TD-100. HAEFELY HIPOTRONICS Technical Document

Similar documents
TD-106. HAEFELY HIPOTRONICS Technical Document. Partial Discharge Pulse Shape Analysis to Discriminate Near and Far End Failures for Cable Location

Evaluation and Limitations of Corona Discharge Measurements An Application Point of View

GENERATOR TESTING APPLICATION GUIDE. reliable. precision.

700 Series AC Dielectric Test Sets

KIT 4.0 HIGH VOLTAGE CONSTRUCTION KIT. reliable. precision. HIGH V O L T A G E T E S T S OLUTION S

EFFECT OF INTEGRATION ERROR ON PARTIAL DISCHARGE MEASUREMENTS ON CAST RESIN TRANSFORMERS. C. Ceretta, R. Gobbo, G. Pesavento

Modular Partial Discharge (PD) & Radio Interference Voltage (RIV) Detector

TRAINING OVERVIEW EDUCATION IS POWER. HIGH V O L T A G E T E S T S OLUTION S. reliable. precision.

TTR2796. Fully Automated Three Phase 250V Transformer Turns Ratio Meter FEATURES AND BENEFITS APPLICATIONS

Mitigating Murphy s Law While Test. Frédéric Dollinger

SG A. Impulse Voltage Test System, kv / kj APPLICATION

Practical aspects of PD localization for long length Power Cables

CABLE FAULT LOCATING APPLICATION GUIDE. HIGH V O L T A G E T E S T S OLUTION S. reliable. precision.

Harmonic Filtering in Variable Speed Drives

Fully automated three phase 250V Transformer Turns Ratio Meter

Automatic Transformer Winding Analyser

TMS 580. Transformer Loss Measuring System FEATURES BENEFITS APPLICATIONS

CHAPTER 4 MEASUREMENT OF NOISE SOURCE IMPEDANCE

Dev Bhoomi Institute Of Technology Department of Electronics and Communication Engineering PRACTICAL INSTRUCTION SHEET REV. NO. : REV.

MIDAS 2881 / 2881G. Mobile Insulation Diagnosis & Analysing System

Non-ideal Behavior of Electronic Components at High Frequencies and Associated Measurement Problems

Sirindhorn International Institute of Technology Thammasat University

TUNED AMPLIFIERS 5.1 Introduction: Coil Losses:

ECE 4670 Spring 2014 Lab 1 Linear System Characteristics

Analysis of Laddering Wave in Double Layer Serpentine Delay Line

Impact of the Output Capacitor Selection on Switching DCDC Noise Performance

AC Dielectric Test Sets

Time Domain Reflectometry (TDR) and Time Domain Transmission (TDT) Measurement Fundamentals

Background (What Do Line and Load Transients Tell Us about a Power Supply?)

Investigation of PD Detection on XLPE Cables

Improving CDM Measurements With Frequency Domain Specifications

2. BAND-PASS NOISE MEASUREMENTS

High Frequency Modeling of Two Limb Series Loop Winding for Partial Discharge Localization

Filter Considerations for the IBC

A Prototype Wire Position Monitoring System

Chapter 2. The Fundamentals of Electronics: A Review

Transmit filter designs for ADSL modems

University Tunku Abdul Rahman LABORATORY REPORT 1

Linear Time-Invariant Systems

HiAS TM 744 HIGHEST RESOLUTION IMPULSE ANALYZING SYSTEM

THE PROPAGATION OF PARTIAL DISCHARGE PULSES IN A HIGH VOLTAGE CABLE

CHAPTER 2 EQUIVALENT CIRCUIT MODELING OF CONDUCTED EMI BASED ON NOISE SOURCES AND IMPEDANCES

Experiment 2: Transients and Oscillations in RLC Circuits

MODEL 5002 PHASE VERIFICATION BRIDGE SET

Long lengths transmission power cables on-site testing up to 500 kv by damped AC voltages

Electronics EECE2412 Spring 2016 Exam #1

Transmit filter designs for ADSL modems

OPEN TEM CELLS FOR EMC PRE-COMPLIANCE TESTING

Comparison of IC Conducted Emission Measurement Methods

MODELLING & SIMULATION OF ACTIVE SHUNT FILTER FOR COMPENSATION OF SYSTEM HARMONICS

Mechatronics. Analog and Digital Electronics: Studio Exercises 1 & 2

DC current interruption tests with HV mechanical DC circuit breaker

1.Explain the principle and characteristics of a matched filter. Hence derive the expression for its frequency response function.

Evaluation Board Analog Output Functions and Characteristics

CVVOZE Power Laboratories (CVVOZEPowerLab)

The University of New South Wales. School of Electrical Engineering and Telecommunications. High Voltage Systems ELEC9712. Appendix Partial Discharge

Module 5. DC to AC Converters. Version 2 EE IIT, Kharagpur 1

Testing Power Sources for Stability

OPEN TEM CELLS FOR EMC PRE-COMPLIANCE TESTING

HARMONIC contamination, due to the increment of nonlinear

University of Jordan School of Engineering Electrical Engineering Department. EE 219 Electrical Circuits Lab

Non-linear Control. Part III. Chapter 8

AN IMPROVED MODULATION STRATEGY FOR A HYBRID MULTILEVEL INVERTER

Implementation of Orthogonal Frequency Coded SAW Devices Using Apodized Reflectors

Laboratory Project 4: Frequency Response and Filters

Distribution Transformer Random Transient Suppression using Diode Bridge T-type LC Reactor

LINEAR MODELING OF A SELF-OSCILLATING PWM CONTROL LOOP

Department of Electronics &Electrical Engineering

Advanced Digital Signal Processing Part 2: Digital Processing of Continuous-Time Signals

SHF Communication Technologies AG. Wilhelm-von-Siemens-Str. 23D Berlin Germany. Phone Fax

Alternative Coupling Method for Immunity Testing of Power Grid Protection Equipment

ET1210: Module 5 Inductance and Resonance

NEW MV CABLE ACCESSORY WITH EMBEDDED SENSOR TO CHECK PARTIAL DISCHARGE ACTIVITY

Synthesis of general impedance with simple dc/dc converters for power processing applications

EXPERIMENT 1: Characteristics of Passive and Active Filters

Reprint E Two Years of Experience with a Mobile Resonant Test System for Testing of Installed Medium- and High Voltage Power Cables

EMI Noise Prediction for Electronic Ballasts

EK307 Passive Filters and Steady State Frequency Response

Design of an Evanescent Mode Circular Waveguide 10 GHz Filter

UNIT 2. Q.1) Describe the functioning of standard signal generator. Ans. Electronic Measurements & Instrumentation

Department of Mechanical and Aerospace Engineering. MAE334 - Introduction to Instrumentation and Computers. Final Examination.

Basics of Partial Discharge. Prepared for 2015 Phenix RSM Meeting January 2015

The steeper the phase shift as a function of frequency φ(ω) the more stable the frequency of oscillation

Parallel Resonance Effect on Conducted Cm Current in Ac/Dc Power Supply

Homework Assignment 03

Modeling and Simulation of Paralleled Series-Loaded-Resonant Converter

Utilizzo del Time Domain per misure EMI

10 Mb/s Single Twisted Pair Ethernet PHY Coupling Network Steffen Graber Pepperl+Fuchs

FAULT IDENTIFICATION IN TRANSFORMER WINDING

Modeling of an EMC Test-bench for Conducted Emissions in Solid State Applications

Constant Current Control for DC-DC Converters

Input Impedance Measurements for Stable Input-Filter Design

Prediction of Transient Transfer Functions at Cable-Transformer Interfaces

IEC Electrical fast transient / Burst immunity test

Transmission Line Transient Overvoltages (Travelling Waves on Power Systems)

ANALYSIS OF BROADBAND GAN SWITCH MODE CLASS-E POWER AMPLIFIER

P a g e 1 ST985. TDR Cable Analyzer Instruction Manual. Analog Arts Inc.

CHAPTER 5 CONCEPT OF PD SIGNAL AND PRPD PATTERN

INVESTIGATION ON THE TECHNOLOGIES FOR DEFECT LOCALIZATION AND CHARACTERIZATION ON MEDIUM VOLTAGE UNDERGROUND LINES

)454 / 03/0(/-%4%2 &/2 53% /. 4%,%0(/.%490% #)2#5)43 30%#)&)#!4)/.3 &/2 -%!352).' %15)0-%.4 %15)0-%.4 &/2 4(% -%!352%-%.4 /&!.!,/'5% 0!2!

Transcription:

HAEFELY HIPOTRONICS Technical Document Breaking the limit of power capacitor resonance frequency with help of PD pulse spectrum to check and setup PD measurement P. Treyer, P. Mraz, U. Hammer, S. Gonzalez Haefely Hipotronics, Tettex Instruments Division TD-100

The 19 th International Symposium on High Voltage Engineering, Pilsen, Czech Republic, August, 23 28, 2015 BREAKING THE LIMIT OF POWER CAPACITOR RESONANCE FREQUENCY WITH HELP OF PD PULSE SPECTRUM TO CHECK AND SETUP PD MEASUREMENT P. Treyer 1*, P. Mraz 1, U. Hammer 1 and S. Gonzalez 1 1 Haefely Test AG, Birsstrasse 300, 4052 Basel, Switzerland *Email: < treyer.patrick@haefely.com> Abstract: Partial discharge (PD) measurement is often performed without prior validation of the calibration pulse spectrum. In most cases, the correct frequency range for PD measurement is well-known but measuring the pulse spectrum is a means to verify that the PD filter limit frequencies (f 1, f 2 ) fit the quasi-integration requirement according to IEC 60270. The pulse spectrum assists to detect wrong connections and defective parts as well as to verify the efficiency of HV noise suppression filters. In case of power capacitors, the resonance frequency is an essential parameter to correctly set the PD measurement frequencies in order to achieve adequate sensitivity as well as compliance with IEC 60270. This paper covers the theory and practical information required to set the correct PD frequency range with respect to the power capacitor resonance frequency. It demonstrates that PD measurement with limit frequencies set beyond the resonance frequency of the power capacitor is possible if an identical capacitor is used as the PD coupling capacitor. Sensitivity issues when using bridge connections are discussed and PD detector and coupling impedance requirements are equally covered. 1 INTRODUCTION Partial discharge (PD) measurement requires correct setting of the PD filter limit frequencies to ensure that the quasi-integration of the PD pulses converts the measured input current into a charge in Coulombs. The Fourier transform of the impulse response of a filter directly provides the frequency response of the filter. For proper derivation of the impulse response, the input impulse should be an ideal Dirac pulse whose magnitude is defined by the pulse area, i.e. amplitude pulse width. The peak magnitude of the filter output is proportional to this Dirac pulse area. However, the result is equally valid as long as the spectrum of the measured pulse slightly exceeds the filter bandwidth (BW). In that case the peak value reflects the measured pulse area, effectively integrating the pulse current. Thus, it is recommended that at least the PD calibration pulse spectrum is checked to satisfy the mentioned requirement. Ideally some of the effectively occurring PD events should be checked likewise in order to ensure that the measurement is valid independent of the effective propagation path of the PD pulse in the test object. When defining an industrial PD testing environment for a fixed product line, it is presumed that the checks described above are conducted at least once and there would be no need to regularly repeat those checks. However, when considering power capacitors even minor changes in the test setup and improvements or modifications to the manufacturing process of the test object can have a huge impact on the PD measurement. The root cause is linked to the resonance frequency f R of the capacitor and to the fact that each centimeter of wiring in the measuring circuit has to be taken into account for correct measurement results. This paper covers these topics and discusses PD measurement of power capacitor at frequencies beyond the capacitor resonance. 2 SELECTING PD FILTER FREQUENCY RANGE 2.1 Impulse response and quasi-integration IEC 60270 [1] as well as the accompanying guide ([2], Figure 18) are based on the assumption that PD measurement is valid as long as the PD pulse spectrum exceeds the upper limit frequency f 2 of the PD detector filter. However, additional characteristics like the amount of error introduced to the measurement when the PD pulse spectrum is close to f 2 as well as potential resonances within the measuring BW are needed to ensure correct measurement setup [3]. It is important to notice that the relevant PD pulse spectrum is the one of the original current pulse in the measuring impedance R M as illustrated in Figure 1. The measuring impedance and analog filters used to suppress power electronics switching noise are part of the PD detector filter and do not change the PD pulse BW to be considered for quasiintegration.

error less than 10 %. If the PD pulse BW is lower than the filter BW then the filter output equals the input pulse magnitude and hence the filter is no longer acting as an integrator. I RM R M Peak Detector PD Detector Figure 1: PD detector and measuring impedance R M. To explain the BW constraint for PD pulse integration we will use a first order RC filter and a rectangular pulse. Figure 3: RC filter peak output magnitude. With the help of the Taylor series expansion of the exponential function and neglecting higher order terms for sufficiently small values of the exponent, i.e. Figure 2: Rectangular pulse signal: Time domain signal g(t) (left) and spectrum magnitude G(f) (right). The Fourier transform of a rectangular pulse of magnitude A and duration T is (1) From Equation 1 the -6dB bandwidth is given by (2) For simplicity, we use a low pass filter instead of a band pass filter (Note: band pass filter synthesis is often based on conversion techniques starting from low pass filter prototypes). The -6dB BW of a first order RC filter is where τ is the RC time constant. (3) The peak magnitude of the response to a rectangular pulse according to Figure 2 is given in Equation 4.!"#$ %&' ( ) * (4) From Equations 2 4 the normalized peak magnitude of the response to the rectangular pulse can be plotted as shown in Figure 3. For example, if the rectangular pulse BW is 10 times the filter BW, the quasi-integration of the pulse results in an $ + ", + -., +/.,01112+23-455611 ",7 (5) Equation 4 can be rewritten as indicated in Equation 6 for small values of T. This reveals that the peak magnitude of the filter output is proportional to the magnitude-time area of the pulse, i.e. proportional to the integral of the pulse waveform. - (6) Note that for T >> τ the peak output of the filter is equal to the peak magnitude of the pulse, i.e.. In that case the pulse spectrum cut-off frequency is significantly smaller than the -6dB BW of the filter and hence the current pulse is no longer correctly integrated. Instead of the pulse charge the pulse current amplitude is misleadingly measured. 2.2 Practical higher order filters The first order filter examined in the previous section is the most stringent in terms of PD pulse BW constraints. Higher order filters permit the use of lower -6dB BW ratios for the PD pulse and filter. This can be either estimated or experimentally verified with a rectangular pulse similar to the one used in Section 2.1. 2.2.1 Estimation for Butterworth filters The required BW for Butterworth filters can be estimated according to the following equation (cf. Equation 3.5.1 in [4]):

899: ";<=>?@",% A A B ) C @ (7) where: 899: Attenuation at frequency f D -3dB cut-off frequency E Filter order Equation 7 can be solved for the frequency ratio to obtain a desired attenuation level the current through R M and the current injected by the calibrator as follows: N OP WAX G (9) N QRSTUV WAX G YX Z YX [ Y\ ] LW 100n /K A F "; G899:1&1H IJ #" A B (8) I_PD_CAL LA 100n CA 1u LK 100n CK 1u Note that D in Equation 8 denotes the -6dB cut-off frequency of the filter. For practical measurements select a L D ratio from the 20dB row in Table 1. RM 1 Table 1: L D ratio for Butterworth filters. Filter Order M 899: (db) 1 2 4 6 6 1 1 1 1 20 7.0 2.6 1.6 1.4 40 70.8 8.4 2.9 2.0 T 0.00-10.00-20.00 Gain (db) -30.00-40.00-50.00 2.2.2 Rectangular pulse measurement Each type of filter implementation will have a different response characteristic, hence the filters are preferably tested using a rectangular pulse. The rectangular pulse must be of constant area A T. The pulse duration T should be increased until the allowed drop in the PD reading is reached. At this point the required BW for the PD spectrum can be calculated from Equation 2. 2.3 Capacitor resonance frequency and impedance In the present work, as opposed to the impulse analysis we have developed in [5], we will use a swept frequency analysis to focus on the PD pulse spectrum. The frequency analysis benefits from simple simulation and comparison to measurements. The top of Figure 4 is the circuit diagram for the well-known PD test setup described in IEC 60270 [1] where we have replaced the test object and coupling capacitors (C A, C K ) by their equivalent LC model. The calibrator is modeled by an ideal swept-frequency current generator which is used to record the frequency spectrum of the current flowing in the measuring impedance R M. The remaining circuit elements are the test object inductance L A, the coupling capacitor inductance L K and the wiring inductance L W. Based on the circuit diagram in Figure 4 and for frequencies higher than the resonance frequency f R of the capacitor (i.e. neglecting C A and C K, respectively) we can calculate the ratio between -60.00-70.00 0 250k 500k 750k 1M Frequency (Hz) Figure 4: IEC test setup with capacitor model (top) and corresponding frequency response (bottom). Equation 9 describes a first order system with a single pole and zero. For frequencies well above the pole frequency, i.e. ^ \ ] X G YX Z YX [ Equation 9 can be simplified as follows: N OP X G _ ] (10) N QRSTUV X G YX Z YX [ _ G Hence, for frequencies above the resonance frequency of the test object the PD sensitivity factor, i.e. the ratio of the measured charge to the injected charge, is exclusively defined by the circuit inductances. The equivalent PD sensitivity for the standard IEC test setup based on C A and C K (as described e.g. in [3], Equation 2) can be expressed as: _ ] _ G D Z D G YD Z (11) Equations 10 and 11 implicate the measured charge q M is proportional to the injected charge q A as long as the measurement frequency band is selected significantly below or significantly above the resonance frequency of the test object capacitor. The PD sensitivity in the inductive region

of the capacitor frequency response (i.e. f > f R ) is lower than in the capacitive region (see Figure 4, bottom). This effect is caused by the wiring inductance L W, which cannot be neglected and is usually equal to or larger than L A. Figures 5 and 6 further illustrate the high pass and low pass filtering effects due to the measuring impedance R M. hand side is the test object (a 4.4µF-440V film capacitor), the black capacitor on the left hand side is the coupling capacitor. The PD calibrator connectors are directly applied across the test object using crocodile clamps. The large clamp in the lower left of the figure is used for ground connection and two metal bars are employed for reduced wiring inductance L W. LW 100n I_PD_CAL CA 1u CK 1u LA 100n LK 100n I_PD_CAL RM 1 RM 1 T 0.00 a b T 0.00 a b -10.00 Gain (db) -5.00-10.00 Gain (db) -20.00-30.00-15.00 A:(10,21k; -6,03) B:(550,38k; -12,03) -40.00 A:(306,44k; -15,56) B:(8,33M; -9,56) -20.00 10.00k 100.00k 1.00M Frequency (Hz) Figure 5: IEC test setup below resonance (top) and corresponding frequency response (bottom). When measuring below the resonance frequency f R a lower R M value is beneficial to increasing the measurement BW. When measuring above the resonance frequency f R a lower R M value is beneficial to flatten the signal spectrum in the lower frequency range. Finally, to improve the q M /q A sensitivity factor, the wiring must be as short as possible and the value of the measuring impedance R M should be maintained low. Using bridge connections is detrimental to these goals since they increase the wiring length (and thus L W ) and at the same time the equivalent R M value is doubled (because two measuring impedances are connected in series). 3 EXPERIMENTAL EXAMPLES 3.1 Below resonance frequency The given test setup in this example, allows to set the PD filter band below the capacitor resonance frequency and simultaneously fulfil the IEC requirements for the limit frequencies of the PD filter. In Figure 7, the black capacitor on the right -50.00 10.00k 100.00k 1.00M 10.00M Frequency (Hz) Figure 6: IEC test setup above resonance (top) and corresponding frequency response (bottom). The frequency response in Figure 7 (bottom) indicates a resonance frequency of about 340 khz and one can clearly recognize that the spectrum level (and hence sensitivity) is higher below than above resonance. This is in good agreement with the simulation results from Figure 4. 3.2 Above resonance frequency In the given example setup of Figure 8 it is impossible to set the PD filter band below the resonance frequency, because there is no flat area in that part of the spectrum. Therefore, the PD filter band is set above the resonance frequency of the test object (a 30µF-350V film capacitor). Even though the measurement does not perfectly comply with the IEC requirements (because the lower limit frequency f 1 is set to 250 khz) the measurement still fulfills the requirements for quasi-integration of the PD pulse. Taking this into consideration it would make sense for the IEC standard to specify a range for BW and center frequency of the PD filter but to abandon a maximum limit for the lower limit frequency f 1.

Metal bars for wiring Calibrator Connectors frequency has been demonstrated with corresponding measurement examples. Metal bars for wiring C A C K C A Ground Connection C K Ground Connection Calibrator Connectors Figure 7: 4.4µF-440V capacitor measurement setup (top) and measured frequency response of the PD calibrator pulse (bottom). The requirements for PD spectrum/filter settings developed in this paper would be a good enhancement of the IEC standard. Keeping the lower limit frequency at f 1 100 khz is particularly important e.g. for transformers as covered in [6]. The PD calibration procedure is still performed according to IEC 60270 [1] with the benefit that the PD calibrator allows the verification of the PD spectrum of the test setup. The frequency response in Figure 8 (bottom) indicates a resonance frequency of about 160 khz and again one can clearly recognize that the spectrum level is higher below than above resonance as previously observed in Figure 7. In case of (power) capacitor testing it is utterly important to connect the calibrator leads directly across the capacitor terminals. Including parasitic wiring during the PD calibration process can easily lead to calibration errors in excess of 50%. 4 CONCLUSION The critical aspects of PD pulse spectrum and filter settings to fulfil the quasi-integration requirements for PD measurement of power capacitors have been analyzed. In addition, the limitations due to the capacitor resonance frequency have been investigated. It has been demonstrated that a rectangular pulse is useful to check correct quasi-integration and that the measured spectrum is a powerful tool when measuring power capacitors. Using a swept frequency analysis the validity of PD measurement beyond the capacitor resonance Figure 8: 30uF-350V capacitor measurement setup (top) and measured frequency response of the PD calibrator pulse. Furthermore, a comparison of the measurement sensitivity below and above the resonance frequency of the test object has been conducted and the limitation of bridge connections has been explained. Part of the presented discussion can be adapted to other types of test objects to check and verify correct PD pulse integration. REFERENCES [1] IEC 60270, High-voltage test techniques Partial discharge measurements, 2000-12. [2] E. Lemke et al., Guide for partial discharge measurements in compliance to IEC60270, Cigré WG D1.33, Technical brochure 366, Electra No. 241, pp. 61-67, 2008 [3] W.S. Zaengl et al., Correlation between the bandwidth of PD detectors and its inherent integration errors, Conference Rec. of the IEEE Int. Symposium on Electrical Insulation, pp. 115-121, 1986 [4] A. I. Zverev, Handbook of Filter Synthesis, John Wiley & Sons, 2005 [5] Haefely Test AG, DDX 9121b Partial Discharge Detector, Operating Manual, V6.1 [6] IEEE C57-113, Recommended Practice for Partial Discharge Measurement in Liquid-Filled Power Transformers and Shunt Reactors, 2010

The original version of this article was published in ISH 2015 proceedings: 19th International Symposium on High Voltage Engineering, Pilsen, Czech Republic, 2015 Locate our local sales representative at www.haefely-hipotronics.com OFFICES: Europe Haefely Test AG Birsstrasse 300 4052 Basel Switzerland ( + 41 61 373 4111 6 + 41 61 373 4912 š sales@haefely.com China Haefely Test AG Representative Beijing Office 8-1-602, Fortune Street No. 67, Chaoyang Road, Chaoyang District Beijing, China 100025 ( + 86 10 8578 8099 6 + 86 10 8578 9908 š sales@haefely.com.cn North America Hipotronics, Inc. 1650 Route 22 N Brewster, NY 10509 United States ( + 1 845 279 3644 6 + 1 845 279 2467 š sales@hipotronics.com HAEFELY HIPOTRONICS has a policy of continuous product improvement. Therefore we reserve the right to change design and specification without notice.