IMPORTANCE OF INSULATION RESISTANCE

Similar documents
The Basics of Insulation Testing

US $9.95 GBP 5.95 A Stitch in Time... The Complete Guide to Electrical Insulation Testing

Insulation resistance testing

Insulation Resistance Testing

Introduction. AC or DC? Insulation Current Flow (AC) 1. TECHNICAL BULLETIN 012a Principles of Insulation Testing. Page 1 of 10 January 9, 2002

Insulation Testing Preventing Equipment Breakdown and Plant Shutdowns

Be on guard for effective testing: Introduction

R Distribution Transformers. Mineral Oil-Immersed, Self-Cooled, 60 Hertz Voltages and Connections. Reference Data

This section is specifically about safety matters

Power Factor Insulation Diagnosis: Demystifying Standard Practices

Hands-On Transformer Testing and Maintenance

This section is specifically about safety matters

7. INSPECTION AND TEST PROCEDURES

Brown University Revised 2/1/2006 Facilities Design & Construction Requirements SECTION 16461C - DRY TYPE TRANSFORMERS

Direct Current Motor Electrical Evaluation Using Motor Circuit Analysis

Partial Discharge Theory, Modeling and Applications To Electrical Machines

Basic Principles and Operation of Transformer

KNOW MORE ABOUT THE TRANSFORMERS. Glossary Transformers

EPG. by Chris C. Kleronomos

Substation Preventive Maintenance

Insulation Resistance Testing Guide

SECTION TRANSFORMERS

Insulation Testing. Distributor Training Program

Understanding the Value of Electrical Testing for Power Transformers. Charles Sweetser, OMICRON electronics Corp. USA

Unit WorkBook 1 Level 4 ENG U31: Electrical Systems and Fault Finding 2018 UniCourse Ltd. All Rights Reserved. Sample

Asset Protection Cathodic Protection Soil Resistivity Measurement. Work Instruction No.:

WESTERN UNDERGROUND COMMITTEE GUIDE 2.6 (2.6/00/0868)

CONSULTANT PROCEDURES & DESIGN GUIDELINES Liquid-Filled Utility Transformers UNIVERSITY OF MISSOURI

CHAPTER 5 CONCEPT OF PD SIGNAL AND PRPD PATTERN

Back to the Basics Current Transformer (CT) Testing

Transformer Testing & Maintenance Fundamentals. AVO Training Institute, Inc. 2018

MIT510/2, MIT520/2 and MIT1020/2

BM25 Automated 5-kV Insulation Tester

Guide to modern insulation testing Code No

Unit 3 Magnetism...21 Introduction The Natural Magnet Magnetic Polarities Magnetic Compass...21

AC/DC DIGITAL CLAMP METER OPERATION MANUAL

RESIDUAL LIFE ASSESSMENT OF GENERATOR TRANSFORMERS IN OLD HYDRO POWER PLANTS

Preface...x Chapter 1 Electrical Fundamentals

Overtravel of 3.5 mm max. Power source DC D5C-1DS0 D5C-1DP0 D5C-1DA0 AC D5C-1AS0 D5C-1AP0 D5C-1AA0 Antenna only D5C-00S0 D5C-00P0 D5C-00A0

Insulation resistance testing. A complete solution for every application.

UNIVERSITY OF MISSOURI Liquid-Filled Utility Transformers 2016 Q1

TIGHTENING TORQUE ON WOODEN CORE CLAMP (Nm) (STEEL FASTENER) 1 M M M M M

SINGLE PHASE BUCK & BOOST TRANSFORMERS INSTRUCTION MANUAL

Single-Phase Instrument Transformers

Model: PR-55. High Voltage Oscilloscope Probe 10 kv, 40 MHz USER MANUAL

Mounting method DIN rail mounting or screw mounting Screw mounting Mass [g] Material Case: Plastics PCB: FR-4

Transformers handling and transport

Variable Transformers Product Design & Engineering Data

SECTION 2 Basic Electric Circuits. UNIT 6 Series Circuits

+ 24V 3.3K - 1.5M. figure 01

CCG Series Instruction Manual

Application Note. Detection of Partial Discharge Using Ultrasound. Detection of Partial Discharge Using Ultrasound. Problem. iriss.

VSD cables in. Working with. industrial & automation applications

High switching capacity 1a/1c 30A power relays

3/29/2012 MAIN TOPICS DISCUSSED ELECTRICAL SYSTEMS AND ELECTRIC ENERGY MANAGEMENT SECTION K ELECTRIC RATES POWER COMPUTATION FORMULAS.

CONTENTS XV300K GB r doc XV300K 2/13

BECAUSE MOTOR & GENERATOR FAILURE IS NOT AN OPTION USCG

Innovative Test Techniques and Diagnostic Measurements to Improve the Performance and Reliability of Power System Transformers

GENERATOR TESTING APPLICATION GUIDE. reliable. precision.

HARMONICS CAUSES AND EFFECTS

DUAL OUTPUT AC CURRENT/VOLTAGE TRANSDUCER

Copper Core & Coil Transformer

PRE COMMISSIONING TESTS ON EQUIPMENT AT 33/11 KV SUB STATIONS. IR Values are to be read on the megger by meggering the Power transformer

Specialists in HV and MV test and diagnostics. Testing in Substations

TRANSFORMER OPERATIONAL PRINCIPLES, SELECTION & TROUBLESHOOTING

1210N 1250N MEGOHMMETER. User Manual 15 V 500V kV. MEGOHMMETER Model 1250N 600V CAT II / 1000V CAT I! 30. x 10.

3. Contact Form A: SPST-NO

TesTIng of Power. Transformers are the largest, most. feature. By brandon dupuis

Technician License Course Chapter 3. Lesson Plan Module 4 Electricity

شركة الوقت للكهرباء والمقاوالت ذ.م.م.

DIGITAL MULTIMETER CONTENTS DIGITAL MULTIMETER CONTENTS

Howard Smart Transformer Specification Guide

Angle Grinder MODEL 9553B MODEL 9555B

The NOVA Recloser shall be designed and tested in accordance with the following standards as applicable:

INSTALLATION, OPERATION AND MAINTENANCE GUIDE

Title: Southern States Type SLS Smart Sectionalizer Solid Dielectric Three Phase Sectionalizer. Product Specification Guide TABLE OF CONTENTS

Megohmmeter Model 1060

A CASE STUDY OF PARTIAL DISCHARGE AND ELECTRICAL TRACKING IN A 11KV METAL CLAD SWITCHGEAR

Electrical TP-18 February 2017 ELECTRICAL TECHNICAL PAPER 18 FREQUENTLY ASKED QUESTIONS ABOUT CATHODIC PROTECTION SYSTEM EQUIPMENT TESTING

Power Transformer Condition Assessment Based on Standard Diagnosis

User's Guide. AC Circuit Load Tester. Model CT70

Armoured Power and Control Cables to BS7917

MIT510, MIT520 and MIT1020

Form-IV. Form of Inspection/Test Report. (Under Regulation 43)

THE ELECTROM itig II MOTOR TESTER AND WINDING ANALYZER

Analog Timer TTL Series

Technical Information

THE ELECTROM itig II MOTOR TESTER AND WINDING ANALYZER

Armoured Power and Control Cables Fire Resistant

HIGH VOLTAGE ENGINEERING(FEEE6402) LECTURER-24

Ratchet Relay. Ordering Information. Unique Ratchet Mechanism Assures Positive Alternate Transfer/Switching Operation. G4Q-jjjj

Item ref: UK MTM01 DIGITAL MULTITESTER. User Manual

NATIONAL SENIOR CERTIFICATE GRADE 12

MGM Transformer. Vacuum Pressure Impregnated (VPI) Dry-Type Substation Transformer Specification Guide

PHASE ROTATION METER. Operating and Instruction Manual. a n d A C C E S S O R I E S

Understanding the Value of Electrical Testing for Power Transformers. Charles Sweetser - OMICRON

Upgrading Your Electrical Distribution System To Resistance Grounding

Industrial and Commercial Power Systems Topic 7 EARTHING

TMC Transformers TMC

AGN 015 Testing Winding Insulation Systems

Transcription:

IMPORTANCE OF INSULATION RESISTANCE What is Good Insulation? Every electric wire in your plant whether it s in a motor, generator, cable, switch, transformer, etc., is carefully covered with some form of electrical insulation. The wire itself is usually copper or aluminium, which is known to be a good conductor of the electric current that powers your equipment. The insulation must be just the opposite from a conductor: it should resist current and keep the current in its path along the conductor. The purpose of insulation around a conductor is much like that of a pipe carrying water and ohm s law of electricity can be more easily understood by a comparison with water flow. Pressure on water from a pump causes flow along the pipe. If the pipe were to spring a leak, you d waste water and lose some water pressure. With electricity, voltage is like the pump pressure, causing electricity to flow along the copper wire. As in a water pipe, there is some resistance to flow, but it is much less along the wire than it is through the insulation. Comparison of water flow with electric current Common sense tells us that the more voltage we have, the more current there ll be. Also, lower the resistance of the wire, the more current for the same voltage. Actually, this is Ohm s law, which is expressed this way in equation form: E = I x R Where, E = voltage in volts I = current in amperes R = resistance in ohms Now, to sum up our answer to the question what is good insulation? we have seen that, essentially, good means a relatively high resistance to current. Used to describe an insulation material, good would also mean the ability to keep a high resistance. So, a suitable way of measuring resistance can tell you how good the insulation is. Also, if you take measurements at regular periods, you can check trends toward its deterioration (more on this later).

What makes Insulation Go Bad? When your plant electrical system and equipment are new, the electrical insulation should be in to notch shape. Furthermore, manufactures of wire, cable, motors, and so on have continually improved their insulations for services in industry. Nevertheless, even today, insulation is subject to many effects which can cause it to fail mechanical damage, vibration, excessive heat or cold, dirt, oil, corrosive vapours, moisture from processes, or just the humidity on a muggy day. In various degrees, these enemies of insulation are at work as time goes on combined with the electrical stresses that exist. As pin holes or cracks develop, moisture and foreign matter penetrate the surfaces of the insulation, providing a low resistance path for leakage current. Once started, the different enemies tend to aid each other, permitting excessive current through the insulation. Sometimes the drop in insulation resistance is sudden, as when requirement is flooded. Usually, however, it drops gradually, giving plenty of warning, if checked periodically. Such checks permit planned reconditioning before service failure/ If there are no checks, a motor with poor insulation, for example, may not only be dangerous to touch when voltage is applied, but also be subject to burn out. What was good insulation has become a partial conductor. How Insulation Resistance is measured You have seen that good insulation has high resistance; poor insulation, relatively low resistance. The actual resistance values can be higher or lower, depending upon such factors as the temperature of moisture content of the insulation (resistance decreases in temperature or moisture). With a little record-keeping and common sense, however, you can get a good picture of the insulation condition from values that are only relative. The insulation tester is small, portable instrument that gives you a direct reading of insulation resistance in ohms or megohms. For good insulation, the resistance usually reads in the megohm range. The insulation tester is essentially a high-range resistance meter (ohmmeter) with a built-in direct-current generator. This meter is of special construction with both current and voltage coils, enabling true ohms to be read directly, independent of the actual voltage applied. This method is non-destructive; that is, it does not cause deterioration of the insulation. Typical Insulation tester test instrument hook-up to measure insulation resistance

The generator can be hand-cranked or line-operated to develop a high DC voltage which causes a small current through and over surfaces of the insulation being tested. This current (usually at an applied voltage of volts or more) is measured by the ohmmeter, which has an indicating scale. A typical scale, which reads increasing resistance values from left up to infinity, or a resistance too high to be measured. Typical scale on the Insulation tester In Summary, here are some general observations about how you can interpret periodic insulation resistance tests, and what you should do with the result: S.NO CONDITION WHAT TO DO 1 Fair to high values and well maintained No cause for concern 2 Fair to high values, but showing a constant tendency towards lower values Locate and remedy the cause and check the downward trend 3 Low but well maintained Condition is probably all right, but cause of low values should be checked 4 So low as to be unsafe Clean, dry out, or otherwise raise the values before placing equipment in service (Test wet equipment while drying out) 5 Fair or high values, previously well maintained but showing sudden lowering Dielectric Absorption Ratio Make tests at frequent intervals until the cause of low values is located and remedied; or until the values have become steady at a lower level but safe for operation; or until values become so low that it is unsafe to keep the equipment in operation. The ratio of two time-resistance readings (such as 60-second reading divided by a 30-second reading) is called a dielectric absorption ratio. It is useful in recording information about insulation. If the ratio is a 10- minute reading divided by a 1-minute reading, the value is called the polarization index. With hand-cranked Insulation tester instrument, it s a lot easier for you to run the test for only 60 seconds, taking your first reading at 30 seconds. If you have a line-operated Insulation tester instrument, you ll get best results by running the test 10 minutes, taking readings at 1- and at 10-minutes, to get the polarization index. Table gives values of the ratios and corresponding relative conditions of the insulation that they indicate.

Condition of insulation indicated by Dielectric Absorption Ratios These values must be considered tentative and relative subject to experience with the time-resistance method over a period of time. In some cases, with motors, values approximately 20% higher than shown here indicate a dry brittle winding which will fail under shock conditions or during starts. For preventive maintenance, the motor winding should be cleaned, treated, and dried to restore winding flexibility. These results would be satisfactory for equipment with very low capacitance such as short runs of house wiring. Test Voltage Vs Equipment Rating Commonly used DC test voltages for routing maintenance are as follows: EQUIPMENT AC RATING DC TEST VOLTAGE Up to 100 volts 100 and 250 volts 440 to 550 volts 500 and 1,000 volts 2,400 volts 1,000 to 2,500 volts or higher 4,160 volts and above 1,000 to 5,000 volts, or higher Test voltages used for proof testing of equipment are considerably higher than those used for routing maintenance. Although there are no published industry standards for DC maximum proof test voltages to be used with rotating equipment, the schedule given below is customarily used. For specific recommendations on your equipment, you should consult the manufacturer of the equipment. Proof Test Voltages for Rotating Equipment: Factory AC Test = 2 x Nameplate Rating + 1000 volts DC Proof Test on Installation = 0.8 x Factory AC Test x 1.6 DC Proof Test after Service = 0.6 x Factory AC Test x 1.6 Example: Motor with 2,400 VAC nameplate rating-

Factory AC Test = 2(2,400) + 1,000 = 5,800 VAC Max. DC Test on Installation = 0.8(5,800)1.6 = 7,424 VDC Max. DC Test after Service = 0.6(5,800)1.6 = 5,568 VDC Effects of Humidity: We have spoken at various points in this manual about the presence of moisture in insulation and its very marked effect upon resistance values. You might expect, therefore, that increasing humidity (moisture content) in the surrounding (ambient) air could affect insulation resistance. And it can to varying degrees. If your equipment operates regularly above the dew-point temperature (the temperature at which the moisture vapour in air condenses as liquid), the test reading normally will not be affected much by the humidity. Even if the equipment to be tested is idle, the same is true so long as its temperature is kept above the dew point. The aforementioned statement assumes that the insulation surfaces are free of contaminants, such as certain lint s and acids or salts, which have the property of absorbing moisture (they re called hygroscopic or deliquescent materials by chemists). Their presence could unpredictably affect your readings; they should be removed before tests are made. In electrical equipment we re concerned primarily with the conditions on the exposed surfaces where moisture condenses and affects the overall resistance of the insulation. Studies show, however, that dew will form in the cracks and crevices of insulation before it is visibly evident on the surface. Dew-point measurements will give you a clue as to whether such invisible conditions might exist, altering the test results. As a part of your maintenance records, therefore, it s a good idea to make note at least of whether the surrounding air was dry or humid when the test was made. Also, whether the temperature was above or below the ambient. When you test vital equipment, record the ambient wet and dry bulb temperatures, from which dew-point and percent relative or absolute humidity can be obtained. Minimum Values for Insulation Resistance: Rotating Machinery The recommended minimum insulation resistance R m for alternating-current and direct-current machine armature windings and for field windings of alternating-current and direct-current machines can be determined by: Where: R m = KV + 1 R m = recommended minimum insulation resistance in megohms at 40ºC of the entire machine winding KV = rated machine terminal to terminal potential, in kilovolts

Transformers: Acceptable insulation resistance values for dry and compound-filled transformers should be comparable to those for Class A rotating machinery, although no standard minimum values are available. Oil-filled transformers or voltage regulators present a special problem in that the condition of the oil has a marked influence on the insulation resistance of the windings. In the absence of more reliable data the following formula is suggested: = R = minimum 1-minute 500-volt DC insulation resistance in megohms from winding to ground, with other winding or windings guarded, or from winding to winding with core guarded C = a constant for 20ºC measurements E = voltage rating of winding under test KVA = rated capacity of winding under test For tests of winding to ground with the other winding or windings grounded, the values will be much less than that given by the formula, R in this formula is based on dry, acid-free, sludge-free oil, and bushings and terminal boards that are in good condition. Values of C at 20ºC 60-Hertz 25-Hertz Tanked oil-filled type 1.5 1.0 Un-tanked oil-filled type 30.0 20.0 Dry or compound-filled type 30.0 20.0 This formula is intended for single-phase transformer. If the transformer under test is of the three-phase type, and the three individual windings are being tested as one, then: E = voltage rating of one of the single-phase windings (phase to phase for delta connected units and phase to neutral for star connected units) KVA = rated capacity of the competed three-phase winding under test. (Megger has came up first with insulation tester and hence people says insulation tester as megger oftenly) Potential system has facility to do insulation resistance measurement with latest techniques and instruments For further information please do call us.. Also we request you to kindly share your valuable comments, suggestions and feedback to improve us