Electrical Power and Energy Systems

Similar documents
Ferroresonance Experience in UK: Simulations and Measurements

Modeling Ferroresonance Phenomena on Voltage Transformer (VT)

2000 Mathematics Subject Classification: 68Uxx/Subject Classification for Computer Science. 281, 242.2

Comparative Performance of Conventional Transducers & Rogowski Coil for Relaying Purpose

High voltage engineering

PREVENTING FLASHOVER NEAR A SUBSTATION BY INSTALLING LINE SURGE ARRESTERS

Modeling insulation in high-voltage substations

Analysis of MOV Surge Arrester Models by using Alternative Transient Program ATP/EMTP

FGJTCFWP"KPUVKVWVG"QH"VGEJPQNQI[" FGRCTVOGPV"QH"GNGEVTKECN"GPIKPGGTKPI" VGG"246"JKIJ"XQNVCIG"GPIKPGGTKPI

Session Four: Practical Insulation Co-ordination for Lightning Induced Overvoltages

A Study on Ferroresonance Mitigation Techniques for Power Transformer

VFTO STUDIES DUO TO THE SWITCHING OPERATION IN GIS 132KV SUBSTATION AND EFFECTIVE FACTORS IN REDUCING THESE OVER VOLTAGES

Ferroresonance Signal Analysis with Wavelet Transform on 500 kv Transmission Lines Capacitive Voltage Transformers

Tab 2 Voltage Stresses Switching Transients

A Special Ferro-resonance Phenomena on 3-phase 66kV VT-generation of 20Hz zero sequence continuous voltage

Utility System Lightning Protection

FERRORESONANCE SIMULATION STUDIES USING EMTP

Accurate Current Measurement Transducer for Relaying Purpose

ABSTRACTS of SESSION 6

DEPARTMENT OF EEE QUESTION BANK

Power Quality and Reliablity Centre

ABSTRACT 1 INTRODUCTION

Research Article A Simplified High Frequency Model of Interleaved Transformer Winding

Module 2 : Current and Voltage Transformers. Lecture 8 : Introduction to VT. Objectives. 8.1 Voltage Transformers 8.1.1Role of Tuning Reactor

Calculation of Transient Overvoltages by using EMTP software in a 2-Phase 132KV GIS

Improving Current and Voltage Transformers Accuracy Using Artificial Neural Network

When surge arres t ers are installed close to a power transformer, overvoltage TRANSFORMER IN GRID ABSTRACT KEYWORDS

Ferroresonance in MV Voltage Transformers: Pragmatic experimental approach towards investigation of risk and mitigating strategy

GIS Disconnector Switching Operation VFTO Study

Lightning performance of a HV/MV substation

AORC Technical meeting 2014

10. DISTURBANCE VOLTAGE WITHSTAND CAPABILITY

Modeling for the Calculation of Overvoltages Stressing the Electronic Equipment of High Voltage Substations due to Lightning

Simulation of Lightning Transients on 110 kv overhead-cable transmission line using ATP-EMTP

TECHNICAL BULLETIN 004a Ferroresonance

The relationship between operating maintenance and lightning overvoltage in distribution networks based on PSCAD/EMTDC

Relay Protection of EHV Shunt Reactors Based on the Traveling Wave Principle

Accurate Modeling of Core-Type Distribution Transformers for Electromagnetic Transient Studies

ROEVER ENGINEERING COLLEGE ELAMBALUR, PERAMBALUR DEPARTMENT OF ELECTRICAL & ELECTRONICS ENGINEERING

DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING QUESTION BANK SUBJECT CODE & NAME : EE 1402 HIGH VOLTAGE ENGINEERING UNIT I

Research on Lightning Over-voltage and Lightning Protection of 500kV. HGIS Substation

Lightning Flashover Rate of an Overhead Transmission Line Protected by Surge Arresters

Modeling of overhead transmission lines with line surge arresters for lightning overvoltages. Poland

Transmission of Electrical Energy

Bus protection with a differential relay. When there is no fault, the algebraic sum of circuit currents is zero

Great Northern Transmission Line: Behind the (Electrical) Design

Electric Stresses on Surge Arrester Insulation under Standard and

Introduce system protection relays like underfrequency relays, rate of change of frequency relays, reverse - power flow

Experimental Investigations and Calculations in 6-35 kv Networks with Various Neutral Conditions

EE 1402 HIGH VOLTAGE ENGINEERING

Analysis of lightning performance of 132KV transmission line by application of surge arresters

Parameter Study of Ferro-Resonance with Harmonic Balance Method

The line-lightning performance and mitigation studies of shielded steelstructure

Insulation Co-ordination For HVDC Station

Capacitive Voltage Substations Ferroresonance Prevention Using Power Electronic Devices

ScienceDirect. Simulation Models for Various Neutral Earthing Methods in Medium Voltage Systems

A Pyrotechnic Fault Current Limiter Model for Transient Calculations in Industrial Power Systems

DIFFERENCE BETWEEN SWITCHING OF MOTORS & GENERATORS WITH VACUUM TECHNOLOGY

2. Current interruption transients

Filters And Waveform Shaping

Investigation of Inter-turn Fault in Transformer Winding under Impulse Excitation

HIGH VOLTAGE ENGINEERING(FEEE6402) LECTURER-24

Spectral analysis of voltages and currents during different modes of ferroresonance in switchgear

Sensitivity studies on power transformer ferroresonance of a 400 kv double circuit

Exercises. 6 Exercises

Simulation Analysis of Ferromagnetic Resonance of Low Magnetic Flux Density-Type PT under Single-Phase Earth Fault of 10kV Power Grid

Distribution Transformer Random Transient Suppression using Diode Bridge T-type LC Reactor

LIGHTNING OVERVOLTAGES AND THE QUALITY OF SUPPLY: A CASE STUDY OF A SUBSTATION

Research Article Resistive Ferroresonance Limiter for Potential Transformers

Effect of Surge Arrester on Overhead Transmission Lines as Shield against Over Voltage

GIS Instrument Transformers: EMC Conformity Tests for a Reliable Operation in an Upgraded Substation

Effect of High Frequency Cable Attenuation on Lightning-Induced Overvoltages at Transformers

Tab 8 Surge Arresters

MODIFICATION OF THE ARRESTER ARRANGEMENT WHEN CONVERTING THE METHOD OF NEUTRAL TREATMENT

In power system, transients have bad impact on its

Impact of the system parameters on the ferroresonant modes

DEVELOPMENT OF NUMERICAL ALGORITHMS FOR FERRORESONANCE MONITORING

CHAPTER 5 POWER QUALITY IMPROVEMENT BY USING POWER ACTIVE FILTERS

Lightning Overvoltage Performance of 110 kv Air-Insulated Substation

Novel Circuit Breaker Modeling in 275kV Substation

ACCURACY OF VOLTAGE TRANSFORMERS DESIGN CRITERIA AND A SURVEY ON THE PRECISION AND REPRODUCIBILITY OF A NEW MODEL-BASED CALIBRATION APPROACH

Switching Induced Transients:

Insulation Coordination Study of 275kV AIS Substation in Malaysia

VOLTAGE OSCILLATION TRANSIENTS CAUSED BY CAPACITOR BANKING ENERGIZING FOR POWER FACTOR CORRECTION IN THE POWER SYSTEM

Comparison between Different InstallationLocations of Surge Arresters at Transmission Line Using EMTP-RV

Lab 1. Resonance and Wireless Energy Transfer Physics Enhancement Programme Department of Physics, Hong Kong Baptist University

The Analysis Results of Lightning Overvoltages by EMTP for Lightning Protection Design of 500 kv Substation

Laboratory no. 3 FLUORESCENT LAMPS FITTINGS

FERRORESONANCE - its Occurrence and Control in Electricity Distribution Networks

Transmission Line Transient Overvoltages (Travelling Waves on Power Systems)

Neutral Reactor Optimization in order to Reduce Arc Extinction Time during Three-Phase Tripping

Fatima Michael College of Engineering & Technology

Chapter 1. Overvoltage Surges and their Effects

A Simple Simulation Model for Analyzing Very Fast Transient Overvoltage in Gas Insulated Switchgear

SUBJECT CODE : EE6702 SUBJECT NAME: Protection & switchgear STAFF NAME : Ms.J.C.Vinitha

KINGS COLLEGE OF ENGINEERING DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING QUESTION BANK UNIT I BASIC CIRCUITS ANALYSIS PART A (2-MARKS)

POWER FACTOR CORRECTION. HARMONIC FILTERING. MEDIUM AND HIGH VOLTAGE SOLUTIONS.

Current limiting characteristic of saturated iron core SFCLs

Parameters Affecting the Back Flashover across the Overhead Transmission Line Insulator Caused by Lightning

Fast Protection of Strong Power System With Fault Current Limiters and PLL - Aided Fault Detection

Transcription:

Electrical Power and Energy Systems 33 (2011) 1536 1541 Contents lists available at ScienceDirect Electrical Power and Energy Systems journal homepage: www.elsevier.com/locate/ijepes Analysis of lightning-caused ferroresonance in Capacitor Voltage Transformer (CVT) A.H.A. Bakar a,, N.A. Rahim a, M.K.M. Zambri b a University of Malaya Power Energy Dedicated Advanced Center (UMPEDAC) Level 4 Block M, Faculty of Engineering, University of Malaya, 50603 Kuala Lumpur, Malaysia b Faculty of Electrical Engineering, Universiti Teknikal Malaysia Melaka(UTeM) Hang Tuah Jaya 76100 Durian Tunggal article info abstract Article history: Received 20 April 2010 Received in revised form 6 February 2011 Accepted 3 June 2011 Available online 5 August 2011 Keywords: Lightning strike Ferroresonance Capacitor Voltage Transformer (CVT) Ferroresonance suppression circuit (FSC) Alternative Transient Program (ATP) Basic Insulation Level (BIL) Power networks contain capacitances and inductances that can saturate, presenting opportunities for ferroresonance to occur. Most power equipment is designed through linear theory but ferromagnetic materials are highly non-linear and when they resonate, the non-linearity produces currents and voltages that are larger than usual. Ferroresonance is a complex, non-linear electrical phenomenon. It can cause dielectric and thermal problems through overvoltage, an intrinsic phenomenon present in all networks. A network dynamic response to lightning and switching will be energy storage and release. The transfer of energy will propagate an overvoltage through the network and damage substation equipment when lightning strikes near the substation. Application of conventional mathematics is inappropriate to ferroresonance study in which actual events are simulated. Lightning strikes that occurred near a substation and that led to explosion of CVTs have been reported, so this study investigates the effect of a lightning strike on a tower with a 132 kv Capacitor Voltage Transformer (CVT). Alternative Transient Program (ATP) was used for the simulation which duplicated the lightning-strike effect that causes a CVT to explode. Ó 2011 Elsevier Ltd. All rights reserved. 1. Introduction Capacitive voltage transformers are predominant sources of voltage signals for monitoring, protection and control applications at transmission level. High-speed protective relays are expected to make decisions based on signal produced by CVT, to preserve system stability and minimize damage to equipment. There have been recent reports in Malaysia on CVT failures and explosions at substations. They are: (1) No output on the secondary side of the transformer. (2) Hot spot on CVT main tank detected through thermo vision. (3) CVT explosions. Owing to energy stored in the capacitive, inductive and non-linear components of the CVT, under transient conditions the CVT may not follow closely its input waveform. A redistribution of the electric and the magnetic energies cannot occur instantly and the power system must go through a transient state before a new steady-state condition occurs. Proper design of CVT components will ensure that under steady-state condition, the required output duplicates the input. During transients, CVT s energy-storage element and magneticsaturation non-linearity however causes its output waveform to deviate from its input waveform. CVT ferroresonance during Corresponding author. E-mail address: halim5389@gmail.com (A.H.A. Bakar). transients may cause thermal overstress, consequently deteriorating CVT components through over-voltage. Application of conventional mathematics is not appropriate in studying ferroresonance [1] because analysis of the characteristic forced non-linear differential equations results in considerably complex algebraic equations. A ferroresonance study simulates actual events. This paper investigates the effect of lightning on a 132 kv tower near the substation where several CVT explosions had been reported. Over-voltages induced in the phase conductor caused by strikes close to ground may happen too but they generally are below 200 kv and matter only to lower voltage systems. In Malaysia the minimum transmission voltage is 132 kv and its minimum BIL is 650 kv. Owing to this and also to Malaysia s lightning current being typically more than 20 ka (up to the maximum 200 ka) the simulation thus investigates the actual CVT explosions that had occurred at the substation due to lightning. 2. Lightning strike and ferroresonance 2.1. Lightning strike Peninsular Malaysia experiences frequent lightning strikes, regarded to be among the highest in the world with thunder-days averaging 200 according to the Malaysian Meteorological Department. Lightning occurrences vary with month, occurring frequently from April to June, and less so from December to 0142-0615/$ - see front matter Ó 2011 Elsevier Ltd. All rights reserved. doi:10.1016/j.ijepes.2011.06.004

A.H.A. Bakar et al. / Electrical Power and Energy Systems 33 (2011) 1536 1541 1537 conductors. Shielding failure occurs when lightning strikes conductor. Magnitude of current shielding failure is 20 ka or less. Since mean current is higher than 20 ka, the simulation considers back flashover only. 2.2. Ferroresonance 150 [V] 100 50 0-50 -100 Fig. 1. Ferroresonance caused by switching transient. Ferroresonance are non-linear dynamic systems and as such their behaviour can be analysed using tools available in chaos theory. Four basic types of ferroresonance have been indentified such as fundamental frequency mode, subharmonic mode, where the period of oscillation is an integral multiple of the period of the supply system, quasi-periodic mode and chaotic mode ferroresonance in which the oscillations appear to be random [3]. In this study, ferroresonance due to lightning is of fundamental mode ferroresonance type. For a ferroresonance to occur, a series LC circuit is excited at or near its natural frequency. A transformer inductance and a system capacitance may sometimes be placed in series. Ferroresonance occurs when components in the series circuit reach critical values. System voltage may surpass rated values, leading to equipment damage or failure. Ferroresonance modes have various physical and electrical displays. Some have very high voltages and currents, while others have voltages close to normal. There might have been or might not have been ferroresonance failures, so in many cases whether or not ferroresonance had occurred is difficult to know, unless there had been witnesses or fault-recording instruments. Conditions considered causes of ferroresonance. -150-200 -250 0.00 0.03 0.06 0.09 0.12 [s] 0.15 (file 20000A.ADF; x-vart) vxx0167xx0175 Fig. 2. Ferroresonance caused by lightning strike. February. Lightning also varies with time of day, peaking from 1700 to 1800 h, with 34.5 kilo amperes (ka) mean discharge current [2]. Types of flashovers occurring when lightning hits transmission lines are back flashover and shielding failure. Back flashover occurs when lightning strikes tower and the resultant voltage across the insulator is large enough to cause flashover from tower to line 2.2.1. Switching Switching transient in power systems have always been of concern in studies of power-equipment insulation coordination. They are commonly caused by arcing faults and static discharge. Also major power-system switching disturbances initiated by utilities to correct line problems may happen several times a day. These trigger ferroresonance inside the power system and the equipment. Fig. 1 shows the voltage waveform through ATP simulation, ferroresonance that had been caused by switching transient. In this figure, the ferroresonance occurs after the fault clearing time at 0.9 s for several cycles before it becomes stabilized. 2.2.2. Lightning strike Direct lightning strike on a structure, could cause it to catch fire and severely damage electronic, electrical and even mechanical M / BUSBAR R / BUSBAR R / BUSBAR LA CVT ISO CT CB ISO ISO ISO ISO CB CT CVT LA VT LA Fig. 3. Layout of a typical transmission.

1538 A.H.A. Bakar et al. / Electrical Power and Energy Systems 33 (2011) 1536 1541 Vsystem C1 Rpr Lpr L1a-1nR1a-1n C2 Rsb Lf LD Rmt Rf S2 LpSR RpSR RsSR LsSR Rmr Fig. 4. Circuit diagram of a typical 132 kv model. Fig. 5. CVT circuit with normal ferroresonance-suppression circuit (FSC). equipment. Lightning strikes are common sources of over-voltage, which also can trigger ferroresonance inside equipment or power system. Fig. 2 shows the voltage waveform through ATP simulation, ferroresonance due to lightning strike. 3. Simulation by using ATP Current study is on ferroresonance due to lightning strikes near the substation [4]. Fig. 3 shows a typical layout of the substation.

A.H.A. Bakar et al. / Electrical Power and Energy Systems 33 (2011) 1536 1541 1539 Table 1 Data description for CVT. Fig. 6. FSC-waveform of secondary side of CVT, normal filter. Description System voltage Frequency Capacitive voltage divider Step down transformer (SDT) Compensating series reactor (SR) Ferroresonance suppression filter (FSF) Stabilizing burden (Rsb) Series gap resistance (Rgap) Gap firing voltage Parameters 132 kv 50 Hz C1 = 5348.8 PF C2 = 76666.6 PF Ce = 5000 PF Drain coil [LD] = 10 mh Rpr = 220 X Lpr = 1.745 H Rmt = 6500000 X Lmt = 8841 H R1a 1n = 0.04 X L1a 1n = 0.007 mh Trans. ratio n = 78.74 RpSR = 220 X LpSR = 1.745 H RsSR = 6500000 X LsSR = 8841 H Rmr = 0.04 X Lmr = 0.007 mh Note: the reactor considered as an autotransformer having N1 [primary turns] 6160 and N2 [secondary turns] 220 Lf = 4.62 H Rf = 12.3 X 75 X 11.2 X 250 V Fig. 7. FSC-waveform of secondary-side of CVT, active filter. Table 2 Results of ferroresonance oscillation of FSC type. Type of FSC Ferroresonance cycle Peak voltage value (V) Normal filter 12 318.6 Active filter 12 260.81 Passive filter 11 252.43 Fig. 8. FSC-waveform of secondary-side of CVT, passive filter. The arrangement for the CVT that is the focus of this research is its location which is after the lightning arrester and before the transformer. There are several current-surge models, but the Heidler surgemodel was chosen. This is due to the fact that the Heidler lightning model is a channel-base current which permits easy modelling of usually measured lightning current quantities at strike point: current peak, current rise time, maximum of current steepness and the charge transfer. The Bergeron tower model was considered because the overhead transmission line is modelled on frequency dependent (Phase) model, which uses curve fitting to duplicate the frequency response of a line or a cable. The Bergeron model is based on distributed LC parameter travelling wave-line, with lumped resistance. It represents in a distributed manner the L and the C elements of a PI Section and it also roughly equals use of an infinite Fig. 9. Simulation of 34.5 ka lightning strike. number of PI Sections except that the resistance is lumped (1/2 in the middle of the line, 1/4 at each end). The CVT model uses a voltage-controlled switch as available in the ATPDraw. The CVT model consists of coupling capacitor, compensating reactor, step-down transformer and ferroresonance-suppression circuit. The ferroresonance circuit is a resistor inductor series circuit, which is normal ferroresonance-suppression circuit. A typical 132 kv model is shown in Fig. 4.

1540 A.H.A. Bakar et al. / Electrical Power and Energy Systems 33 (2011) 1536 1541 Fig. 10. Simulation of 100 ka lightning-strike. Fig. 13. Waveform at the overvoltage protection device for 200 ka, with 40 X series resistor. Fig. 11. Simulation of 200 ka lightning strike. Fig. 14. Waveform at the overvoltage protection device for 200 ka, resistor parallel with spark gap. Fig. 12. Waveform at the overvoltage protection device for 200 ka, without sparkgap improvement. Fig. 15. Waveform at the overvoltage protection device for 200 ka, resistor series with capacitor and parallel with spark gap. 4. Results and discussion Simulations done to predict and mitigate the ferroresonance were: (i) Ferroresonance suppression circuit (FSC). (ii) Various magnitudes of lightning current. (iii) Improvement to overvoltage protection device. Fig. 5 shows a normal filter used in the CVT is usually a resistor in series with an inductor. Active and passive filters were also used in the simulations. A 34.5 ka current, the mean value injected between the second and the third spans of the substation s Table 3 Results of ferroresonance oscillation due to spark gap improvement. Spark gap improvement Ferroresonance cycle Without improvement 15 11728 Series resistor 14 11715 Parallel resistor 2 27 Parallel resistor and capacitor 7 125 Peak voltage value (V) transmission tower as an injection towards the first tower near the substation is considered a direct hit to the CVT. The simulation result is as shown in Fig. 6 for normal filter, Fig. 7 for active filter

A.H.A. Bakar et al. / Electrical Power and Energy Systems 33 (2011) 1536 1541 1541 and Fig. 8 for passive filter respectively. Table 1 shows the data description of the CVT diagram. The results of ferroresonance oscillation of FSC type in Table 2 show that the oscillation of the lightning strike improved by one cycle from 12 cycles to 11 cycles when passive filter is used [5]. Figs. 9 11 simulate 34.5 ka (the mean value), 100 ka and 200 ka respectively. These values are lightning magnitudes recorded in Malaysia. The results also show that the higher the magnitude, the more severe the ferroresonance. Figs. 12 15 show the waveform taken from the overvoltage protection device of the CVT system which is located at the primary side of the CVT system. The waveform shows the result of re-model spark gap system by putting a passive element of RLC. As for the overvoltage protection device, the previous design is just a spark gap. A suggested improvement is for a 40 X resistor to be inserted in series with the spark gap resulting in slight improvement from 15 cycles to 14 cycles as shown in Table 3. A parallel resistor with spark gap would improve the oscillation to two cycles, however oscillation still persist. A design proposed in this study is for the resistor in series with a spark gap to be replaced by parallel connection of a 5 O resistor in series with a 47 lf capacitor. The improvement is from 15 cycles to 7 cycles. Of three designs, the one that mitigated ferroresonance and also the oscillation was the design proposed. 5. Conclusions This paper presents dynamic simulations of ATP/EMTP that analysed the contribution of lightning-caused ferroresonance to the CVT explosions in Malaysia. The following are concluded: (i) A lightning strike can cause ferroresonance in a CVT. (ii) The primary side of the CVT is most severely affected. (iii) To mitigate ferroresonance on the primary side, an improved overvoltage protection device can be considered. Presently the overvoltage circuit uses spark gap. The addition of a resistor does not fully mitigate ferroresonance. (iv) A new design proposed for the overvoltage protection device is for the spark gap to be parallel with the resistor and in series with the capacitor. Ferroresonance and its oscillation can then be mitigated. This study shows that CVT components matter to CVT s transient response. A CVT properly designed for a particular power system will enhance performance and eliminate expensive equipment failure caused by ferroresonance. References [1] Emin Z, Al Zahawi BAT, Auckland DW, Tong YK. Ferroresonance in electromagnetic voltage transformer: a study based on nonlinear dynamic. IEE P-Gener Transm D 1997;144(4);383 7. [2] Halim Ab, Bakar Abu. Economic positioning of lightning arrester: transient phenomena in large electric power systems. In: Cigre symposium, Zagreb, Croatia; 18 21 April, 2007. [3] Emin Z, Milicevic Kruno. Impact of initial conditions on the initiation of ferroresonance. Electrical Power and Energy System 2009;31(August). [4] Gonos LF et al. Probability of back flashover in transmission lines due to lightning strikes using Monte-Carlo simulation. Electr Power Energy Syst 2005;25. [5] Hou Daqing, Roberts J. Capacitive voltage transformer: transient overreach concerns and solutions for distance relaying. In: Canadian conference on electrical and computer engineering, 1996, vol. 1, session 6, vol. 6.4; 26 29 May, 1996. p. 119 25.