NFPA-70E. Electrical Safety in the Workplace. Standard for Edition

Similar documents
AN EXAMPLE OF A STANDARD ARC FLASH PPE LABELING STRATEGY

AN EXAMPLE OF A STANDARD ARC FLASH PPE LABELING STRATEGY

2015 NFPA 70E. SESHA 2015 ARIZONA MINI CONFERENCE December 10, 2015 Intel Corporation

STANDARDIZING ARC FLASH PPE LABELS

First Draft Language

Paul Dobrowsky Innovative Technology Services

Electrical Safety Policy Health and Safety FCX-HS03 Release 07/2018 Version 1

Electrical Arc Hazards

Arc Flash and NFPA 70E

Arc Flash Analysis and Documentation SOP

Key factors to maintaining arc flash safety

Steve Kovach District Sales Engineer

DC ARC FLASH. THE IMPLICATIONS OF NFPA 70E 2012 ON BATTERY MAINTENANCE

ARC FLASH & PPE UPDATE. Michael Olivo, P.E. Aaron Ramirez, E.I.T.

Arc Flash Hazard and Mitigation 2 nd Workshop on Power Converters for Particle Accelerators June 14 16, 2010

A Guide to Establish an Arc Flash Safety Program for Electric Utilities

Arc Flash Hazard Standards:

Arc Flash Mitigation An Overview. Gus Nasrallah, P.E. Electroswitch May 30, 2013

{40C54206-A3BA D8-8D8CF }

NOTICE ER Roland Flood Pumping Station Arc Flash Study

Arc Flash Analysis Training

Webinar: An Effective Arc Flash Safety Program

2014 NEC Changes Part 1

Electrical Overcurrent Studies

2017 ELECTRICAL SAFETY SERVICES. Arc Flash Electrical Maintenance Lockout/Tagout And More

APPLYING LOW-VOLTAGE CIRCUIT BREAKERS TO LIMIT ARC FLASH ENERGY

SECTION OVERCURRENT PROTECTIVE DEVICE COORDINATION STUDY

2018 Consultant s Handbook Division 26 Electrical ARC Flash Hazard Analysis

Arc Flash Calculation Methods

RMEL Safety Conference

Selection of PPE Practical experience of different arc assessment methods and their comparison

Electrical testing safety Part 1: Preparing for absence of voltage testing

PREFACE ********************************************************** IT IS NOT INTENDED THAT THESE STANDARDS BE COPIED AND USED AS A SPECIFICATION!

Electrical Severity Measurement Tool Revision 4

Electrical Measurement Safety. Sponsored By:

SECTION SHORT CIRCUIT, COMPONENT PROTECTION, FLASH HAZARD AND SELECTIVE COORDINATION STUDY

How does an Arc occur?

SECTION POWER SYSTEMS STUDIES

NORTHWEST FLORIDA STATE COLLEGE MONUMENT SIGNS WITH LED DISPLAYS

ADDENDUM NO. 2 PROJECT: COURTLAND PUMP STATION CONTRACT: IFB NO COM.00030

THREE PHASE PAD MOUNTED DISTRIBUTION TRANSFORMER ARC FLASH TESTING JUNE 23, 2009 FERRAZ SHAWMUT HIGH POWER LABORATORY NEWBURYPORT, MA

How does an Arc occur?

Cause, Effect & Mitigation Strategies

Ft Worth IEEE-PES. Presented by: Doug Harris Specifications Engineer Dallas, TX. Arc-Flash Hazard Mitigation & Selectivity

Arc Flash Study Principles & Procedures for below 15 kv AC Systems. Xuan Wu, Dennis Hoffman, Ronald Wellman, and Manish Thakur

high RESISTANCE GROUNDING SYSTEM the power to protect www. ElectricalPartManuals. com Instruction Manual C-102

Education & Training

A DUMMIES GUIDE TO GROUND FAULT PROTECTION

NATIONAL ELECTRIC SAFETY CODE 2012 EDITION

National Marine Manufacturers Association Compliance Specialist Examination A.C. Electrical (2018 Model Year) ABYC E-11 Supplement 56

MECKLENBURG COUNTY. Land Use and Environmental Service Agency Code Enforcement 9/8/10 ELECTRICAL CONSISTENCY MEETING. Code Consistency Questions

Safeguarding Machinery

DESIGN STANDARD DS 29

PRODUCTIVELY SAFER LOCK-OUT TAG-OUT PROCEDURE

CHANGEABILITY OF ARC FLASH PARAMETERS AND ITS IMPACT ON HAZARD MITIGATION IN LOW VOLTAGE POWER SYSTEMS

Environmental Health and Safety Office Hazardous Dust Control Guide

ARC FLASH PPE GUIDELINES FOR INDUSTRIAL POWER SYSTEMS

SECTION PANELBOARDS

15B+/17B+/18B+ Calibration Manual. Digital Multimeter

Electrical CSA Z462. oberonsafety oberonsafety (USA & Canada) (55) (Mexico)

British Columbia Institute of Technology WOOD DUST EXPOSURE CONTROL PLAN (CARPENTRY)

Application Note (Revision NEW) Original Instructions. EMI Control in Electronic Governing Systems

Best Practice Reducing The Risk of Arc Flash Cross Over

Design Approaches for Hospital Distribution Systems With Considerations for Future Expansion, Operator Safety, and Cost

EXPERIMENT 1 Safety, Instrumentation, and Measurement

SAFETY AND HEALTH STANDARD ELECTRICAL GROUNDING Effective Date: 07/17/10 Standard: Document Number: KUCSH0039 Rev: 4

COMMON SOURCES OF ARC FLASH HAZARD IN INDUSTRIAL POWER SYSTEMS

Series NRX with PXR - Instructions for Neutral Current Sensor Type NF

Arc Hazard Assessment for DC Applications in the Transit Industry

HIGH VOLTAGE RULES. Document Owner: HV Group. Authorised: Electrical Services Manager Liberty Primary Steel

The advantages of transformers. EMC-ESD in de praktijk Jan-Kees van der Ven

Enclosed circuit breaker (ECB) with Arcflash Reduction Maintenance System

Pre-Installation Guide

General Installation Instructions LED

PHASE ROTATION METER. Operating and Instruction Manual. a n d A C C E S S O R I E S

Standards for MV switchgear rated for arc flash protection

Broadband Step-Up Transformer. User Manual

REVIEWED HES MANAGER

Earthing, HV Switching and Associated Operational Equipment. Approval: Chief Operating Officer

LOCKOUT / TAGOUT PROGRAM

A controlled arc-flash, produced in a flashtube. Even though the energy level used is fairly low (85 joules), the low-impedance, low-inductance

Model 4210-MMPC-L. Multi-measurement Prober Cable Kit. Overview. Quick start guide topics. Related documents

WAVEFORM CORRECTOR (WAVEFORM CORRECTORS) REPLACES SURGE PROTECTION DEVICES (SPD) PREVIOUSLY KNOWN AS (TVSS)

INDUSTRIAL WORK GARMENTS

Installation Instructions

Wisconsin Contractors Institute Continuing Education

High Voltage Testing. Team 5: Justin Bauer, Matt Clary, Zongheng Pu, DeAndre Dawson, Adam McHale

SHOP SAFETY AND TRAINING IN ACADEMIC DEPARTMENTS

Mole VSP2 Floor carver

NSA, Double layered system: Two Layers of Style IC UQ60 (XCYE) 9.0 oz/yd² 305 g/m² Woven, 88% Cotton 12% Nylon, Navy, January, 2011

FLUX CORE 90 WELDER ASSEMBLY & OPERATING INSTRUCTIONS

High Frequency Sinewave Guardian TM Filter

2015 RIGOL TECHNOLOGIES, INC.

C-Bus 8 Channel Low Voltage Relay

2011 / Circuit Tracer

Article 225: Outside Branch Circuits And Feeders

REDUCING ARC FLASH HAZARD BY REMOTE SWITCHING

7. INSPECTION AND TEST PROCEDURES

High Frequency SineWave Guardian TM Filter

AM-510 Commercial / Residential Multimeter. AM-510-EUR Digital Multimeter. Users Manual

Transcription:

NFPA-70E Standard for Electrical Safety in the Workplace 2015 Edition

NFPA-70E 90.1 Purpose. The purpose of this standard is to provide a practical safe working area for employees relative to the hazards arising from the use of electricity.

NFPA-70E Chapter 1 Safety-Related Work Practices Chapter 2 Safety-Related Maintenance Requirements Chapter 3 Safety Requirements for Special Equipment Annexes A-P

NFPA-70E Chapter 1 Safety-Related Work Practices Definitions Application of Safety-Related Work Practices General Requirements for Electrical Safety-Related Work Practices Establishing an Electrically Safe Work Condition Work Involving Electrical Hazards.

Article 130 Work Involving Electrical Hazards 130.1 General. Article 130 covers the following: When an electrically safe work condition must be established. The electrical safety-related work practices when an electrically safe work condition cannot be established.

Article 130 Work Involving Electrical Hazards Electrically Safe Work Condition. A state in which an electrical conductor or circuit part has been disconnected from energized parts, locked/tagged in accordance with established standards, tested to ensure the absence of voltage, and grounded if determined necessary.

130.2 Electrically Safe Working Conditions Energized electrical conductors and circuit parts shall be put into an electrically safe work condition before an employee performs work if any of the following conditions exist: The employee is within the limited approach boundary. The employee interacts with equipment where conductors or circuit parts are not exposed but an increased likelihood of injury from and exposure to an arc flash hazard exists.

EEWP Flow Chart

130.2 Electrically Safe Working Conditions Exception: Where a disconnecting means or isolating element that has been properly installed and maintained is operated, opened, closed, removed, or inserted to achieve an electrically safe work condition for connected equipment or to return connected equipment to service that has been placed in an electrically safe work condition, the equipment supplying the disconnecting means or isolation element shall not be required to be placed in an electrically safe work condition provided an risk assessment is performed and does not identify unacceptable risks for the task.

Think once, think twice Turn it off. Coordination with Owners, GC s and other trades Many times energized work can be avoided by: Adjusting start/stop or lunch times. Advance planning.

Quiz is defined as: A state in which an electrical conductor or circuit part has been disconnected from energized parts, locked/tagged in accordance with established standards, tested to ensure the absence of voltage, and grounded if determined necessary. Electrically Safe Work Condition

Quiz Energized electrical conductors and circuit parts shall be put into an electrically safe work condition an employee performs work on energized equipment. A) Before B) After C) During

110.1 Electrical Safety Program (G) Risk Assessment Procedure. An electrical safety program shall include a risk assessment procedure that addresses employee exposure to electrical hazards. The procedure shall identify the process to be used by the employee before work is started to carry out the following: Identify hazards Assess risks Implement risk control according to a hierarchy of methods.

110.1 Electrical Safety Program Informational Note No. 1: The hierarchy of risk control methods specified in ANSI/AIHA Z10, American National Standard for Occupational Health and Safety Management Systems, is as follows: (1) Elimination (2) Substitution (3) Engineering controls (4) Awareness (5) Administrative controls (6) PPE

Arc Rating The value attributed to materials that describes their performance to exposure to an electrical arc discharge. The arc rating is expressed in cal/cm 2 and is derived from the determined value of the arc thermal performance value (ATPV) or energy of break open threshold (E BT ) (should a material system exhibit a break open response below the ATPV value). Arc rating is reported as either ATPV or (E BT ) whichever is the lower value.

Arc Rating Arc Rating video; Dakota Testing video Informational Notes: All arc rated clothing is flame resistant, not all flame resistant clothing is arc rated. ATPV is defined as the incident energy on a material or multilayer system of materials that results in a 50% probability that sufficient heat transfer through the tested specimen is predicted to cause the onset of a second degree burn injury. E bt is defined as the incident energy on a material or material system that results in a 50% probability of break open. (causing a hole or opening).

Arc Rating

Turn it off Turn it off PPE the least effective solution Turn it off.

Quiz An electrical safety program shall include a that addresses employee exposure to electrical hazards. The procedure shall identify the process to be used by the employee before work is started to carry out the following: Identify hazards Assess risks Implement risk control according to a hierarchy of methods.

Quiz An electrical safety program shall include a risk assessment procedure that addresses employee exposure to electrical hazards. The procedure shall identify the process to be used by the employee before work is started to carry out the following: Identify hazards Assess risks Implement risk control according to a hierarchy of methods.

Quiz ATPV is defined as the incident energy on a material or multilayer system of materials that results in a %probability that sufficient heat transfer through the tested specimen is predicted to cause the onset of a second degree burn injury. E bt is defined as the incident energy on a material or material system that results in a % probability of break open. (causing a hole or opening).

Quiz ATPV is defined as the incident energy on a material or multilayer system of materials that results in a 50 % probability that sufficient heat transfer through the tested specimen is predicted to cause the onset of a second degree burn injury. E bt is defined as the incident energy on a material or material system that results in a 50 % probability of break open. (causing a hole or opening).

Quiz Donning PPE is nationally recognized as the effective means to mitigate risks associated with energized work. A) Best B) Least

130.2 (A) Energized Work 3 acceptable reasons for energized work. Additional Hazards or Increased Risk Infeasibility Less than 50 volts

130.2 (A) Energized Work (1) Additional Hazards or Increased Risk. Energized work shall be permitted where the employer can demonstrate that de-energizing introduces additional hazards or increased risk. Informational Note : Examples of additional hazards or increased risk include, but are not limited to, interruption of life-support equipment, deactivation of emergency alarm systems, and shutdown of hazardous location ventilation equipment.

130.2 (A) Energized Work (2) Infeasibility. Energized work shall be permitted where the employer can demonstrate that the task to be performed is infeasible in a de-energized state due to equipment design or operational limitations. Informational Note: Examples of work that might be performed within the limited approach boundary of exposed energized electrical conductors or circuit parts because of infeasibility due to equipment design or operational limitations include performing diagnostics and testing (for example, start-up or troubleshooting) of electric circuits that can only be performed with the circuit energized and work on circuits that for an integral part of a continuous process that would otherwise need to be completely shut down in order to permit work on one circuit or piece of equipment.

130.2 (A) Energized Work (3) Less Than 50 Volts. Energized electrical conductors and circuit parts that operate at less than 50 volts shall not be required to be de-energized where the capacity of the source and any overcurrent protection between the energy source and the worker are considered and it is determined that there will be no increased exposure to electrical burns or to explosion due to electric arcs.

Informative Annex J EEWP flow chart

Quiz What are the 3 acceptable reasons for energized work? Additional Hazards or Increased Risk Infeasibility Less than 50 volts

130.2 (B) Energized Electrical Work Permit (1) When Required. When energized work is permitted in accordance with 130.2(A), an energized electrical work permit shall be required under the following conditions: (1) When work is performed within the restricted approach boundary (2) When the employee interacts with the equipment when conductors or circuit parts are not exposed but an increased likelihood of injury from an exposure to an arc flash hazard exists.

130.2 (B) Energized Electrical Work Permit (3) Exemptions to Work Permit. Any energized electrical work permit shall not be required if a qualified person is provided with and uses appropriate safe work practices and PPE in accordance with Chapter 1 under any of the following conditions:

130.2 (B) Energized Electrical Work Permit (1) Testing, troubleshooting, and voltage measuring (2) Thermography and visual inspections if the restricted approach boundary is not crossed. (3) Access to and egress from an area with energized electrical equipment if no electrical work is performed and the restricted approach boundary is not crossed (4) General housekeeping and miscellaneous nonelectrical tasks if the restricted approach boundary is not crossed.

130.2 (B) Energized Electrical Work Permit EEWP and JHA Wilsons 70E calculator Shock Boundaries Limited 3 6 Restricted 1 Arc Flash Boundaries Incident energy calculation or Table 130.7(C) (15)(A)(b)

130.2 (A) Energized Work (4) Normal Operation. Normal operation of electric equipment shall be permitted where all of the following conditions are satisfied: 1-The equipment is properly installed. 2-The equipment is properly maintained. 3-The doors are closed and secured. 4-There is no evidence of impending failure.

130.2 (A) Energized Work Informational Note: The phrase properly installed means that the equipment is installed in accordance with the applicable industry codes and standards and the manufacturer s recommendations. The phrase properly maintained means that the equipment has been maintained in accordance with the manufacturer s recommendations and applicable industry codes and standards. The phrase evidence of impending failure means that there is evidence such as arcing, overheating, loose or bound equipment parts, visible damage, or deterioration.

130.5(D) Equipment Labeling DuraLabel Equipment Labels video

130.5(D) Equipment Labeling Electrical Equipment such as switchboards, panelboards, industrial control panels, meter socket enclosures, and motor control centers that are in other than dwelling units and that are likely to require examination, adjustment, service, or maintenance while energized shall be field-marked with a label containing all the following information:

130.5(D) Equipment Labeling (1) Nominal system voltage (2) Arc flash boundary (3) At least one of the following: a. Available incident energy and the corresponding working distance, or the arc flash PPE category in Table 130.7(C)(15)(A)(b) or Table 130.7(C)(15)(B) for the equipment, but not both b. Minimum arc rating of clothing c. Site-specific level of PPE

130.5(D) Equipment Labeling

130.5(D) Equipment Labeling Exception: Labels applied prior to September 30, 2011 are acceptable if they contain the available incident energy or required level of PPE.

130.5(D) Equipment Labeling Reading labels and tool inspections. Eaton-reading labels DuraLabel PPE

Quiz When do I need to fill out an EEWP? When inside the restricted approach boundary. When I interact with equipment that increases the possibility of an arc flash. When selecting PPE based on calculations/equipment labels, should I round up or down? Up

AIC Using AIC to estimate incident energy levels

Amperage interrupting Capacity (AIC) Circuit breakers have two types of current ratings. 1- continuous current rating 2-fault current interrupting capacity

Amperage interrupting Capacity (AIC)

Amperage interrupting Capacity (AIC) The amperage interrupting capacity (AIC) of a circuit breaker is the maximum short circuit current at which the breaker will safely interrupt the circuit. The AIC is at the related voltage and frequency.

What affects incident energy? Available fault current Clearing time of upstream overcurrent protective device. (how much time the arc has to come thru; the quicker the trip time, the better) Wire size (smaller wire, more resistance decreases IE) Wire distance (distance provides resistance) Whether a transformer involved in the system. (Generally voltage is induced in transformers, therefore no physical link to carry the IE).

AIC Values/Incident Energy 10ka at 208v=0.67cal/cm 2 14ka at 208v=0.87 18ka at 208v=1.05 22ka at 208v=1.23 25ka at 208v=1.35 42ka at 208v=2.01 45ka at 208v=2.11 65ka at 208v=2.79

AIC Values/Incident Energy 10ka at 240v=0.71 cal/cm 2 14ka at 240v=0.92 18ka at 240v=1.12 22ka at 240v=1.31 25ka at 240v=1.45 42ka at 240v=2.17 45ka at 240v=2.29 65ka at 240v=3.05

AIC Values/Incident Energy 10ka at 480v=1.05 cal/cm 2 14ka at 480v=1.44 18ka at 480v=1.81 22ka at 480v=2.18 25ka at 480v=2.45 42ka at 480v=3.96 45ka at 480v=4.22 65ka at 480v=5.92

AIC Values/Incident Energy NFPA 70E Table H.3(b)

AIC Values/Incident Energy 10ka at 208v=0.67cal/cm 2 14ka at 208v=0.87 18ka at 208v=1.05 22ka at 208v=1.23 25ka at 208v=1.35 42ka at 208v=2.01 45ka at 208v=2.11 65ka at 208v=2.79

AIC Values/Incident Energy 10ka at 240v=0.71 cal/cm 2 14ka at 240v=0.92 18ka at 240v=1.12 22ka at 240v=1.31 25ka at 240v=1.45 42ka at 240v=2.17 45ka at 240v=2.29 65ka at 240v=3.05

AIC Values/Incident Energy 10ka at 480v=1.05 cal/cm 2 14ka at 480v=1.44 18ka at 480v=1.81 22ka at 480v=2.18 25ka at 480v=2.45 42ka at 480v=3.96 45ka at 480v=4.22 65ka at 480v=5.92

130.5(C) Arc Flash PPE 130.5(C)(1) Incident Energy Analysis Method. The incident energy exposure level shall be based on the working distance of the employees face and chest areas from a prospective arc source for the specific task to be performed. Arc-rated clothing and other PPE shall be used by the employee based on the incident energy exposure associated with the specific task. Recognizing that incident energy increases as the distance from the arc flash decreases, additional PPE shall be used for any parts of the body that are closer than the distance at which the incident energy was determined.

10 ft. 15 ft. MDP 65 KA 65 XFMR Transformer 75 ft. 22 22 125 ft. 10

10 ft. 15 ft. MDP 65 KA 22 XFMR Transformer 75 ft. 22 22 Which of these AIC ratings is suspicious? 125 ft. 10

Bottom Line Breakdown for AIC to EEWP & PPE quick glance <10ka Need EEWP & JHA Usually below 1.2 cal/cm 2 Need shock protection 22ka at 208 volt; 14ka at 480 volt> Need EEWP & JHA Need shock and arc protection Usually need HRC 2 equivalent clothing

Bottom Line 42> Need EEWP & JHA Need shock and arc protection Usually need HRC 4 equivalent clothing Need involvement of the Safety Director PPE possibly reduced depending on an Incident Energy calculation

130.5(C) Arc Flash PPE NFPA 70E Table H.3(b) Arc Rating video

Quiz AIC stands for: Amperage Interrupting Capacity At what incident energy value is there a possibility of second degree burns? 1.2 cal/cm 2 Generally, what AIC ratings are these associated with? 22ka> at 208 volts and 14ka> at 480 volts

Face shield (as needed) Hearing protection Hard hat Safety glasses Long sleeve cotton shirt Rubber gloves with leather protectors cotton jeans

Hearing protection Face shield (as needed) Hard hat Safety glasses Cotton t-shirt Arc rated long sleeve shirt Rubber gloves with leather protectors cotton jeans

Hard hat, arc-rated face shield, arc rated balaclava, safety glasses, hearing protection Equal to or greater than arc-rated coverall Rubber gloves with leather protectors Leather footwear

Hard hat, arc-rated face shield, arc rated balaclava, safety glasses, hearing protection Cotton t-shirt Equal to or greater than arc-rated long sleeve shirt Rubber gloves with leather protectors Equal to or greater than arc-rated pants Leather footwear

Hearing protection Equal to or greater than arc-rated flash suit hood, hard hat, safety glasses Equal to or greater than arc-rated flash suit Rubber gloves with leather protectors Leather footwear

130.5(C) Arc Flash PPE 130.5(C)(2) Arc Flash PPE Categories Method. The requirements of 130.7(C)(15) and 130.7(C)16 shall apply when the arc flash PPE category method is used for the selection of arc flash PPE.

Categories PPE Categories Method Tables

130.5(C) Arc Flash PPE One of the following methods shall be used for the selection of PPE. Either, but not both, methods shall be permitted to be used on the same piece of equipment. The results of an incident energy analysis to specify an arc flash PPE Category in Table 130.7(C)(16) shall not be permitted. Incident Energy Analysis Method. Arc Flash PPE Categories Method.

130.6 Other Precautions for Personnel Activities 130.6 pp.31 130.6 pp.32

130.5(C) Arc Flash PPE https://www.youtube.com/watch?v=acch6m NJ-6o

Quiz The two methods used to determine PPE are the: Incident Energy method Categories method