Excel 10 W7761A Remote Input/Output Device

Similar documents
Excel 15 S7760A COMMAND DISPLAY

Excel 10 W7751B,D,F VAV Controllers

A local 3.5 mm network jack allows a convenient way to connect an installation or diagnostic tool to the network without disconnecting any wires.

MNL-5Rxx. Application. Model Chart. TAC I/A Series MicroNet MN 50 Controller Installation Instructions

H7625A, H7635A, H7626A, H7636A Series 2000 Humidity/Temperature Sensors

ECB-103 BACnet B-ASC 10-Point Programmable Controllers

LX Scheduler. Installation Instructions LX-SCHEDL-0. Mounting. Applications. North American Emissions Compliance. Installation

H7625B, H7626B, H7635B,C H7636B, H7655B, H7656B

H7625A, H7635A, H7626A, H7636A Series 2000 Humidity/Temperature Sensors

Compact I/O Module XIO-8AI UNIVERSAL ANALOG INPUT MODULE

W7070A2000 ZAPP WIRELESS RECEIVER

Environmental Combustion and Control. Stryker CVAHU System Engineering Guide. August

W7100A-E Discharge Air Controller

FTT-10A Free Topology Twisted Pair Transceiver Model 50051

Power connections, minimum and maximum wiring capabilities, tightening torque

200 Watt Passive Shunt Module

Installation Instructions

Digital Lighting Systems, Inc. PD804-DMX. Eight Channel DMX Pack. (includes information for PD804-DMX-S) USER'S MANUAL. PD804-DMX-UM Rev.

VFSC9 ELECTRONIC SPEED CONTROLLER. Mounting and operating instructions

ECL-VAV-N. Features & Benefits

User's Manual: Series 350T AC Current Input (External Sensor), DC-Powered Transmitters

User's Manual: Series 450T AC Current Input (External Sensor), AC-Powered Transmitters

Micro Thermo Standard Wiring Guide

Modbus communication module for TCX2: AEX-MOD

CD-Pxx-00-0 Series Duct Mount CO 2 Transmitter

Jaguar Motor Controller (Stellaris Brushed DC Motor Control Module with CAN)

SELECTIVE CALL INTERCOM SYSTEM MODEL: IM-5000 MASTER STATION

Mini-Catalog of CONTROL INTERFACES. SIGNAL TRANSDUCERS and SIGNAL CONDITIONERS

Lighting Stryker BACnet CLB6438S Configurable Lighting Controller

NX Series Inverters. HVAC Pocket Programming Guide

24V dc Analog Block I/O Module

Electronically Commutated (EC) Motor Control with Solo, Select and Sync PWM Boards

Excel 800 / Excel Web II CABLE SPECIFICATIONS

TECHNICAL PRODUCT DATASHEET

READ THESE INSTRUCTIONS BEFORE YOU BEGIN INSTALLATION. Ground yourself before touching board. Some components are static sensitive.

n FRONT PANEL CONFIGURATIONS

TCX 850 Installation Guide. Andover Controls Corporation. Downloaded from -

Ambient Conditions Storage Conditions Installation Minimum Clearances and Air Flow...2 3

April 1994 UCM-420A. Setpoint Controller. Operating and Installation Instructions

Excel 10 W7763C,D,E CHILLED CEILING CONTROLLERS LNS PLUG-INS

Com-Trol ADV-6000 Trouble Shooting Guide Click on red text to go to that page in guide

SRC-110 Series Zone Controllers with Modbus RTU

02/11/2015

GUIDE SPECIFICATIONS CONTROLS SPECIFICATIONS AND CONTROL POINT DATA MAP GENERAL DESCRIPTION

Technical Information

AU INSTALLATION INSTRUCTIONS. Revision B1 Rapid City, SD, USA, 02/2010 II_201A-AU_B1

Brushed DC Motor Control. Module with CAN (MDL-BDC24)

02/11/2015

02/11/2015

Zlinx Wireless I/O. Peer-to-Peer and Modbus I/O PRODUCT INFORMATION B&B ELECTRONICS

The wireless alternative to expensive cabling...

BAPI-Stat 4 X-Combo, Room %RH and Temp. Sensor BA/BS4XC Installation & Operating Instructions

ZZxD-Nx-xR Series. Wireless Modbus I/O B&B ELECTRONICS PRODUCT INFORMATION

DUAL 4-20 MA NETWORK BRIDGE. Voltage. Regulator. Neuron CPU. Ohm Sense Resistor. Model 1400A Block

READ THIS BEFORE ATTEMPTING TO COMBINE

MG350V Globe Valve SmartX Actuator

MC450/MC650 (MC750) OPERATING INSTRUCTIONS

H LONTalk Integration Node For Use With H704 and H663 Branch Current Monitors (BCM) H NOTICE DANGER INSTALLATION GUIDE DIMENSIONS

SMX Transceivers Models 77010, 77030, 77040, 77050, and 77162

8 Input/8 Output AC Block I/O Module

Load Cell Accessories and Services

NSD Safety Mat Controller Modules Both Modules are compliant to OSHA & ANSI Standards - EN ISO EN EN 81-1 EN NSD VDC

TECHNICAL DATASHEET #TD1400AX PWM Controlled Solenoid Driver (DIN rail mount) P/N: PWMC-DR-2A, PWMC-DR-1.2A

Bypass Panels FRENIC-EcoPAK. Fuji Electric Corp. of America FECA-IN-105 / Information subject to change without notice.

Analog Input Module HART Ex i / I.S. Inputs, Channels Type 9461/

TECHNICAL DATASHEET #TDAX INPUTS, 5 OUTPUTS VALVE CONTROLLER

Viconics VT76x7 Series Rooftop Unit Controllers Engineering Guide Specification

The wireless alternative to expensive cabling...

905U Wireless. New Products... New Solutions. The wireless alternative to expensive cabling... Simple but Reliable. Easy to Use

Model RFT9709 Transmitter Instruction Manual

DESCRIPTION NOTE. Power Supply MODEL 2200A PM

Emergency PHM Series. Emergency PowerHUBB Node - Master/Control/Tunable White. Dimensional Data. Ordering Information (Example: PHM4PC EM)

TAC ATV38, IP55. Variable Speed Drives for Asynchronous Motors. 3-phase. 380/460 V, Hz

F2A3X Frequency to Analog Converter Module

Compact room automation stations, BACnet MS/TP, AC 24 V

DET-TRONICS SPECIFICATION DATA. Eagle Quantum Premier 8 Channel Enhanced Discrete Input/Output Module (EDIO) EQ3730EDIO DESCRIPTION

POWER DELEGATOR SERIES 7200A POWER DISTRIBUTION UNIT WITH POWER CONDITIONING GENERAL SPECIFICATIONS

SIMATIC. ET 200B Distributed I/O Station. Preface, Contents. System Overview. Technical Description. Mechanical and Electrical Installation

MODEL AT-10 ANALOG TRANSMITTER

Digital Input Module 24 V Ex n Inputs, 16 Channels Series 9471

The MP SERIES CONTROLLER. User s Manual. ISE, Inc.

WAVEFORM CORRECTOR (WAVEFORM CORRECTORS) REPLACES SURGE PROTECTION DEVICES (SPD) PREVIOUSLY KNOWN AS (TVSS)

OPERATING MANUAL SERIES R B F BRUSHLESS RACK SYSTEM

Continental Hydraulics Installation Manual CEM-RA-A

Installation Manual February Model 752E Phase Selector Model 754E Phase Selector Model 760E Card Rack Model 759 Auxiliary Interface Panel

Variable Speed Brushed DC Motor Drive

The wireless alternative to expensive cabling...

Section 1, General information Introduction... 3 Description... 3 Specifications... 4 Wiring connections... 5

Starbox. Installation guide

Signet 8900 Multi-Parameter Controller

Series R48 Single Zone Load Sequenced Economizer System: Installation & Troubleshooting

Power supply CP-D 24/1.3

Technical description MT24. User manual WARNING GENERAL INSTRUCTIONS GENERAL DESCRIPTION

R7426A. MicroniK 200 TEMPERATURE CONTROLLER WITH AND WITHOUT REAL-TIME CLOCK

Provides line voltage capable single Pole Double-Throw (SPDT) switch and 140Ω, 1KΩ, 2KΩ or 10KΩ feedback potentiometric.

Continental Hydraulics Installation Manual CEM-PA-A

TECH/DATA SHEET. Application. Model Chart. slon-5. slon-6. slon Fan Coil Controller INSTALLATION. Inspection

ADC5000 SERIES. AC/DC Switch Mode Power Supplies and Rectifiers for Industrial and Telecom Applications. 60W, 125W and 250 W

Product overview. Features. Product specifications. Order codes. 1kΩ Resistance Output Module

Power Supplies 3. SDN-C Compact DIN Rail Series

Transcription:

Excel 0 W776A Remote Input/Output Device INSTALLATION INSTRUCTIONS PRODUCT DESCRIPTION The W776A Remote Input/Output (RIO) Device is a Free Topology Transceiver (FTT) LonMark compliant device in the Excel 0 family product line. This device can be used to monitor/control HVAC equipment, lighting, and other miscellaneous loads in a distributed network. The device is field-mounted to the equipment that it controls, and the device wiring is attached to the screw terminals located on the device (see Fig. ). The W776A Device communicates via the 78 kilobaud Echelon LonWorks E-Bus Network. For the W776A, any hardware driven by the Triac outputs must have a minimum current draw, when energized, of 5 ma and a maximum current draw of 500 ma. 3 30 9 8 7 6 5 4 3 0 9 8 7 6 DI-4 DI-3 DI- DI- VAC 4 4 VAC 3 COM 4 5 6 7 8 E NOT NOT USED USED AI- AI- AI-3 A-4 AI-5 V/mA AI-6 V/mA VDC 3 4 5 6 7 8 9 0 3 4 5 J3 M573 Fig.. Excel 0 W776A Remote I/O Device. Put Bar Code Here 95-7539 0

EXCEL 0 W776A REMOTE INPUT/PUT DEVICE INSTALLATION Mount the W776A in a position that allows clearance for wiring, servicing, and device removal. Avoid mounting the W776A in areas where acid fumes or other deteriorating vapors can attack the metal parts of the device, or where escaping gas or other explosive vapors are present. See Fig. for mounting dimensions. Use screws appropriate for the mounting surface. The W776A can be mounted in any orientation. Ventilation openings were designed into the cover to allow proper heat dissipation regardless of the mounting orientation. The W776A can also be mounted using DIN rail (obtain locally). If using DIN rail also purchase from Augat Inc. part number TKD DIN rail (adapter) two each (see Fig. 3). The enclosure on the W776A is constructed of a sheet metal housing and a plastic factory-snap-on cover. The device mounts using two screws inserted through the plastic cover. -/8 (54) 3 30 9 8 7 6 5 4 3 0 9 8 7 6 4 4 VAC 3 4 5 6 7 8 DI-4 DI-3 DI- DI-VAC COM 5-5/8 (43) E NOT USED NOT USED AI- AI- AI-3 AI-4 AI-5 V/mA AI-6 VDC V/mA 3 4 5 6 7 8 9 0 3 4 5 J3 3-/6 (77) 5-3/6 (3) 6 (5) M574 Fig.. W776A mounting dimensions in in. (mm). 95-7539 0

EXCEL 0 W776A REMOTE INPUT/PUT DEVICE 3 Power The 4 Vac power from an energy limited Class II Power Source must be provided to each W776A Device. To conform to Class II restrictions, transformers must not be larger than 00 VA (U.S. only). A transformer that meets CE mark requirements and that meets the Low Voltage Directive (LVD) requirements must be used in Europe for all installations of this product. More than one W776A can be powered by a single transformer. Fig. Fig. 4 shows power wiring details for a single device and Fig. 5 depicts multiple devices using one transformer. WIRING Fig. 3. W776A DIN rail mounting. All wiring must comply with applicable electrical codes and ordinances or as specified on installation wiring diagrams. Device wiring on the W776A is terminated to the screw terminal blocks located on the top and the bottom of the device. NOTES: For multiple devices operating from a single transformer, the same side of the transformer secondary must be connected to the same power input terminal in each device. The ground terminal ( on the W776A) must be connected to a verified earth ground for each device in the group (see Fig. 5). Device configurations are not necessarily limited to three devices, but the total power draw including accessories cannot exceed 00 VA when powered by the same transformer (U.S. only). See System Engineering form 74-699 for power wiring recommendations. All loads on an Excel 0 W776A Device must be powered by the same transformer that powers the Excel 0 RIO Device. Keep the earth ground connection (terminal ) wire run as short as possible (refer to Fig. 9 through 3). Do not connect the analog or digital ground terminals (5, 8,, 7 and 30) to earth ground (refer to Fig. 9 through 3). M6857 IMPORTANT Use the heaviest gauge wire available, up to 4 AWG (.0 mm ) with a minimum of 8 AWG (.0 mm), for all power and earth ground wiring. Screw type terminal blocks are designed to accept up to two 4 AWG (.0 mm) conductors, one on each side of the terminal screw. More than two wires that are 4 AWG (.0 mm ) can be connected with a wire nut. Include a pigtail with this wire group and attach the pigtail to one side of the terminal block. NOTES: Unswitched 4 Vac power wiring can be run in the same conduit as the E-Bus cable. Maintain at least a three-inch (76 mm) separation between Triac outputs and E-Bus wiring throughout the installation. TRANSFORMER CONNECT POWER TO TERMINALS 4 AND 5 W776A EARTH GROUND PUT DEVICE POWER 54 TRIAC LINES TO ACTUATORS AND CONTACTORS M569 Fig. 4. Power wiring details for one Excel 0 per transformer. 0 3 95-7539 0

EXCEL 0 W776A REMOTE INPUT/PUT DEVICE TRANSFORMER 0/40 VAC W776A W776A W776A 54 54 54 EARTH GROUND EARTH GROUND EARTH GROUND M570 Fig. 5. Power wiring details for two or more Excel 0s per transformer. See the following IMPORTANT on Heating and Cooling Equipment (UL 995, U.S. only). IMPORTANT If the W776 Device is used on Heating and Cooling Equipment (UL 995, U.S. only) and the transformer primary power is more than 50 volts, connect the transformer secondary to earth ground (see Fig. 6). For these applications, only one Excel 0 device can be powered by each transformer. LINE VOLTAGE GREATER THAN 50 VAC TRANSFORMER EARTH GROUND EARTH GROUND W776A IF THE W7750 CONTROLLER IS USED IN UL 995 EQUIPMENT AND THE PRIMARY POWER IS MORE THAN 50 VOLTS, GROUND ONE SIDE OF TRANSFORMER SECONDARY. M57 Fig. 6. Transformer power wiring details for one Excel 0 used in UL 995 equipment (U.S. only). Communications Refer to E-Bus Wiring Guidelines, form 74-865, for a complete description of E-Bus network topology rules. Approved cable type for E-Bus communications wiring is Level IV AWG (0.34 mm ) plenum or non-plenum rated unshielded, twisted pair, solid conductor wire. For nonplenum areas, U.S. part AK378 (one pair) or U.S. part AK378 (two pair) can be used. In plenum areas, U.S. part AK379 (one pair) or U.S. part AK379 (two pair) can be used. Communications wiring can be run in a conduit, if needed, with non-switched 4 Vac or sensor wiring. If a longer E-Bus network is required, a Q7740A -way or Q7740B 4-way repeater can be added to extend the length of the E-Bus. Also a Q775A Router can be added to partition the system into two segments and effectively double the length of the E-Bus. Only one router is allowed with each Excel 0 Zone Manager, and each network segment can have a maximum of one repeater. Pull the cable to each device on the E-Bus and connect to communication terminals 4 and 5 on the W776A. IMPORTANT Notes on Communications Wiring: All field wiring must conform to local codes and ordinances (or as specified on the installation drawings). Approved cable types for E-Bus communications wiring are Level IV AWG (0.34 mm ) plenum or non-plenum rated unshielded, twisted pair, solid conductor wires. For nonplenum areas, U.S. part AK378 (one pair) or U.S. part AK378 (two pair) can be used. In plenum areas, U.S. part AK379 (one pair) or U.S. part AK379 (two pair) can be used. Unswitched 4 Vac power wiring can be run in the same conduit as the E-Bus cable. Do not bundle output wires with sensor, digital input or communications E-Bus wires. 95-7539 0 4

EXCEL 0 W776A REMOTE INPUT/PUT DEVICE Do not use different wire types or gauges on the same E-Bus segment. The step change in line impedance characteristics would cause unpredictable reflections on the E-Bus. When using different wire types is unavoidable, use a Q775A Router at the junction. In noisy (high EMI) environments, avoid wire runs parallel to noisy power cables, motor control centers, or lines containing lighting dimmer switches, and keep at least 3 in. (76 mm) of separation between noisy lines and the E-Bus cable. Each daisy-chained E-Bus segment that is on one side of a Q775A,B Router (can contain up to 60 Excel 0s) and has a length greater than 640 ft. (500m) must have two E-Bus 0954B Termination Modules, one at each end of the daisy-chain wiring run. Make sure that neither of the E-Bus wires is grounded. NOTE: NOTE: If a 0954B Termination Module is required at a the RIO device, connect two of the three termination module wires to the E-Bus terminals. Selecting the appropriate two wires depends on the E-Bus network topology. Refer to the E-Bus Wiring Guidelines, form 74-865, and the Excel 0 FTT Termination Module Installation Instructions, form 95-7554. For example, using a doubly terminated daisy-chained bus topology, if devices are on either end of an E-Bus wire run, mount the termination module on the appropriate terminals as shown in Fig. 7. When two or more wires are to be attached to the same terminal, other than 4 AWG (.0 mm), be sure to twist them together. Deviation from this rule can result in improper electrical contact (see Fig. 8). W776A W776A W776A 45 45 45 BROWN ORANGE PART NO. 0954B TERMINATION MODULE PART NO. 0954B TERMINATION MODULE BROWN ORANGE M57 Fig. 7. Termination modules (place a wire nut on each remaining wire that is not connected to a controller or device). Wire to the terminal blocks as follows:. For single conductors being inserted into one terminal location, strip 3/8 in. (5 mm) of insulation from the conductor.. Insert the wire in the required terminal location and tighten the screw to complete the termination. 3. If two or more wires are being inserted into one terminal location, strip / in. (3 mm) of insulation from the conductors then twist the wires together a minimum of three turns before inserting them. 4. Cut the twisted end of the wires to 3/6 in. (5 mm) before inserting them into the terminal and tightening the screw. 5. Pull on each wire in all terminals to check for good mechanical connection. Wiring Details The W776A Device has the terminal arrangement shown in Fig. 9 through 3. Connection for operator access to the E-Bus is provided by plugging the Serial LonTalk Adapter (SLTA) connector into the E-Bus jack. NOTE: If an Excel 0 W776A Device or a Zone Manager is not connected to a good earth ground, the device internal transient protection circuitry is compromised and the function of protecting the device from noise and power line spikes cannot be fulfilled. This can result in a damaged circuit board and require replacement of the device. Refer to installation diagrams for specific wiring. 5 95-7539 0

EXCEL 0 W776A REMOTE INPUT/PUT DEVICE TWO 4 AWG (.0 MM ) WIRES 3/8 (0). STRIP 3/8 IN. (0 MM) FROM WIRES. TWIST WIRES TOGETHER TO BE ATTACHED AT ONE TERMINAL. WITH PLIERS (A MINIMUM OF THREE TURNS). 3. CUT TWISTED END OF WIRES TO 3/6 IN. (5 MM) BEFORE INSERTING INTO TERMINAL AND TIGHTENING SCREW. THEN PULL ON EACH WIRE IN ALL TERMINALS TO CHECK FOR GOOD MECHANICAL CONNECTION. M0086 Fig. 8. Attaching two or more wires at terminal blocks. 3 30 9 8 7 6 5 4 3 0 DI-4 DI-3 DI- DI- COM 3 4 9 8 7 6 5 6 7 8 + - 3 30 9 8 7 6 5 4 3 0 DI-4 DI-3 DI- DI- COM 3 4 9 8 7 6 5 6 7 8 W776A REMOTE I/O DEVICE TRIAC EQUIVALENT CIRCUIT W776A REMOTE I/O DEVICE TRIAC EQUIVALENT CIRCUIT E AI- AI- AI-3 3 4 5 6 7 8 AI-4 AI-5 V/mA AI-6 V/mA VDC 9 0 3 4 5 J3 E AI- AI- AI-3 3 4 5 6 7 8 AI-4 AI-5 V/mA AI-6 V/mA VDC 9 0 3 4 5 J3???? 3 4 EARTH GROUND WIRE LENGTH SHOULD BE HELD TO A MINIMUM. USE THE HEAVIEST GAUGE WIRE AVAILABLE, UP TO 4 AWG (.O MM ) WITH A MINIMUM OF 8 AWG (.O MM ), FOR EARTH GROUND WIRE. TO ASSURE PROPER ELECTRICAL CONTACT, WIRES MUST BE TWISTED TOGETHER BEFORE INSERTION INTO THE TERMINAL BLOCK. M575 SENSOR NET NET TR-J WALL MODULE M963 Fig. 9. W776A device wiring diagram. (For note, refer to Fig. 8.) Fig. 0. Typical T7770B and C7770A wiring diagram. (For note, refer to Fig. 8.) 95-7539 0 6

EXCEL 0 W776A REMOTE INPUT/PUT DEVICE MMC35 PNEUMATIC TRANSDUCER M WINDOW CONTACT (CONTACT CLOSED = WINDOW CLOSED) 4 (H) 4 (N) 4 (H) 4 (N) INCREASE DECREASE M B 4 OCCUPANCY SENSOR (CONTACT CLOSED = OCCUPIED) 3 30 9 8 7 6 5 4 3 0 DI-4 DI-3 DI- DI- COM + - 3 4 9 8 7 6 5 6 7 8 3 30 9 8 7 6 5 4 3 0 DI-4 - + DI-3 DI- DI- 3 COM 3 4 PNEUMATIC VALVE 9 8 7 6 5 6 7 8 W776A REMOTE I/O DEVICE TRIAC EQUIVALENT CIRCUIT W776A REMOTE I/O DEVICE TRIAC EQUIVALENT CIRCUIT E AI- AI- AI-3 3 4 5 6 7 8 AI-4 AI-5 V/mA AI-6 V/mA VDC 9 0 3 4 5 J3 E AI- AI- AI-3 3 4 5 6 7 8 AI-4 AI-5 V/mA AI-6 V/mA VDC 9 0 3 4 5 J3 5 EARTH GROUND WIRE LENGTH SHOULD BE HELD TO A MINIMUM. USE THE HEAVIEST GAUGE WIRE AVAILABLE, UP TO 4 AWG (.O MM ) WITH A MINIMUM OF 8 AWG (.O MM ), FOR EARTH GROUND WIRE. TO ASSURE PROPER ELECTRICAL CONTACT, WIRES MUST BE TWISTED TOGETHER BEFORE INSERTION INTO THE TERMINAL BLOCK. M577 3 4 REVERSE WIRES (INCREASE/DECREASE) TO REVERSE ACTION (DIRECT/REVERSE). MAKE SURE ALL TRANSFORMER/POWER WIRING IS AS SHOWN: REVERSING TERMINATIONS WILL RESULT IN EQUIPMENT MALFUNCTION. OPTIONAL WIRING TO NEXT CONTROLLER. USE /4 IN (6 MM) PNEUMATIC TUBING. MINIMUM BRANCH LINE MUST BE 6 FT. (.8M) OR LONGER. Fig.. Occupancy sensor wiring diagram. (For note, refer to Fig. 8.) 5 EARTH GROUND WIRE LENGTH SHOULD BE HELD TO A MINIMUM. USE THE HEAVIEST GAUGE WIRE AVAILABLE, UP TO 4 AWG (.O MM ) WITH A MINIMUM OF 8 AWG (.O MM ), FOR EARTH GROUND WIRE. M578 Fig.. Typical pneumatic transducer to W776A. 7 95-7539 0

EXCEL 0 W776A REMOTE INPUT/PUT DEVICE 3 30 9 8 7 6 5 4 3 0 DI-4 E W776A REMOTE I/O DEVICE 3 4 5 6 7 8 - + PWM VALVE ACTUATOR ML7984B 4 (H) 4 (N) DI-3 DI- AI- PWM (H ) PWM PUT FROM CNTRL T6 T5 C B W R DI- AI- AI-3 COM AI-4 EARTH GROUND WIRE LENGTH SHOULD BE HELD TO A MINIMUM. USE THE HEAVIEST GAUGE WIRE AVAILABLE, UP TO 4 AWG (.O MM ) WITH A MINIMUM OF 8 AWG (.O MM ), FOR EARTH GROUND WIRE. TO ASSURE PROPER ELECTRICAL CONTACT, WIRES MUST BE TWISTED TOGETHER BEFORE INSERTION INTO THE TERMINAL BLOCK. M579 Fig. 3. Typical PWM Valve Actuator and Fan to W776A. (For note, refer to Fig. 8.) AI-5 V/mA 3 LINE POWER FAN CONTACTOR () 4 AI-6 V/mA 9 8 7 6 5 VDC 9 0 3 4 5 J3 6 7 TRIAC EQUIVALENT CIRCUIT 8???? CHECK W776A Checkout Step. Check Installation and Wiring Inspect all wiring connections at the W776A terminals, and verify compliance with installation wiring diagrams. If any wiring changes are required, first be sure to remove power from the device before starting work. Pay particular attention to: 4 Vac power connections. Verify that multiple devices powered by the same transformer are wired with the transformer secondary connected to the same input terminal numbers on each W776A (see Fig. 5). (Device configurations are not necessarily limited to three devices, but the total power draw including accessories cannot exceed 00 VA when powered by the same transformer (U.S. only). See System Engineering form, 74-699, for power wiring recommendations. Device wiring. Be sure that each device is wired (terminal ) on the W776A to a verified earth ground using a wire run as short as possible with the heaviest gauge wire available, up to 4 AWG (.0 mm) with a minimum of 8 AWG (.0 mm) for each device in the group (see Fig. 4). Verify Triac wiring to external devices uses the proper load power/4 Vac hot terminal (terminal 5 on the W776A). NOTE: All wiring must comply with applicable electrical codes and ordinances or as specified on installation wiring diagrams. VERIFY TERMINATION MODULE PLACEMENT The installation wiring diagrams should indicate the locations for placement of 0954B Termination Module(s). Refer to the E-Bus Wiring Guidelines form, 74-865, and the Excel 0 FTT Termination Module Installation Instructions form, 95-7554. Correct placement of the termination module(s) is required for proper E-Bus communications. Step. Startup W776A DEVICE STATUS LED The LED on the front and center of a W776A Device provides a visual indication of the status of the device (see Fig. 4). When the W776A receives power, the LED should appear in one of the following allowable states:. Off no power to the processor.. Continuous On processor is in initialized state. 3. Slow Blink controlling, normal state. 4. Fast Blink when the Excel 0 has an alarm condition. 95-7539 0 8

EXCEL 0 W776A REMOTE INPUT/PUT DEVICE W776A 3 30 9 8 7 6 5 4 3 0 9 8 7 6 DI-4 DI-3 DI- DI- VAC 4 4 VAC COM 3 4 5 6 7 8 There is one method of broadcasting the Service Message from an Excel 0 W776A Device. This uses a hardware button on the side of the device (see Fig. 5). When an Assign ID command is issued from the commissioning tool, the node goes into the SERVICE_MESSAGE mode for five minutes. In the SERVICE_MESSAGE mode, pressing the service pin on the device or the bypass button on a wall module causes the Service Message to be broadcast on the network. All other functions are normal in the SERVICE_MESSAGE mode. SERVICE PIN BUTTON E NOT NOT USED USED AI- AI- AI-3 A-4 AI-5 V/mA AI-6 V/mA VDC 3 4 5 6 7 8 9 0 3 4 5 J3 STATUS LED M580 Fig. 4. LED location on W776A. ALARMS When an Excel 0 has an alarm condition, it reports it to the central node on the E-Bus (typically the Excel 0 Zone Manager or Small Building Controller). See Table. The information contained in an alarm message follows. Subnet Number: This is the E-Bus subnet that contains the Excel 0 node that has the alarm condition. Subnet is on the Zone Manager side of the router; Subnet is on the other side. Node Number: This is the Excel 0 node that has the alarm condition (see Network Statics). Alarm Type: The specific alarm being issued. An Excel 0 can provide the alarm types listed in Table. NOTE: The node can be reset by switching the node to MANUAL and then switching to the normal operating mode (using DestManMode). Also, the Excel 0 variables, AlarmLogX, where X is through 5, that store the last five alarms to occur in the device, are available. These points can be viewed through XBS, XI584 or E-Vision. Broadcasting the Service Message The Service Message allows a device on the E-Bus to be positively identified. The Service Message contains the device ID number and, therefore, can be used to confirm the physical location of a particular Excel 0 in a building. Fig. 5. Location of the service pin button. Step 3. I/O Tests M0094 The device must be configured using the Excel 0 E-Vision PC configuration tool. Once this is done, the W776A can be commanded to MANUAL mode, and each output can be exercised/viewed to verify proper wiring connections and equipment operation. See the Excel 0 E-Vision Users Guide form, 74-588, for details on configuring and testing W776A Devices. Step 4. Verify Sequences of Operation For the detailed descriptions of the sequences of operation, see the Excel 0 RIO System Engineering form, 74-699 Appendix B. 9 95-7539 0

EXCEL 0 W776A REMOTE INPUT/PUT DEVICE Table. Excel 0 Alarms. Name of alarm or error bit Alarm type number Meaning of alarm code or error bit NO_ALARM 0 No alarms presently detected. INPUT_NV_FAILURE One or more NV inputs have failed while receiving an update within their specified FAILURE_DETECT_TIME. NODE_DISABLED The control algorithm stopped because the device is in DISABLED_MODE, or FACTORY_TEST mode. The control is shut down and disabled until power is cycled or the node is reset. See NOTE below. SENSOR_FAILURE 3 One or more sensors have failed. RETURN_TO_NORMAL 8 Return to no alarm after being in an alarm condition. This code is added numerically to another alarm code to indicate that the alarm condition has returned to normal. ALARM_NOTIFY_DISABLED 55 The alarm reporting was turned off by the nvimanualmode. No more alarms are reported until nvimanualmode turns on alarm reporting or upon application restart. 95-7539 0 0

EXCEL 0 W776A REMOTE INPUT/PUT DEVICE 95-7539 0

EXCEL 0 W776A REMOTE INPUT/PUT DEVICE Automation and Control Solutions Honeywell International Inc. Honeywell Limited-Honeywell Limitée 985 Douglas Drive North 35 Dynamic Drive Golden Valley, MN 554 Toronto, Ontario MV 4Z9 Honeywell GmbH Böblinger Straße 7 D-70 Schönaich customer.honeywell.com U.S. Registered Trademark 009 Honeywell International Inc. 95-7539 0 K.K. Rev. 06-09