Zdeslav Čerina, dipl. ing. Robert Kosor, dipl. ing. Sergio Gazzari, dipl. ing. Hrvatska elektroprivreda d.d., Croatia ABSTRACT

Similar documents
Introduce system protection relays like underfrequency relays, rate of change of frequency relays, reverse - power flow

Level 6 Graduate Diploma in Engineering Electrical Energy Systems

Simulations of open phase conditions on the high voltage side of YNd05-power plant transformers

PRC Generator Relay Loadability. Guidelines and Technical Basis Draft 5: (August 2, 2013) Page 1 of 76

Power System Stability. Course Notes PART-1

COMPARATIVE PERFORMANCE OF SMART WIRES SMARTVALVE WITH EHV SERIES CAPACITOR: IMPLICATIONS FOR SUB-SYNCHRONOUS RESONANCE (SSR)

A Guide to the DC Decay of Fault Current and X/R Ratios

PRC Generator Relay Loadability. Guidelines and Technical Basis Draft 4: (June 10, 2013) Page 1 of 75

LARGE-SCALE WIND POWER INTEGRATION, VOLTAGE STABILITY LIMITS AND MODAL ANALYSIS

Chapter -3 ANALYSIS OF HVDC SYSTEM MODEL. Basically the HVDC transmission consists in the basic case of two

A Pyrotechnic Fault Current Limiter Model for Transient Calculations in Industrial Power Systems

IJSER. Fig-1: Interconnection diagram in the vicinity of the RajWest power plant

PSV3St _ Phase-Sequence Voltage Protection Stage1 (PSV3St1) Stage2 (PSV3St2)

A Study on Ferroresonance Mitigation Techniques for Power Transformer

Stability Improvement for Central China System

Unit Auxiliary Transformer (UAT) Relay Loadability Report

DYNAMIC SIMULATIONS CHALLENGE PROTECTION PERFORMANCE

Long lasting transients in power filter circuits

Analysis of Effect on Transient Stability of Interconnected Power System by Introduction of HVDC Link.

ReliabilityFirst Regional Criteria 1. Disturbance Monitoring and Reporting Criteria

Modelling of the back-to-back converter between Uruguay and Brazil in A.T.P.

IDAHO PURPA GENERATOR INTERCONNECTION REQUEST (Application Form)

OPEN-PHASE DETECTION TECHNIQUES FOR CRITICAL STANDBY SUPPLIES

Resonances in Collection Grids of Offshore Wind Farms

SWITCHING OVERVOLTAGES IN A 400-KV CABLE SYSTEM

MEASUREMENT CAMPAIGN AND ASSESSMENT OF THE QUALITY OF SUPPLY IN RES AND DG FACILITIES IN SPAIN

CHAPTER 4 POWER QUALITY AND VAR COMPENSATION IN DISTRIBUTION SYSTEMS

Analysis of Power Oscillations and Their Treatment in Hydro Power Plant with Large Bulb Turbines

In Class Examples (ICE)

Dynamic Phasors for Small Signal Stability Analysis

Voltage Sag Index Calculation Using an Electromagnetic Transients Program

Transient stability improvement by using shunt FACT device (STATCOM) with Reference Voltage Compensation (RVC) control scheme

Exercises. 6 Exercises

A NEW DIRECTIONAL OVER CURRENT RELAYING SCHEME FOR DISTRIBUTION FEEDERS IN THE PRESENCE OF DG

ETAP PowerStation. Electrical Transient Analyzer Program. ETAP PowerStation. Short Circuit Analysis. ANSI Standard 3-Phase Fault Currents

Three-Phase/Six-Phase Conversion Autotransformers

STATCOM-SMES SYSTEM Co-ordination in Controlling Power System Dynamic

Initial Application Form for Connection of Distributed Generation (>10kW)

ABSTRACT 1 INTRODUCTION

Application Example Document ID: SA Rev. - September 24, 2004

Lightning current field measurement on a transmission line, comparison with electromagnetic transient calculations

Končar TMS - Bushing monitoring

Transmission Interconnection Requirements for Inverter-Based Generation

When surge arres t ers are installed close to a power transformer, overvoltage TRANSFORMER IN GRID ABSTRACT KEYWORDS

SHORT CIRCUIT ANALYSIS OF 220/132 KV SUBSTATION BY USING ETAP

Power Systems Modelling and Fault Analysis

Induction Machine Test Case for the 34-Bus Test Feeder -Distribution Feeders Steady State and Dynamic Solutions

Transmission Lines and Feeders Protection Pilot wire differential relays (Device 87L) Distance protection

BE Semester- VI (Electrical Engineering) Question Bank (E 605 ELECTRICAL POWER SYSTEM - II) Y - Y transformer : 300 MVA, 33Y / 220Y kv, X = 15 %

EMERGING distributed generation technologies make it

S1-3: New and re-discovered theories and practices in relay protection

Modeling and electromagnetic transients study of two 1800MVA phase shifting transformers in the Italian transmission network

Problems connected with Commissioning of Power Transformers

Doãn Văn Đông, College of technology _ Danang University. 2. Local Techniques a. Passive Techniques

PJM Manual 07:: PJM Protection Standards Revision: 2 Effective Date: July 1, 2016

G. KOEPPL Koeppl Power Experts Switzerland

A Real-Time Platform for Teaching Power System Control Design

Fault Ride Through Principles. and. Grid Code Proposed Changes

Control of Over-voltages on Hydro-Québec 735-kV Series-Compensated System During a Major Electro-mechanical Transient Disturbance.

Real-Time Power System Simulation:

Generator Protection GENERATOR CONTROL AND PROTECTION

Anti-Islanding Protection of Distributed Generation Resources Using Negative Sequence Component of Voltage

Short Circuit Calculation in Networks with a High Share of Inverter Based Distributed Generation

IEEE Power Engineering Society 2001 Winter Meeting Columbus, OH. Panel Session. Data for Modeling System Transients

Course ELEC Introduction to electric power and energy systems. Additional exercises with answers December reactive power compensation

ISO Rules Part 500 Facilities Division 502 Technical Requirements Section Wind Aggregated Generating Facilities Technical Requirements

System grounding of wind farm medium voltage cable grids

Sequence Networks p. 26 Sequence Network Connections and Voltages p. 27 Network Connections for Fault and General Unbalances p. 28 Sequence Network

Power Plant and Transmission System Protection Coordination of-field (40) and Out-of. of-step Protection (78)

Conventional Paper-II-2011 Part-1A

Power Plant and Transmission System Protection Coordination Fundamentals

Effect of Series Capacitor on Line Protection - A Case Study

Solving Customer Power Quality Problems Due to Voltage Magnification

AORC Technical meeting 2014

Assessment of Saturable Reactor Replacement Options

Application of a thyristor-controlled series reactor to reduce arc furnace flicker

Power System Protection Where Are We Today?

Analysis of Temporary Over-Voltages from Self-Excited Large Induction Motors in the Presence of Resonance - Case Studies

ADVANCED VECTOR SHIFT ALGORITHM FOR ISLANDING DETECTION

Generation Interconnection Study Data Sheet Synchronous Machines

Harmonic Analysis of a High Speed Automatic Reclosing on a 400 kv Overhead Transmission Line

Power Quality enhancement of a distribution line with DSTATCOM

Using a Multiple Analog Input Distance Relay as a DFR

Ferroresonance Experience in UK: Simulations and Measurements

Modeling for the Calculation of Overvoltages Stressing the Electronic Equipment of High Voltage Substations due to Lightning

Ferroresonance in MV Voltage Transformers: Pragmatic experimental approach towards investigation of risk and mitigating strategy

Simulation of Lightning Transients on 110 kv overhead-cable transmission line using ATP-EMTP

Power Quality Basics. Presented by. Scott Peele PE

PRC Compliance Using Bitronics 70 Series Recorders

R10. III B.Tech. II Semester Supplementary Examinations, January POWER SYSTEM ANALYSIS (Electrical and Electronics Engineering) Time: 3 Hours

Islanding and Detection of Distributed Generation Islanding using Negative Sequence Component of Current

System Protection Schemes in Power Network based on New Principles

Influence of Wind Generators in Voltage Dips

Solution for Effect of Zero Sequence Currents on Y-Y Transformer Differential Protection

Arvind Pahade and Nitin Saxena Department of Electrical Engineering, Jabalpur Engineering College, Jabalpur, (MP), India

2. Current interruption transients

Protective Relaying for DER

Shortcomings of the Low impedance Restricted Earth Fault function as applied to an Auto Transformer. Anura Perera, Paul Keller

1

Overcurrent Protection / 7SJ45

Transcription:

CURRENT AND VOLTAGE WAVEFORMS UPON THE CONDUCTOR RUPTURE IN ONE PHASE OF THE 11 KV RADIAL CONNECTION OF THE GENERATOR AT HPP DUBROVNIK TO THE POWER SYSTEM SIMULATION AND MEASUREMENT Mr. sc. Milan Stojsavljević, dipl. ing. Mr. sc. Darko Nemec, dipl. ing. Dr. sc. Muharem Mehmedović, dipl. ing. Institut za elektroprivredu i energetiku d.d., Zagreb, Croatia Zdeslav Čerina, dipl. ing. Robert Kosor, dipl. ing. Sergio Gazzari, dipl. ing. Hrvatska elektroprivreda d.d., Croatia ABSTRACT This paper presents results of time-domain simulation of single-phase opening (the effect of the 11 kv phase conductor rupture) of the 11 kv transmission line Komolac Trebinje (a part of radial connection of HPP Dubrovnik to the system) in realistic operating conditions. The simulation results comprise instantaneous and RMS values of phase currents, phase voltages and residual current in the 11 kv line bay Komolac at the HPP Dubrovnik switchyard and in the 11 kv transmission line bay Trebinje at the substation Komolac. Simulation results are compared with quantities recorded by the numerical line protection device REL511 installed at HPP Dubrovnik. Simulation includes electromechanical transients with excitation system and turbine governor being modelled. Rather good correspondence between simulation results and measurements in this particular case shows that such calculation results could be used as a basis for tuning and coordination of protection systems. Keywords: electric power system, generator, radial connection, protection system, simulation 1. INTRODUCTION Application of the protection devices based on the numerical technology and its foolhardy progress, profusion of the offered functions and possibilities of the numerical protection devices / relays and the power system management, have also given the techniques for the analysis of electric power plants and systems a new dimension. Owing to increased use of numerical protection devices with fault recording capabilities, it is now much easier to compare simulation results with measurements from the real power system for purpose of model validation. As the result, higher quality of modelling and deeper insight into system behaviour can be achieved. A well-known and widely used class of program tools for time domain modelling of power systems in terms of instantaneous values of network variables is the family of so-called electromagnetic transient programs (EMTP). Besides detailed modelling of individual network elements, standard versions of such programs offer also the possibility for flexible modelling of measuring, control and protection devices in power plants and systems. In that way more realistic models can be built, provided that enough input data with sufficient level of detail are available. Standard simulation results are given in form of voltage and current waveforms in a specified interval. Usually, some post-processing of simulation results should be done for better and clearer presentation. This is easily achieved by exporting the results in a standard format (e.g. ASCII) to some general-purpose application for calculation and graphical presentation. Modelling of a rather specific case of phase conductor rupture of the 11 kv transmission line in the particular part of the electric power system is addressed in this paper. The part of power

system under investigation comprises 11 kv radial connection of one 12 MVA hydrogenerator (HPP Dubrovnik) to the electric power system realized through two 11 kv transmission line sections (11 kv TL HPP Dubrovnik Komolac and Komolac Trebinje) with local passive consumption supplied from the transformer 11/35 kv in substation Komolac at the end of the first section.and the second section of the 11 kv connection ends in the node with transformation 11/22 kv in substation Trebinje as the coupling point to the electrical power system. The phase conductor rupture occurred at the very beginning of the second 11 kv section (substation Komolac), i.e. at so called "current bridge" at the connection point of the transmission line. The simulation model comprised detailed dynamic representation of the generating unit with its control systems (excitation system and turbine governor). Simulation results were validated by comparison with the current and voltage waveform records made by the numerical protection device of the transmission line. This protection is installed at the beginning of the first section of the 11 kv radial connection (i.e. at HPP Dubrovnik). Calculations of the current and voltage waveforms are made for the positions at the beginning of the both sections of 11 kv connection (HPP Dubrovnik and substation Komolac). Rather good accordance between simulation and measurements is achieved thanks to accuracy of input data (model parameters, initial steady state) and relatively simple transmission network configuration. Of course, further refinment of the model is still possible, particularly now when there is a new generating unit monitoring system installed at HPP Dubrovnik which is capable of recording instantaneous values of generator currents and voltages as well as currents and voltages in the 11 kv bay. 2. THE SIMULATION MODEL The generator G1 at HPP Dubrovnik, situated in the southern part of the Croatian power system, is a 12 MVA unit connected to the 11 kv substation Komolac via 11 kv transmission line HPP Dubrovnik Komolac (designation D164/1+D165). Note that the generating unit circuit breaker at HPP Dubrovnik serves at the same time as the line circuit breaker of the 11 kv TL Dubrovnik - Komolac. From the substation Komolac there are two 11 kv connections, one to the substation Ston and the other to the substation Trebinje. The 11 kv transmission line Komolac Trebinje (designated as D138) is the interconnection line between electric power systems (EPS) of Croatia and Republika Srpska. In the present configuration the electric power system of the Republika Srpska is in the II. UCTE synchronous zone, while the Croatian electric power system is in the first UCTE synchronous zone. That means that simultaneous operation of both before mentioned transmission lines is not allowed, which leaves the generator G1 of the HPP Dubrovnik working either on the Croatian EPS or on the EPS of Republika Srpska. In the configuration considered in this case the transmission line D138 Komolac Trebinje was in operation, and D137 Komolac Ston was disconnected. In the year 2, the new numerical transmission line protection REL511 ver. 1.2, manufactured by ABB was installed in the HPP Dubrovnik. That protection relay protects D164/1+165 HPP Dubrovnik Komolac and among other functions has a fault recorder function. A full three phase model of the local electric power system is used for calculations. The model, consisting of the generating unit G1 in HPP Dubrovnik with the excitation and turbine governing system, two 11 kv transmission lines: HPP Dubrovnik Komolac and Komolac Trebinje, power transformer 11/35 kv in the substation Komolac with local consumption represented with the constant impedance model and equivalent representation of the 22 kv electric power system connected via power transformer 11/22 kv, 15 MVA at the substation Trebinje, has been set up in LEC ATP program package and is presented schematically in the fig. 1. The transmission lines were modelled as pi-equivalents with lumped parameters.

TL 138 11 kv KOMOLAC - TREBINJE TREBI 11 kv 111.23 2.6 kv 15 MVA 22/11 kv u k =1% YNyn Z Z d =8.82 + j26.94 =3.492 +j7.646 phase rupture KOTRM 72.26 MW -26.87 MVAr 3x.7678 µ F MTREB 22 kv 226.58 kv 3x.7678 µ F 557.7 24.23 A KOMTR I KoTr TL Komolac - Ston 538.9 24.44 A SS KOMOLAC 112.86 3.83 kv KO11 KOMP1 Z Z d TL 164/1 + TL165 11 kv HPP-DUBROVNIK - KOMOLAC =6.99 + j15.45 =1.385 +j4.731 PLAT1 Z Z d =.35 +j 1.28 =.83 + j.42 113.91 4.67 kv 213.92-13.93 A T111 11 kv 3x.5124 µ F 3x(.5124+.387) µ F 738.8 I HDuKo 14.32 A 11.6 MW -17.3 MVAr HE_DU H-DUB 3x.387 µ F 2x(4/4/13.3) MVA YNynD5 11/35/1.5 kv 1.5/11.6/7.3 % 7 Ω T351 35 kv 35.54 1.8 kv REL 511 _BTH_ 113.91 4.67 kv 3x(42.75 + j 9.92) Ω 28.35 MW 6.56 MVAr 13 MVA 115.2/14.4 kv YNd5 11.43% 661.22-11.26 A _ GEN 14.116-14 kv GS 12 MW -7 MVAr Figure 1 Simulation model used for the calculations of the current and voltage waveforms upon the singlephase conductor rupture of the 11 kv transmission line Komolac Trebinje with calculation results of the initial (pre-fault) steady state 12 MVA 144 V 5 Hz Location of current measurements on the 11 kv transmission lines HPP Dubrovnik Komolac and Komolac Trebinje used in the model, are clearly marked (I HDuKo, I KoTr, figure 1) Initial steady state, based on the realistic operating conditions recorded before the mentioned fault (power flow 72 MW / -28 Mvar on the TL 138 Komolac Trebinje, local load 28 MW / 6.5 Mvar at the substation Komolac) was modelled. Basic calculation results of the initial steady state made on the model are also shown in fig. 1 as phase RMS values of voltages and currents. All voltage and current phase angles in fig. 1 are referred to phase A, that is L1 (initial state is balanced). Active and reactive power flows are referred to the total three-phase power in the respective monitored branches. 3. RESULTS OF ANALYSIS 3.1 Course of fault A realistic operating incident is modelled the phase conductor L2 rupture in the substation Komolac at the very beginning of the 11 kv TL Komolac Trebinje. Sudden phase unbalance caused the electromechanical swinging of the generator G1 at HPP Dubrovnik against the system. Distance protection LZ92 installed in the 11 kv line bay of the TL Komolac Trebinje in the substation Komolac could not have operated upon such fault and there was no overcurrent earth fault protection. It was the operation of the overcurrent earth fault protection function comprised by the protection device REL511 (with setting: 12 A, 4 seconds) that switched off the circuit breaker in the 11 kv line bay of the TL HPP Dubrovnik Komolac. This happened approximately 4 seconds after the fault had occured, which is in compliance with the adjusted time delay of that protection function. By this action the generator at the HPP Dubrovnik was disconnected from the system but the Komolac substation and the 11 kv TL HPP Dubrovnik Komolac were still connected to the power system through the two healthy phases of the 11 kv line Komolac Trebinje. The fault recorder function within the numerical protection REL 511 at HPP Dubrovnik was triggered by operation of the earth fault protection. Having total recording length of 4 seconds and the prefault interval set to 5 milliseconds it could not have recorded the entire phenomenon from the inception of the fault to the opening of the circuit breaker.

3.2 Comparison of simulation results and measurements The results are presented in form of the phase currents and voltages waveforms and residual current (I N =3I ) waveforms (instantaeous values) along the time axis in an interval approximately 1 ms before and 1 ms after the switching off of the circuit breaker in the line bay of the HPP Dubrovnik switchyard. Instantaneous values of currents and voltages in the line bay at HPP Dubrovnik switchyard obtained from simulation are shown in fig. 2 simultaneously with the same quantities recorded by the numerical protection REL 511, thus allowing direct comparison between simulation and measurement. Pretty good accordance of simulation results with actual measurements can be observed. The currents and voltages on the line Komolac Trebinje could not have been compared in the same way since there was no recording device at the Komolac substation. Vector diagram showing amplitude and phase relations of the measured and calculated currents and voltages immediately before the switching off of the circuit breaker in the line bay of the HPP Dubrovnik switchyard (i.e. generating unit circuit breaker) is shown in fig. 3. UL1/kV 5-5 -1 IL1/A -5 UL2/kV 5-5 -1 IL2/A -2 UL3/kV 5-5 -1 IL3/kA,5, -,5-1, IN/A,6,65,7,75,6,65,7,75,6,65,7,75,6,65,7,75,6,65,7,75,6,65,7,75,6,65,7,75 UL1/kV 1 5-5 -1 IL1/A 1 5-5 -1 UL2/kV 1 5-5 -1 IL2/kA 4 2-2 -4 UL3/kV 1 5-5 -1 1 IL3/A 5-5 -1 IN/A 5 4. 4.5 4.1 4.15 4. 4.5 4.1 4.15 4. 4.5 4.1 4.15 4. 4.5 4.1 4.15 4. 4.5 4.1 4.15 4. 4.5 4.1 4.15 Figure 2-5 MEASUREMENT -5 4. 4.5 4.1 4.15 SIMULATION Instantaneous values of voltages and currents on the TL HPP Dubrovnik Komolac (line bay in the HPP Dubrovnik switchyard) with open phase L2 on the TL Komolac Trebinje, zoomed approximately 1 ms before and after opening of the circuit breaker in the line bay of the TL HPP Dubrovnik Komolac in the HPP Dubrovnik switchyard

+9 69.4 kv UL3 15 12 9 8 6 6 UL3=68.49 kveff 4 3 2 ±18 18 UL2 62.7 kv UL1 62.2 kv 21 UL2=64.5 kveff 33 UL1=61.92 kveff 8, kv -9 24 27 3 +9 656 A IL3 15 12 9 8 IL3=726 Aeff 6 4 6 3 2 ±18 226 A IL2 IN 374 A IL1 637 A 18 IL2=287 Aeff 21 IN=383 Aeff IL1=612 Aeff 33 8, A -9 MEASUREMENT 24 27 3 CALCULATION Figure 3 Vector representation of line currents and voltages in the 11 kv TL HPP Dubrovnik Komolac immediately before switching off the circuit breaker at HPP Dubrovnik /kv 6 4 2 /A 8 6 4 2 4 2. 2. 4..5 1. 1.5 2.5 3. 3.5 4.5 5. /kv. 2. 4..5 1. 1.5 2.5 3. 3.5 4.5 5. 6 ka. 2. 4..5 1. 1.5 2.5 3. 3.5 4.5 5. /kv. 2. 4..5 1. 1.5 2.5 3. 3.5 4.5 5. 8 6 4 2 /A 5 5. 2. 4..5 1. 1.5 2.5 3. 3.5 4.5 5. N/A. 2. 4..5 1. 1.5 2.5 3. 3.5 4.5 5. 4 3 2 1. 2. 4..5 1. 1.5 2.5 3. 3.5 4.5 5. U L 1 / k V 6 4 2 I L 1 / A..5 1. 1.5 2. 2.5 3. 3.5 4. 4.5 8 6 4 2 U L 2 / k V..5 1. 1.5 2. 2.5 3. 3.5 4. 4.5 6 4 2 I L 2 / k A..5 1. 1.5 2. 2.5 3. 3.5 4. 4.5 4 3 2 1 U L 3 / k V..5 1. 1.5 2. 2.5 3. 3.5 4. 4.5 6 4 2 I L 3 / A..5 1. 1.5 2. 2.5 3. 3.5 4. 4.5 8 6 4 2..5 1. 1.5 2. 2.5 3. 3.5 4. 4.5 I N / A 1 8 6 4 2..5 1. 1.5 2. 2.5 3. 3.5 4. 4.5 Figure 4 Simulated time responses of currents and voltages (RMS values) on the 11 kv TL HPP Dubrovnik - Klomolac (left) and on the 11 kv TL Komolac-Trebinje (right) The whole course of the phenomenon, as obtained from simulation, is shown in fig. 4 in form of time responses of RMS values of voltages and currents in the 11 kv line bay at HPP Dubrovnik and on the 11 kv TL Komolac- Trebinje (in 11 kv line bay at Komolac substation). Local mode oscillations (swings) of the generating unit G1 at HPP Dubrovnik can be readily observed in all phase currents and in the residual current at both locations. Oscillation frequency is approximately.84 Hz and maximum peak to peak value of the oscillatory component in RMS residual current I N on the TL HPP Dubrovnik Komolac amounts to 7 A while mean value of the total I N is about 35 A, well above the threshold of the overcurrent ground fault function in REL511 (12 A). At the same time, the maximum amplitude of the damped oscillatory component of the same frequency (.84 Hz) in the residual current I N on the 11 kv TL Komolac Trebinje is approximately 13 A.

After switching off of the circuit breaker in the HPP Dubrovnik switchyard the oscillatory component in all three currents vanishes because it had been caused by the electromechanical swinging of the generating unit G1 in the HPP Dubrovnik in relation to electric power system, and the residual current I N as a vector sum of the currents in the healthy phases amounts to approximately 4 A. From the I N current response it can be read off that the share of the HPP Dubrovnik generator in that current without oscillatory component is approximately 36 A. Obviously, the unsymmetry on the transmission line Komolac Trebinje was still present after opening the circuit breaker at HPP Dubrovnik. Considering that the calculation results are very sensitive to the input data, relatively good amplitude and phase correspondence of the measurements and simulation results is achieved. The poorest matching of measured values and simulation results can be observed in the current in the L2 phase where the measured value is 22% lower than the value obtained from the simulation. Measured currents in the other two phases have equal values (their mutual difference is approximately 3%) while in the simulation the current in the L1 phase is about 18% lower than the L3 current. The residual current I N in the simulation is lower by 2.4%. Obviously, the earth fault overcurrent protection was necessary to protect the 11 kv TL Komolac Trebinje against such faults. As a temporary solution until installation of a dedicated protection device, it was decided to use the existing time overcurrent protection with definite time characteristic which had been already installed at TS Komolac in the role of line overcurrent protection. Residual current measurement is obtained from suitably connected current transformers and fed to the measuring circuit of the relay in phase L2. The relay setting is 12 A with time delay of 2.5 seconds which is coordinated with the earth fault overcurrent protection of the 11 kv transmission line HPP Dubrovnik Komolac (12 A, 4 seconds). 4. CONCLUSION An attempt to simulate a non-typical fault by means of a rather simple model set up in the EMTP program is presented in the paper. Simulated time domain responses of characteristic variables are compared to measurements of the same quantities from the real system, obtained from numerical protection devices with fault recorder function. Valuable experience regarding some aspects of modelling is gained from the here presented case. Rather good correspondence between simulation and measurement is encouraging in the sense that such simulation models could be used in the process of protection coordination and tuning as well as in the post mortem analysis of various disturbances. It is shown that modelling of electromechanical transients could also have impact on the results, especially when it is necessary to observe periods which are long enough to allow such transients to develop (i.e. several seconds or longer). In the paper it is clearly illustrated by the time diagrams of voltage and current envelopes (RMS values) during fault. Powerful simulation tools such as EMTP programs enable modelling of machine rotor dynamics as well as excitation systems and turbine governors along with dynamics of network elements and with currently available computer processing power it is feasible to use such complex models for practical engineering analyses. Modelling accuracy will remain dependent on available system and equipment data and validation of simulation results against measurements will become even more important step in establishing credible models. Wider use of numerical protection devices with fault recorder capabilities at various points in the power system will make possible further improvement. Closer cooperation between protection engineers and power system analysts will be necessary in order to exploit those new possibilities and achieve more realistic simulation models which would then serve as a reliable basis for protection system analysis and tuning. BIBLIOGRAPHY [1] Dommel, H. EMTP Reference Manual (Theory Book), BPA 1986 [2] Alternative Transient Program Rule Book, Leuven EMTP Center, 1987 [3] Test protocols of the numerical protection REL511 of the 11 kv line HPP Dubrovnik Komolac, June, 12 th 2, HEP, Transmission area Split, Relay protection department [4] Tuned and calculated settings of the distance protection LZ92 of the 11 kv transmission line Komolac Trebinje, HEP, Transmission area Split, Relay protection department [5] Test report of the excitation control system of the generator G1 in HPP Dubrovnik, Energy Institute Zagreb, september 1997