Design Specifications Low Voltage Active Harmonic Filter

Similar documents
Low Voltage Power Factor Correction Equipment Specifications Automatic, Automatic Detuned, Automatic Tuned

Type AHF Active Harmonic Filter

APQline Active Harmonic Filters. N52 W13670 NORTHPARK DR. MENOMONEE FALLS, WI P. (262) F. (262)

Active Harmonic Filter

SECTION LOW VOLTAGE ACTIVE HARMONIC FILTER SYSTEM NEMA 1 ENCLOSED

S11 Adjustable Speed Drive Engineering Specification

SECTION 16483D ADJUSTABLE FREQUENCY DRIVE - MICRODRIVE (MVX <10-HP)

DPM - Mesta Electronics, Inc. Low Voltage Active Harmonic Filters

TOSHIBA International Corp

VF-nC1 Adjustable Speed Drive Engineering Specification

E3 Adjustable Speed Drive Engineering Specification

These true on-line inverters incorporate pulse width modulation (PWM) control combined with high frequency igbt power transistors.

Power Processor - Series 700F 10KVA to 150KVA

Phoenix DX Clean Power (18 Pulse) AC Drive

PRODUCT SPECIFICATION FOR A 15 AND 75 kva, THREE PHASE MODULAR POWER DISTRIBUTION SYSTEM WITH REGULATION AND CONDITIONING (Varian)

Variable Frequency Drive Packages with Harmonic Mitigation. Low Harmonic Drive Packages Engineered by Rockwell Automation

ADJUSTABLE SPEED DRIVES. HX7 Series. 18-Pulse

Power IT LV Active Filters PQFA - PQFL - PQFT

ADJUSTABLE SPEED DRIVES. HX7 Series. 18 Pulse. Phone: Fax: Web: -

Harmonic Correction Unit NEMA 1 Enclosure

Power IT LV Active Filters PQFI PQFM PQFK. The ABB comprehensive solution for active filtering of harmonics

POWER DELEGATOR SERIES 7200A POWER DISTRIBUTION UNIT WITH POWER CONDITIONING GENERAL SPECIFICATIONS

StatiVolt. Inverter UPS Systems. Features. Contents

INTELLIMETER REGISTER

Power-Sure 700. Technical Data TD158001EN. Contents

ADJUSTABLE SPEED DRIVES. W7 Series. 18 Pulse

These true online inverters integrate pulse width modulation (PWM) control combined with high frequency IGBT power transistors.

ULTRA-K Series 600K - he

POWER FACTOR CORRECTION. HARMONIC FILTERING. MEDIUM AND HIGH VOLTAGE SOLUTIONS.

WAVEFORM CORRECTOR (WAVEFORM CORRECTORS) REPLACES SURGE PROTECTION DEVICES (SPD) PREVIOUSLY KNOWN AS (TVSS)

SECTION AUTOMATIC TRANSFER SWITCH

2.1 Performance Standards The UPS is designed with the applicable sections of UL, CUL, and ISO The UPS has UL and CUL listing.

PowerGard Series C 18-Pulse Enclosed Drive Controllers

Power Quality Solutions

SECTION THREE-PHASE UNINTERRUPTIBLE POWER SYSTEM

High Frequency SineWave Guardian TM Filter

Technical Data Sheet. Uninterruptible Power Supply On-line VH Series UPS. Critical Power UL / 208V

High Frequency Sinewave Guardian TM Filter

Low Pass Harmonic Filters

Gutor PxW AC UPS Designed for North American Market

INSTRUCTION MANUAL. Type SWF. Sine Wave Filters 690 Volts, 50Hz

1. Institute of Electrical and Electronic Engineers (IEEE) a. Standard , IEEE Guide for Harmonic Content and Control.

SPECIFICATION FOR HORIZONTAL AIRFLOW OUTDOOR RESISTIVE LOAD BANK

SUGGESTED SPECIFICATION for Series 300 Automatic Transfer Switches

NGS INVERTER REPLACEMENT SCOPE OF WORK & SPECIFICATIONS

Brown University Revised 2/1/2006 Facilities Design & Construction Requirements SECTION 16461C - DRY TYPE TRANSFORMERS

ARE HARMONICS STILL A PROBLEM IN DATA CENTERS? by Mohammad Al Rawashdeh, Lead Consultant, Data Center Engineering Services

MGM Transformer. Vacuum Pressure Impregnated (VPI) Dry-Type Substation Transformer Specification Guide

Power Quality Solutions PQSine P-Series of Active Harmonic Filters and Power Optimizers

Est Static Frequency Converter. SFX 10kVA - 10MVA

LIFE LINE PRODUCT SPECIFICATION FOR A 1 TO 3 KVA, SINGLE PHASE, POWER DISTRIBUTION SYSTEM WITH REGULATION AND CONDITIONING

GUIDE SPECIFICATIONS 40-80kVA, kVA and kVA Scalable Three-Phase Uninterruptible Power System 1.0 GENERAL

STATIC UNINTERRUPTIBLE POWER SYSTEM Revised 4/30/ Electrical Systems

SECTIONS , (15040, 15767, 15950, 16269) Guide Specification for VARIABLE SPEED DRIVES with Optional Bypass

PIRANHA 3 (3-phase, Power Conditioning Voltage Regulator)

Tap Changer Analyzer & Winding Ohmmeter RMO25TD

Dry Type Transformers Full Line Catalog. jeffersonelectric.com

Tap Changer Analyzer & Winding Ohmmeter RMO60TD

Power Meter PQM (EnerSure Enkapsis) Guide Form Specification PART 1: GENERAL

Liebert Datawave GUIDE SPECIFICATIONS kva Magnetic Synthesizer Power Conditioning System

G8000MM Series IGBT. 100 to 750 KVA UPS UNINTERRUPTIBLE POWER SYSTEMS. 94% Efficiency. Input PF >0.98 DESIGN

2.2 American National Standards Institute Corporation and its applicable standards C39.1, C80.1, C89, C84.1.

SINGLE PHASE BUCK & BOOST TRANSFORMERS INSTRUCTION MANUAL

PowerFlex 400 Submittal

SHORE TO SHIP FREQUENCY

2017 Advanced Energy Industries, Inc. HITEK POWER MV2000 SERIES MEDIUM-VOLTAGE HIGH-CURRENT POWER SUPPLIES

Winding Ohmmeter & Tap Changer Test Set RMO40TD with Demagnetizer

GE Ventilated Dry-Type Transformers. Secondary Substation Transformers - 5 and 15kV Class

UBC Technical Guidelines Section Edition Medium-Voltage Transformers Page 1 of 5

LCL Series. SIngle Output Industrial Supplies. High Efficiency. Low Cost. 150 W Convection Cooled. 300 W & 500 W with Internal Fans

Liebert Datawave. GUIDE SPECIFICATIONS kva Magnetic Synthesizer Power Conditioning System 1.0 GENERAL

MITSUBISHI ELECTRIC 2033A DDC SERIES SPECIFICATIONS

TECHNICAL DATA SHEET B9600FXS kva

SECTION PANELBOARDS

RELIABLE SOLUTIONS in POWER ELECTRONICS VRST SERIES. Power Management Instruments ELECTRONIC STABILIZER FROM PMI & OES GROUP COMPANIES SUD

SECTION DISTRIBUTION SWITCHBOARDS

INPUT VOLTAGE STARTING MINIMUM NORMAL MAXIMUM MAXIMUM INPUT RANGE VOLTAFE VOLTAGE VOLTAGE VOLTAGE CURRENT

MANUFACTURING GUIDELINES FOR PLC (LEVEL-1 AUTOMATION)

Section 16621A - AUTOMATIC TRANSFER SWITCH. Part 1 General

INSTALLATION, OPERATION AND MAINTENANCE GUIDE

AccuSine PCS Active Harmonic Filter. Cruise through rough waves in your electrical network

IDEAL INDUSTRIES, INC. TECHNICAL MANUAL MODEL: MODEL: Multimeter Service Information

SWF DV/DT Solutions Sinewave Filters. N52 W13670 NORTHPARK DR. MENOMONEE FALLS, WI P. (262) F. (262)

2.10. Adjustable Frequency Drives. Clean Power Drives. Clean Power Drives

UNINTERRUPTIBLE POWER SUPPLY MODEL 9900B SPECIFICATIONS

P. O. BOX 269 HIGHLAND, ILLINOIS, U.S.A PHONE FAX

Liebert AF2 Next Generation Active Harmonic Filter. Power Protection for Business-Critical Continuity TM

1. All electrical switches and outlets used shall be equal to Hubbell heavy duty, specification grade or equivalent quality.

Harmonic control devices. ECE 528 Understanding Power Quality


USER MANUAL LDY CW Diode Driver Power Supplies

E S C R I P T I V E B U L L E T I N .,.,.,. Bulletin DB-106. October, Square D Company Power System Studies ---1 I SQU ARED COMPANY --

GENERAL PURPOSE DRY-TYPE DISTRIBUTION TRANSFORMERS

EMI Installation Guidelines

Introduction: TAS PowerTek Ltd. MAVROS

Models 31120/31120A/31180/31180A Programmable AC Power Source

Utility Systems Technologies, Inc. Sag Fighter. Deep Voltage Sag Protection:

BOP 1 KILOWATT 1000 WATTS OF FOUR-QUADRANT BIPOLAR POWER FROM KEPCO AN ISO 9001 COMPANY

Est Static Frequency Converter. SFX 10kVA - 10MVA

Types VIS and CRE. A e. Compliance with Standards. Uses. Features

Transcription:

Design Specifications Low Voltage Active Harmonic Filter 1.0 General Description This section contains the design standards, general equipment type and configuration, components, product description, warranty and installation requirements for active harmonic mitigation and power factor correction, as provided by an active harmonic filter. Such equipment shall be utilized for the improvement of harmonic rich environments, along with the improvement of power factor, in AC electrical power systems. The manufacturer shall have been engaged in the engineering and production of electrical power equipment for a minimum of ten years. The finished product shall be designed, assembled, tested and shipped as a complete system by the manufacturer. Equipment finished in any other manner is not acceptable. 2.0 System and Environment Active filter equipment and systems shall be suitable for environments of either indoor or outdoor, intended as either stand-alone or integrated with other equipment, such as motor control centers, switchboards, switchgear and static switches, UPS or distributed generation. Equipment is intended for use with voltage classifications from 208 to 480vac. A step-up transformer shall be used for voltages above 480vac. Equipment shall be used on three phase, 3 wire, grounded wye, ungrounded wye, or delta wire systems at 50hz or 60hz. Equipment is designed for reliable operation in ambient temperatures of 0 degrees C to 40 degrees C, up to 3250 feet (1000 meters) above sea level, with relative humidity of 95%. The finished Electrotek / Enersine ESD33 equipment shall be listed to UL508, C-UL. 3.0 Basic Equipment Type The Electrotek / Enersine ESD33 active harmonic filter is an assembly intended to monitor the non-linear load and dynamically correct a wide spectrum of harmonic orders. Active filter technology shall utilize power electronics for its operation and functions such as switching, cancellation, injection, monitoring and controlling AC and DC power. Power semi- conductors shall switch the AC power to modulate and control output, which cancels detrimental harmonic and/or reactive currents. DC bus power shall provide storage for semiconductor switching. Semi-conductors shall have current limiting protection. A microprocessor shall provide control, monitoring and operational functions for the complete active harmonic filter apparatus. When installed, the active filter shall provide 5% (Total Demand Distortion) TDD; 5% (Total Harmonic Distortion-Voltage) THDv; and specific power factor correction value at the load, where applicable, while not affecting the load in the form of a resonance condition. Corrected current distortion shall include all odd orders from the 3rd through the 51 st harmonic order. Each harmonic order shall maintain a consistent and maximum level of performance. 1

A resonant condition occurring within the electrical power system between the active filter and the load shall not cause the active filter to stop functioning properly. Equipment which cannot correct a wide harmonic spectrum and be capable to operate in a resonance condition to a minimum of the 51 st harmonic order is not acceptable. A constant, proportional value of power factor correction compensation shall be inherent in the design of the active filter, along with the capability to allow for the use of separate, additional power factor correction capacitor modules. Active filters shall operate in full compensation mode without shut-down, should additional loads be added (no overload). Heat loss (watts) shall be at a minimum. Active harmonic filter apparatus that derates harmonic cancellation performance when a power factor correction mode is operational is not acceptable. The expandable design of the active filter shall allow for additional (up to six) active filters to be installed in a parallel arrangement, and also allow use of existing active filters on the electrical system. Placement of the equipment shall be to mitigate single, or multiple loads, or a complete facility load. The active harmonic filter shall be installed at either the load or source location. Individual ampere ratings shall be provided at 25 ampere, 50 ampere, 100 ampere, 150 ampere and 200 ampere. The power electronics of the active filter shall be designed to operate well within the tolerance of the intended environment, utilize fan cooling and be properly ventilated. Power fuses (Class J), rated at 200kaic, shall be provided for protection of the power electronic IGBT (switched at 20 khz) modules. When initially energized, the active filter DC capacitor charge - soft start time shall be 10 seconds. Steady state at 100% step load (zero amperes to rated compensation amperes) shall be <40ms. Equipment shall allow for wall mounting (to 50 amperes) and free-standing (100 amperes and above) configurations. In addition, and where integration is required, equipment shall provide incoming, active filter, capacitor, motor control, or switchgear sections, where applicable. Compartments or sections shall be segregated as required. The active filter shall be available as a three wire apparatus. The active filter shall include two current transformers (CT s), for connection during installation (phases A and C), for a three wire connection. Standard split-core type CT size shall be 2000:1, 20va, 400 hz, with <1ms transient response time to detect load current. A DSP controller, with Discrete Fourier Transform (DFT) algorithm topology and analysis/calculate performance response time of minimum <20ms shall be provided. Controller shall allow for global or specific harmonic order settings (such as 3 rd, 5 th, 7 th, 9 th, 11 th simultaneously). Controller shall be positioned on the front panel of the enclosure with display and keypad as part of the active filter system and shall be easily viewed. The graphic display shall be an LCD type, with multiple functions for operation and maintenance control, with 16 line and 40 character capability. Management and control access to the load, source and Electrotek / Enersine ESD33 data shall be provided to the user. 2

The display shall provide man-machine interface, and analyzer, operating data status and alarm information, while functioning, and allow the operator to utilize keypad/scrolling utilities. Parameters available for display, at a minimum shall include: Graphics display with wave form, measurements and spectrum data to the 31 st order, four LED indicator and eight control/keypad utilities for On/Off, Reset (Alarm-Reset), Power On indicator, Filtering indicator, Full Correcting indicator, Error indicator, Confirmation (keypad), Direction Scrolling (keypad), Escape/Cancel (keypad). At a minimum, AC line voltage, total rms current, harmonic current, reactive current, output harmonic and reactive current of power correction shall be displayed values. A total of (5) five dry contacts (250vac/2amp) shall be provided for remote monitoring. Communications via RS 232 shall be provided as standard. Additional communications for RS 422, RS 485, USB, TCP/IP and Ethernet RJ45 shall be included where applicable. Controllers without capabilities as described above are not acceptable. The active harmonic filter shall meet specific performance standards for harmonic mitigation, surge immunity, electromagnetic compatibility, design and safety: IEEE519 / EN61000-3-4 Harmonic Mitigation Guidelines IEEE587/ANSI C62.41/ EN61000-4-5 Surge Immunity FCC Part 15 / EN55011 Electromagnetic compatibility UL508, C-UL / EN60146 Safety/Design EN50178 Vibration Testing, Safety/Design 4.0 Equipment Specifications and References A. Low voltage power distribution equipment, motor control centers, switches switchboards, switchgear, static switches, fixed motor load and switched power factor correction capacitors and harmonic mitigation systems B. Medium voltage switchgear, switches and static transfer switches C. Medium voltage metal enclosed capacitors and harmonic filters D. Engine-generator control, distributed generation systems, paralleling switchgear E. Energy management and other power quality equipment and components A. American National Standards Institute (ANSI) B. Institute of Electrical and Electronic Engineers (IEEE) C. National Electrical Manufacturers Association (NEMA) D. Underwriters Laboratories, Inc (UL) E. Canadian Standards Association (CSA) F. International Electromechanical Commission (IEC) G. European Standards (EN) H. National Electric Code (NEC) 3

5.0 Submittals Documentation for approval or reference shall be submitted in a CAD format. Common information, where applicable, shall include equipment plan view and outline dimensions, active filter sections, incoming locations, cable entry, main bus, fuse and active filter ratings, and where applicable capacitor ratings, mounting locations, and component technical descriptions. 6.0 Construction Guidelines Equipment design shall follow the most recent applicable standards and guidelines and shall serve to meet the intended application requirements. Installation and operation of equipment is for general business, commercial, industrial, government and energy or utility service providers. The enclosure assembly shall be from 14-gauge sheet steel, with wall mounted enclosure and freestanding enclosure construction of bolted design, to allow for ease of expansion, where applicable. Enclosures shall be finished with a texture and painted light gray, or other color as specified. The complete assembly shall be painted using electrostatically applied polyester powder coated paint, or a liquid enamel application, both, which provides for enhanced durability and extended protection. The finished enclosure shall provide both front and rear access via hinged doors or bolted, removable panels. Wall mounted enclosures shall allow for front access to internally mounted components. Doors shall be equipped with a latch-close system and include a key lockable feature, where applicable. Hardware shall be environmentally sound; either zinc plated or stainless steel, for optimum corrosion resistance. The entire assembly shall provide adequate personnel safety and component security. Cable entry shall be from the bottom with a grounding termination point included within the enclosure. A separate disconnect means may be required by NEC. Lifting lugs shall be provided for transport and to facilitate ease of installation of the finished equipment. Such removable lugs shall be located at the top of the equipment. Equipment manufactured in accordance to Electrotek / Enersine. Enclosures shall be rated as NEMA 1 or NEMA 12 (indoor) and NEMA 3R (outdoor). Where applicable, louvers shall be included for proper ventilation. For specific indoor or outdoor applications, aluminum mesh filters, fan(s) and heater(s)/thermostat(s) shall be incorporated in the assembly. The design and construction integrity of the finished assembly shall allow for the equipment to be lifted, or slid into place. The ready to ship equipment shall meet stringent, applicable engineering and design standards and be neatly constructed and finished, meeting all Electrotek / Enersine ESD33 quality and production control standards, prior to shipment. 4

7.0 Systems Integration The active filter shall be compatible to allow other power quality related components and devices to be incorporated, allowing for maximum equipment provisions. Where applicable, the equipment shall be designed in such a manner for system and physical integration or match and line with new or existing power distribution equipment. The active filter itself shall be suitable for mounting in other power distribution or control equipment, where applicable. AC or DC variable frequency drive applications shall utilize a 3% (minimum impedance) line reactor/isolation transformer, where applicable. 8.0 Testing and Safety The equipment shall be production tested, prior to shipment. This will include, at a minimum, mechanical functional operation, electrical functional operation, control wiring and circuit continuity, and polarity verification. Major electrical, electronic, and mechanical components and devices integral to the equipment shall include testing reports and technical information and other such data, where applicable. A manual for the purpose of operation and maintenance instruction shall be included with the finished equipment. The finished equipment shall include nameplates, labels, and other decals, providing applicable safety and general operation instruction. Such markings shall be visually accessible and conveniently located both internally and externally. 9.0 Equipment Documentation The finished equipment shall be provided with design and construction documentation as a minimum: Physical dimension data, outline/plan elevation drawings, general component layout and technical information, weight and installation detail. Single line and three line drawings (where applicable) Control schematic and control program (where applicable) Component Bill of Materials Operations and Maintenance Instructions 10.0 Equipment Installation Correct installation is required for proper performance and function of the Electrotek / Enersine ESD33 active filter. Physical inspection of equipment for damage is recommended, prior to any installation. Indoor storage for indoor and outdoor rated equipment should be in a clean, dry environment, and where recommended, may require removal of packaging materials. 5

Outdoor storage of outdoor equipment shall require installation of any materials shipped for site assembly, such as fans and bus ducts and the mating of equipment shipping splits. Where recommended, packaging materials may be required to be removed. Equipment includes removable lifting lugs, for transport and site installation handling. As a cautionary note, placement of the active filter shall be at a level and solid location, for correct operation. National Electrical Code (NEC), electric utility company or service provider codes shall be adhered to during the installation. Electrical connections shall also be in compliance with required codes. Installer/Contractor shall inspect and verify proper alignment, anchorage and ground, proper connections and tightness of connections, prior to any start-up functions. Appropriate personnel shall start-up and operate equipment upon installation approval. This may also include use of portable measuring devices or analyzers to verify performance of the Electrotek / Enersine ESD33 active filter. Section 2 2-1. Operational Guidelines Electrotek / Enersine ESD33 is a solid-state power converter that brings about the following advantages: Eliminate all harmonic currents from non-linear loads. Compensate reactive power factor of lagging loads. Act as a virtual damping resistor to prevent possible harmonic resonance. Electrotek / Enersine ESD33 behaves like a harmonics current generator. E l e c t r o t e k / Enersine ESD33 will measure the harmonics generated from the non-linear loads and cancel these harmonics with a newly generated, opposite phase shifted harmonics current of the same amplitude. By cancelling the harmonic currents in the circuit, there will be (1) No risk of harmonic resonance; (2) Significantly reduce the voltage waveform distortion; (3) Reduced voltages drop on transformers & cables; (4) Reduced temperatures rise on transformers & cables; (5) Improved power factor. 2-2. Components of Electrotek / Enersine ESD33 Electrotek / Enersine ESD33 provides 3 phase harmonic current compensations, and the main components of the APF are as follow: 1 set of Ripple Current Filter module. Its main function is to absorb the high frequency ripple current and compensate specific amount of reactive power. 1 set of Electromagnetic Contactor module for soft-starting. It helps to limit the amplitude of the inrush current when DC capacitor set is charging. 6

1 set of High Frequency Inductor-Capacitor module. It acts as the power transmission interface component between power converter and power system. 1 set of IGBT Power Converter module. This is to transform the harmonics energy from the connected power system and re-generate an equal but opposite phase shifted harmonic current back to the power system. This re-generated energy will cancel the harmonics produced by the power system. 1 set of DC Capacitor module which store energy taken from the power system before the IGBT Converter can use it to re-generate the opposite phase shifted compensating harmonic current. c d 4 5 6 3 7 c Power Breaker-Switch d High-Speed Fuse 3 Ripple Current Filter Module 4 Soft-start Electromagnetic Contactor Module 5 High Frequency Inductor-Capacitor Module 6 IGBT Power Converter Module 7 DC Capacitor Module 7

2-3. Brief Description of Components This section describes the working principles of the main components inside Electrotek / Enersine ESD33. 2-4 Ripple Current Filter Module The Ripple Current Filter is shunt-connected at the output terminals of the Electrotek / Enersine ESD33. Its main function is to absorb high frequency ripple current and provide specific amount of reactive power compensation. Its main components consist of the following: (1) Parallel/Series link resonance filter. (2) Over-current protection relay (OL1). (3) Abnormal trip control device. Under the normal working condition, Ripple Current Filter will also provide partial reactive power factor to improve lagging power factor. The Over-Current Protection Relay (OL1) is incorporated to protect the Electrotek / Enersine ESD33. In the event when the IGBT Power Converter is malfunction, it may generate a large amount of high frequency current drifting into the Ripple Current Filter. This will cause the Over- Current Protection Relay to trip, thus shutting down the APF system to prevent further damage to the entire APF system. 2-5 Soft Start Electromagnetic Contactor Module The main function of this module is to inhibit inrush current when DC capacitor module is charging. When the voltage of the DC capacitor reaches its default value, the Electrotek / Enersine ESD33 will then be switched on to its normal operating mode. The main components for Soft Start Electromagnetic Contactor are as followings: (1) Current-limiting Resistor. (2) Electromagnetic Contactor. This module inhibits the inrush current going through the IGBT Power Converter into the DC capacitor module within a certain level, while closing the power break-switch. After switching on the Electrotek / Enersine ESD33, the Electromagnetic Contactor will close to make the IGBT Power Converter truly connected with the power system and bypasses the current-limiting resistor. 2-6 High Frequency Inductor-Capacitor Module The Inductor & Capacitor are the power transmission interface components between the IGBT Power Converter and the connected power system. It also compensates the reactive power for the lagging power factor. The main components of the High Frequency Inductor-Capacitor Module are: (1) High frequency response inductor. (2) High frequency response capacitor. (3) Current transformer. 10

The current transformer is use to feedback the harmonic compensating current to a control circuit, this will allow the Electrotek / Enersine ESD33 to performance a high-speed compensation and ensure a current-limit if the harmonics energy exceeded its capacity. 2-7 IGBT Power Converter Module The IGBT Power Converter is the major architecture of the Electrotek / Enersine ESD33 in the cancellation of the harmonic current (ILh) generated by the connected non-linear load. The IGBT Power Converter make use of this harmonic energy (ILh) as an initial power, to produce an opposite phase shifted harmonic current waveform (IE). This waveform is then re-injected into the connected power system to cancel the existing harmonics distortions (ILh), ensuring a near perfect sine waveform (Is) returning to the Power Mains. The main components of the IGBT Power Converter Module are: (1) IGBTs bridge (2) Driver circuit (3) Snubbers The electronics bridge of the power converter is made up of Isolated Gate Bipolar Transistor (IGBT) and utilizes Pulse Width Modulation (PWM) technology to drive the IGBTs to produce compensating current waveform. Built-in Snubbers are use with the IGBT for protection from spikes when the Power Converter is in operation. 2-8 DC Capacitor Module DC Capacitor Module stores the energy (ILh ) generated by the connected power system, to be use by the IGBT Power Converter for re-generation of the opposite phase shifted compensating harmonic current waveform (IE). The storing and releasing of energy of the DC Capacitor Module is electrically control by the IGBT Power Converter. The DC Capacitor Module is made up of a specific numbers of similar rating DC capacitors connected electrically in parallel. 11

1-4. System Structure Schematic Diagrams Drawing 1-1 Electrotek / Enersine ESD33 System Structure Schematic Diagram 12

3-0 Characteristics & Specifications 3-1 - 1 General Characteristics Equipment storage temperature -20ºC to +70ºC Operating Temperature +12ºC to +25ºC (Recommend Range), + 0ºC to +40ºC (Tolerate Range) Relative Humidity < 95% Operating Altitude < 1000 m Reference Harmonic Standard EN 61000-3-4, IEEE 519-1992 Reference Design Standard EN60146 Safety Standard EN50178 Electromagnetic Compatibility EN55011, EN50081-2, EN61000-4-2, EN61000-4-3, EN61000-4-4, EN61000-4-5, EN61000-4-6, EN61000-6-2 3-1 - 2 Electrical Specification Category Unit 25A 50A 100A 150A 200A Line Voltage V 208/380/400/480 ±15% Phase/Wires ES33 series for 3 phase 3 wires Frequency Hz 50/60 ±3 Compensating Current in Phase Arms 25 50 100 150 200 (2) Transient Response Time msec < 1 Inrush Current Less than rated current Current Limitation Yes, at full correcting Soft Start Sec 10 Heat-losses Watt 550 950 2000 3000 4100 Audible Noise from 1 Meter dba 60 60 63 63 65 3-1 - 3 Mechanical Specification Category Unit 25A 50A 100A 150A 200A Color RAL9001 Protection Index IP20 Dimensions (W x D x H) Weight ES33 series ES33 series mm kg 410 x 390 x 880 600 x 810 x 1930 1200 x 810 x 1930 55 70 230 260 430 (1) It is the total time from detection to steady compensation at 100% step load is less than 40 msec. 13

4-0 Compensation Ability The Compensation ability of the Electrotek / Enersine ESD33 is defined in term of Harmonic Attenuation Ratio (HAR). HAR = ILh / ISh HAR : Harmonic attenuation ratio ILh : Harmonic current at load side ISh : Harmonic current at power source side ISh IE ESD33 5-0 Equipment Warranty The manufacturer shall provide its standard warranty for equipment of this type. The warranty shall provide for repair of replacement of the equipment, should it be found to be defective within twelve months from the date shipment. Approved Supplier: Electrotek Ltd. 1016 34 AV SE Calgary, AB T2G 1V4 www.electrotekltd.com Tel: 403 287 2200 (1 800 404 9114)