Effect of Shielded Distribution Cable on Very Fast Transients

Similar documents
Effect of Shielded Distribution Cables on Lightning-Induced Overvoltages in a Distribution System

Effect of High Frequency Cable Attenuation on Lightning-Induced Overvoltages at Transformers

Prediction of Transient Transfer Functions at Cable-Transformer Interfaces

Surge Protective Properties of Medium Voltage Underground Cable

THE PROPAGATION OF PARTIAL DISCHARGE PULSES IN A HIGH VOLTAGE CABLE

Investigation of PD Detection on XLPE Cables

Fundamentals of Partial Discharge in the Context of Field Cable Testing Key words: Partial discharge, power cable, electrical testing

GIS Disconnector Switching Operation VFTO Study

Calculation of Transient Overvoltages by using EMTP software in a 2-Phase 132KV GIS

Modeling insulation in high-voltage substations

Online Localisation of Partial Discharge Using Pulse Propagation Parameters in Medium Voltage Cable Network

Comparison of switching surges and basic lightning impulse surges at transformer in MV cable grids

TD-106. HAEFELY HIPOTRONICS Technical Document. Partial Discharge Pulse Shape Analysis to Discriminate Near and Far End Failures for Cable Location

Analysis of MOV Surge Arrester Models by using Alternative Transient Program ATP/EMTP

DIFFERENCE BETWEEN SWITCHING OF MOTORS & GENERATORS WITH VACUUM TECHNOLOGY

Current state of surge testing induction machines

CHAPTER 2. v-t CHARACTERISTICS FOR STANDARD IMPULSE VOLTAGES

VFTO STUDIES DUO TO THE SWITCHING OPERATION IN GIS 132KV SUBSTATION AND EFFECTIVE FACTORS IN REDUCING THESE OVER VOLTAGES

ON-LINE PARTIAL DISCHARGE TESTING OF SOME OF THE WORST PERFORMING CIRCUITS ON A UTILITY DISTRIBUTION SYSTEM

Accurate Modeling of Core-Type Distribution Transformers for Electromagnetic Transient Studies

Partial Discharge Theory, Modeling and Applications To Electrical Machines

EFFECT OF INTEGRATION ERROR ON PARTIAL DISCHARGE MEASUREMENTS ON CAST RESIN TRANSFORMERS. C. Ceretta, R. Gobbo, G. Pesavento

AORC Technical meeting 2014

Condition Assessment of High Voltage Insulation in Power System Equipment. R.E. James and Q. Su. The Institution of Engineering and Technology

Alternative Coupling Method for Immunity Testing of Power Grid Protection Equipment

Electric Stresses on Surge Arrester Insulation under Standard and

10. DISTURBANCE VOLTAGE WITHSTAND CAPABILITY

Modeling and Analysis of a 3-Phase 132kv Gas Insulated Substation

Standing Waves and Voltage Standing Wave Ratio (VSWR)

Measurement of Surge Propagation in Induction Machines

Coherence and time-frequency analysis of impulse voltage and current measurements

High-Voltage Test Techniques

Simulation and Analysis of Lightning on 345-kV Arrester Platform Ground-Leading Line Models

Calculation of Transients at Different Distances in a Single Phase 220KV Gas insulated Substation

Practical aspects of PD localization for long length Power Cables

Partial Discharge Inception and Propagation Characteristics of Magnet Wire for Inverter-fed Motor under Surge Voltage Application

Underground System Design TADP 547

A TECHNICAL REVIEW ON CAPACITOR BANK SWITCHING WITH VACUUM CIRCUIT BREAKERS

FUNDAMENTAL LIMITATIONS IN THE MEASUREMENT OF CORONA AND PARTIAL DISCHARGE

Pulse Transmission and Cable Properties ================================

Improving CDM Measurements With Frequency Domain Specifications

LOW VOLTAGE PWM INVERTER-FED MOTOR INSULATION ISSUES

Objective Methods to Interpret Partial-Discharge Data on Rotating-Machine Stator Windings

Research Article A Simplified High Frequency Model of Interleaved Transformer Winding

FGJTCFWP"KPUVKVWVG"QH"VGEJPQNQI[" FGRCTVOGPV"QH"GNGEVTKECN"GPIKPGGTKPI" VGG"246"JKIJ"XQNVCIG"GPIKPGGTKPI

Adi Mulawarman, P.E Xcel Energy Minneapolis, MN. Pratap G. Mysore, P.E Pratap Consulting Services, LLC Plymouth, MN

Sources of transient electromagnetic disturbance in medium voltage switchgear

Neutral Reactor Optimization in order to Reduce Arc Extinction Time during Three-Phase Tripping

CHAPTER 5 CONCEPT OF PD SIGNAL AND PRPD PATTERN

MAHALAKSHMI ENGINEERING COLLEGE

Power Conditioning Equipment for Improvement of Power Quality in Distribution Systems M. Weinhold R. Zurowski T. Mangold L. Voss

USING DAMPED AC VOLTAGES

Power Quality and Reliablity Centre

TECHNICAL NOTE 2.0. Overvoltages origin and magnitudes Overvoltage protection

GIS Instrument Transformers: EMC Conformity Tests for a Reliable Operation in an Upgraded Substation

Characteristics of Insulation Diagnosis and Failure in Gas Turbine Generator Stator Windings

SUPPRESSION METHODS FOR VERY FAST TRANSIENT OVER- VOLTAGES ON EQUIPMENT OF GIS

Analysis by Simulation of the Over-voltages in PWM-Inverter Fed Induction Motors

Lumped Network Model of a Resistive Type High T c fault current limiter for transient investigations

EVALUATION AND COMPARISON OF ON-LINE PD DETECTION METHODS FOR HIGH-VOLTAGE POWER CABLE

Abstract. 1 Introduction

On-line Hydrogenerator Rotor Winding Condition Assessment Using Flux Monitoring. S.R. Campbell, G.C. Stone, M. Krikorian, G.

Lightning transient analysis in wind turbine blades

Chapter 1. Overvoltage Surges and their Effects

Shunt Reactor Switching

FAULT IDENTIFICATION IN TRANSFORMER WINDING

Analysis of lightning performance of 132KV transmission line by application of surge arresters

UNIT 2. Q.1) Describe the functioning of standard signal generator. Ans. Electronic Measurements & Instrumentation

RESULTS OF EXPERIMENTAL HIGH CURRENT IMPULSE 4/10 s OF METAL OXIDE VARISTORS ZINC IN THE HIGH VOLTAGE 220KV SURGE ARRESTER

EP A1 (19) (11) EP A1 (12) EUROPEAN PATENT APPLICATION. (43) Date of publication: Bulletin 2011/48

Transmission Line Transient Overvoltages (Travelling Waves on Power Systems)

Multi-Resolution Wavelet Analysis for Chopped Impulse Voltage Measurements

Embedded Generation Connection Application Form

A Study on Ferroresonance Mitigation Techniques for Power Transformer

Breakdown in short rod-plane air gaps under positive lightning impulse stress

Maximum Lightning Overvoltage along a Cable due to Shielding Failure

Extended analysis versus frequency of partial discharges phenomena, in support of quality assessment of insulating systems

Power Quality and Circuit Imbalances Northwest Electric Meter School Presented by: Chris Lindsay-Smith McAvoy & Markham Engineering/Itron

Simulation of characteristics of impulse voltage generator for testing of equipment using MATLAB Simulink

Return to Session BREAKDOWN CAUSED BY ABRUPT DC-VOLTAGE GROUNDING OF XLPE CABLE INSULATION ABSTRACT KEYWORDS INTRODUCTION

EXPERIMENTAL INVESTIGATION OF A TRANSIENT INDUCED VOLTAGE TO AN OVERHEAD CONTROL CABLE FROM A GROUNDING CIRCUIT

Software System for Finding the Incipient Faults in Power Transformers

ANALYSIS OF VOLTAGE TRANSIENTS IN A MEDIUM VOLTAGE SYSTEM

DIELECTRIC HEATING IN INSULATING MATERIALS AT HIGH DC AND AC VOLTAGES SUPERIMPOSED BY HIGH FREQUENCY HIGH VOLTAGES

HVDC Transmission. Michael Muhr. Institute of High Voltage Engineering and System Performance Graz University of Technology Austria P A S S I O N

HV AC TESTING OF SUPER-LONG CABLES

6. du/dt-effects in inverter-fed machines

A Reflectometer for Cable Fault Location with Multiple Pulse Reflection Method

Simulation of Lightning Transients on 110 kv overhead-cable transmission line using ATP-EMTP

Impact Assessment Generator Form

Name: Craig Goodwin. Company Name: HV Diagnostics Inc

Estimation of Re-striking Transient Overvoltages in a 3-Phase 132KV Gas insulated Substation

Detection of Partial Discharges and its Effect on Solid Insulation used in High Voltage Cable

Long lengths transmission power cables on-site testing up to 500 kv by damped AC voltages

Estimation of Re-striking Transient Over voltages in a 132KV Gas insulated Substation

PD Solutions. On-Line PD Measurement Devices

FISCHER CUSTOM COMMUNICATIONS, INC.

CONTENTS. 1. Introduction Generating Stations 9 40

Chapter 12: Transmission Lines. EET-223: RF Communication Circuits Walter Lara

HIGH VOLTAGE ENGINEERING(FEEE6402) LECTURER-24

Transcription:

IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 15, NO. 3, JULY 2000 857 Effect of Shielded Distribution Cable on Very Fast Transients Li-Ming Zhou and Steven Boggs, Fellow, IEEE Abstract Fast transients in power systems can be generated by switching of vacuum and SF 6 insulated devices as well as by solid state devices such as those used in variable speed drives. Transients with ns risetimes can be generated which, in a cable-connected system, propagate down the cable to inductive devices such as motors and transformers. In general, the amplitude of such surges is not out of the ordinary; however, the very short risetime can cause unacceptable voltages across the first turn of an inductive device. A cable with high frequency loss does not generally decrease the amplitude of such surges appreciably but can lengthen the risetime substantially by absorbing high frequency energy from the surge. This reduces the voltage across the first turn of inductive devices and thereby protects them from damage and failure caused by such surges. In the present contribution, we quantify the high frequency losses and effect thereof on very fast transients for four types of shielded, 15 kv distribution cable, three made from various EPR compounds and one made from TR XLPE. I. INTRODUCTION THE AMPLITUDE of fast transients generated by switching of devices such as vacuum interrupters, SF interrupters, and solid state switching devices used in variable speed drives is usually well below the system BIL, which means that surge protective devices such as ZnO arresters will have little effect on such surges. However, the risetime of such transients can be so short that the propagation time around the first turn of an inductive device is of the same order as the surge risetime, which results in a substantial portion of the surge voltage appearing across the first turn of a motor or transformer. This can cause progressive degradation and eventual failure of the insulation. In the present contribution, we quantify the influence of various types of shielded distribution cables on the nonlinear voltage distribution in motors and transformers. Such cables have substantial high frequency loss caused by the semicons and dielectric. Such high frequency loss lengthens the risetime of a fast transient which propagates down the cable. Thus the severity of the surge presented to an inductive device such as a motor or transformer decreases as a function of the distance and type of cable through which the surge propagates. The frequency range of interest corresponds to risetimes from about 10 ns to 1 s, i.e., 30 MHz to about 300 khz, respectively. While vacuum and SF interrupters can generate transients well below 10 ns risetime, by the time such transients are coupled Manuscript received October 4, 1999. L.-M. Zhou is with the Electrical Insulation Research Center, Institute of Materials Science, University of Connecticut, Storrs, CT 06269-3136 USA. S. Boggs is with the Electrical Insulation Research Center, Departments of Electrical Engineering and Physics, University of Connecticut. He is also with the Department of Electrical and Computer Engineering, University of Toronto. Publisher Item Identifier S 0885-8977(00)07581-6. into the cable, the risetime has generally lengthened to no less than 10 ns. II. HIGH FREQUENCY LOSS IN POWER CABLE The theory of high frequency loss in shielded power cables has been examined in detail [1] [3], [8] and results from two primary sources. The first, which applies to all shielded power cables, is the loss in the semicons caused by conduction of the radial displacement current through the resistance of the inner and outer semicons. If we consider the dielectric to be lossless, which is a good approximation for pure XLPE, then the dielectric can be viewed as a high impedance (as a result of the relatively small capacitance per unit length across it relative to that of the semicons) which determines the current through the semicons. In the MHz range, the semiconducting layers generally have a large dielectric constant (in the range of 100 1000 or more) along with a substantial resistance. The loss in the semicons is maximized when the resistive impedance equals the capacitive impedance at the frequency of interest [4]. Thus to maximize the high frequency loss caused by the semicons, the dielectric constant of the semiconducting layers would be minimized while the conductivity of the semicons would be optimized so that conductivity is approximately equal to the product of the radial frequency ( ) times the absolute dielectric constant in the frequency range of interest. The loss in the semicon reduces away from this optimum in all directions, i.e., if the semicon dielectric constant increases or decreases, or if the semicon conductivity increases or decreases from the optimum. The high frequency loss of cable dielectrics other than pure XLPE must be considered. However these losses, and the phase shift they cause in the current through the semicons, is so small that the loss in the semicons and the loss in the dielectric are simply additive under all conditions of technical interest [4]. Thus the loss of a cable can be predicted by measuring the dielectric properties of the dielectric and the dielectric properties of the semicons over the frequency range of interest and inserting these data into an electrical model for the cable. This has been done with good agreement to the measured loss of the cable. We should note that the loss of properly functioning semicons is always negligible at power frequency, and optimization of loss at high frequency has no impact on the power frequency loss of the cable. As noted above, the semicon loss can only be optimized at one frequency (unless the semicon properties change with frequency in a way which allows optimization over a range of frequencies, as does sometimes occur). Thus if the semicon is optimized for high frequency loss, it will be far from optimized 0885 8977/00$10.00 2000 IEEE

858 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 15, NO. 3, JULY 2000 Fig. 1. High frequency attenuation of four types of shielded power cables, three cables made with different EPR dielectrics and one cable made with TR XLPE. Note the substantial differences in attenuation of the various cables over the frequency range of interest. Fig. 2. Measured fraction of voltage across the first turn of a motor as a function of waveform risetime as measured by two researchers [5], [6], [9], along with a curve fit to the data which is used in later analysis. The data taken by different researchers on different motors are in good agreement. For risetime less than 500 ns, the voltage across the first increases rapidly. for power frequency loss. The high frequency and power frequency loss of a cable or cable dielectric need not be correlated. Thus a cable might be developed which has very large high frequency loss without increased loss at power frequency. The high frequency loss of four types of 15 kv class shielded power cables was measured using an HP 4191 A high frequency impedance analyzer in the range from 1 MHz to 50 MHz and a GR bridge at lower frequencies. Fig. 1 shows the measured high frequency loss of the four cable types. Note that the attenuation of the cable types differs by nearly a factor of four from the most lossy to the least lossy. III. VOLTAGE DISTRIBUTION IN INDUCTIVE DEVICES When a fast transient impinges on an inductive device such as a motor or transformer, the transient propagates down the winding, which can be viewed, in one approximation, as a transmission line. If the risetime of the transient is less than the propagation time around the first turn of the inductive device, the full voltage of the transient can appear across the first turn. The voltage which actually appears across the first turn is a function of the transient risetime, decreasing with increasing risetime until, beyond some risetime, the voltage across the winding approaches its low frequency design distribution. Figs. 2 and 3 show data for measured voltage across the first turn of a motor and top 10% of a transformer winding as compiled from several sources, along with equations fit to the data which are used in the analysis below. These data indicate that the voltage across the top of the winding increases rapidly as the waveform risetime becomes shorter but approaches a normal, low frequency distribution for risetimes longer than about 1 s, which corresponds roughly to a lightning impulse. Thus to protect an inductive device from switching transients we do not normally need to decrease the amplitude of the transient but only increase the risetime of the transient. IV. IMPACT OF CABLE LOSS ON WAVEFORM RISETIME As noted above, the high frequency loss in the cable causes the risetime of a wave propagating down the cable to lengthen as Fig. 3. Measured fraction of voltage across the top 10% of a transformer winding for two different transformers [7], along with a curve fit to the data which is used in later analysis. a function of distance propagated in the cable. A short risetime implies substantial energy at high frequencies, and if such energy is absorbed from the waveform, the risetime must become longer. Obviously, the greater the high frequency cable loss, the greater the effectiveness in lengthening the waveform risetime or the less length of cable required to achieve a given minimum risetime. Figs. 4 7 show 3-D plots of the 10 90% pulse output risetime as a function of input risetime and cable length through which the pulse has propagated. The general shape of these 3-D plots requires some explanation for which we will refer to Fig. 5 which corresponds to EPR2, the cable with the greatest high frequency attenuation. We will first explain the shape of the output risetime as a function of cable length for short input risetime, the minimum for which is 10 ns on these plots. The output risetime results from the superposition of two effects, viz., the input risetime and the lengthening of the input risetime caused by the attenuation of the cable. For simple 1-pole (6 db/octave) filters, the input risetime, and the output risetime of the filter

ZHOU AND BOGGS: SHIELDED DISTRIBUTION CABLE 859 Fig. 4. 10 90% pulse output risetime as a function of pulse input risetime and the length of cable through which the pulse has propagated for EPR1. Fig. 6. 10 90% pulse output risetime as a function of pulse input risetime and the length of cable through which the pulse has propagated for EPR3. Fig. 5. 10 90% pulse output risetime as a function of pulse input risetime and the length of cable through which the pulse has propagated for EPR2. for a perfect stepwave input, add as the root mean square. In other words, if we take a 7 ns risetime waveform and observe it with an oscilloscope which has a 5 ns risetime, we will observe a risetime of 8.6 ns [sqrt( )] on the oscilloscope. The input waveform and cable attenuation represent an analogous situation except that the filter represented by the cable is not a simple 1-pole filter so that the above rule for computing the output risetime becomes an approximation. Still, it provides us with a conceptual basis for understanding what is going on. Thus for very short cable lengths, the risetime of the cable (i.e., the output risetime for a perfect step wave into the cable) is substantially less than the minimum input risetime of 10 ns, so that Fig. 7. 10 90% pulse output risetime as a function of pulse input risetime and the length of cable through which the pulse has propagated for TR XLPE. the resulting overall risetime does not differ appreciably from the input risetime until the cable length is about 50 m for EPR2. Beyond 50 m, the cable risetime increasingly dominates the overall risetime, as we can see from the flat region in the direction of increasing input risetime, which indicates that over this limited range (the flat region), the output risetime is essentially independent of the input risetime. We note the concave shape of the output risetime vs cable length which indicates that the output risetime lengthens less than linearly with distance propagated through the cable. This is the result of frequency dependent attenuation of the cable. As seen in Fig. 1, the cable attenuation is frequency-dependent, increasing roughly linearly with frequency. Thus as a transient propagates down the cable,

860 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 15, NO. 3, JULY 2000 Fig. 8. Voltage across the first turn of a motor as a function of cable input transient risetime and cable length for cable EPR1. Fig. 10. Voltage across the first turn of a motor as a function of cable input transient risetime and cable length for cable EPR3. Fig. 9. Voltage across the first turn of a motor as a function of cable input transient risetime and cable length for cable EPR2. the highest frequencies are attenuated more rapidly than lower frequencies and are effectively lost from the waveform. The remaining frequencies are attenuated less rapidly which results in less than linear lengthening of the risetime with distance propagated through the cable. If we now consider the output risetime as a function of input risetime, at zero cable length the two are, of course, the same. For very large input risetimes, the cable has only a modest effect on the waveform risetime as a function of distance propagated, as the attenuation at the (low) frequencies corresponding to such a long risetime is not very great. For a very long cable length, the minimum risetime becomes large and constant as a function of input risetime until the input risetime becomes comparable to the cable risetime. At 250 m, the cable risetime is about 1 s Fig. 11. Voltage across the first turn of a motor as a function of cable input transient risetime and cable length for cable TR XLPE. (for short input risetimes), and the output risetime increases to about 1.5 s for an input risetime of 1 s, which is close to the 1.414 s which would be expected from the root mean square. V. FIRST TURN MOTOR VOLTAGE VS CABLE LENGTH Figs. 8 11 show the voltage across the first turn of a motor as a function of input transient risetime and cable length for the four types of cables based on the data of Fig. 2. As would be expected from the attenuation data of Figs. 4 7, EPR2 reduces the surge magnitude across the first turn most quickly as a result of having substantially greater high frequency attenuation than the other cables. Seventy-five (75) meters of EPR2 reduce the

ZHOU AND BOGGS: SHIELDED DISTRIBUTION CABLE 861 Fig. 12. Voltage across the top 10% of a transformer winding as a function of cable input transient risetime and cable length for EPR1. Fig. 14. Voltage across the top 10% of a transformer winding as a function of cable input transient risetime and cable length for EPR3. Fig. 13. Voltage across the top 10% of a transformer winding as a function of cable input transient risetime and cable length for EPR2. voltage across the first turn to near normal levels for any cable input risetime. 250 m of EPR1 or EPR3 would be required to effect a similar reduction or in the range of 400 m TR XLPE. Thus modest lengths of cable can be very effective in limiting the voltage drop across the first turn of a motor caused by very fast transients as generated by vacuum or SF switchgear or by solid state switching devices in variable speed drives. VI. TRANSFORMER VOLTAGE VS CABLE LENGTH Figs. 12 15 show the voltage across the top 10% of a transformer winding as a function of cable input risetime and cable length. Again and as expected, cable EPR2 reduces the voltage across the top 10% of the winding most quickly as a function Fig. 15. Voltage across the top 10% of a transformer winding as a function of cable input transient risetime and cable length for TR XLPE. of cable length with only 75 m required to reduce substantially the overvoltage, as compared to 250 m for EPR1 or EPR3, and over 400 m of TR- XLPE. Thus, again, the effect of fast transients can be eliminated through modest lengths of cable which has relatively large high frequency attenuation. Figs. 16 and 17 summarize the data for motors and transformers based on reasonable worst cases for the two situations from the literature. Of course, the transient which can be generated by switching phenomena should not depend on whether a motor or transformer is connected to the system, so that both surges should be plausible worst cases for either a transformer or motor. In both cases, we see that the length for diminishing returns of EPR2 is in the range of 100 m while that for EPR1

862 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 15, NO. 3, JULY 2000 Fig. 16. Voltage across the first turn of a motor as a function of cable length for a 0.2 s transient with an amplitude of 4.5 pu which is a reasonable worst case based on field measurements [5], [9]. Fig. 18. Probability density distribution vs cable length of EPR2 for measured worst case transient magnitude and risetime distribution for typical motor installations [5], [9]. Fig. 17. Voltage across the top 10% of a transformer winding as a function of cable length for a 15 ns, 4.9 pu surge into the cable which is a reasonable worst case based on field measurements [6]. and EPR3 is in the range of 350 m, at least for the transformer case. TR-XLPE has relatively little attenuation. Figs. 18 and 19 show the effect of various lengths of EPR2 and TR XLPE cable on the probability density distribution (i.e., the area under the curve is normalized to unity) of fast transient induced voltages across the first turn of a motor based on measured distribution of largest transient magnitudes (and corresponding risetimes) measured at various motor installations [5], [9]. 100 m of EPR2 cable reduces the maximum voltage across the first turn from about 0.9 pu to about 0.55 pu (Fig. 18), while a similar length of TR XLPE cable reduces the maximum voltage from 0.9 pu to 0.8 pu (Fig. 19). Thus the high frequency attenuation of the cable has a substantial effect on the surge voltages to which the motor winding is subjected during normal service. VII. CONCLUSIONS Attenuation or loss in power cables is generally seen as a bad attribute, and clearly low loss at power frequency Fig. 19. Probability density distribution vs cable length of TR XLPE for measured worst case transient magnitude and risetime distribution for typical motor installations [5], [9]. is preferable to high loss, all other characteristics being the same. However, loss at high frequencies can be a very positive attribute in that such loss can protect industrial plant and utility power system components from the detrimental effects of very fast transients generated by switching devices and power electronics. In present cables, high and low frequency loss tend to be correlated to some degree; however, this correlation is not fundamental, and design of a shielded power cable which has large high frequency loss without increased power frequency loss is within the realm of possibility. In the present contribution, we have quantified the effect of presently available cables on high frequency transients and found that the loss of such cables varies widely. While the high frequency loss of power cables is not a specified characteristic, we feel confident that the loss characteristics of the higher loss

ZHOU AND BOGGS: SHIELDED DISTRIBUTION CABLE 863 cables is dominated by the dielectric rather than the semicons and should therefore be a characteristic of any cable made with that dielectric. The high frequency loss of lower loss cables may not be so well defined, as such loss may be dominated by the semicons, which are not well specified for conductivity and dielectric constant, both of which could vary with cable manufacturing conditions, moisture, temperature, etc. Of course, full characterization of the higher loss cables should also include measurement of the loss vs temperature, and while the loss of most dielectrics does change with temperature, that change is not nearly as great as the change in conductivity of a semicon with temperature. The alternative to using a cable to protect an inductive device from the effect of fast transients is often the use of a capacitor across the device terminals, which is most common for motors. However, capacitors are substantially less reliable than either cable or motors, and the inclusion of such a capacitor may protect an expensive motor from failure at the cost of reduced overall system reliability. Cable is extremely reliable, and use of a cable as the protective device may be more economical than use of a capacitor, especially when the implications of capacitor failure on overall system reliability are considered. In summary, high frequency loss of power cables protects power system components from the detrimental effects of fast surges. Where a motor or transformer is connected directly to switchgear or power electronics, a cable installation might be designed specifically to protect the motor or transformer. In other situations, use of a cable with large high frequency loss throughout a power system will reduce the magnitude of transients propagating therein and thereby reduce the failure rate of transformers, motors, capacitors, and other components connected to the power system. REFERENCES [1] G. C. Stone and S. A. Boggs, Propagation of partial discharge pulses in shielded power cable, in 1982 Ann. Rep. Conf. Electrical Insulation and Dielectric Phenomena. Washington, DC, pp. 275 280. [2] S. A. Boggs and G. C. Stone, Fundamental limitations to the measurement of corona and partial discharge, in 1981 Annual Report of the Conference on Electrical Insulation and Dielectric Phenomena. Washington, DC. [3] Surge attenuating cable, U.S. Patent 4 687 882. [4] S. A. Boggs, A. Pathak, and P. Walker, Partial discharge XXII: high frequency attenuation in shielded solid dielectric power cable and implications thereof for PD location, IEEE Electrical Insulation Mag., vol. 12, pp. 9 16, Jan./Feb. 1996. [5] B. K. Gupta, B. A. Lloyd, G. C. Stone, D. K. Sharma, and N. E. Nilson, Turn insulation capability of large AC motors Part 1: surge monitoring, IEEE Trans., vol. EC-2, no. 4, pp. 658 665, 1987. [6] K. J. Cornick and A. M. Kunji, Nanosecond switching transients recorded in a mining transformer installation, IEEE Trans., vol. PD-8, no. 3, pp. 1130 1137, 1993. [7] L. M. Burrage, E. F. Veverka, and B. W. McConnell, Steep front short duration low voltage impulse performance of distribution transformers, IEEE Trans., vol. PWRD-2, no. 4, pp. 1152 1156, 1987. [8] S. A. Boggs and G. C. Stone, Fundamental limitations to the measurement of corona and partial discharge, IEEE Trans., vol. EI-17, p. 143, April 1982. [9] B. K. Gupta, B. A. Lloyd, G. C. Stone, D. K. Sharma, and J. P. Fitzgerald, Turn insulation capability of large AC motors Part 2: Impulse strength, IEEE Trans., vol. EC-2, no. 4, pp. 666 673, 1987. Li-Ming Zhou was graduated with a Ph.D. degree in electrical engineering from Xi an Jiaotong University (Xi an, P. R. China) in 1995. From 1995 to 1998, he visited Eindhoven University of Technology (The Netherlands), Technical University of Ilmenau (Germany), ABB Corporate Research Ltd. (Switzerland), and University of Oklahoma as a Research Scientist. His past research interests have included SO /NO removal from flue gas by pulsed corona discharge, dielectric barrier discharge for conversion greenhouse gases to methanol and synthesis gas (H +CO), and dielectric and arc interruption capability of SF and its mixtures. He has authored and co-authored more than 40 technical articles. He is presently a Post Doctoral Fellow at the Electrical Insulation Research Center, University of Connecticut. Steven Boggs received his Ph.D. and MBA degrees from the University of Toronto in 1972 and 1987, respectively. He spent 12 years with the Research Division of Ontario Hydro and 6 years as Director of Engineering and Research for Underground Systems, Inc. Steve is presently Director of the Electrical Insulation Research Center of the University of Connecticut and Research Professor of Materials Science, Physics, and Electrical Engineering. He is also an Adjunct Professor of Electrical Engineering at the University of Toronto. He has published widely in the areas of partial discharge measurement, high frequency phenomena in power apparatus, high field degradation of solid dielectrics, and SF insulated systems. He was elected a Fellow of the IEEE for his contributions to the field of SF insulated systems.