Statistical Characteristics of Partial Discharge Caused by Typical Defects in Cable Joint under Oscillating Voltage

Similar documents
Testing and PD Diagnosis of MV Cable Systems with DAC Voltage Educational Session May St Pete Beach, Fl

NOVEL METHOD FOR ON-SITE TESTING AND DIAGNOSIS OF TRANSMISSION CABELS UP TO 250KV

Aspects of PD interpretation in HV power cables. by Edward Gulski, Piotr Cichecki, Rogier Jongen

USING DAMPED AC VOLTAGES

INSULATION DIAGNOSIS OF HIGH VOLTAGE POWER CABLES

Investigation of PD Detection on XLPE Cables

Long lengths transmission power cables on-site testing up to 500 kv by damped AC voltages

SENSITIVITY ASPECTS OF ON-LINE PD DIAGNOSIS OF MV POWER CABLES

Partial Discharge Measurement and Monitoring on High Voltage XLPE Cables

C I R E D 21 st International Conference on Electricity Distribution Frankfurt, 6-9 June 2011

OFFLINE PD DIAGNOSTICS USING SEVERAL EXCITATION VOLTAGES

BEST PRACTICES FOR OFFLINE DIAGNOSIS OF MV CABLES

EFFECT OF INTEGRATION ERROR ON PARTIAL DISCHARGE MEASUREMENTS ON CAST RESIN TRANSFORMERS. C. Ceretta, R. Gobbo, G. Pesavento

THE PROPAGATION OF PARTIAL DISCHARGE PULSES IN A HIGH VOLTAGE CABLE

Basics of Partial Discharge. Prepared for 2015 Phenix RSM Meeting January 2015

Investigations on a Combined Resonance/VLF HV Test System Partial Discharge (PD) characteristics at VLF and DAC voltages

INFLUENCE OF VOLTAGE WAVEFORMS ON PARTIAL DISCHARGES DEVELOPED IN POWER CABLE INSULATION

The University of New South Wales. School of Electrical Engineering and Telecommunications. High Voltage Systems ELEC9712. Appendix Partial Discharge

Partial discharge diagnostics on very long and branched cable circuits

Suppression of Pulse Interference in Partial Discharge Measurement Based on Phase Correlation and Waveform Characteristics

HV AC TESTING OF SUPER-LONG CABLES

IN HOUSE CALIBRATION OF PD DETECTOR SYSTEM FOR FIELD TEST RESULT RELIABILITY

Testing 320 kv HVDC XLPE Cable System

INVESTIGATION ON THE TECHNOLOGIES FOR DEFECT LOCALIZATION AND CHARACTERIZATION ON MEDIUM VOLTAGE UNDERGROUND LINES

BY JASON SOUCHAK, Megger

Field Test and Analysis of Partial Discharge. on GIS Under Impulse Voltage

TD-106. HAEFELY HIPOTRONICS Technical Document. Partial Discharge Pulse Shape Analysis to Discriminate Near and Far End Failures for Cable Location

PD Testing Considerations for MV Plant Cables

Practical aspects of PD localization for long length Power Cables

EVALUATION AND COMPARISON OF ON-LINE PD DETECTION METHODS FOR HIGH-VOLTAGE POWER CABLE

High-Voltage Test and

Software System for Finding the Incipient Faults in Power Transformers

Electrical Power Engineering Group, School of Electronics and Computer Science, University of Southampton, Highfield, Southampton, SO17 1BJ, UK 2

Simultaneous Partial Discharge and Tan Delta Measurements: New Technology in Cable Diagnostics

High Voltage Diagnostics Sarl 4, Rue de Lac CH 1897 Le Bouveret Switzerland

11-SDMS-03 REV. 02 SPECIFICATIONS FOR

VLF. DAC tandelta. Partial Discharge. Experience the world of Megger electrical testing

The Simulation Experiments on Impulse Characteristics of Tower Grounding Devices in Layered Soil

Online Localisation of Partial Discharge Using Pulse Propagation Parameters in Medium Voltage Cable Network

Kurzfassung. Abstract. 1 Introduction

NEW MV CABLE ACCESSORY WITH EMBEDDED SENSOR TO CHECK PARTIAL DISCHARGE ACTIVITY

Type Test of a 145 kv Termination Type TS 145-II

Fault location on power cables. Fault location on power cables

Abstract. 1 Introduction

Field Measurement of Transmission Cable Dissipation Factor

Diagnosis of Water Tree Aging in XLPE Cable by the Loss Current Harmonic Component Under Variable Frequency Power

Condition Assessment of High Voltage Insulation in Power System Equipment. R.E. James and Q. Su. The Institution of Engineering and Technology

OPTIMIZATION OF ON-SITE PD MEASUREMENTS AND EVALUATION OF DIAGNOSTIC PARAMETERS FOR ASSESSING CONDITION OF DISTRIBUTION CABLE SYSTEM ELPIS J SINAMBELA

How to Analyze and Test the Location of Partial. Discharge of Single-winding Transformer Model

Diagnostic testing of cast resin transformers

Name: Craig Goodwin. Company Name: HV Diagnostics Inc

Assuring the Reliability of Critical Power Cable Systems

ON-LINE PARTIAL DISCHARGE TESTING OF SOME OF THE WORST PERFORMING CIRCUITS ON A UTILITY DISTRIBUTION SYSTEM

Underground System Design TADP 547

Cable testing and diagnostics

Partial Discharge Patterns in High Voltage Insulation

On-line Partial Discharge Assessment and Monitoring of MV to EHV Cables

EXTREMELY LOW MAGNETIC FIELD (ELMF) XLPE INSULATED CABLES, TYPE N2XY/FR1 0.6/1 KV

Open Access Application of Partial Discharge Online Monitoring Technology in ± 660kV Converter Transformer

Design of Meander Antenna for UHF Partial Discharge Detection of Transformers

Field Experiences. Partial Discharge Diagnosis on MV Cables. Philipp Legler. XVI. Szigetelésdiagnosztikai Konferencia (

Comparison of measurement methods for partial discharge measurement in power cables

IEEE Transactions on Dielectrics and Electrical Insulation Vol. 11, No. 5; October

SDMF based Interference Rejection and PD Interpretation for Simulated Defects in HV Cable Diagnostics

Dielectric response and partial discharge measurements on stator insulation at varied low frequency. Nathaniel Taylor

Influence of Impurity Concentration on Insulation Strength of Insulating Oil under Different Voltage Types

CONTINUOUS ON-LINE MONITORING OF PARTIAL DICHARGES IN HV DISTRIBUTION CABLES

process has few stages and is highly repeatable. Excellent mechanic properties and electro-magnetic compatibility. Planar design gives the height lowe

10. DISTURBANCE VOLTAGE WITHSTAND CAPABILITY

Reprint E Two Years of Experience with a Mobile Resonant Test System for Testing of Installed Medium- and High Voltage Power Cables

THE POWER OF LIFE. WinTech Partial Discharge based Predictive Intelligence of insulation system to eliminate power failure risk.

TRANSMISSION ENGINEERING STANDARD TES-P , Rev. 0 TABLE OF CONTENTS 1.0 SCOPE 2.0 BONDING METHODS

Prediction of Transient Transfer Functions at Cable-Transformer Interfaces

Detection of Partial Discharges and its Effect on Solid Insulation used in High Voltage Cable

Cable fault location in power cables. Systematics for cable testing, diagnosis and cable fault location

H V T E S T S O L U T I O N S PA RT N E RS F O R H V & E M C

Simulation Model of Partial Discharge in Power Equipment

A6.6 9 th International Conference on Insulated Power Cables A6.6

Partial Discharge Classification Using Acoustic Signals and Artificial Neural Networks

PD Diagnostic Applications and TechImp solutions

Extended analysis versus frequency of partial discharges phenomena, in support of quality assessment of insulating systems

TECHIMP Technologies & Services for Diagnostics and Monitoring of High Voltage Assets

MV Power Cable Testing Training

IEEE Transactions on Power Delivery. 15(2) P.467-P

Coherence and time-frequency analysis of impulse voltage and current measurements

AORC Technical meeting 2014

Error vs. Uncertainty Historical Perspective

CIGRE- AORC Technical Meeting 2016 and International Conference on Global Trends in the Development of Power T&D System including Smart Grid

Chapter 1. Overvoltage Surges and their Effects

Practical Experience in On-Line Partial Discharge Measurements of MV Switchgear Systems

Frequency Spectrum Analysis of Electromagnetic Waves Radiated by

شركة الوقت للكهرباء والمقاوالت ذ.م.م.

International Conference on Information Sciences, Machinery, Materials and Energy (ICISMME 2015)

CONDITION ASSESSMENT OF XLPE MV CABLE JOINTS BY USING AN INSULATION TESTER

Standard Technical Specifications for Electrical Works CABLES AND ACCESSORIES. 11 kv XLPE-Insulated Three-Core Underground Cables

CHAPTER 5 CONCEPT OF PD SIGNAL AND PRPD PATTERN

CONTINUOUS ON-LINE SYSTEM FOR PARTIAL DISCHARGE MONITORING FOR HA1 AT CHE ROBEŞTI

Power Cables and their Application

Specialists in HV and MV test and diagnostics. Testing in Substations

SMART CABLE GUARD A TOOL FOR ON-LINE MONITORING AND LOCATION OF PD S AND FAULTS IN MV CABLES ITS APPLICATION AND BUSINESS CASE

Transcription:

Journal of Energy and Power Engineering 9 () 3-3 doi:.7/93-897/.3. D DAVID PUBLISHIG Statistical Characteristics of Partial Discharge Caused by Typical Defects in Cable Joint under Oscillating Voltage Guangmao Li, Zuwei Luo, Jun Xiong, Zucheng Huang and Yajun Wang. Test and Research Institute of Guangzhou Power Supply Bureau, Guangzhou Power Supply Bureau, Guangzhou, China. State Key Laboratory of Power Transmission Equipment & System Security and ew Technology, Chongqing University, Chongqing 3, China Received: ovember, / Accepted: December 3, / Published: March 3,. Abstract: The oscillating voltage test is a nondestructive detection method for partial discharge of XLPE (cross linked polyethylene) cable and has been applied recently. This paper made three kinds of varying severity artificial defect models of cable joints in kv XLPE cable. Oscillating voltage is applied to the model, by use of pulse current method to detect partial discharge signals. In order to study the statistical characteristics of partial discharge of cable joint under the oscillating voltage, three-dimensional statistical map has been made. The results show that for the same kind of defects, with the increases of the defect severity, the discharge interval extended, the magnitude and the number of partial discharge increase, for different kinds of defects, obvious differences exist among the maps, this may established a foundation for the further study of the partial discharge pattern recognition of XLPE cable under oscillating voltage. Key words: XLPE cable, cable joint defect model, partial discharge, oscillating voltage, three-dimensional statistical map.. Introduction With the advantage of simple process, reasonable structure and excellent electrical performance, XLPE (cross linked polyethylene) cable has gradually replace the traditional paper oil insulation cable and widely applied around the world. Bad construction technology, artificial destruction and severe environment may cause insulation defect after cable leave factories, especially for the cable accessory defect, which will affect its insulating property []. Researches have shown that, the severity of partial discharge in XLPE cable can indicate the change of its insulation state. Partial discharge test is recommended as the main diagnostic method of the XLPE cable insulation by international authority such as IEEE Corresponding author: Guangmao Li, junior engineer, research fields: online monitoring and fault diagnosis of electrical equipment. E-mail: 8978@qq.com. (Institute of Electrical and Electronic Engineers) and CIGRE (International Council on Large Electric Systems) [, 3]. It has been found that it is difficult to carry the partial discharge test for the power source is usually too big because of the long length and high equivalent electric capacity of XLPE cable []. The current XLPE cable handover and preventive test such as ultra-low frequency voltage (. HZ) method and DC (direct current) voltage method cannot work effectively in the off-line partial discharge detection test, because they all need long action time and may cause other defects [, ]. However, OWTS (oscillating wave testing system) is now widely used in partial discharge detection in the off-line state of XLPE cable [7, 8]. This method has advantages such as short action time, harmless to the insulation and its voltage waveform meet the demand of IEC (International Electrotechnical Commission)

Statistical Characteristics of Partial Discharge Caused by Typical Defects 3 7 [9], testing voltage characteristic. Due to the favorable equivalence to power frequency voltage, oscillating voltage has been widely applied as it could accomplish the cable insulation defect test under the circumstance similar to power frequency. Studies have shown that the application of OWTS mainly concentrates on the detection and locates of cable insulation defect, but the research on the statistical property of partial discharge signal under the oscillatory wave is insufficient [-]. This paper made three kinds of varying severity artificial defect models of cable joints in real kv XLPE cable, oscillating wave testing system is used to carry out partial discharge test. In order to study the effectiveness of partial discharge test in detecting cable defect and the characteristic of partial discharge signal under oscillating voltage, three-dimensional statistical map of the partial discharge is made to analyze the data.. Testing Circuit and Defect Making. Oscillating Voltage Testing Circuit In order to study the characteristic of partial discharge signal under oscillating voltage, the testing adopt oscillating wave testing system to generate oscillating voltage, three kinds of varying severity artificial defects on the cable joint which is of high fault rate are made at the same time. As shown in Fig., the OWTS constitutes of high voltage DC source, resistance R, no halo reactor L, high voltage switch S and test cable, etc. The basic principle of oscillating voltage test method is to build an L-R-C (inductance-resistance-capacitance) underdamped oscillator circuit with inductance L, resistance R and the equivalent capacitance C of the test cable []. According to the state of switch S, the generation of oscillating voltage can be divided into two stages. First, off state of high voltage switch S. High voltage DC source, no halo reactor L and test cable C will act as a DC circuit till the cable reaches the preset voltage. In the second stage, the high voltage switch closed. The high voltage switch S immediately closed when the preset voltage is reached. The equivalent capacitance C of the cable, inductor L and the resistance R formed an LRC underdamping oscillation circuit and generated oscillating voltage. The decay rate of oscillating voltage is rather high which only last for about -3 ms, however, it is enough to stimulate the partial discharge signal in the cable insulation defects without destroy the cable at the same time. A sensor is used to collect the partial discharge signal, the cable insulation detection could be accomplished [].. Defect Making The testing cable is copper core with cross-linked polyethylene insulation tape armored PVC (polyvinyl chloride) sheathed flame-retardant power cable, the type is ZC-YJV, with rated voltage 8.7/ kv and specifications is 3 7 mm. The testing cables all are new cable have not been put into operation, before made detect. In order to guarantee the unicity of test variable, we made artificial defect model in cable joint after the testing cable has been confirmed that there is no partial discharge with OWTS partial discharge test. Three kinds of typical artificial defects are made separately at the middle of three 8-m cables with cold shrink joint. The armor layers and copper shielding layers of XLPE cable joint were well-connected. The specific defects are show in Figs. a-c: () Air gap in outer semi-conductive layer defect: the poor quality of cable or improper over stripping of outer semi-conductive layer may cause air gap. As shown in Fig. a, this defect can be simulated by scraping mm, mm and 7 mm gap on the outer semi-conductive layer; () Metal cusp at high potential defect: to simulate metal particle mixed on the core between insulation and compression coupling by accident, twin copper wire on the surface of core to form mm, 3 mm and mm tips. It is showed in Fig. b; (3) Too short or long lap of stress cone defect: simulate the improper installment that cause too long or

3 High voltage source Statistical Characteristics of Partial Discharge Caused by Typical Defects Tested cable (a) Air gap in outer semi-conductive layer defect Partial discharge analysis Partial discharge detector Data storage Fig. OWTS testing system schematic diagram. short lap of stress cone and outer semi-conductive layer. As shown in Fig. c, phase A represent too short lap of stress cone by mm, phases B and C represent too long lap of stress cone by mm, 7 mm. 3. Oscillating Voltage Test The test cable was connected to OWTS by high voltage connection cable, the cupper shielding layer joined OWTS grounding by one-point grounding. Calibration of discharge quantity is required for the test of partial discharge in XLPE cable. To get a more accurate apparent discharge magnitude, the test cable was injected by different quantity of calibration pulse signal by partial discharge calibrator after the testing circuit is connected. According to electromagnetic wave theory, the incident calibration pulse will refracted and reflected when it reached the end of cable. The calibration of apparent discharge magnitude could be realized by figuring out its calibration factor extracting peak value of incident and reflected impulse. Partial discharge test starts when the calibration is done. Applied oscillating voltage to main insulation of XLPE cable, increase voltage by step and the voltage should be no more than. U. Select two voltage classes above the partial discharge inception voltage to collect partial discharge signals. One hundred partial discharge tests had been done for each voltage class and the data have been saved for further analysis.. Test Results Analysis To study the statistical property of partial discharge (b) Metal cusp at high potential defect (c) Too short or long lap of stress cone defect Fig. The picture of three kinds of defect in cable joint. signal under oscillating voltage, three-dimensional statistical maps which base on statistical method for oscillating voltage phase feature are built for the three defects [7]. It is shown in Figs. 3-. By comparing the three-dimensional statistical maps of the same kind defect, for the defect of air gap in outer semiconductive layer, the severity positive increase with the length of air gap. The partial discharge inception voltage drops from.9 U to.7 U together with larger magnitude and number. For the defect of high potential metal tip, its discharge magnitude is little less than the former one while the defect of stress cone is the lowest one which has positive increase with the malposition. By comparing the three-dimensional statistical maps of three different kinds of defects, the developing process as well as the shape is vary from each other. The higher voltage classes, the larger magnitude and number of apparent discharge magnitude in partial discharge. Air gap in outer semiconductive layer and high potential metal tip, these two defects has rather acute partial discharge under high voltage classes. The bimodal characteristics showed up in corresponding maps, which based on the statistical method for oscillating voltage phase feature is a result of the amplitude in different period changed its phase when

Statistical Characteristics of Partial Discharge Caused by Typical Defects 33 8 ( 次数 ) ( 次数 ) ( 次数 ) 3 9 8 7 3 9 8 7 3 9 8 7 3.9 U.3 U. U Fig. 3 Phase A of air gap in outer semi-conductive layer defect. ( 次数 ) ( 次数 ) ( 次数 ) 9 8 7 3 9 8 7 3 9 8 7 3.7 U.9 U.3 U Fig. Phase B of air gap in outer semi-conductive layer defect. ( 次数 ) ( 次数 ) ( 次数 ) 8 9 8 7 3 9 8 7 3 x 9 8 7 3.7 U.9 U. U Fig. Phase C of air gap in outer semi-conductive layer defect. 8 ( 次数 ) ( 次数 ) ( 次数 ) 9 8 7 3 3 9 8 7 3 9 8 7 3.9 U.3 U. U Fig. Phase A of metal cusp at high potential defect.

3 Statistical Characteristics of Partial Discharge Caused by Typical Defects ( 次数 ) ( 次数 ) ( 次数 ) 9 8 7 3 3 9 8 7 3 9 8 7 3.9 U.3 U. U Fig. 7 Phase B of metal cusp at high potential defect. ( 次数 ) ( 次数 ) ( 次数 ) 8 9 8 7 3 9 8 7 3 9 8 7 3.9 U.3 U. U Fig. 8 Phase C of metal cusp at high potential defect. 8 8 ( 次数 ) ( 次数 ) ( 次数 ) 9 8 7 3 9 8 7 3 9 8 7 3.9 U.3 U. U Fig. 9 Phase A of too short or long lap of stress cone defect. ( 次数 ).. ( 次数 ) 3 ( 次数 ) 3 9 8 7 3 9 8 7 3 8 9 7 3.9 U.3 U. U Fig. Phase B of too short or long lap of stress cone defect.

Statistical Characteristics of Partial Discharge Caused by Typical Defects 3 ( 次数 ) ( 次数 ) ( 次数 ) 8 9 7 3 9 8 7 3 8 9 7 3.9 U.3 U. U Fig. Phase C of too short or long lap of stress cone defect. the oscillating voltage attenuation. For the defect of stress cone, it has not show bimodal characteristics because the apparent discharge magnitude and number of partial discharge is quite small.. Conclusions This paper make three artificial defects in the joint of kv XLPE, oscillating voltage is applied to the test cable and partial discharge signal which caused by defect has been detected. The three-dimensional statistical maps for partial discharge signal are made, statistical property of partial discharge under the oscillating voltage has been studied, conclusions are as below: () Oscillating voltage can stimulate the partial discharge of defect in the cable joint, and can detect it effectively; () Partial discharge will become severe when the oscillating voltage amplitude become larger, obvious bimodal characteristics can be seen in the three-dimensional statistical maps at the same time; (3) The distinguish differences lie in three-dimensional maps of three defects may lay a foundation for the further research in pattern recognition. References [] Guanghui, S., Xiaoliang, Z., and Haiqing,. 3. Statistical Analysis of kv Distribution Cable Fault in the Pearl River Delta Region. Electrotechnical Application : 3. [] Working Group.9. 977. After Laying Tests on High Voltage Extruded Insulation Cable System. Electra 73: 33-. [3] Boggs, S., and Densley, J.. Fundamentals of Partial Discharge in the Context of Field Cable Testing. Electrical Insulation Magazine (): 3-8. [] Junhua, L., and Shouzhi, C.. Study on Test Methods of XLPE Power Cable Rated up to 3 kv. Power System Technology (): 8-. [] Junhua, L., Liming, Y., and Jikang, S.. Review of Power Cable and Test Technology. High Voltage Engineering 3 (S): 8-. [] Deqiang, X.. Detection Technology of XLPE Power Cables. Transactions of China Electro Technical Society (): 7-8. [7] Petzold, F., and Beigert, M.. Experiences of PD Diagnosis on MV Cables Using Oscillating Voltages (OWTS). In Proceedings of Transmission and Distribution Conference and Exhibition: Asia and Pacific, -7. [8] Oyegoke, B., Hyvonen, P., and Aro, M. 3. Selectivity of Damped AC (DAC) and VLF Voltages in After-laying Tests of Extruded MV Cable Systems. Dielectrics and Electrical Insulation (): 87-8. [9] IEC (International Electrotechnical Commission). 998. Statistical Characteristic and Location of Partial Discharge Caused by Typical Defects in Power Cable under Damped Oscillation Voltage. Geneva: The Grid Technology. [] Chengwei, C.. Study of kv XLPE Cable Detection Using Oscillating Voltage. South China University of Technology. [] Hao, Z., Jiating, T., and Lizhi, Z. 8. Typical Case Analysis of Oscillating Wave Test System in Cable Partial Discharge Test and Localization in Power Cable. Electrical Apparatus 9 (): 3-. [] Shiyang, T. 9. PD Detection Technique in XLPE power Cables based on Oscillating Wave Test System. Electric Power (): 98-.

3 Statistical Characteristics of Partial Discharge Caused by Typical Defects [3] Rong, X., Jiankang, Z., and Benhong, O.. Dielectric Property Detection of kv XLPE Power Cables Using Damped AC Voltages. High Voltage Engineering 3 (7): 73-. [] Yi, F., Peng, L., and Mingtao, X. 9. Application of Oscillating Wave Testing System in the Cable Partial Discharge Detection. Distribution & Utilization (3): 7-9. [] Gulski, E., Wester, F. J., and Smit, J. J.. Advanced Partial Discharge Diagnostic of MV Power Cable System Using Oscillating Wave Test System. Electrical Insulation Magazine (): 7-. [] Gulski, E., Smit, J. J., and Seitz, P.. 998. PD Measurements On-site Using Oscillating Wave Test System. Electrical Insulation, Conference Record of the 998 IEEE International Symposium on 998, -3. [7] Wenzhi, C., Zhendong, G., and Xiang, S. 3. Statistical Characteristic and Location of Partial Discharge Caused by Typical Defects in Power Cable under Damped Oscillation. Voltage Power System Technology 37 (3): 7-.