. b) Copy of Despatch Instruction. c) Inspection Test Certificate. d) Guarantee Certificate. e) Proforma Invoice. f) Calculation Sheet for price Variation on the basis of IEEMA or CACMAI as applicable with base date of order. g) Seal list and packing list. h) Challan in triplicate. i) Way bill, if applicable.

SPECIFIC TECHNICAL PARAMETERS- I TYPE OF ARRESTOR STATION CLASS DISTRIBUTION HEAVY DUTY CLASS GAPLESS i) Nominal system voltage (KV) 33 11 ii) Highest system voltage (KV) 36 12 System Neutral Earthing NEE(Grounded Through Earthing Transformer) EE BIL of transformers (KVp) 170 75 v) System fault level (KA) 25 16 vi) Maxm. System BIL (KVp) 170 75 LA RATINGS : i) Rated Voltage (KV) 42 12 ii) Maxm. Continuous operating voltage 36 10 (KVrms) Nominal Discharge Current (KAp) 10 5 Line discharge class 2 Distribution Class v) Minimum Energy Discharge capability 5 5 (KJ/KV) [If there is any Deviation the same may be mentioned in the Deviation Sheet] vi) Temporary over voltage withstand 42 12 capability (KVrms) for 10.0 secs vii) Insulation Housing withstand voltages i) Lightning Impulse(Dry) ii) Power frequency(wet) Minimum values as per IEC for 10 KA for 5 KA v Minimum creepage Distance acceptable (mm) 1100 300 i) Pressure Relief Class To be tested in accordance with IEC ix) (Minimum) High Current Impulse withstand 100 65 (4/10) KA (peak) x) Maxm.Lightning Impulse (8/20 microsecond impulse) residual voltage (KVp) : 5 KA 112 40 10KA - - xi) Maxm. switching surge (30/60 microsecond wave) protective level (KVp) 500 Amps 98 21 1000 Amps - - 2000 Amps - - xii) Maxm. Steep Impulse (1/20 micro-seconds 130 45 impulse) residual voltage at 10 KA (KVp) x RIV/Partial Discharge (micro-volt / picocoulomb) when energised at 1.05 times its continuous operating voltage shall not exceed 250 microvolt/ less than 50 pico-coulomb 1000 microvolt/ less than 500 picocoulomb x Terminal connection Suitable for ACSR Dog Conductor Suitable for Weasel/Rabit ACSR Conductor xv) Rated Frequency (Hz) 50 50 xvi) Minimum Visible Corona Discharge - - voltage(kv rms)

TYPE OF ARRESTOR GUARANTEED TECHNICAL PARAMETERS STATION CLASS HEAVY DUTY GAPLESS (42KV) DISTRIBUTION CLASS (12KV) i) Nominal system voltage (KV) ii) Highest system voltage (KV) System Neutral Earthing BIL of transformers (KVp) v) System fault level (KA) vi) Maxm. System BIL (KVp) LA RATINGS : i) Rated Voltage (KV) ii) Maxm. Continuous operating voltage (KVrms) Nominal Discharge Current (KAp) Line discharge class v) Minimum Energy Discharge capability (KJ/KV) [If there is any Deviation the same may be mentioned in the Deviation Sheet] vi) Temporary over voltage withstand capability (KVrms) for 10.0 secs vii) Insulation Housing withstand voltages i) Lightning Impulse(Dry) ii) Power frequency(wet) for 10 KA for 5 KA v Minimum creepage Distance acceptable (mm) i) Pressure Relief Class ix) (Minimum) High Current Impulse withstand (4/10) KA (peak) x) Maxm.Lightning Impulse (8/20 micro-second impulse) residual voltage (KVp) : 5 KA 10KA xi) Maxm. switching surge (30/60 micro-second wave) protective level (KVp) 500 Amps 1000 Amps 2000 Amps xii) Maxm. Steep Impulse (1/20 micro-seconds impulse) residual voltage at 10 KA (KVp) x RIV/Partial Discharge (micro-volt / picocoulomb) when energised at 1.05 times its continuous operating voltage shall not exceed x Terminal connection xv) Rated Frequency (Hz) xvi) Minimum Visible Corona Discharge voltage(kv rms) Date: Place: Signature: Name: Name of the Company: Seal of the Company: