Rated power VA (50 Hz)/W 0.6/ / / /0.3 Operating range V AC (50/60 Hz)

Similar documents
Rated power VA (50 Hz)/W 0.6/ / / /0.3 Operating range V AC (50/60 Hz)

77 Series - Modular Solid State Relay 5 A. Features. Timers and Monitoring relays

38 SERIES. Relay interface modules A. EMR Electromechanical Relays. Common features. SSR Solid State Relays. 6.

38 Series - Relay interface modules A

Multi-function (MI, ME, M2, M1) 2 NO (2 SPST-NO) 12 / / 400 3,000 1, / 0.3 / (5 / 5) AgNi

38 Series - Relay interface modules A

Multi-voltage Multi-function. Wiring diagram (without control signal)

MasterINTERFACE 39 Series - Relay interface modules

38 Series - Relay interface modules A. Features /

MasterINTERFACE 39 Series - Relay interface modules

83 Series - Modular timers 16 A. Features

3.5 mm contact pin pitch 1 Pole 12 A PCB direct or via socket

Modular step relays 16 A

3.5 mm contact pin pitch 1 Pole 12 A PCB direct or via socket

Modular timers A

Step relays 10 A SЕRIES. Lighting control in corridors (for hotels, offices and hospitals) Bedroom light control. Living room light control

mm wide Low coil power PCB or 93 series sockets. Copper side view. 1 CO (SPDT) 6/10 250/400 1, /0.2/ (12/10) AgNi

48 Series - Relay interface modules A. Features

13 SERIES. Electronic step relays A

38 Series - Relay Interface Modules A

83 SERIES. 83 Series - Modular timers A. Features

Electronic step, call/reset and monostable relays

62.22 Copper side view

2 or 4 pole changeover contact Plug-in/Faston 187

48 SERIES. Relay interface modules 8 A CO forcibly guided contacts relay interface modules,15.8 mm wide Type 48.12

2 Pole CO, 8 A Plug-in 2 CO (DPDT) 1 CO (SPDT) 8/15 16/25* 250/ /400 2,000 4, /0.5/ /0.5/ (5/5) 300 (10/5)

2 pole (1 NO + 1 NC) 1 NO + 1 NC 2 NO + 2 NC, 3 NO + 1 NC 4 NO + 2 NC Rated current / Max. peak current Rated load AC1

Relay interface modules A

58 SERIES. Relay interface modules 7-10 A 58.P3 58.P4

Time switches 16 A NEON SЕRIES. Heating and cooling. Shop displays. Lighting for parks. Streetlights and car park lighting.

62 Series - Power relays 16 A. Features SERIES / / Printed circuit mount 16 A Power relay

24 V DC, 12 W output 12 V DC, 12 W output 24 V DC, 36 W output

The power in relays and timers since Catalogue

62 Series - Power relays 16 A. Features / /

3.5 mm contact pin pitch 1 Pole 12 A PCB direct or via socket

60 Series - General purpose relays 6-10 A. Features Plug-in mount 10 A General purpose relay

3.6. Control Relays and Timers D A M D 2. Contents. Product Overview. Catalog Number Selection. Solid-State Relays

Multi-voltage Multi-function. BE: Off-delay with control signal BE: Off-delay with control signal CE: On- and off-delay with control signal

Subject to changes 11/2003 Page 1/7

13 Series - Electronic step relays A. Features SERIES

Mechanical daily time switch. 35 mm rail (EN 60715) mount

Sensitivity range ( ) kω adjustable Delay time (0.5s or 7s) switch selectable Emptying or filling functions switch selectable

Multi-function 11 pin Plug-in for use with 90 series sockets

13 Series - Electronic step relays A. Features Residential applications

30 A rated contacts Flange mount Faston 250 connections. 30 A rated contacts PCB mount - bifurcated terminals. Copper side view

A rated contacts Flange mount/faston 250 (6.3 x 0.8 mm) connection

3RF A A 0 2. Switching function. Control voltage Operating voltage with heat sink 10 = 10.5 A. A = Zero-point switching

87 Series - Modular timers 5-8 A. Features

08/07/2015

Sensitivity range ( ) kω adjustable Delay time (0.5s or 7s) switch selectable Emptying or filling functions switch selectable

Fixed - Over/Under voltage limits, ( ) U N respectivity Link selectable - 5 min or 10 min delay. Fixed limits

NEW Series STH Output to 75A, 600 Vac High Industrial Performance (HIPpak) Solid-State Relays

Fixed - Over/Under voltage limits, ( ) U N respectivity Link selectable - 5 min or 10 min delay. Fixed limits

Sensitivity range ( ) kω adjustable Delay time (0.5s or 7s) switch selectable Emptying or filling functions switch selectable

Semiconductor contactors, Solid-state relays

Solid State Relay, 1-phase

Solid State Relays 1- and 2 Pole SOLITRON With Integrated Heatsink

RN Thyristor Controllers

13 Series - Electronic step/monostable & call/reset relays 8-16 A. Features

Electronic timer CT-SDS.22 Star-delta change-over with 2 n/o contacts Data sheet

CONTA-ELECTRONICS. Relay systems

40 Series - Miniature P.C.B. Relays A

Thermistor motor protection relays

A rated contacts PCB mount - bifurcated terminals. Copper side view

Type CP-S, CP-C & CP-A Switch mode

Electronic timer CT-SDS.22

CARREL-ELECTRADE LTD not just products... solutions!

Electronic timer CT-SDE Star-delta change-over with 1 n/c + 1 n/o contact

02/11/2015

Three-phase monitoring relays CM-PFE and CM-PFE.2

12 Series - Time switches 16 A. Features

Features. LED Driver RACT Watt. TRIAC Dimmable. Single Output RACT AC/DC Converter

Features. LED Driver RACT Watt. TRIAC Dimmable. Single Output RACT12- AC/DC Converter

Multi-function 11 pin Plug-in for use with 90 series sockets

08/07/2015

No-wear isolation of potentials in terminal block design

02/11/2015

Electronic timer CT-MVS.23 Multifunctional with 2 c/o (SPDT) contacts

DATASHEET - ETR4-70-A. Delivery program. Timing relay, 2W, 0.05s-100h, multi-function, VAC/DC, potentiometer connection

Solid State Relays Industrial, 1-Phase ZS (IO) w. LED and Built-in Varistor Types RM 23, RM 40, RM 48, RM 60

Electronic timer CT-TGD.12 Pulse generator with 1 c/o (SPDT) contact

DATASHEET - ETR4-51-A. Delivery program. Technical data General. Timing relay, star-delta, 50 ms, 1W, 3-60s, VAC/DC

Measuring and monitoring relays CM-SRS.1 Current monitoring relays, single-phase AC/DC

Three-phase monitoring relay CM-PVE

CI-tronic Analogue Power Controller ACI 30-1 and ACI 50-1

Semiconductor contactors, Solid-state relays

Electronic timer CT-YDE Star-delta change-over with 1 c/o (SPDT) contact

Type: EASY719 AC RC Article No.: Ordering information Relay outputs Quantity 6 Power supply V DC 115/230 V AC. Description

Electronic timer CT-SDD.22

05/09/2012

Electronic timer CT-EBE Flasher starting with OFF, 1 c/o (SPDT) contact

Controls Contactors and Contactor Assemblies Special Applications

SOLID STATE RELAY RATINGS

Electronic timer CT-MBS.22 Multifunctional with 2 c/o (SPDT) contacts

celduc SIL Phase angle controller Output : VAC 32A(*) Input : Analog 0-10V celpac r e l a i s Proud to serve you

SMARTimer, digital timer 16 A

46.61 Series, SPDT 16A. Part Number Price Coil Voltage

Current monitoring relays CM-SRS.2 for single-phase AC/DC currents

Controls Solid-State Switching Devices

Electronic timer CT-MFS.21

Transcription:

77 Modular Solid State Relay 5 A 77 5 A modular SSR, 1 NO AC output 17.5 mm housing 60 to 240 V AC output (with back to back SCR) 5 kv (1.2/50 µs) insulation between and Output Zero-crossing and random switch-on versions available High switching speed High endurance Silent switching Spark and bounce-free switching Low control power 3-phase general purpose 35 mm rail (EN 60715) mount 77.01 Screw terminal 77.01.x.xxx.8050 Suggested applications: Lamp inrush current reduction (CFL - Compact Fluorescent energy-saving Lamps and similar) Heater control Solenoid, contactor driver 77.01.x.xxx.8051 Random switch-on Suggested applications: Finer control requiring short operate time (specially motor control) AC phase different from AC Output phase * See L77-3 diagram page 11 ** See L77-1 and L77-2 diagrams page 10 For outline drawing see page 14 Output configuration 1 NO (SPST-NO) 1 NO (SPST-NO) Rated current I N /Max. peak current* (10 ms) A 5/300* 5/300* Rated V AC (50/60 Hz) 230 230 Switching range V AC (50/60 Hz) 48 265 48 265 Repetitive peak off-state V pk 800 800 Rated load AC7a (cos ϕ = 0.8) A 5 5 Rated load AC15 A 5 3 Single phase motor rating (230 V AC) kw 0.37 Nominal lamp rating: 230 V incandescent/halogen W 1000 800 electronic ballast W 1000 800 electromechanical ballast W 1000 800 CFL W 800 400 230 V LE W 800 400 LV halogen or LE with electronic ballast W 800 400 LV halogen or LE with electromechanical ballast W 1000 800 Minimum switching current @ 230 V ma 100 100 Typical OFF-state leakage current @ 230 V ma 1 1 Max ON-state drop @ 25 C and 5 A/100 ma V 0.85/1.5 0.85/1.5 Power loss @ 5 A W 4 4 specification Nominal (U N ) V AC (50/60 Hz) 24 230 24 230 V C 12 24 12 24 Rated power VA (50 Hz)/W 0.6/0.5 3.6/0.3 0.6/0.5 3.6/0.3 Operating range V AC (50/60 Hz) 16 32 90 265 16 32 90 265 V C 9.8 32 9.8 32 Must drop-out V AC (50/60 Hz)/C 2.4 24 2.4 24 Technical data Electrical life cycles 10 10 6 10 10 6 Operate/release time ms 20/12 9/8 Insulation between input and output (1.2/50 µs) kv 5 5 Ambient temperature C 20 +70** 20 +70** Protection category IP 20 IP 20 Approvals (according to type) 1

77 77 Modular Solid State Relay 7-15 A 7-15 A modular SSR, 1 NO C output 17.5 mm housing 2 versions, for 24 and 125 V C mosfet output 4 kv (1.2/50 µs) insulation between and Output Short circuit protection High switching speed High endurance Silent switching Spark and bounce-free switching Low control power Suitable for railway applications 35 mm rail (EN 60715) mount 77.01 Screw terminal * See L77-12 and L77-13 diagrams page 10 77.01.9.024.9024 77.01.9.024.9125 24 V C output switching 15 A rated Applications in Energy, Automation and Machines: Control of electric, pneumatic and hydraulic electromagnetic valves irect control of loads such as motors and electromagnets 110 125 V C output switching 7 A rated Applications in Energy, Automation and Machines: Control of electric, pneumatic and hydraulic electromagnetic valves irect control of loads such as motors and electromagnets For outline drawing see page 14 Output configuration 1 NO (SPST-NO) 1 NO (SPST-NO) Rated current I N /Max. peak current (10 ms) A 15/160 7/60 Rated V C 24 125 Switching range V C 16 32 85 140 Rated load C13 A 5 2.5 C motor rating kw 0.2 Minimum switching current ma 100 50 Typical OFF-state leakage current ma 3 6 Max ON-state drop @ 25 C and I N V 0.06 0.2 Power loss @ I N W 1 1.5 specification Nominal (U N ) V C 6 24 6 24 Rated power W 0.5 0.5 Operating range V C 4 32 4 32 Must drop-out V C 3 3 Technical data Electrical life cycles 10 10 6 10 10 6 Operate/release time ms 0.05/2 0.05/2 Insulation between input and output (1.2/50 µs) kv 4 4 Ambient temperature C 20 +70* 20 +70* Protection category IP 20 IP 20 Approvals (according to type) 2

77 Modular Solid State Relay 15 A 77 15 A modular SSR, 1 NO output 22.5 mm housing, heat-sink + plastic cover 24 to 277 V AC output (with triac) 6 kv (1.2/50 µs) insulation between and Output Zero-crossing and random switch-on versions available High switching speed High endurance Silent switching Spark and bounce-free switching Low control power 3-phase general purpose Relay-style terminal arrangement (input and output terminals on opposite sides) 35 mm rail (EN 60715) mount 77.11 Screw terminal 77.11.x.xxx.8250 Suggested applications: Lamp inrush current reduction (CFL - Compact Fluorescent energy-saving Lamps and similar) Heater control Solenoid, contactor driver 77.11.x.xxx.8251 Random switch-on Suggested applications: Fine controls involving shorter time (specially motor control) * See L77-7 diagram page 11 ** See L77-6 diagrams page 10 For outline drawing see page 14 Output configuration 1 NO (SPST-NO) 1 NO (SPST-NO) Rated current I N /Max. peak current* (10 ms) A 15/400* 15/400* Rated V AC (50/60 Hz) 230 230 Switching range V AC (50/60 Hz) 19 305 19 305 Repetitive peak off-state V pk 800 800 Rated load AC7a (cos ϕ = 0.8, @ 25 C) A 20 20 Rated load AC15 A 15 15 Single phase motor rating (230 V AC) kw 1.2 Nominal lamp rating: 230 V incandescent/halogen W 4000 2500 electronic ballast W 4000 2500 electromechanical ballast W 2000 1000 CFL W 3000 1500 230 V LE W 3000 1500 LV halogen or LE with electronic ballast W 3000 1500 LV halogen or LE with electromechanical ballast W 3000 1500 Minimum switching current @ 250 V ma 100 100 Typical OFF-state leakage current @ 250 V ma 1 1 Max ON-state drop @ 25 C and 15 A V 1.55 1.55 Power loss @ 15 A W 14 14 specification Nominal (U N ) V AC (50/60 Hz) 230 230 V C 24 24 Rated power VA (50 Hz)/W 0.4 7.5/0.9 0.4 7.5/0.9 Operating range V AC (50/60 Hz) 40 305 40 305 V C 4 32 4 32 Must drop-out V AC (50/60 Hz)/C /2 6/ /2 6/ Technical data Electrical life cycles 10 10 6 10 10 6 Operate/release time ms < 10/< 10 < 10/< 30 < 1/< 10 < 2/< 25 Insulation between input and output (1.2/50 µs) kv 6 6 Ambient temperature C 20 +80** 20 +80** Protection category IP 20 IP 20 Approvals (according to type) 3

77 77 Modular Solid State Relay 30 A 30 A modular SSR, 1 NO output 22.5 mm housing, heat-sink + plastic cover 60 to 440 V AC output (with back to back SCR) 6 kv (1.2/50 µs) insulation between and Output Zero-crossing and random switch-on versions available High switching speed High endurance Silent switching Spark and bounce-free switching Low control power 3-phase general purpose Relay-style terminal arrangement (input and output terminals on opposite sides) 35 mm rail (EN 60715) mount 77.31 Screw terminal * See L77-5 diagram page 11 ** See L77-4 diagrams page 10 77.31.x.xxx.8050 Suggested applications: Lamp inrush current reduction (CFL - Compact Fluorescent energy-saving Lamps and similar) Heater control Solenoid, contactor driver 77.31.x.xxx.8051 Random switch-on Suggested applications: Finer control requiring short operate time (specially motor control) For outline drawing see page 14 Output configuration 1 NO (SPST-NO) 1 NO (SPST-NO) Rated current I N /Max. peak current* (10 ms) A 30/520* 30/520* Rated V AC (50/60 Hz) 400 400 Switching range V AC (50/60 Hz) 48 480 48 480 Repetitive peak off-state V pk 1100 1100 Rated load AC7a (cos ϕ = 0.8) A 30 30 Rated load AC15 A 20 20 Single phase motor rating (230 V AC) kw 2.5 Nominal lamp rating: 230 V incandescent/halogen W 6000 4500 electronic ballast W 6000 4000 electromechanical ballast W 3000 1800 CFL W 4000 2500 230 V LE W 4000 2500 LV halogen or LE with electronic ballast W 4000 2500 LV halogen or LE with electromechanical ballast W 4000 2500 Minimum switching current @ 400 V ma 300 300 Typical OFF-state leakage current @ 400 V ma 1 1 Max ON-state drop @ 25 C and 30 A V 0.85 0.85 Power loss @ 30 A W 16 16 specification Nominal (U N ) V AC (50/60 Hz) 230 230 V C 24 24 Rated power @ U MAX VA (50 Hz)/W 0.4 7.5/0.9 0.4 7.5/0.9 Operating range V AC (50/60 Hz) 40 280 40 280 V C 4 32 4 32 Must drop-out V AC (50/60 Hz)/C /2 6/ /2 6/ Technical data Electrical life cycles 10 10 6 10 10 6 Operate/release time ms < 10/< 10 < 10/< 30 < 1/< 10 < 2/< 25 Insulation between input and output (1.2/50 µs) kv 6 6 Ambient temperature C 20 +80** 20 +80** Protection category IP 20 IP 20 Approvals (according to type) 4

77 Modular Solid State Relay 30 A 77 30 A modular SSR, 1 NO output 22.5 mm housing, heat-sink + plastic cover 60 to 440 V AC output (with back to back SCR) 6 kv (1.2/50 µs) insulation between and Output Zero-crossing and random switch-on versions available High switching speed High endurance Silent switching Spark and bounce-free switching Low control power 3-phase general purpose Contactor-style terminal arrangement (input and output terminals on adjacent sides) 35 mm rail (EN 60715) mount 77.31 Screw terminal 77.31.x.xxx.8070 Suggested applications: Lamp inrush current reduction (CFL - Compact Fluorescent energy-saving Lamps and similar) Heater control Solenoid, contactor driver 77.31.x.xxx.8071 Random switch-on Suggested applications: Fine controls involving shorter time (specially motor control) * See L77-5 diagram page 11 ** See L77-4 diagrams page 10 For outline drawing see page 14 Output configuration 1 NO (SPST-NO) 1 NO (SPST-NO) Rated current I N /Max. peak current* (10 ms) A 30/520* 30/520* Rated V AC (50/60 Hz) 400 400 Switching range V AC (50/60 Hz) 48 480 48 480 Repetitive peak off-state V pk 1100 1100 Rated load AC7a (cos ϕ = 0.8) A 30 30 Rated load AC15 A 20 20 Single phase motor rating (230 V AC) kw 2.5 Nominal lamp rating: 230 V incandescent/halogen W 6000 4500 electronic ballast W 6000 4000 electromechanical ballast W 3000 1800 CFL W 4000 2500 230 V LE W 4000 2500 LV halogen or LE with electronic ballast W 4000 2500 LV halogen or LE with electromechanical ballast W 4000 2500 Minimum switching current @ 400 V ma 300 300 Typical OFF-state leakage current @ 400 V ma 1 1 Max ON-state drop @ 25 C and 30 A V 0.85 0.85 Power loss @ 30 A W 16 16 specification Nominal (U N ) V AC (50/60 Hz) 230 230 V C 24 24 Rated power VA (50 Hz)/W 0.4 7.5/0.9 0.4 7.5/0.9 Operating range V AC (50/60 Hz) 40 280 40 280 V C 4 32 4 32 Must drop-out V AC (50/60 Hz)/C /2 6/ /2 6/ Technical data Electrical life cycles 10 10 6 10 10 6 Operate/release time ms < 10/< 10 < 10/< 30 < 1/< 10 < 2/< 25 Insulation between input and output (1.2/50 µs) kv 6 6 Ambient temperature C 20 +80** 20 +80** Protection category IP 20 IP 20 Approvals (according to type) 5

77 77 Hockey puck Solid State Relay 25-40 - 50 A 25, 40 And 50 A panel SSR, hockey puck style hockey puck housing with cover 24 to 240 V AC output Zero-crossing version High switching speed High endurance Silent switching Spark and bounce-free switching Low control power 3-phase general purpose Relay-style terminal arrangement (input and output terminals on opposite sides) Mounting on heatsink with screws 77.25.x.xxx.8250 77.45.x.xxx.8250 77.55.x.xxx.8250 Output: 25 A/230 V AC Suggested applications: heater control Output: 40 A/230 V AC Suggested applications: heater control Output: 50 A/230 V AC Suggested applications: heater control 77.x5 Screw terminal (plate clamp) * See L77-11 diagrams page 11 ** See L77-8, L77-9 and L77-10 diagrams page 11 For outline drawing see page 14 Output configuration 1 NO (SPST-NO) 1 NO (SPST-NO) 1 NO (SPST-NO) Rated current I N /Max. peak current* (10 ms) A 25/300* 40/500* 50/520* Rated V AC (50/60 Hz) 230 230 230 Switching range V AC (50/60 Hz) 21.6 280 21.6 280 21.6 280 Repetitive peak off-state V pk 600 600 600 Nominal lamp rating: 230 V incandescent/halogen W 2000 4000 6000 electronic ballast W 2000 4000 6000 electromechanical ballast W 1000 2000 3000 CFL W 800 3000 4000 230 V LE W 800 3000 4000 LV halogen or LE with electronic ballast W 800 3000 4000 LV halogen or LE with electromechanical ballast W 1000 3000 4000 Minimum switching current @ 250 V ma 120 250 250 Typical OFF-state leakage current @ 250 V ma 10 10 10 Max ON-state drop @ 25 C and I N V 1.6 1.6 1.6 Power loss @ I N W 40 64 80 specification Nominal (U N ) V AC (50/60 Hz) 230 230 230 V C 24 24 24 Rated power @ U MAX VA (50 Hz)/W /0.6 2.4/ /0.6 2.4/ /0.6 2.4/ Operating range V AC (50/60 Hz) 90 280 90 280 90 280 V C 3 32 3 32 3 32 Must drop-out V AC (50/60 Hz)/C /1 10/ /1 10/ /1 10/ Technical data Electrical life cycles 10 10 6 10 10 6 10 10 6 Operate/release time ms 10/10 40/80 10/10 40/80 10/10 40/80 Insulation between input and output (1.2/50 µs) kv 5.6 5.6 5.6 Ambient temperature C 30 +80** 30 +80** 30 +80** Protection category IP 20 IP 20 IP 20 Approvals (according to type) 6

77 Hockey puck Solid State Relay 25-40 - 50 A 77 25, 40 And 50 A panel SSR, hockey puck style 77.25.x.xxx.8650 77.45.x.xxx.8650 77.55.x.xxx.8650 hockey puck housing with cover 48 to 600 V AC output Zero-crossing version High switching speed High endurance Silent switching Spark and bounce-free switching Low control power 3-phase general purpose Relay-style terminal arrangement (input and output terminals on opposite sides) Mounting on heatsink with screws Output: 25 A/600 V AC Suggested applications: heater control Output: 40 A/600 V AC Suggested applications: heater control Output: 50 A/600 V AC Suggested applications: heater control 77.x5 Screw terminal (plate clamp) * See L77-11 diagrams page 11 ** See L77-8, L77-9 and L77-10 diagrams page 11 For outline drawing see page 14 Output configuration 1 NO (SPST-NO) 1 NO (SPST-NO) 1 NO (SPST-NO) Rated current I N /Max. peak current* (10 ms) A 25/300* 40/500* 50/520* Rated V AC (50/60 Hz) 600 600 600 Switching range V AC (50/60 Hz) 43.2 660 43.2 660 43.2 660 Repetitive peak off-state V pk 1200 1200 1200 Nominal lamp rating: 230 V incandescent/halogen W 2000 4000 6000 electronic ballast W 2000 4000 6000 electromechanical ballast W 1000 2000 3000 CFL W 800 3000 4000 230 V LE W 800 3000 4000 LV halogen or LE with electronic ballast W 800 3000 4000 LV halogen or LE with electromechanical ballast W 1000 3000 4000 Minimum switching current @ 250 V ma 120 250 250 Typical OFF-state leakage current @ 250 V ma 10 10 10 Max ON-state drop @ 25 C and I N V 1.6 1.6 1.6 Power loss @ I N W 40 64 80 specification Nominal (U N ) V AC (50/60 Hz) 230 230 230 V C 24 24 24 Rated power @ U MAX VA (50 Hz)/W /0.6 2.4/ /0.6 2.4/ /0.6 2.4/ Operating range V AC (50/60 Hz) 90 280 90 280 90 280 V C 4 32 4 32 4 32 Must drop-out V AC (50/60 Hz)/C /1 10/ /1 10/ /1 10/ Technical data Electrical life cycles 10 10 6 10 10 6 10 10 6 Operate/release time ms 10/10 40/80 10/10 40/80 10/10 40/80 Insulation between input and output (1.2/50 µs) kv 5.6 5.6 5.6 Ambient temperature C 30 +80** 30 +80** 30 +80** Protection category IP 20 IP 20 IP 20 Approvals (according to type) 7

77 77 Solid State Relay Ordering information Example: 77 series modular SSR, 1 output 30 A AC, input 230 V AC, relay style terminals arrangement, zero-crossing switch-on. A B C 7 7. 3 1. 8. 2 3 0. 8 0 5 0 Series Type/rated current 0 = 5/7/15 A output (77.01) 1 = 15 A output (77.11) 2 = 25 A output (77.25) 3 = 30 A output (77.31) 4 = 40 A output (77.45) 5 = 50 A output (77.55) No. of poles/mounting 1 = 1 pole, modular housing (plastic or heat sink/plastic), IN rail mounting 5 = 1 pole, heat-sink or directly panel mounting ( hockey puck ) version 0 = C/AC (50/60 Hz) 8 = AC (50/60 Hz) 9 = C Supply See input specification Codes/Module width 77.01.8.230.8050/17.5 mm 5 A 77.11.8.230.8250/22.5 mm 15 A 77.01.0.024.8050/17.5 mm 5 A 77.11.9.024.8250/22.5 mm 15 A 77.01.8.230.8051/17.5 mm 5 A 77.11.8.230.8251/22.5 mm 15 A 77.01.0.024.8051/17.5 mm 5 A 77.11.9.024.8251/22.5 mm 15 A 77.01.9.024.9125/17.5 mm 7 A 77.01.9.024.9024/17.5 mm 15 A Technical data ielectric strength 77.31.8.230.8050/22.5 mm 30 A 77.31.9.024.8050/22.5 mm 30 A 77.31.8.230.8051/22.5 mm 30 A 77.31.9.024.8051/22.5 mm 30 A 77.31.8.230.8070/22.5 mm 30 A 77.31.9.024.8070/22.5 mm 30 A 77.31.8.230.8071/22.5 mm 30 A 77.31.9.024.8071/22.5 mm 30 A : Switch-on mode 0 = Zero-crossing 1 = Random C: Terminals arrangement 5 = Relay style (input and output on opposite sides) 7 = Contactor style (input and output on adjacent sides) AB: Output circuit (rated ) 80 = 230 V AC (77.01), 400 V AC (77.31) 82 = 230 V AC (77.11, 77.x5) 86 = 600 V AC (77.x5) 9024 = 24 V C 9125 = 110 125 V C 77.25.8.230.8250/hockey puck 25 A 77.25.9.024.8250/hockey puck 25 A 77.25.8.230.8650/hockey puck 25 A 77.25.9.024.8650/hockey puck 25 A 77.45.8.230.8250/hockey puck 40 A 77.45.9.024.8250/hockey puck 40 A 77.45.8.230.8650/hockey puck 40 A 77.45.9.024.8650/hockey puck 40 A 77.55.8.230.8250/hockey puck 50 A 77.55.9.024.8250/hockey puck 50 A 77.55.8.230.8650/hockey puck 50 A 77.55.9.024.8650/hockey puck 50 A 77.01.8xxx 77.01.9xxx 77.11 77.31 72.25/45/55 Impulse (1.2/50 µs) ielectric strength Impulse (1.2/50 µs) ielectric strength Impulse (1.2/50 µs) ielectric strength Impulse (1.2/50 µs) ielectric strength Impulse (1.2/50 µs) Between input and output 2500 V AC 5 kv 3000 V AC 4 kv 3000 V AC 6 kv 3000 V AC 6 kv 4000 V AC 5.6 kv Between input and ground (heat-sink) 3000 V AC 6 kv 3000 V AC 6 kv 4000 V AC 5.6 kv Between output and ground (heat-sink) 2500 V AC 4 kv 4000 V AC 6 kv 4000 V AC 5.6 kv EMC specifications Reference standard 77.01.8xxx 77.01.9xxx 77.11 77.31 72.25/45/55 24 V AC/C 230 V AC 24 V C 24 V AC/C 230 V AC 24 V AC/C 230 V AC 24 V AC/C - 230 V AC Electrostatic discharge contact discharge EN 61000-4-2 4 kv 4 kv 4 kv 4 kv 4 kv air discharge EN 61000-4-2 8 kv 8 kv 8 kv 8 kv 8 kv Radiated electromagnetic field (80 1000 MHz) EN 61000-4-3 30 V/m 20 V/m 30 V/m Fast transients on supply terminals (burst 5/50 ns, 5 and 100 khz) EN 61000-4-4 1 kv 4 kv 2 kv 1 kv 3 kv 1 kv 3 kv 2 kv Voltage pulses on supply common mode EN 61000-4-5 2 kv 4 kv 1 kv 3 kv 3 kv 3 kv 3 kv 2 kv terminals (surge 1.2/50 µs) differential mode EN 61000-4-5 1 kv 4 kv 0.5 kv 0.5 kv 1.5 kv 0.5 kv 1.5 kv 1 kv Radio-frequency common mode (0.15 230 MHz) on supply terminals EN 61000-4-6 10 V 10 V 10 V Terminals 77.01.8xxx 77.01.9xxx 77.11 77.31 72.25/45/55 Output Screw torque Nm 0.8 0.8 0.8 0.8 0.5 1.2 Max. wire size solid stranded solid stranded solid stranded solid stranded solid and stranded mm 2 1 x 6 / 2 x 4 AWG 1 x 10 / 2 x 12 1 x 4 / 2 x 2.5 1 x 12 / 2 x 14 1 x 6 / 2 x 4 1 x 10 / 2 x 12 1 x 4 / 2 x 2.5 1 x 12 / 2 x 14 1 x 6 / 2 x 4 1 x 10 / 2 x 12 1 x 6 / 2 x 4 1 x 10 / 2 x 12 1 x 6 / 2 x 4 1 x 10 / 2 x 12 1 x 6 / 2 x 4 1 x 10 / 2 x 12 1 (with ferrule) 18 (with ferrule) Wire strip length mm 9 9 9 9 10 10 Other data Power lost to the environment without output current W 0.5 0.5 0.9 0.9 0.6 with rated current W 4.0 4.0 14 16 40/64/80 4 (with ferrule) 10 (with fork tip) 12 (with ferrule) 8 (with fork tip) 8

77 Solid State Relay 77 specification 77.01 Nominal code Operating range AC C Must drop-out current U N U min U max U min U max (AC/C) I N at U N V V V V V V ma 24 0.024 16 32 9.8 32 2.4 25 24 9.024 4 32 3.0 18 230 8.230 90 265 24 15 77.11 Nominal code Operating range AC C Must drop-out current Led indication LE LE (77.01.9.024.9xxx only) Supply OFF ON Short circuit* NO YES U N U min U max U min U max (AC/C) I N at U N V V V V V V ma 4 9.024 4 32 2 11 230 8.230 40 305 6 25 77.31 * To restore normal operation it is necessary to disconnect the power, resolve the short circuit and then restore power. Nominal code Operating range AC C Must drop-out current U N U min U max U min U max (AC/C) I N at U N V V V V V V ma 24 9.024 4 32 2 11 230 8.230 40 280 6 25 77.x5.x.xxx.8250 Nominal code Operating range AC C Must drop-out current U N U min U max U min U max (AC/C) I N at U N V V V V V V ma 24 9.024 3 32 1 22 230 8.230 90 280 10 20 77.x5.x.xxx.8650 Nominal code Operating range AC C Must drop-out current U N U min U max U min U max (AC/C) I N at U N V V V V V V ma 24 9.024 4 32 1 25 230 8.230 90 280 10 10 9

77 77 Solid State Relay L77-1 Output RMS current v ambient temperature 77.01.0.024.805x @ 32 V C L77-2 Output RMS current v ambient temperature 77.01.8.230.805x @ 265 V AC 5 A 5 A I - Modular SSR installed as a group (without gap) II - Modular SSR installed as a group (9 mm gap between each SSR) III - Modular SSR installed individually in free air (without a significant influence from nearby components) L77-12 Output C current v ambient temperature 77.01.9.024.9024 @ 32 V C L77-13 Output C current v ambient temperature 77.01.9.024.9125 @ 32 V C 15 A 8 6 7 A 4 2 I - Modular SSR installed as a group (without gap) II - Modular SSR installed individually in free air, or with a gap 9 mm, which implies a not significant influence from nearby components L77-6 Output RMS current v ambient temperature 77.11.x.xxx.82xx L77-4 Output RMS current v ambient temperature 77.31.x.xxx.80xx 15 A 30 A I - Modular SSR installed as a group (without gap) II - Modular SSR installed individually in free air, or with a gap 20 mm, which implies a not significant influence from nearby components I - Modular SSR installed as a group (without gap) II - Modular SSR installed as a group (20 mm gap between each SSR) III - Modular SSR installed individually in free air, or with a gap 40 mm, which implies a not significant influence from nearby components) 10

77 Solid State Relay 77 L77-10 Output RMS current v ambient temperature 77.25.x.xxx.8x50 L77-9 Output RMS current v ambient temperature 77.45.x.xxx.8x50 60 25 A 60 40 A 40 40 1 - Installation on 077.25 heat-sink (2 K/W) 2 - Installation individually in free-air L77-8 Output RMS current v ambient temperature 77.55.x.xxx.8x50 1 - Installation on 077.55 heat-sink (0.9 K/W) 2 - Installation individually in free-air 60 50 A 40 L77-3 Inrush peak current (AC) v inrush time 77.01.x.xxx.80xx 1 - Installation on 077.55 heat-sink (0.9 K/W) 2 - Installation individually in free-air L77-7 Inrush peak current (AC) v inrush time 77.11.x.xxx.82xx L77-5 Inrush peak current (AC) v inrush time 77.31.x.xxx.80xx L77-11 Inrush peak current (AC) v inrush time 77x5.x.xxx.8x50 3 - Cold conditions (ambient temperature = 23 C, no output current during the last 15 minutes) 4 - Hot conditions (ambient temperature = 50 C, rated output current) 11

77 77 Solid State Relay Max recommended switching frequency (Cycles/Hour, with 50% uty-cycle) Load 77.01.8xxx 77.01.9xxx 77.11 77.31 77.25 77.45 77.55 5 A 230 V (AC1) 5000 5 A 24 V C L/R = 20 ms 3600 1 A (AC15) 10000 0.5 A (AC15) 20000 15 A 305 V cos ϕ = 0.8 1800 15 A 305 V cos ϕ = 0.5 1200 30 A 480 V cos ϕ = 0.8 1800 30 A 480 V cos ϕ = 0.5 1200 25 A 230 V cos ϕ = 0.7 1800 40 A 230 V cos ϕ = 0.7 1800 50 A 230 V cos ϕ = 0.7 1800 Critical rising dv/dt without input control (gate open) @ T j = 125 C Other data 77.01.8xxx 77.01.9xxx 77.11 77.31 77.25 77.45 77.55 > 1000 V/µs > 1000 V/µs > 500 V/µs > 10 V/µs (with di/dt = 20 A/ms) > 1000 V/µs 300 V/µs (..8250) 500 V/µs (..8650) 500 V/µs (..8250) 1000 V/µs (..8650) 1000 V/µs (..8250) 1000 V/µs (..8650) Critical rising current di/dt > 50 A/µs > 50 A/µs > 50 A/µs > 150 A/µs @ T j = 125 C I 2 t for fusing @ t p = 10 ms 450 A 2 s 450 A 2 s 1000 A 2 s* 1350 A 2 s** 450 A 2 s 1250 A 2 s 1350 A 2 s Suggested fuse (depending on application) for short-circuit protection (Ultra-Fast acting types for semiconductors): * 20 A, 660 V AC, 10 x 38 mm, 200 ka, 360 A 2 s. ** 30 A, 660 V AC, 10 x 38 mm, 200 ka, 1000 A 2 s. 12

77 Solid State Relay 77 Wiring diagrams Single-phase connection (77.01...802x) Single-phase connection C (77.01...9x2x) Single-phase connection (77.11) Single-phase connection (77.31...5x) LOA Single-phase connection (77.31...7x) Single-phase connection (77.x5) Example of three-phase connection (with 3 x 77.01) Note: this connection can be used with all 77 series types. 13

77 77 Solid State Relay Outline drawings 77.01 Screw terminal 77.11/31 Screw terminal 77.01 C Screw terminal 77.x5 Screw terminal (plate clamp) Accessories Adaptor for panel mounting, plastic, 17.5 mm wide for 77.01 only 020.01 020.01 Separator for rail mounting, plastic, 9 mm wide 022.09 022.09 060.48 Sheet of marker tags (CEMBRE'S Thermal transfer printers) for all relays (48 tags), 6 x 12 mm 060.48 14

77 Solid State Relay 77 Accessories 077.25 Heat-sink, anodized aluminium, 2 K/W, 65 x 100 mm, for 77.25 only 077.25 - Both the SSR and 35 mm rail clip mount to the heat-sink using M4 screws (supplied with heat-sink) - Before assembling to the heat-sink, it is necessary to apply a thin and even layer of thermal conductive paste (not supplied) to the lower metal surface of the SSR 077.25 with 77.25 077.55 Heat-sink, anodized aluminium, 0.9 K/W, 111 x 100 mm, for 77.45 and 77.55 077.55 - Both the SSR and 35 mm rail clip mount to the heat-sink using M4 screws (supplied with heat-sink) - Before assembling to the heat-sink, it is necessary to apply a thin and even layer of thermal conductive paste (not supplied) to the lower metal surface of the SSR 077.55 with 77.45/55 15