Partial Discharge Theory, Modeling and Applications To Electrical Machines

Similar documents
CHAPTER 5 CONCEPT OF PD SIGNAL AND PRPD PATTERN

PARTIAL DISCHARGE MEASUREMENT ON ROTATING MACHINES

Characteristics of Insulation Diagnosis and Failure in Gas Turbine Generator Stator Windings

Analysis of Partial Discharge Patterns for Generator Stator Windings

PARTIAL DISCHARGE MEASUREMENT ANALYSIS ON RING MAIN UNIT

Further Experience in the Use of Existing RTDs in Windings of Motors and Generators for the Measurement of Partial Discharges

Why partial discharge testing makes good sense

Software System for Finding the Incipient Faults in Power Transformers

II. TRADITIONAL APPROACH OF PD MEASUREMENTS

Ramp Testing in Identifying and Preventing Insulation Failure

PARTIAL DISCHARGE MEASUREMENT

Specialists in HV and MV test and diagnostics. Testing in Substations

IMPORTANCE OF INSULATION RESISTANCE

CONTINUOUS ON-LINE SYSTEM FOR PARTIAL DISCHARGE MONITORING FOR HA1 AT CHE ROBEŞTI

Africa Utility Week Focus Day Substation Condition Monitoring Benefits of Ultrasound

Electrical Equipment Condition Assessment

Application of Polarisation Depolarisation Current (PDC) technique on fault and trouble analysis of stator insulation

International Journal of Advance Engineering and Research Development. Comparison of Partial Discharge Detection Techniques of Transformer

EXPERIENCE WITH ON-LINE PARTIAL DISCHARGE MEASUREMENT IN HIGH VOLTAGE INVERTER FED MOTORS

Practical Experience in On-Line Partial Discharge Measurements of MV Switchgear Systems

Condition Assessment of High Voltage Insulation in Power System Equipment. R.E. James and Q. Su. The Institution of Engineering and Technology

Ieee Guide For Partial Discharge Testing Of Shielded Power

A NOVEL APPROACH TO PARTIAL DISCHARGE MONITORING

WIRE AND CABLE ENGINEERING GUIDE

The Basics of Insulation Testing

TRANSFORMER OPERATIONAL PRINCIPLES, SELECTION & TROUBLESHOOTING

PROPAGATION OF PARTIAL DISCHARGE AND NOISE PULSES IN TURBINE GENERATORS

IRIS POWER TGA-B. Periodic Online Partial Discharge Monitoring Instrument for Turbine Generators and Motors

THE PROPAGATION OF PARTIAL DISCHARGE PULSES IN A HIGH VOLTAGE CABLE

RTD as a Valuable Tool in Partial Discharge Measurements on Rotating Machines

IRIS POWER PDTracII. Continuous On-line Partial Discharge Monitoring for Motors, Generators, Dry Type Transformers, and Air-Insulated Switchgear.

Dielectric response and partial discharge measurements on stator insulation at varied low frequency. Nathaniel Taylor

Impulse Testing as a Predictive Maintenance Tool

Basics of Partial Discharge. Prepared for 2015 Phenix RSM Meeting January 2015

Doble Solutions for Partial Discharge. Greg Topjian Solutions Manager

THE POWER OF LIFE. WinTech Partial Discharge based Predictive Intelligence of insulation system to eliminate power failure risk.

Investi ations Into the Use of Temperature Detectors as # tator Winding Partial Discharge Detectors

IRIS POWER PDTracII. Continuous On-line Partial Discharge Monitoring for Motors, Generators, Dry Type Transformers, and Air-Insulated Switchgear.

DEFERRING REPLACEMENT OF A 600 MVA, 345GRD Y/138GRD Y/ 13.8 kv SHELL TYPE WESTINGHOUSE AUTOTRANSFORMER

Stator Winding Partial Discharge Activity for Air- Cooled Generators

On-line Hydrogenerator Rotor Winding Condition Assessment Using Flux Monitoring. S.R. Campbell, G.C. Stone, M. Krikorian, G.

LOW VOLTAGE PWM INVERTER-FED MOTOR INSULATION ISSUES

Effect of Shielded Distribution Cable on Very Fast Transients

Hands-On Transformer Testing and Maintenance

Partial discharge diagnostics on very long and branched cable circuits

Testing and PD Diagnosis of MV Cable Systems with DAC Voltage Educational Session May St Pete Beach, Fl

For Medium Voltage Motors, Generators, Switchgear, Bus Duct and Cable Terminations

Measurement Of Partial Discharge (PD) In High Voltage Power Equipment

Power Factor Insulation Diagnosis: Demystifying Standard Practices

Knowledge Is Power SM Apparatus Maintenance and Power Management for Energy Delivery. Application of EMI Diagnostics to Hydro Generators

Advancements in online partial discharge monitoring and assessment of MV through EHV Substation assets

PERMANENT ON-LINE MONITORING OF MV POWER CABLES BASED ON PARTIAL DISCHARGE DETECTION AND LOCALISATION AN UPDATE

PARTIAL DISCHARGE MEASUREMENTS ON GENERATORS USING A NOISE GATING SYSTEM

Review of Partial Discharge and Dielectric Loss Tests for Hydropower Generator Bars

ON-LINE PARTIAL DISCHARGE TESTING OF SOME OF THE WORST PERFORMING CIRCUITS ON A UTILITY DISTRIBUTION SYSTEM

ONLINE OFFLINE B Y WIL L IAM H IG INBOT H AM,

ONLINE MONITORING OF TURN INSULATION DETERIORATION IN MAINS-FED INDUCTION MACHINES USING ONLINE SURGE TESTING

The importance of partial discharge testing throughout the development and operation of power transformers

A New Approach for Transformer Bushing Monitoring. Emilio Morales Technical Application Specialist Qualitrol

Insulation State On-Line Monitoring and Running Management of Large Generator

EFFECT OF INTEGRATION ERROR ON PARTIAL DISCHARGE MEASUREMENTS ON CAST RESIN TRANSFORMERS. C. Ceretta, R. Gobbo, G. Pesavento

Introduction. AC or DC? Insulation Current Flow (AC) 1. TECHNICAL BULLETIN 012a Principles of Insulation Testing. Page 1 of 10 January 9, 2002

Investigation of PD Detection on XLPE Cables

Current state of surge testing induction machines

Xu Xiao Ming, AP Services, March 2010 Machine services Life expectance analysis program (LEAP)

TECHIMP Technologies & Services for Diagnostics and Monitoring of High Voltage Assets

Insulation Testing Preventing Equipment Breakdown and Plant Shutdowns

Partial Discharge Inception and Propagation Characteristics of Magnet Wire for Inverter-fed Motor under Surge Voltage Application

Objective Methods to Interpret Partial-Discharge Data on Rotating-Machine Stator Windings

The Multi-Technology Approach to Motor Diagnostics

Case Studies of Electric Power Equipment Diagnostics Using Acoustic Emission

Technical White Paper

Relative Ability of UHF Antenna and VHF Capacitor Methods to Detect Partial Discharge in Turbine Generator Stator Windings

MONTRANO. Continuous monitoring system for power transformers

A1-209 EXPERIENCES IN IDENTIFICATION OF PARTIAL DISCHARGE PATTERNS IN LARGE HYDROGENERATORS

PORTABLE PARTIAL DISCHARGE MONITORING INSTRUMENT

The Generators and Electric Motor Monitoring and Diagnostics Systems

Rotary Machine Prognostic Based on Gamma Process

High Field Electrical Conduction and Breakdown in Solid Dielectrics

On-line Partial Discharge Assessment and Monitoring of MV to EHV Cables

Partial Discharge Detection For Condition Monitoring Of An 11-kV XLPE Cable-Part II

PARTIAL DISCHARGE DETECTION - AN OVERVIEW

Insulation resistance testing

Bring sense of Peace and Security to your equipment with Eaton Partial Discharge diagnostics capabilities

GENERATOR TESTING APPLICATION GUIDE. reliable. precision.

PD Testing Considerations for MV Plant Cables

Partial Discharge (PD) techniques for measuring the condition of ageing HV/MV switchgear

RESIDUAL LIFE ASSESSMENT OF GENERATOR TRANSFORMERS IN OLD HYDRO POWER PLANTS

Field Measurement of Transmission Cable Dissipation Factor

PATTERN CLASSIFICATION OF PARTIAL DISCHARGE IN LV WINDING OF 1- TRANSFORMER USING PCA

Application Note. Detection of Partial Discharge Using Ultrasound. Detection of Partial Discharge Using Ultrasound. Problem. iriss.

Partial Discharge Characteristics and Insulation Life with Voltage Waveform

Insulation resistance testing. A complete solution for every application.

Monitoring Solutions For Power Transformers, Reactors, Bushings and Instrument Transformers

Evaluation of Distribution Line Spacers Located Near the Coast

EE171. H.H. Sheikh Sultan Tower (0) Floor Corniche Street Abu Dhabi U.A.E

Simultaneous Partial Discharge and Tan Delta Measurements: New Technology in Cable Diagnostics

ABB Power Products Service

Analysis of Off-Line and On-Line Partial Discharge in High Voltage Motor Stator Windings

Simulation Model of Partial Discharge in Power Equipment

Transcription:

Partial Discharge Theory, Modeling and Applications To Electrical Machines V. Vahidinasab, A. Mosallanejad, A. Gholami Department of Electrical Engineering Iran University of Science and Technology (IUST) TEHREAN - IRAN Abstract: Partial discharge monitoring is an effective on-line predictive maintenance test for motors and generators, as well as other electrical distribution equipment. The benefits of on-line testing allow for equipment analysis and diagnostics during normal production. Corrective actions can be planned and implemented, resulting in reduced unscheduled downtime. This paper will present a theory to promote the understanding of partial discharge technology, as well as various implementation and measurement techniques that have evolved in the industry. Then modeling and partial discharge modeling in electrical machines will be introduced. At last traditional partial discharge test methods in electric machines will compare to new method of partial discharge monitoring and corrective actions will interpret. Key Words: PD, Modeling, Online Detection, Electrical Machines 1 Introduction Reliable manufacturing operations will always be concerned with process production motors. Comprehensive programs to maintain electrical equipment for peak performance have been recommended and implemented at various plants. Detailed motor failure analysis has been completed; resulting in the identification of approximately 30% of failure causes being related to electrical failures [1]. The IEEE publication, "IEEE P1434 - Guide to Measurement of Partial Discharges in Rotating Machinery" [2] identifies similar failure causes for motor systems. These include thermal, electrical, environmental and mechanical stresses. These factors correlate to the two studies, since they result in the stator ground and turn failure (EPRI Study); as well as can be interpreted as normal deterioration (IEEE Study). The next section provides a review of partial discharge theory. Then in third section partial discharge testing related to traditional testing methods will be introduced. After that corrective actions for MV motors is presented and in last section conclusions are said. 2 Partial Discharge Theory Partial discharge theory involves an analysis of materials, electric fields, arcing characteristics, pulse wave propagation and attenuation, sensor spatial sensitivity, frequency response and calibration, noise and data interpretation [3]. In an effort to promote a better understanding of partial discharge (PD), this paper attempts to provide simplified models and relates the characteristics of these models to the interpretation of PD test results. First, we will present a few technical concepts relating to partial discharges. Partial Discharge can be described as an electrical pulse or discharge in a gas-filled void or on a dielectric surface of a solid or liquid system. This pulse or discharge only partially bridges the gap between phase to ground, and phase-to-phase. These discharges might occur in any void between the copper conductor and the grounded motor frame reference. The voids may be located between the copper conductor and wall, or internal to the itself, between the outer wall and the grounded frame, or along the surface of the. The pulses occur at high frequencies; therefore they attenuate quickly as they pass to ground. The discharges are effectively small arcs occurring within the system, therefore deteriorating the, and can result in eventual complete failure. The possible locations of voids within the

system are illustrated in Fig.1. The other area of partial discharge, which can eventually result, is tracking. This usually occurs on the surface. These discharges can bridge the potential gradient between the applied voltage and ground by cracks or contaminated paths on the surface. This is illustrated in Fig.2. The above can be illustrated by development of a simplified model of the partial discharges occurring within the system. Copper Conductor copper and and iron core exposed to the partial discharges, acts to attenuate the signal, therefore weakening this damaging signal that we are trying to identify at our sensor locations. In addition, the attenuated partial discharge signal can be masked by sources of electrical noise, which shall be reviewed later in this paper. Simplified Insulation Model Fig.3 Simplified Insulation Model and Model for an Electronic Attenuator Void internal to The above concept of the system being an effective attenuator circuit gives rise to critical detection issues, such as: Fig.1 PD within Insulation System Copper Conductor Contaminated Insulation Cracks Contaminated Insulation Surface Fig.2 Surface Partial Discharge Sensor locations and sensitivity Measurement system response to attenuated signals Noise detection and elimination 2.2 Partial Discharge Void Model Simplified models of the area of the void have been described as consisting of capacitors only. A review of the progressive failure mode of these voids indicates an additional resistive component in parallel with the capacitive component. Therefore the model of the partial discharge void is similar to that of the medium itself. 2.1 Insulation System Model A simplified model of an system can be represented by a capacitance and resistance in parallel [4]. This is the concept employed in the use of power factor testing of systems. The leakage current is split between the resistive and capacitive paths. The power factor is the cosine of the phase angle between the total leakage current and the resistive component of leakage current [5]. The above model is also used for attenuator circuits in electronics [6]. Signal attenuation results in reducing the amplitude of the electrical signal. This underlies the problem with partial discharge detection. The medium, which is being Simplified PD Void Model Fig.4 Simplified Partial Discharge Void Model Actual failure modes have indicated a drop in partial discharge intensity shortly prior to complete failure. This would occur when the internal arcing had carbonized to the point where the resistive component of the model was low enough to prevent a build-up of voltage across the void. This new low

resistive component would also allow higher current flows, and additional heating and resultant damage. The above model, including the resistive component correlates to the actual failure mode of a partial discharge void, with the resistive component passing more leakage current as the partial discharges increase with time. One form of this resistive component is visible tracking on the surface of. An explanation of tracking, and how surface partial discharges are related to the development of tracking follow [4]: "Tracking damage has been traced entirely to the locally intense heat caused by leakage currents. These currents flow through any contaminated moisture film on the bridging insulating surface. As long as this film is fairly broad and continuous, the heat associated with the leakage current is spread over a wide area and is dissipated. However, heating promotes film evaporation. This causes the film to break up into small pools or islands. Each break in the film tends to interrupt a segment of the leakage current, causing a tiny arc. Even though the arc is small, severe local heating results. The intense heat of the leakage current arc is sufficient to cause a molecular and chemical breakdown of the underlying. On organic materials, a frequent by-product of arcing is carbon." The above "tiny arc" along the surface can be represented by partial discharge activity. Fig.5 illustrates the failure mode of deteriorated related to the intensity of partial discharge measurements. PD Intensity PD drop before final failure Insulation Deterioration Failure Fig.5 PD Versus Insulation Failure Mode At the point near eventual failure, the tracking and resistive component of the have increased to the point where partial discharges have been reduced, since the "tiny arcs" have caused the carbonization and tracking, therefore providing a direct path for current flow. At this point, evidence of deterioration is usually detected by traditional methods of resistance, or megger testing. For the above reason, partial discharge on-line testing and traditional resistance testing are complimentary. On-line partial discharge testing can detect in the progressive phases of deterioration, with trending identifying problems long before eventual failure. Traditional resistance testing provides a "current-state" of the system. With the development of the above models, we can illustrate a complete model of the various system discharges represented in Fig.1. Fig.6 is be used to provide an understanding of partial discharge activity. Copper Conductor copper and Void internal to and iron core Internal void Copper Conductor Fig.6 Insulation System Partial Discharge Model 3 Partial Discharge Testing Related To Traditional Testing Methods Table 1 illustrates the relative relationships between the results of partial discharge testing and traditional testing methods. The model, contained in the first column, illustrates the internal copper conductors, the outer surface and various formations of voids within the. The second column states the condition. The third, forth and fifth columns indicated the expected results from the following traditional testing methods: Insulation Resistance Testing or "Megger Test" which is at a reduced DC voltage, Polarization Index Test (1 and 10 minute readings of the resistance test to equalize the effects of humidity and temperature) and High-Potential Testing (higher DC voltage test with leakage current monitored). The fifth column includes the expected results from Partial Discharge Testing. For

considered "Good" or "Marginal" the results are similar for all test methods. For which is "Dry but delaminated", traditional test methods will provide a false sense of a "Fair" condition; whereas partial discharge testing indicates the presence of internal voids. "Poor" or "Unacceptable" conditions can not be differentiated with traditional testing methods; whereas partial discharge testing identifies the regions of voids, and the appropriate corrective actions. For "Near-Failure" conditions, partial discharge arcing may have progressed to the point where permanent damage, or tracking, has occurred; therefore the level of partial discharges has decreased. This is also illustrated in Fig.5. During this condition, traditional test methods more accurately reflect the condition, whereas a High-Potential traditional test may cause failure during the test period. For this reason, trending is recommended for the first year of partial discharge testing. 4 Data Interpretation And Corrective Actions Of MV Motors Table 2 summarizes the data interpretation and recommended corrective actions. The first column includes the partial discharge results. This is followed by the possible root-cause, based on the partial discharge levels and the regions of associated voids. The next two columns include the short-term and long-term recommendations. The root causes vary from normal partial discharges to significant regions of voids within the system. Concerning recommendations, trending is recommended within a 3 to 6 month period at the first indication of substantial partial discharges. In most cases the root cause and partial discharge activity is comparative except for the situation when the is old and shows signs of external wear, or if there is evidence of surface tracking. These situations may indicate at a "nearfailure state where the partial discharge arcing has progressed to the point where permanent carbonization, or tracking, has occurred to the system. In this case it is recommended to schedule an outage for traditional resistance testing, and possible installation of permanent partial discharge sensors for improved on-line measurements. 5 Conclusions Partial discharge monitoring is an effective on-line predictive maintenance test for motors and generators, as well as other electrical distribution equipment. The benefits of on-line testing allow for equipment analysis and diagnostics during normal production. Corrective actions can be planned and implemented, resulting in reduced unscheduled downtime. Understanding of partial discharge theory allows for improved interpretation of results, and the benefits of such measurements. Data interpretation and corrective actions can be clearly identified with cost effective field corrections implemented, prior to further equipment deterioration. Partial discharge monitoring technology fully satisfies the cornerstone of a maintenance program designed to address the critical process support equipment. The technology has advanced, with improvements resulting in a minimal initial investment, thereby allowing for partial discharge testing becoming a part of everyday predictive maintenance. References: [1] G. Paoletti, A. Rose, "Improving Existing Motor Protection for Medium Voltage Motors," IEEE Transactions on Industry Application, May/June, 1989. [2] IEEE standard 1434-2000, IEEE Trial Use Guide to the Measurement of PD in Rotating Machinary,, New-york, Aug. 16 th 2000. [3] R. Bartnikas, "Partial Discharges, Their Mechanism, Detection and Measurement", IEEE Trans. On Dielectrics and Electrical Insulation, Oct. 2002. [4] D. Fink, H. W. Beaty, Standard Handbook for Electrical Engineers, Pages 4-117, 118, McGraw-Hill Book Company, 1987. [5] Westinghouse Electrical Maintenance Hints, Pages 19-14 and 15, and Page 7-23, Westinghouse Electric Corporation Printing Division, Trafford, Pa, 1976. [6] J. Millman, H. Taub, Pulse, Digital and Switching Waveforms, McGraw-Hill Book Company, 1965.

Table 1 Partial Discharge Testing related to Traditional Testing Methods Insulation Megger Polarization High-potential Partial Discharge Initial Model Condition Test Index Test Test Testing Good High Good Linear leakage current vs. voltage is minimal Unmeasurable partial discharge activity Marginal Dry But delaminated Poor Cleaning or Overhaul Required Fair False Fair result Low Fair False Fair value Poor Linear leakage current vs. voltage is stable False linear leakage current vs. voltage High leakage current. Maybe required to limited test voltage. Minimal discharge activity, balanced both positive and negative discharge Partial discharges observed, therefore accurately showing problems which are missed by traditional tests High positive polarity discharges indicate probable surface tracking Unacceptable Major Repair or Rewind Requested Near-Failure condition PD arcing has caused carbon tracking Low Very low Poor Very low Potential failure during testing High leakage current and probable failure during testing High negative polarity discharges indicate internal voids near the copper conductor. Minimal partial discharge activity. Partial discharge arcing has progressed to the point where permanent damage (tracking) had occurred. Internal copper conductor Insulation void experiencing internal partial discharge Outer surface Insulation Model Description Internal copper conductor Surface tracking resulting from partial discharges Outer surface

Table 2 Motor Partial Discharge Data Interpretation & Corrective Actions Possible Root-Cause Short Term Corrective -PD site Actions Partial Discharge Results Long Term Corrective Actions Moderate to low partial discharge magnitude and repetition rate Normal Partial Discharge Beginning of PD activity Insulation near failure At first indication repeat on-line testing in 3 months If is old and show signs of external wear, or any evidence of surface tracking, then scheduled outage for traditional resistance testing. If trending is level, extend on-line testing to 6 months, or as scheduled. If is near failure, traditional testing should indicate low resistance values. Trending indicated increasing partial discharge activity Slot/Surface tracking PD Internal voids Winding looseness if indicates by the "Load Variation Test" (Increase in positive polarity pulses with increased loading) Repeat on-line testing in 1 to 3 months, depending on the severity of the increase. If the trend increase is substantial, schedule outage and test monthly until outage. Add permanent sensors if required to improve PD testing. During outage complete offline/ Incremental testing and traditional resistance testing. If positive polarity, schedule field or shop cleaning and reinsulating with endturn bracing. If negative polarity, budget for major rewind and schedule outage. If winding loose-ness indicated, schedule for removal and shop rewedging. Positive Polarity pulses prevalent Voids in the slot between and iron Same as above Schedule field or shop cleaning and reinsulating with endturn bracing Balance of Positive and Negative pulses Voids internal to system Same as above Budget for rewind and major outage