Performance Evaluation of Mho and Quadrilateral Characteristic Relays on UPFC Incorporated Transmission Line

Similar documents
SIMULATION OF D-Q CONTROL SYSTEM FOR A UNIFIED POWER FLOW CONTROLLER

Application of Fuzzy Logic Controller in UPFC to Mitigate THD in Power System

Performance Of Distributed Power Flow Controller (DPFC) Under Fault Condition

PSCAD Simulation High Resistance Fault in Transmission Line Protection Using Distance Relay

Performance Analysis of ZSI Based UPFC in Transmission System under Faulty Condition

A Voltage Controlled D-STATCOM for Power Quality Improvement with DVR

Design Strategy for Optimum Rating Selection of Interline D-STATCOM

Power Quality Improvement in Distribution System Using D-STATCOM

factors that can be affecting the performance of a electrical power transmission system. Main problems which cause instability to a power system is vo

Increasing Dynamic Stability of the Network Using Unified Power Flow Controller (UPFC)

Real and Reactive Power Control by using 48-pulse Series Connected Three-level NPC Converter for UPFC

Bhavin Gondaliya 1st Head, Electrical Engineering Department Dr. Subhash Technical Campus, Junagadh, Gujarat (India)

Performance of DVR under various Fault conditions in Electrical Distribution System

Improving the Transient and Dynamic stability of the Network by Unified Power Flow Controller (UPFC)

POWER FLOW CONTROL WITH UPFC IN POWER TRANSMISSION SYSTEM

FACTS devices in Distributed Generation

Arvind Pahade and Nitin Saxena Department of Electrical Engineering, Jabalpur Engineering College, Jabalpur, (MP), India

MITIGATION OF VOLTAGE SAG AND SWELL FOR POWER QUALITY IMPROVEMENT USING DISTRIBUTED POWER FLOW CONTROLLER

Designing Of Distributed Power-Flow Controller

INTERNATIONAL JOURNAL OF PURE AND APPLIED RESEARCH IN ENGINEERING AND TECHNOLOGY

Damping Power system Oscillation using Static Synchronous Series Compensator (SSSC)

Performance of DVR & Distribution STATCOM in Power Systems

Improvement of Power Quality in Distribution System using D-STATCOM With PI and PID Controller

Enhancement of Power Quality in Distribution System Using D-Statcom for Different Faults

Stability Enhancement for Transmission Lines using Static Synchronous Series Compensator

Application of Distribution Static Synchronous Compensator in Electrical Distribution System

A Direct Power Controlled and Series Compensated EHV Transmission Line

SIMULATION OF D-STATCOM AND DVR IN POWER SYSTEMS

International Journal of Advance Engineering and Research Development

SIMULATION OF DSTATCOM FOR POWER FACTOR IMPROVEMENT

Improvement of Voltage Profile using D- STATCOM Simulation under sag and swell condition

Chapter-5 MODELING OF UNIFIED POWER FLOW CONTROLLER. There are a number of FACTS devices that control power system

Power System Stability Enhancement Using Static Synchronous Series Compensator (SSSC)

ELEMENTS OF FACTS CONTROLLERS

Designing and Control of Converters used in DPFC for Mitigation of Voltage Sag and Swell In Transmission Line

Volume I Issue VI 2012 September-2012 ISSN

Power System Oscillations Damping and Transient Stability Enhancement with Application of SSSC FACTS Devices

Improvement in Power Quality of Distribution System Using STATCOM

Transient stability improvement by using shunt FACT device (STATCOM) with Reference Voltage Compensation (RVC) control scheme

Performance Analysis of Distance Relay on Shunt/ Series Facts-Compensated Transmission Line

Interline Power Flow Controller: Review Paper

INTERNATIONAL JOURNAL OF ELECTRICAL ENGINEERING & TECHNOLOGY (IJEET)

CHAPTER 4 POWER QUALITY AND VAR COMPENSATION IN DISTRIBUTION SYSTEMS

Experimental Verification and Matlab Simulation of UPFC for Power Quality Improvement

Available ONLINE

Power flow improvement using Static Synchronous Series Compensator (SSSC)

Improvement of Rotor Angle Stability and Dynamic Performance of AC/DC Interconnected Transmission System

Optimal Placement of Shunt Connected Facts Device in a Series Compensated Long Transmission Line

Simulation and Implementation of DVR for Voltage Sag Compensation

I. INTRODUCTION. Keywords:- FACTS, TCSC, TCPAR,UPFC,ORPD

STATCOM WITH POD CONTROLLER FOR REACTIVE POWER COMPENSATION Vijai Jairaj 1, Vishnu.J 2 and Sreenath.N.R 3

[Mahagaonkar*, 4.(8): August, 2015] ISSN: (I2OR), Publication Impact Factor: 3.785

Power Quality enhancement of a distribution line with DSTATCOM

I. INTRODUCTION IJSRST Volume 3 Issue 2 Print ISSN: Online ISSN: X

Analysis of Single and Multi Resonance Point in Reactance Characteristics of TCSC Device

Modeling and Simulation of Wind Farm with STATCOM in PSCAD/EMTDC Environment

Power Quality Compensation by using UPFC

Voltage Control and Power System Stability Enhancement using UPFC

Modeling and Simulation of STATCOM

Transmission Lines and Feeders Protection Pilot wire differential relays (Device 87L) Distance protection

Modeling and Analysis of DPFC to Improve Power Quality

Performance and Analysis of Reactive Power Compensation by Unified Power Flow Controller

Comparison of FACTS Devices for Power System Stability Enhancement

Implementation of UPQC for Voltage Sag Mitigation

Fundamental Concepts of Dynamic Reactive Compensation. Outline

The Influence of Thyristor Controlled Phase Shifting Transformer on Balance Fault Analysis

Comparison of Simulation and Experimental Results of UPFC used for Power Quality Improvement

INSTANTANEOUS POWER CONTROL OF D-STATCOM FOR ENHANCEMENT OF THE STEADY-STATE PERFORMANCE

Design and Simulation of Fuzzy Logic controller for DSTATCOM In Power System

Power Quality and the Need for Compensation

POWЕR QUALITY IMPROVEMENT IN POWЕR SYSTЕM BY USING SVPWM BASED STATIC SYNCHRONOUS SЕRIЕS COMPЕNSATOR

PRECISION SIMULATION OF PWM CONTROLLERS

Mitigating Voltage Sag Using Dynamic Voltage Restorer

Analysis of D-STATCOM Impact on Protection of Distribution Network

Compensation of Distribution Feeder Loading With Power Factor Correction by Using D-STATCOM

Power Quality Enhancement and Mitigation of Voltage Sag using DPFC

Modified Approach for Harmonic Reduction in Transmission System Using 48-pulse UPFC Employing Series Zig-Zag Primary and Y-Y Secondary Transformer

Transient Stability Enhancement with Application of FACTS Devices

Analysis the Modeling and Control of Integrated STATCOM System to Improve Power System

Performance of Indirectly Controlled STATCOM with IEEE 30-bus System

Modeling and Simulation of SRF and P-Q based Control DSTATCOM

IJESR/Nov 2012/ Volume-2/Issue-11/Article No-21/ ISSN International Journal of Engineering & Science Research

Performance Improvement of Power System Using Static Synchronous Compensator (STATCOM) Priya Naikwad, Mayuri Kalmegh, Poonam Bhonge

Power Control Scheme of D-Statcom

Voltage-Current and Harmonic Characteristic Analysis of Different FC-TCR Based SVC

ADVANCE DISTANCE PROTECTION OF TRANSMISSION LINE IN PRESENCE OF SHUNT COMPENSATOR

Chapter 10: Compensation of Power Transmission Systems

Implementation of D-STACTOM for Improvement of Power Quality in Radial Distribution System

A NOVEL APPROACH ON INSTANTANEOUS POWER CONTROL OF D-STATCOM WITH CONSIDERATION OF POWER FACTOR CORRECTION

[Kumar*, 4.(7): July, 2015] ISSN: (I2OR), Publication Impact Factor: 3.785

Analysis and modeling of thyristor controlled series capacitor for the reduction of voltage sag Manisha Chadar

An Enhanced Adaptive Algorithm to Mitigate Mis-coordination Problem of the Third Zone of Distance Relays

Real and Reactive Power Coordination for a Unified Power Flow Controller

A Versatile Control Scheme for UPQC for Power Quality Improvement using fuzzy controller

Koganti Sri Lakshmi, G.Sravanthi, L.Ramadevi, Koganti Harish chowdary

Comparison and Simulation of Open Loop System and Closed Loop System Based UPFC used for Power Quality Improvement

Comparative Analysis of Multiple-pulse VSC-Based STATCOM s for Voltage-Dip Mitigation

Investigation of D-Statcom Operation in Electric Distribution System

Effect of Fault Resistance and Load Encroachment on Distance Relay- Modeling and Simulation PSCAD/EMTDC

Improving the Electric Power Quality by UPFC Systems in Electrical Networks

Transcription:

International Journal of Electronic and Electrical Engineering. ISSN 0974-2174 Volume 7, Number 8 (2014), pp. 827-835 International Research Publication House http://www.irphouse.com Performance Evaluation of Mho and Quadrilateral Characteristic Relays on UPFC Incorporated Transmission Line Nidhi Chauhan 1, M. Tripathy 2 and R. P. Maheshwari 3 1,2,3 Department of Electrical Engineering, Indian Institute of Technology Roorkee, Roorkee-247 667, Uttarakhand (India) Abstract The paper presents the errors in the estimation of impedance seen by mho relay due to the presence of UPFC in transmission line. These errors occur due to rapid change in the compensation parameters such as shunt reactive current and series voltage injection into the transmission line. The study presents the cause of under reach/ over reach of mho relay in this case. This error in impedance calculation results in mal operation of the relay for the faults like single line to ground fault specifically. Effect of fault location, fault resistance has also been investigated. Performance of quadrilateral characteristic relay under such scenario is also evaluated. The study suggests the supremacy of quadrilateral relay over mho relay during high resistance fault on UPFC compensated transmission lines. The paper also presents the need of adaptive measures of generating tripping boundaries to improve distance relaying scheme for FACTS compensated transmission line protection. The complete simulation including UPFC structure modeling, mho and quadrilateral relays setting has been carried out with PSCAD software tool. Keywords: Unified Power Flow Controller (UPFC), Line to Ground fault (LG), Static Compensator (STATCOM), Static Synchronous Series Compensator (SSSC), PSCAD/ EMTDC. 1. Introduction FACTS technology has emerged as a sophisticated and reliable state of art providing with the flexibility to enhance power flow, maintain voltage stability etc., all at utilities choice. Thus in this era of incessant electricity demand, restricted right of ways and soaring prices, FACTS devices have helped in utilizing the transmission

828 Nidhi Chauhan, M. Tripathy and R. P. Maheshwari corridors to its fullest capacity. Unified Power Flow Controller (UPFC) is a versatile FACTS device, capable of regulating all the power flow parameters i.e. voltage, impedance and load angle, simultaneously and selectively [1]. UPFC via its controlling parameters like injected series voltage and reactive shunt current respond to the changes in the power system configuration rapidly, as desired. However, its adverse effects are faced by protection utilities where the distance relay operation for transmission line protection gets inadvertently affected owing to its dependence on power frequency voltage and current signals at the relay point, getting distorted in the presence of UPFC [2, 3]. The relay compares this apparent impedance calculated in the presence of UPFC, along with its impedance setting. Thus resulting in erroneous results for tripping decisions. Different relay characteristics like mho and quadrilateral are used for protecting high voltage long and medium transmission lines in different scenarios. Till date all the theoretical performance evaluation of distance relay in presence of UPFC incorporated transmission line has been done using mho relay only [4, 5, 6]. Work in [7] presents synchrophasors assisted adaptive reach setting method of distance relay in presence of FACTS devices. Quadrilateral relay possesses flexible operating characteristic and encloses the desired fault region. The present paper discusses the theoretical analysis simply to illustrate the influence of UPFC incorporation, its location effect and effect of fault resistance during LG fault on both mho relay and quadrilateral relay establishing comparative overview. 2. Transmission Line Modeling With UPFC System consisting of two terminal 230 kv, 50 Hz, 200 km long transmission line with 100 MVA short-circuit levels is simulated with load angle of 20 degree with PSCAD/ EMTDC software tool. Positive sequence impedance of line is (0.3624e-4+j0.5031e- 4) ohm/m and zero sequence impedance is (0.37958e-3+j0.13277e-2) ohm/m. Simulation is done using step size of 0.05ms. Fault duration is 0.2 s, fault resistance varies from 0 to 60 ohms. UPFC constitutes two back-to-back GTO based six-pulse voltage source converters (VSC) connected via a dc link with capacitance of 500µF. A three phase 230 kv/ 20 kv Y/Δ transformer is used to connect one VSC i.e. the STATCOM, in shunt with the transmission line. The other VSC i.e. the SSSC, is connected in series with the line with the help of three single phase series transformers of rating 20 kv/60 kv Y/Y as shown in Fig. 1. The series converter of UPFC does the major function by injecting controllable series voltage into the line with varying magnitude (0 to 15 % of line voltage) and phase-angle (0 to 360 degree). The line current interacts with this voltage to provide real and reactive power flow control. The shunt converter generally provides for the real power demand of the series converter along with voltage support if desirable and also regulates the dc link voltage.160 MVA UPFC is connected at mid-point of the transmission line.

Performance Evaluation of Mho and Quadrilateral Characteristic Relays 829 Fig. 1 Model of transmission line with UPFC simulated in PSCAD UPFC controller s modeling for both STATCOM and SSSC has been used as presented in [8, 9]. It employs PWM control strategy to generate the firing pulse of converter valves to respond to desired reference settings of voltage and current. Automatic voltage control and automatic power flow modes of UPFC are its most practical operational modes and the rapidly changing reactive shunt current and variable series voltage during these modes presents UPFC as a major source or sink of impedance to the rest of the power system. The effect of UPFC on distance protection of transmission lines during LG fault is analytically presented by the equations below: Z s Vs V 1 Vse V2 Is Relay 0.5Z Ish I Line (n-0.5)z R f I f Es Fig. 2: The single line network of the system from the relay end to the fault end (known as fault loop) when UPFC is at mid-point as: The apparent impedance seen by the relay when fault occurs after UPFC is given Z = n + ( n-0.5 ) + + +. (1)

830 Nidhi Chauhan, M. Tripathy and R. P. Maheshwari where, I = I + I. (2) as, When only STATCOM is present then apparent impedance seen by relay is given Z = = nz + ( n-0.5 ) Z. (3) Apparent impedance seen by relay in the absence of UPFC is given as, Z = = nz. (4) V and I are phase voltage and current at the relay point and I is zero sequence phase current, Z and Z are positive sequence and zero sequence impedance of the transmission line, I is shunt reactive current injected by UPFC (via STATCOM), V is series voltage injected by UPFC (via SSSC) and R and I are fault resistance and fault current respectively. Further, n is per-unit distance of a fault from the relay location. 3. Results and Discussions The mho and quadrilateral relays are set for first zone of protection i.e. 80% of positive sequence impedance [2], and their reach setting method is given in [10, 11]. Resistance and reactance is calculated assuming ideal CTs and CVTs at the relay end. The measured impedance trajectory is plotted on the R-X diagram along with ideal characteristics of mho and quadrilateral relays. Case 1: Voltage regulation mode of UPFC (STATCOM only): When fault resistance is absent and fault loop includes STATCOM (fault location after STATCOM, at160 km), STATCOM regulates the connecting point voltage by injecting reactive current I into the line (Eq. 3). This leads to increase in apparent impedance, causing underreaching of mho relay as shown in Fig. 3(a). The quadrilateral relay on the other hand, is able to detect the fault under such condition (Fig. 3(b)), improving dependability of line protection. Magnitude of fault resistance involved in ground fault is always a matter of concern which varies from zero to several ohms. Mho relay is highly affected and mal-operates because of underreaching with increase in fault resistance (Fig 4(a)). It is seen that quadrilateral relay is able to enclose the fault region with high fault resistance and hence is more reliable than mho relay (Fig. 4(b)).

Performance Evaluation of Mho and Quadrilateral Characteristic Relays 831 Fig. 3(a) and 3(b): Apparent impedance trajectory with mho and quadrilateral characteristics respectively, with and without STATCOM in absence of fault resistance Fig. 4(a) and 4(b): Apparent impedance trajectory with mho and quadrilateral characteristics respectively, with and without STATCOM in presence of fault resistance Case 2: Power flow mode of UPFC (Full UPFC with both SSSC and STATCOM): When fault loop excludes UPFC (fault location before UPFC, at 90 km) and fault resistance is zero (Eq. 4), then the apparent impedance trajectory seen by both the relays is approximately similar with or without UPFC (Fig. 5(a) and 5(b)). But the estimated impedance changes widely in the presence of fault resistance (Fig. 6(a)), causing mho relay to mal-operate. Hence, fault resistance becomes the major factor in relays underreaching. To mitigate its effect quadrilateral relay if used, is proved to be highly effective (Fig. 6(b)).

832 Nidhi Chauhan, M. Tripathy and R. P. Maheshwari Fig. 5(a) and 5(b): Apparent impedance trajectory with mho and quadrilateral characteristics respectively, with and without UPFC when fault resistance is zero ohm and fault loop excludes UPFC Fig. 6(a) and 6(b): Apparent impedance trajectory with mho and quadrilateral characteristics respectively, with and without UPFC in the presence of fault resistance when fault loop excludes UPFC When fault loop includes UPFC (fault location at 160 km), the apparent impedance seen by the relay is then given by Eq. 1. Due to insertion of magnetizing branch of series transformer of the series converter of UPFC (i.e. SSSC), there is large amount of zero sequence voltage injection into the lines during the most commonly encountered LG fault. Thus, apparent impedance in presence of UPFC is tremendously large. Validation by PSCAD also gives the same results. From Fig. 3(a) and Fig. 7(a) it is observed that mho relay suffers huge underreaching effect when full UPFC is in operation as compared to the presence of STATCOM only. This also determines effect of the presence of SSSC only, which gives approximately same results as in the presence of UPFC. This due to the fact that the faulted circuit

Performance Evaluation of Mho and Quadrilateral Characteristic Relays 833 encounters the same series injected voltage via series transformer of SSSC as in UPFC. Hence, it is inferred that collective effect of both SSSC and STATCOM is quite detrimental for mho relay performance. Still quadrilateral relay seems workable in UPFC integrated transmission line, as seen from Fig. 7(b). If fault resistance is present and is too high, even quadrilateral relay under-reaches and fails to detect the fault in the presence of UPFC (Fig. 8(b)). Overreaching of relay occurs when there is capacitive voltage injection into the lines and is a difficult issue to deal with the conventional fixed operating relay characteristics like mho and quadrilateral. Fig. 7(a) and 7(b): Apparent impedance trajectory with mho and quadrilateral characteristics respectively, with and without UPFC when fault resistance is absent and fault loop includes UPFC Fig. 8(a) and 8(b): Apparent impedance trajectory with mho and quadrilateral characteristics respectively, with and without UPFC when fault resistance is present and fault loop includes UPFC

834 Nidhi Chauhan, M. Tripathy and R. P. Maheshwari During phase to phase, double phase to ground and three phase fault, impact of UPFC remain same on the mho and quadrilateral relay performance as in single line to ground fault. The mho relay mal-operates and fails to detect fault during all such types of faults when faulted circuit includes the UPFC. The quadrilateral relay seems to be very effective and reliable during high resistance fault on UPFC incorporated transmission lines, relative to mho relay. 4. Conclusion UPFC effects for all its mode of operation on distance relays has been investigated thoroughly. Transmission line protection when compensated with UPFC is difficult to achieve with the help of conventional relaying methods. Mho relay undergoes underreaching and over-reaching problems as has been described. Therefore, the quadrilateral relay seems as a viable alternative to mho relay because of its flexible operating characteristics to cover fault region in the presence of high resistance fault on UPFC compensated transmission lines. But enormously high fault resistance causes relay underreaching and capacitive reactive power exchange via UPFC leading to relay over-reaching. In such case even the quadrilateral relay mal-operates. This invokes the need of going for adaptive trip boundaries generation methods which is able to accommodate the rapidly changing control parameters of UPFC, fault resistance, fault location, change in load angle etc. and correctly gives the tripping decision. Thus distance relaying scheme can further be improved and made reliable by adaptive methods during faults on compensated transmission lines. References [1] N. G. Hingorani and L. Gyugyi, Understanding FACTS: Concepts & Technology of Flexible AC Transmission Systems. New York: IEEE, 2000. [2] IEEE Guide: for Protective Relay Applications to Transmission Lines, IEEE Standard C37.113, 1999. [3] Dawei F., Chengxue Z, Zhijian H., and Wei W., The Effects of Flexible AC Transmission Systems Device on Protective Relay, Proc. Power System Technology, 2002, vol. 4, p.p. 2608-2611. [4] M. Khederzadeh, UPFC operating characteristics impact on transmission line distance protection, in Proc. IEEE PES General Meeting, Pittsburgh, July 2008, PA, pp. 1-6. [5] X. Zhou, H. Wang, R. K. Aggarwal, and P. Beaumont, Performance evaluation of a distance relay as applied to a transmission system with UPFC, IEEE Trans. Power Del., July, 2006, vol. 21, no. 3, pp. 1137-1147. [6] Mostafa J., Gholamzadeh M., and Mohammad P., Analysis of Over/Underreaching of Distance Relay on Transmission Line in Presence of UPFC, Trends in Applied Sciences Research 6(6) Academic Journal, 2011, p.p. 580-594. [7] K. Seethalekshmi, S. N. Singh, and S. C. Srivastava, Synchrophasors assisted

Performance Evaluation of Mho and Quadrilateral Characteristic Relays 835 adaptive reach setting of distance relay in the presence of UPFC, IEEE system general, September, 2011, vol. 5, no.3,p.p. 396-405. [8] Pramod Kumar Gouda, Ashwin K. Sahoo, and P. K. Hota, Modeling and simulation of UPFC using PSCAD/EMTDC, International Journal of Physical Sciences, Nov. 2012 vol. 7(45), pp. 5965-5980. [9] Applications of PSCAD/EMTDC, Manitoba HVDC Research Centre Inc., 2007. [10] Yashasvi B., Vidushi K., Ramesh P., Simulation of mho characteristics for transmission line protection using PSCAD International Journal of Research in Engineering & Applied Sciences, February, 2012, vol.2, Issue 2, pp. 2249-3905. [11] J. Holbach, V. Vadlamani, and Y. Lu, Issues and Solutions in Setting a Quadrilateral Distance Characteristic, Proceedings of the 61st Annual Conference for Protective Relay Engineers, College Station, TX, April, 2008.