Measurement Of Partial Discharge (PD) In High Voltage Power Equipment

Similar documents
Simulation Model of Partial Discharge in Power Equipment

Simulation of Partial Discharge in High Voltage Power Equipment

High Field Electrical Conduction and Breakdown in Solid Dielectrics

Partial Discharge Analysis of a Solid Dielectric Using MATLAB Simulink

PARTIAL DISCHARGE MEASUREMENT ANALYSIS ON RING MAIN UNIT

Basics of Partial Discharge. Prepared for 2015 Phenix RSM Meeting January 2015

Partial Discharge Patterns in High Voltage Insulation

The Effect of Practical Voltages on Maximum Amplitude of Partial Discharge with Considering Different Number of Cavities

CHAPTER 5 CONCEPT OF PD SIGNAL AND PRPD PATTERN

Partial Discharge Classification Using Novel Parameters and a Combined PCA and MLP Technique

International Journal of Advance Engineering and Research Development. Comparison of Partial Discharge Detection Techniques of Transformer

The University of New South Wales. School of Electrical Engineering and Telecommunications. High Voltage Systems ELEC9712. Appendix Partial Discharge

Design and construction of double-blumlein HV pulse power supply

CONDITION MONITORING OF MEDIUM VOLTAGE ELECTRICAL CABLES BY MEANS OF PARTIAL DISCHARGE MEASUREMENTS

PARTIAL DISCHARGE MEASUREMENT AS A DIAGNOSTIC TOOL FOR CURRENT TRANSFORMER

Extended analysis versus frequency of partial discharges phenomena, in support of quality assessment of insulating systems

Characteristics of Insulation Diagnosis and Failure in Gas Turbine Generator Stator Windings

Generation of Sub-nanosecond Pulses

USING DAMPED AC VOLTAGES

3.2 Measurement of high voltages

PARTIAL DISCHARGE MEASUREMENT ON ROTATING MACHINES

Detection of Partial Discharges and its Effect on Solid Insulation used in High Voltage Cable

Testing and PD Diagnosis of MV Cable Systems with DAC Voltage Educational Session May St Pete Beach, Fl

PARTIAL DISCHARGE DETECTION - AN OVERVIEW

Dielectric response and partial discharge measurements on stator insulation at varied low frequency. Nathaniel Taylor

[Mathur* et al., 5(6): June, 2016] ISSN: IC Value: 3.00 Impact Factor: 4.116

Partial Discharge Theory, Modeling and Applications To Electrical Machines

Comparison of measurement methods for partial discharge measurement in power cables

High-Voltage Test Techniques

PARTIAL DISCHARGE MEASUREMENT

PARTIAL DISCHARGE MEASUREMENT ON RING MAIN UNIT

High Frequency Voltage Stress. Presented by: Flore Chiang Date: March 30, 2012

Practical aspects of PD localization for long length Power Cables

Insulation Testing Preventing Equipment Breakdown and Plant Shutdowns

IJSRD - International Journal for Scientific Research & Development Vol. 2, Issue 04, 2014 ISSN (online):

Calculation of Transients at Different Distances in a Single Phase 220KV Gas insulated Substation

MAHALAKSHMI ENGINEERING COLLEGE

REVIEW: PARTIAL DISCHARGE TEST FOR INSULATOR

CHAPTER 2. v-t CHARACTERISTICS FOR STANDARD IMPULSE VOLTAGES

SF 6 Capacitive Voltage Divider

Condition Assessment of High Voltage Insulation in Power System Equipment. R.E. James and Q. Su. The Institution of Engineering and Technology

Advancements in online partial discharge monitoring and assessment of MV through EHV Substation assets

THE PROPAGATION OF PARTIAL DISCHARGE PULSES IN A HIGH VOLTAGE CABLE

High Voltage Engineering

Comprehensive modeling of Dry type foil winding transformer to analyse inter turn insulation under Lightning Impulse Voltage

Gas-Insulated Metal-Clad Switchgears Express-Diagnostics Method on Partial Discharge Characteristics

Lecture 36 Measurements of High Voltages (cont) (Refer Slide Time: 00:14)

Doble Solutions for Partial Discharge. Greg Topjian Solutions Manager

PATTERN CLASSIFICATION OF PARTIAL DISCHARGE IN LV WINDING OF 1- TRANSFORMER USING PCA

HVDC Transmission. Michael Muhr. Institute of High Voltage Engineering and System Performance Graz University of Technology Austria P A S S I O N

THE POWER OF LIFE. WinTech Partial Discharge based Predictive Intelligence of insulation system to eliminate power failure risk.

Type 297, High-Voltage Mica Capacitors Corona-free Mica Coupling Capacitors for Medium-Voltage PDA s

Partial Discharge Characteristics of Micro-gaps

OPTICAL EMISSION CHARACTERISTICS OF HELIUM BREAKDOWN AT PARTIAL VACUUM FOR POINT TO PLANE GEOMETRY

GUJARAT TECHNOLOGICAL UNIVERSITY

ROEVER ENGINEERING COLLEGE ELAMBALUR, PERAMBALUR DEPARTMENT OF ELECTRICAL & ELECTRONICS ENGINEERING

MODELING OF PARTIAL DISCHARGE IN TRANSFORMER WINDINGS AND ITS DETECTION

Electric Stresses on Surge Arrester Insulation under Standard and

ONLINE OFFLINE B Y WIL L IAM H IG INBOT H AM,

OPTIMIZATION OF ON-SITE PD MEASUREMENTS AND EVALUATION OF DIAGNOSTIC PARAMETERS FOR ASSESSING CONDITION OF DISTRIBUTION CABLE SYSTEM ELPIS J SINAMBELA

International Journal of Advance Engineering and Research Development. Analysis of Surge Arrester using FEM

Modeling and Analysis of a 3-Phase 132kv Gas Insulated Substation

process has few stages and is highly repeatable. Excellent mechanic properties and electro-magnetic compatibility. Planar design gives the height lowe

Electric Field Analysis of High Voltage Condenser Bushing

1409. Comparison study between acoustic and optical sensors for acoustic wave

A New Approach for Transformer Bushing Monitoring. Emilio Morales Technical Application Specialist Qualitrol

HARMONICS CAUSES AND EFFECTS

High Voltage Engineering

In power system, transients have bad impact on its

Prognostic Modeling for Electrical Treeing in Solid Insulation using Pulse Sequence Analysis

Diagnostic testing of cast resin transformers

Africa Utility Week Focus Day Substation Condition Monitoring Benefits of Ultrasound

PULSED BREAKDOWN CHARACTERISTICS OF HELIUM IN PARTIAL VACUUM IN KHZ RANGE

High Voltage Testing. Team 5: Justin Bauer, Matt Clary, Zongheng Pu, DeAndre Dawson, Adam McHale

Fault Detection in Transformer Using Frequency (Sweep) Response Analysis

DEPARTMENT OF ELECTRICAL ENGINEERING DIT UNIVERSITY EHV AC AND DC TRANSMISSION

Simplified Approach to Calculate the Back Flashover Voltage of Shielded H.V. Transmission Line Towers

Introduction. AC or DC? Insulation Current Flow (AC) 1. TECHNICAL BULLETIN 012a Principles of Insulation Testing. Page 1 of 10 January 9, 2002

Breakdown in short rod-plane air gaps under positive lightning impulse stress

Design and performance analysis of transmission line-based nanosecond pulse multiplier

A Review on Partial Discharge Behavior in Insulators

Sessile Water Droplets on Insulating Surfaces Subject to High AC Stress: Effect of Contact Angle.

700 Series AC Dielectric Test Sets

PD ANALYSIS OF GAS INSULATED MEDIUM VOLTAGE SWITCHGEAR DURING FACTORY ASSEMBLY AND SITE COMMISSIONING

10. DISTURBANCE VOLTAGE WITHSTAND CAPABILITY

Evaluation and Limitations of Corona Discharge Measurements An Application Point of View

Investigation of Inter-turn Fault in Transformer Winding under Impulse Excitation

LESSON PLAN LP-EE Sub Code: EE 2353 Sub Name: HIGH VOLTAGE ENGINEERING Unit: I Branch: EEE Semester: VI

Siemens Transformer Technology Seminar Low Partial Discharge Transformers

Corona Current-Voltage Characteristics in Wire-Duct Electrostatic Precipitators Theory versus Experiment

Software System for Finding the Incipient Faults in Power Transformers

IN HOUSE CALIBRATION OF PD DETECTOR SYSTEM FOR FIELD TEST RESULT RELIABILITY

Coherence and time-frequency analysis of impulse voltage and current measurements

AC CREEPAGE DISCHARGES IN SF 6, CO 2, N 2 AND SF 6 -CO 2 AND SF 6 - N 2 MIXTURES

Why partial discharge testing makes good sense

Increasing arc length Current [A]

ALLOWABLE LIMITS TO SHORT TIME VOLTAGE DROPS IN HV WITHSTAND TESTS

CONTINUOUS ON-LINE SYSTEM FOR PARTIAL DISCHARGE MONITORING FOR HA1 AT CHE ROBEŞTI

PD Diagnostic Applications and TechImp solutions

Design and Fabrication of Tesla Coil

Transcription:

First International Conference on Emerging Trends in Engineering, Management and Scineces December 28-3, 214 (ICETEMS-214)Peshawar,Pakistan Measurement Of Partial Discharge (PD) In High Voltage Power Equipment Engr.Manzoor Ahmad Khan Unieversity of Engineering and Technology Peshawar,Peshawar,KPK, Pakistan manzoor698@gmail.com Dr. Amjadullah Unieversity of Engineering and Technology Peshawar,Peshawar,KPK, Pakistan Amjad67@gmail.com ABSTRACT In high voltage (HV) power equipment the quality of insulator plays vital role in power systems. For insulation purpose various type of materials are used in different states like solid, liquid and gaseous form. Due to the application of high voltages, aging factor and cumulative effect of electrical, chemical and mechanical stresses, the quality of these materials degrades with the passage of time. These insulators are not in pure form and having some impurities, due to which small air bubbles are created inside the insulator which are called voids. Due to these voids the strength of insulators weakens and become the cause of Partial Discharge (PDs). Due to the presence of PDs originated at voids in insulators, the quality of such insulation degrades which results in the insulation failure in HV power equipment. In this work the PD activity of an equivalent electric model circuit having void inside solid insulator has studied. A small (air bubble) cylindrical void inside the solid insulator is placed under uniform electric field using parallel plane arrangement. In this study the maximum amplitude of PDs, the frequency of PDs, The duration of PDs and the number of PDs generated in a cycle is measured. In addition, relationship between void parameter and induced charge for cylindrical void is discussed. Keywords (Partial Discharge, PDs, Insulator failure, PDs detection, PDs measurement) 1.Introduction In high voltage (HV) power systems the insulation is one of the most important parameter to determine the performance of power services [1-8]. In industries most of the HV equipments e.g. transformers, switch gears, HV carrying and cables rotating machines (motors and generator) are used, for the smooth operation of power systems the reliability of these equipments is very necessary. Partial discharge mostly occurs in the insulation of these equipments. The insulators of these equipments is designed, monitored, cared and safely handled under the supervision of expert power engineer [6]. For insulation purpose various types of materials are used in different states like solid, liquid and gases form. Due to the application of high voltages, aging factor and cumulative effect of electrical, chemical and mechanical stresses, the quality of these materials degrades with the passage of time [1-8]. These insulators are not in pure form and having some impurities, due to which small air bubble are created inside the insulator which is called void. Due to these voids, the strength of insulators weaken and become the cause of partial discharge (PDs). Partial Discharges is the phenomena, in which an electric spark is generated inside the insulation medium of equipment placing under the HV electrode. PDs occur wherever the applied electric field strength exceeds the breakdown electric field strength of insulation material used in insulator. Due to the presence of PDs originated at voids in insulators, the quality of such insulation degrades which results

in the insulation failure in HV power equipment s. Keeping the above reasons in view, PDs detection and measurement are required to predict the failure of insulation and to ensure a reliable operation of High voltage power equipment s. Throughout the decades different techniques have been developed for detection, measurement and behavior study of PDs inside the insulation model. Many authors are presented their work about the detection and measurement of PDs as well as study the characteristics of PDs [1-8]. In this work a model is suggested which is based on induced charge. The transients associated with partial discharges in voids can be described in terms of the charges induced on the terminal electrodes of the system [4]. This work discussed the relationship between the induced charge and the properties which are usually measured. The method is illustrated by applying it to a cylindrical void located in a sample of epoxy resin, which is used as dielectric material in most of the equipments. In this work, the relation between amplitude and the number of PDs with the applied high voltages. 2. Electrical Equivalent Circuit for PDs measurement. The equivalent circuit diagram for the detection of partial discharge is shown in Fig. 1.it consists of high voltage source (Vs), Low Pass Filter (Z),measuring capacitor (Cm), Coupling Capacitor (Cc), Solid insulation model (Ct), measuring instrument (MI) and high pass filter PD detector circuit parallel combination of resistor, capacitor and inductor [1-3]. In this model, the test object is shown in the form of small capacitances in which C3 represent the void capacitance, C2 represent the remaining series (upper and lower) capacitance of the solid insulator and C1 represent the remaining discharge free capacitance of the material. Figure 1. Electrical equivalent circuit model. Such circuit is energized with the high voltage AC source. The applied voltage source energized the void within the test object, the charge q stored in the void creates an opposite potential to the instantaneous applied voltage. A partial discharge occurs if the difference between the instantaneous voltage V3 and stored potential reaches the break down field of void. The voltage across the capacitors C1, C2 and C3 are V1, V2 and V3 respectively. The calculated voltage across the void C3 is 3 = 1 (1)

The voltage across the capacitance C1, C2 and C3 are V1, V2 and V3 respectively. The apparent charge measured across the C3 during the Partial Discharge activity inside the solid insulator material is given by the empirical formula: = 1 2 (2) By using the above apparent charge the design model is fail to gives the accurate results as it does not include all the relevant void parameter. To overcome this problem Pederson has suggested a model which is based on the induced charge [4]. = ℇ ℇ ( ) (3) Whereas S is void geometric factor, ℇ is permittivity of free space, ℇr is relative permittivity of dielectric, V is volume of cylindrical void and is given by πr 2 h, r is radius of void, h is height of void, E i is inception voltage for streamer inception, E l is limiting field for ionization and ΔZ is reciprocal of space between two electrodes is (1/d). The value of (E i -E l ) can be calculated by Equation. (4) = 1 + (4) Where H is constant characteristics of void, p is pressure of air inside void and r is radius of cylindrical void El/p is taken 24.2 v/pa. m. The important constant parameter value are given in the Table 1. Table 1 Sr. No Parameter name Symbol Value Unit 1 Permittivity of free space Ɛ 8.852 X 1-12 F/m 2 Relative permittivity of dielectric (for epoxide resin) Ɛ r 3.5 3 Constant characteristics of gas H 8.6 Pa.5 m.5 4 Pressure p 1 5 N/m2 5 Gap spacing between electrodes d.2 m 3. Design description for partial discharge activity for simulation in MATLAB Partial discharge is limited to localized region of insulation Material in high voltage (HV) power equipments. The partial discharge phenomena usually occurs within the void, cracks, in air cavity inside the liquid insulation or usually at the boundaries of different type of insulation material, poor conductor profile, contamination and floating metal element in high voltage devices. To evaluate the basic quantities of the PD pulse, the equivalent capacitor circuit of insulating material is taken under test for this work. In test system C3 represent the void capacitance, C2 represent the remaining series (upper and lower) capacitance of the solid insulator and C1 represent the remaining discharge free capacitance of the material. Normally the values of C1 is very large then C2 and C2 is very large then C3.A cube of epoxy resin (having size.3 meter in length,.3 meter in width and.5 meter in height) is considered as the sample for test. A cylindrical void of height.4 meter and radius.2 meter is taken. The capacitance for the above sample is calculated C1 = 4.836 x 1-12 f, C2 = 3.889 x 1-13 f and C3 = 2.75 x 1-14 f. 4. Generation of partial discharge pulse To elaborate the PD pulse generation inside the insulating material placed in between the two parallel plate electrodes is considered shown in Figure 3. By applying the high voltage across the test object, the

potential appears across the void depends on the entire arrangement. The capacitance across the void C3 is calculated as C3 = ℇ, the voltage across C3 is 3 = 2, the capacitance of healthy part of insulator is C2 calculated by the equation 2 = ℇ ℇ, where A1 is area of the surface of void, d is the distance between electrodes and h is height of the cylindrical void. The voltage across C2 is V2=V1-V3. The electric field is denoted by (E). The electric field intensity is measured by =. As applied voltage is sinusoidal so if the rate charge accumulation within the void is faster than the increase rate of applied voltage, the field intensity within the cavity falls quickly due to accumulation of charge, so the amount of field required to maintain the discharge is lesser then that for PD inception. Due to the fast accumulation of charges across the cavity, the field intensity goes below PD breakdown value and the generation of PDs stops. (i) (ii) d + + + + + + + - - - - E r E o r q h E C2 C3 Vs V2/2 V3 + + + + C2 V2/2 - - - - - - - Figure 2. (i) Void representation (ii) Equivalent capacitance circuit Consider that the q is the charge stored at the surface of void, the surrounding of cavity is assumed to be perfect insulator that charge q will remain store in void, which creates a potential across the cavity so the electric field is measured as = (5) 1 ------- Vd ------- V3 1 5 5 ɸ 1 ɸ 2 ɸ 3 ɸ n -5-5 -1 5 1 15 2 25 3 35 4-1 Angle ( ) Figure 3 Applied voltage and potential across the void

The partial discharge takes place whenever the field produced across the void is greater than PD break down Electric field which means the applied field must follow the below relation. E void =E l > PD break down (6) The Figure 3 shows the applied voltage (V3) and actual apparent voltage (Vd) across the void. The field intensity across the cavity after phase ɸ1 is greater than the breakdown potential required for occurring of PDs, therefore at angle ɸ1 a PD pulse is generated. Now the void is charged by q1 which means that the amount of potential required to discharge the void must be greater than the previous value as calculated by the equation(6). 5. Result and discussion 3 =. (7) To study the PD activity of insulation material simulation of MATLAB model is considered in this work. To study the PD activity inside the insulating materiel an increasing voltage is applied from to 1 kv to the void model design in MATLAB. It is noted that a very few PDs are found by the application of -4kV to cylindrical void model. The field intensity of cavity does not exceed by the breakdown strength of air inside void below the application of 5kV applied voltage. The PDs inception voltage is found at 4.7 kv of applied high voltage. By increasing the applied voltage beyond 5kV the number of PDs increases. The generation of PDs is observing by applying the voltage up to 1kV. The number of PDs is counted by applying a cutoff value of 5 percent of the maximum amplitude of PDs observed from the corresponding applied voltage. It is observed that the amplitude of PDs is changes by varying the applied voltage, also it is observed that a very small amplitude signal is produced by the application of just above 4kV from which it is considered that the inception voltage and breakdown voltage is found ahead of the applied high voltage 1kV. The amplitude of PD is measured by the equation (8). = cos( ) (8) Whereas the q is the apparent charge inside the void, Cc is the coupling capacitance, = + 1 and = ( + 1/4 ). 5 V PDs pulses by applying High Voltage -5 2 x 1V -5 5 1 15 2 25 3 35 4-2 Phase angle (ϴ) Figure 4

By applying the 5kV on the solid insulator test material total 89 PDs are observed. The observed PDs as shown in the Figure 4 are half in the first half cycle and half in the second half cycle. In the first half cycle positive PD pulse produce when applied voltage is increasing up to 9 degree and become negative while the applied voltage going down. It is also observed that the PD amplitude is greater in the start because of the more time taken to reach the break down field intensity due to the accumulation of charge (q) which is calculated by equation (3) as compared to the peak of applied voltage signal. Also it is observed that the minimum No of PDs is seen at the stable value of applied voltage. In order to study the design test model a complete cycle of applied voltage from -1kV is taken under consideration whose result for 5kV is shown in Figure 4 and Figure 5. Vin 5 High Voltage source sample size = -5 5 1 15 2 25 3 35 4 time(sec/sample Voltage(V) 2 Potential across the Void (vd) Vs = 5KV -2 5 1 15 2 25 3 35 4 time(sec/sample Voltage(V) 2 x 1-5 Amplitude of PD (Vpd) Vs = 5KV -2 5 1 15 2 25 3 35 4 time(sec/sample Figure 5 The results are shown in table 2 after analyze the simulation of design equivalent model in MATLAB. It shows that the no of PDs and amplitude of PDs is varying with changing the applied voltage, it is noted that the no of PDs and Amplitude of PDs varying by changing the size of void parameter, which results that by measuring the PDs amplitude and quantity we easily detect the quality degradation with passage of time. Applied Voltage Vs (kv) Table 2 No of PDs/Cycle 1 1 8.9E-6 2 17 9.9E-6 3 29 1.12E-5 4 38 1.3E-5 5 89 1.49E-5 6 117 1.6E-5 7 147 1.75E-5 8 175 1.81E-5 9 24 1.62E-5 1 234 1.4E-5 Amplitude of PDs Generated/ Cycle

The behavior of the number of PDs and its amplitude collected in Table 2, the result of above simulation is shown in graphic form in Figure 6 and Figure 7. It is observed that the amplitude of the PDs is first increased by increasing the applied high voltage up to 8kV and then decreases by further increase in the applied high voltage. PD amplitude (V) 2.E-5 1.8E-5 1.6E-5 1.4E-5 1.2E-5 1.E-5 8.E-6 6.E-6 4.E-6 2.E-6.E+ 1 2 3 4 5 6 7 8 9 1 Applied voltage (kv) 1 Figure 6 In this study it is observed from Figure 6 that amplitude of PD is changing with the variation of applied voltage. The amplitude of PD Initially rises with the application of high voltage from 1kV to 7kV and then decay from 8kV onward up to 1kV. It shows that the amplitude of PD is a function of applied voltage. 25 Number of PD per cycle 2 15 1 5 1 2 3 4 5 6 7 8 9 1 Applied voltage (kv) Figure 7 In this study the number of PDs is observed by varying the applied voltage from -1kV. The number of PDs increases by increasing the value of applied voltage, as shown in the Figure 7. A very small change is observed by applying voltage up to 4kV, while above 4kV the number of PDs observed increasing very quickly as earlier than.

6. Conclusion Partial discharge indicate the failuare of insulation in High voltage power system, PD is required to properly monitored to reduce the incipient failuare in HV power system. In this study we include the entire geomatry of the void inside the solid insulation materiel. In this study a MATLAB based model is discussed in detail by applying various technique to observe beheaviour of the solid insulator equivalent model, by which PD presence is detected which express the health of insulting material in high voltage power system. In this study it is concluded that the number of PDs increase with the increasing voltage across the solid insulating material. In this study an efforts has been made to explore the maximum PD amplitude, frequency and number of generated PDs. This study will help the power engineers to analyze quality of insulation material to ensure the reliable operation of power equipment. This work is a comprehensive for further study in various HV power devices such as transformers, Switch gears and circuit breakers. 7. References [1] A. A. Paithankar, A. D. Mokashi,(1997) Can PD Phenomena be Analysed by Deterministic Chaos?, EIC 97,Chicago, (IEEE) Conference preceedings, pp. 283-29. [2] C. Y. Ren et al., (24) Simulation of Partial Discharges in Single and Double voids Using SIMULINK, Journal of Xi an Jiatong University, Vol. 38, No. 1, pp. 12-122. [3] E. Kuffelet al.,(2), Non-destructive insulation test techniques, High Voltage Engineering: Fundamentals, Second Edition, Butterworth-Heinemann, Oxford, pp.395-459. [4] G. C. Crichton et al., (April 29). Partial Discharges in Ellipsoidal and Spherical Voids, IEEETrans.on Dielectric and Electrical Insulation, Vol. 24, No. 2, pp. 335-342. [5] IEC Standard 627.(1996), High Voltage Testing: Partial Discharge Measurement. [6] N. Kolev et al.,(1998), Partial Discharge Phenomena Simulation using General-purpose Analysis Program, Proc of 6th IEEE International Conference on Conduction and Breakdown in solid Dielectrics-ICSD 98, pp. 149-152, June 22-25, Vasteras, Sweden. [7] R. J. Van Brunt,(1994) Physics and Chemistry of partial discharges and corona, IEEE Trans. on dielectric and Electrical Insulation, Vol. 1, No. 5, pp. 761-784. [8] S. Karmakar et al., (29) Partial Discharge Measurement of Transformer with ICT Facilities, Third International Conference on Power Systems, Kharagpur, INDIA December 27-29 Paper No.: 327.