Comparison of Various Reference Current Generation Techniques for Performance Analysis of Shunt Active Power Filter using MATLAB Simulation

Similar documents
Design and Simulation of Three Phase Shunt Active Power Filter Using SRF Theory

CHAPTER 6 UNIT VECTOR GENERATION FOR DETECTING VOLTAGE ANGLE

Power Quality Improvement using Shunt Passive Filter

IJSTE - International Journal of Science Technology & Engineering Volume 2 Issue 12 June 2016 ISSN (online): X

Implementation of SRF based Multilevel Shunt Active Filter for Harmonic Control

Shunt Active Power Filter based on SRF theory and Hysteresis Band Current Controller under different Load conditions

Literature Review for Shunt Active Power Filters

Harmonics Reduction using 4-Leg Shunt Active Power Filters

PI-VPI Based Current Control Strategy to Improve the Performance of Shunt Active Power Filter

Application of Fuzzy Logic Controller in Shunt Active Power Filter

Control Of Shunt Active Filter Based On Instantaneous Power Theory

5DESIGN PARAMETERS OF SHUNT ACTIVE FILTER FOR HARMONICS CURRENT MITIGATION

HYSTERESIS CONTROL FOR CURRENT HARMONICS SUPPRESSION USING SHUNT ACTIVE FILTER. Rajesh Kr. Ahuja

ABSTRACT I. INTRODUCTION

SCIENCE & TECHNOLOGY

Sinusoidal Current Control based Shunt Active Power Filter for Current Harmonics Reduction

Kanuru; Krishna (Dt); A.P, India. DOI: / Page. 1 G. Aruna Jyothi, 2 DR. P. V. R. L.

A Novel FPGA based PWM Active Power Filter for Harmonics Elimination in Power System

ANALYSIS OF SYNCHRONOUS-REFERENCE-FRAME-BASED CONTROL METHOD FOR UPQC UNDER UNBALANCED AND DISTORTED LOAD CONDITIONS Salava Nagaraju* 1

Improvement of Power Quality Using Hybrid Active Power Filter in Three- Phase Three- Wire System Applied to Induction Drive


Analysis of Reference Current Generation for Shunt Active Power Filter Using SRF Algorithm to Compensate Harmonic Current

Power Quality improvement of a three phase four wire system using UPQC

INVESTIGATION OF HARMONIC DETECTION TECHNIQUES FOR SHUNT ACTIVE POWER FILTER

HARMONIC ELIMINATION IN THREE PHASE SYSTEM BY MEANS OF A SHUNT ACTIVE FILTER

A Static Synchronous Compensator for Reactive Power Compensation under Distorted Mains Voltage Conditions

IJSRD - International Journal for Scientific Research & Development Vol. 2, Issue 06, 2014 ISSN (online):

A MATLAB-SIMULINK APPROACH TO SHUNT ACTIVE POWER FILTERS

Comparison of Shunt Active Power Filter Control Strategies for Harmonic Compensation in a Paper Industrial Factory

Enhancement of Power Quality Using Advanced Series Active Power Filters

Harmonic Reduction of Arc Furnaces Using D-Statcom

Mitigation of Voltage Sag/Swell Using UPQC

Power Quality improvement with Shunt Active Power filter using p-q control technique

INSTANTANEOUS POWER CONTROL OF D-STATCOM FOR ENHANCEMENT OF THE STEADY-STATE PERFORMANCE

Harmonics Elimination Using Shunt Active Filter

Assessment of Different Compensation Strategies in Hybrid Active Power Filters

DESIGN AND DEVELOPMENT OF ACTIVE POWER FILTER FOR HARMONIC MINIMIZATION USING SYNCHRONOUS REFERENCE FRAME (SRF)

Current Control Technique for Three Phase Shunt Active Power Filter by Using Adaptive Hysteresis Current Controller

Synchronous Reference Frame Theory For Nonlinear Loads using Mat-lab Simulink

CHAPTER 5 DESIGN OF DSTATCOM CONTROLLER FOR COMPENSATING UNBALANCES

INTERNATIONAL JOURNAL OF PURE AND APPLIED RESEARCH IN ENGINEERING AND TECHNOLOGY

DRIVE FRONT END HARMONIC COMPENSATOR BASED ON ACTIVE RECTIFIER WITH LCL FILTER

Power Quality Improvement of Non-Linear Load by Using Instantaneous P-Q Theory

Power Quality Improvement using Active shunt Power filter using PI Controller

STUDY OF UNIFIED POWER QUALITY CONDITIONER FOR POWER QUALITY IMPROVEMENT RAJIV KUMAR SINKU

PERFORMANCE ANALYSIS OF SVPWM AND FUZZY CONTROLLED HYBRID ACTIVE POWER FILTER

ISSN: Page 20. International Journal of Engineering Trends and Technology- Volume2Issue3-2011

Design of Shunt Active Power Filter by using An Advanced Current Control Strategy

Synchronous Reference Frame Control Algorithm Based Four -Leg Inverter DSTATCOM For Power Quality Improvement

CHAPTER 5 POWER QUALITY IMPROVEMENT BY USING POWER ACTIVE FILTERS

Three Phase PFC and Harmonic Mitigation Using Buck Boost Converter Topology

Power Quality Improvement Using Hybrid Power Filter Based On Dual Instantaneous Reactive Power Theory With Hysteresis Current Controller

Control of Shunt Active Power Filter for Improvement of Power Quality

ISSN: ISO 9001:2008 Certified International Journal of Engineering Science and Innovative Technology (IJESIT) Volume 2, Issue 3, May 2013

Simulation of Multi Converter Unified Power Quality Conditioner for Two Feeder Distribution System

A Versatile Control Scheme for UPQC for Power Quality Improvement using fuzzy controller

Cascaded Multilevel Inverter based Active Filter for Power Line Conditioners using Instantaneous mitigates

SIMULATION AND COMPARISON OF SPWM AND SVPWM CONTROL FOR TWO LEVEL UPQC

International Journal of Advance Research in Engineering, Science & Technology

Multi Level Inverter Based Active Power Filter for Harmonic Reduction

2020 P a g e. Figure.2: Line diagram of series active power filter.

Cascaded H-Bridge Five Level Inverter for Harmonics Mitigation and Reactive Power Control

ISSN Vol.03,Issue.07, August-2015, Pages:

Modeling and Simulation of SRF and P-Q based Control DSTATCOM

CHAPTER 4 PV-UPQC BASED HARMONICS REDUCTION IN POWER DISTRIBUTION SYSTEMS

Modified Three-Phase Four-Wire UPQC Topology with Reduced DC-Link Voltage Rating

Power Quality enhancement of a distribution line with DSTATCOM

A Simple Control Algorithm for Three-Phase Shunt Active Power Filter for Reactive Power and Current Harmonic Compensation

Power Control Scheme of D-Statcom

Improvement of Power Quality using Unified Power Quality Conditioner with Distributed Generation

Design of Shunt Active Filter to Improve Power Quality using Pq Theory

A Five Level DSTATCOM for Compensation of Reactive Power and Harmonics

NEUTRAL CURRENT COMPENSATION USING FOUR LEG SHUNT ACTIVE POWER FILTER

Performance Analysis of Shunt Active Power Filter Base On Active Reactive Power Theory

PSPWM Control Strategy and SRF Method of Cascaded H-Bridge MLI based DSTATCOM for Enhancement of Power Quality

Review on Shunt Active Power Filter for Three Phase Four Wire System

PERFORMANCE OF DISTRIBUTION STATIC COMPENSATOR IN LOW VOLTAGE DISTRIBUTION SYSTEM

Harmonics Reduction of 3 Phase Diode Bridge Rectifier by Implementing P-Q Theory with Active Filter

Simulation and Comparison of DVR and DSTATCOM Used For Voltage Sag Mitigation at Distribution Side

Mitigation of Line Current Harmonics Using Shunt Active Filter With Instantaneous Real and Reactive Power Theory

Comparative Analysis of Harmonics with and Without Shunt Active Power Filter

A Review on Improvement of Power Quality using D-STATCOM

A CONTROL TECHNIQUE FOR INSTANT MITIGATION OF VOLTAGE SAG/SWELL BY DYNAMIC VOLTAGE RESTORER

Active Harmonics Filtering of Distributed AC System

Voltage Quality Enhancement in an Isolated Power System through Series Compensator

International Journal of Advance Engineering and Research Development CONTROL OF REDUCED-RATING DYNAMIC VOLTAGE RESTORER

Control of grid connected inverter system for sinusoidal current injection with improved performance

KKR &KSR institute of Technology and sciences,vinjanampadu(v),vatticherukuru(m) Guntur(D) , Andhra Pradesh,India. I.

This SRF theory is experimentally implemented with dspace module CP1104 which has been used for real time interfacing.

Power Control and Quality Management in DG Grid Interfaced Systems

Active Power Filter with Fast PI Controller Using Matlab/simulink

Compensation of Harmonics Power by using Shunt Active Filter

Three Phase Active Shunt Power Filter with Simple Control in PSIM Simulation

Performance of DVR under various Fault conditions in Electrical Distribution System

Power Quality Improvement using Passive & Active Filters

ENHANCEMENT OF POWER QUALITY USING 9-LEVEL CASCADED H-BRIDGE BASED D-STATCOM WITH IRP THEORY SK. Meeravali* 1, Dr. K.

ICCCES Application of D-STATCOM for load compensation with non-stiff sources

Analysis of Grid Connected Single Phase Rooftop Photovoltaic System with MPPT

Comparison of Reference Current Extraction Methods for Shunt Active Power Filters

Multi-Pulse Voltage Source Converter Statcom For Voltage Flicker Mitigation

Transcription:

International Journal of Current Engineering and Technology E-ISSN 2277 4106, P-ISSN 2347 5161 2016 INPRESSCO, All Rights Reserved Available at http://inpressco.com/category/ijcet Research Article Comparison of Various Reference Current Generation Techniques for Performance Analysis of Shunt Active Power Filter using MATLAB Simulation Satish.U.Bhople * and Santhosh Kumar Rayarao Electrical Engineering Department, Matsyodari Shikshan Santh s, College of Engineering and Technology, Jalna, India Accepted 16 April 2016, Available online 19 April 2016, Vol.6, No.2 (April 2016) Abstract This paper deals with mitigation of harmonics using shunt active power filter. Due to use of nonlinear load harmonics generated in the power system. To solve this problem various reference current generation techniques have been used. In this paper Synchronous Reference Frame (SRF) and Instantaneous Reactive Power Theory (IRP) Theory are discussed. This harmonics are introduced because of nonlinear load in system that causes severe damage to our system. This harmonics are mitigate using above two techniques. The performance and result is simulated on MATLAB/ Simulink platform. Keywords: SRF, IRP, SAPF, Non Linear Load, Power Quality, PCC, THD, TDD. 1. Introduction 1 Day by day growing number of power electronic based equipment introduced an impact on the power quality. Both domestic and industrial load causes harmonics in the system. The nonlinear load may be power semiconductor device, fans, Variable speed drives, arc furnace, CFL, personal computer, fri8dge, PLC, printer, large decaying DC component, etc. generate harmonics and that effect on power quality. Disturbance occurs in voltage, current, and frequency deviation that results in failure of equipments is called as power quality. Power quality is also defined as quality of both current and voltage. Due to effect on power quality huge financial loss happen. Power quality has some problems like voltage swell, voltage sag, very long interruption, very short interruption, harmonic distortion, voltage fluctuation, noise, voltage imbalance, etc. from above mentioned power quality problems harmonics is one of the important problems that effect on power system performance. When harmonics present in system then system shows symptoms like frequent blackout, communication interference, lamp flickering, sensitive equipment frequently dropout, etc. Due to presence of harmonics in system problems occurred like tripping of circuit breaker, parallel and series resonance will occurred, blowing of fuse, fault in energy meter, damage to sensitive electronic equipment, loss of motor windings, increase of rms and peak value, excessive neutral *Corresponding author: Satish.U.Bhople current, electromagnetic interference with communication system, overheating of all cable and equipment. Due to all this reason power quality is main research topic in power system. Mitigation of harmonics is very important to increase power quality. To mitigate harmonics in system filter are used. There are two types of filter used to mitigate harmonics in system like passive filter and active filter. Passive filter is oldest type electronic filter. Passive filter is quite simple, cost effective and reliable. Passive filter consist of resistor, inductor and capacitor and this filter does not depend on any type of external power supply. Passive filter have some drawback like it may cause gives overcompensation of reactive power, it may cause series and load resonance in system, it is heavy and bulky, it gets overloaded when load harmonics increases. Due to this drawback of passive filter harmonics get amplified on the source side and causes serious distortion in voltage. To overcome problems in passive filter power engineers developed new filter called as active filter. Active filter is able to compensate current harmonics. The performance of shunt active power filter depends on control algorithm used for generation of reference current. 2. Shunt Active Power Filter The basic working principle of shunt active power filter is that it generates a reference current that has equal and opposite in polarity to harmonic current drawn by the load and inject to the point of common coupling, thereby forcing the source current to be pure sinusoidal. 606 International Journal of Current Engineering and Technology, Vol.6, No.2 (April 2016)

Figure 1 Basic diagram for Shunt active power filter Harmonic and reactive current are thus cancelled at source end and the result is undistorted sinusoidal balance current such equipment shown in Figure called as shunt active power filter. Main purpose of shunt active power filter is to generate reference current. In this paper I used two techniques called Synchronous reference frame (SRF) and Instantaneous reactive power (IRP) for reference current generation discussed in details. The result is obtained in MATLAB/Simulink. The measure of the performance of algorithm is source current Total harmonic distortion (THD) and Total demand content (TDC) and magnitude of neutral current. The rest of paper organized as follow. In section III control algorithm is presented. In section IV Performance indices presented. In section V Simulation and result are described. In section VI comparison of SRF and IRP are done and finally in section VII conclusion are drawn. 3. Control Algorithm A) Synchronous Reference Frame Theory application has only been focused in three-phase APFs. One of important characteristics of this algorithm is to obtain reference currents starting directly from the nonlinear load currents, regardless of grid voltage. This based on transformation of current in synchronously rotating d-q frame. Fig 2 shows the basic block diagram of this. From block diagram it is clear that sensed inputs v a,v b,and v c and ila, ilb and ilc are fed to controller. Voltage singal are processed by phase-locked loop to generate sine and cosine signal. Current signal transformed to d-q frame and these signals are filtered and transformed back to abc frame then which fed to hysteresis based pulse width modulated signal generator to generate final switching signal. During implementation of this method we have taken care of delays, if we cannot do this is may cause the controller to be unstable hence the whole system becoming unstable. However, where control is concerned, the integral component of the PI controller can lead to integrator windup resulting into instability of the controller and hence poor performance of the shunt active power filter. In synchronous reference frame, Clark s and Park s transformation is used to change the harmonic frequency, and to eliminate this frequency LPF is used. To generate the reference currents reverse Park s and Clark s transformation is used. PLL block is used to generate the angle θ which is used in reference current generation. This transformation done in two step. First step The transformation from a-b-c frame to α-β-0 frame which is also known α-β transformation or Clarke transformation and is given by [ ]= [ ] [ ] (1) Second Step The transformation from α-β-0 frame to d q 0 frame which is also known as park s transformation or dq transformation and is given by [ ]= [ ] [ ] (2) Figure 2 Block diagram of the reference current generation using SRF This technique is also known as Id Iq method or d-q. This technique is widely applied in three phase system and it is considered as one of the simple and most preferred techniques. The SRF can achieve fast and accurate extraction of the harmonic content and of the reactive component of a distorted current, but the Output of this equation contains AC component or Oscillating component value as well as DC component or average value. To eliminate AC component which contain harmonic component low pass filter is used. So that DC component which is output of above equation is harmonic free. [ ]= [ ] (3) The algorithm is further carried a step forward, where the current reference signal in 0-d-q rotating frame is 607 International Journal of Current Engineering and Technology, Vol.6, No.2 (April 2016)

converted back into a -b-c stationery frame, the reference signal for the Pulse Width Modulation (PWM). The reverse transformation from 0 -d-q rotating frame to a-b-c stationery frame is achieved with two steps 0-d-q to 0-α-β and again 0-α-β to a-b-c. Third Step This transformation is called as Reverse Park s transformation, in which 0-d-q to 0-α-β transformation is done and given by [ ]= [ ] [ ] (4) Fourth Step This transformation is called as Reverse Clark s transformation, in which 0-α-β to a-b-c transformation is done and given by [ ]= [ ] [ ] (5) These reference currents are used for the generation of the PWM pulses by using the HCC i.e. hysteresis current controller. In the HCC we compare reference current with the load current and filter current to get the pulses for the inverter. Table:1 Parameters used for simulation For SRF Theory Name Parameter Value Voltage Vsabc 400Vp-prms Frequency F 50Hz Source Source Resistance Rsabc 0.0287Ω Source Inductance LSabc 0.00001mH 3-phase AC line inductance LLabc 2.5mH Load 3-phase DC inductance Ldc 5mH (Diode Bridge Rectifier) 3-phase DC Resistance Rdc 100Ω DC-link Voltage VDC 700V Capacitor CDC 2600Μf SAPF Ac Line coupling Inductance LCabc 30mH Settling Time 0.3sec B) Instantaneous Reactive Power Theory Figure 3 Block diagram of the reference current geneartion using IRP Akagi in 1984 have presented new Instantaneous reactive power comprising switching devices without energy storage elements. This techniques based on αβ0 transformation which transforms three phase voltage and current into two phase α-β stationary reference frame. Basic block diagram of this is shown in figure 2.From block diagram it is clear that sensed input v a,v b and,v c and ila,ilb, and ilc are fed to the controller and these quantities are processed to generate reference current commands, which are fed to hysteresis based pulse width modulation signal generator as shown in figure 3 to generate final switching signal. From transformed quantities instantaneous real and reactive power of load is calculated which consist of DC component and oscillating component. Oscillating component extracted using low pass filter and taking inverse α-β transformation compensating command signal in terms of either current or voltage are derived. To deal with instantaneous voltage and current in three phase circuit it is adequate to express their quantities as space vector. In a-b-c co-ordinate a,b and c axes are fixed on same plane apart from each other by 120 0.In this method three phase voltage and current are transformed into 0-α-β by using Clark s transformation as follow [ ]= [ [ ]= [ ] [ ] (6) ] [ ] (7) Where α and β are orthogonal co-ordinate shown in Figure Later on active and reactive power for three phase system can be obtained. For three phase circuit conventional instantaneous power can be given by 608 International Journal of Current Engineering and Technology, Vol.6, No.2 (April 2016)

Table 2: Parameters used for simulation For IRP Theory Name Parameter Value Voltage Vsabc 400Vp-prms Frequency F 50Hz Source Source Resistance Rsabc 0.0287Ω Source Inductance LSabc 0.00001mH 3-phase AC line inductance LLabc 2.5mH Load 3-phase DC inductance Ldc 5mH (Diode Bridge Rectifier) 3-phase DC Resistance Rdc 25Ω Voltage VDC 700V DC-link Capacitor CDC 2000μF SAPF Ac Line coupling Inductance LCabc 8mH Settling Time 0.3sec p = (vα*iα) + (vβ*iβ) (8) q= (vα*iβ) (vβ*iα) (9) Matrix form of above equation can be given by [ ]=[ ] [ ] (10) This active and reactive power can be expressed in two parts i.e. AC and DC as given by following equation 4. Simulation Results The shunt active power filter is analyzed by using three phase source and the three phase non-linear load. In MATLAB simulation the source voltage is 400Vatfrequency 50Hz. The load used is three phase rectifier with RL. Following figures shows the MATLAB simulation diagram. p = + (11) q = + (12) In order to get DC part of active and reactive power p and q signal need to be passed through low pass filter. Low pass filter will filter out high frequency component and will give expected signal i.e. Fundamental part. As per this active power is given by DC part of α-β reference current and it can be given by following equation. From this real and reactive power the reference current for 0-α-β is given by Figure 4 MATLAB simulation block diagram of SRF [ ] = [ ] [ ] (13) Further three phase reference current can be obtained by transforming these two phase reference current to three phase using following equation and that is known as reverse Clark s transformation. [ ] = [ ] [ ] (14) Figure 5 MATLAB simulation block diagram of IRP where i 0 is the zero sequence component, which is zero in three- phase three-wire system. These current are compared with source current and obtained error is processed through PI to generate reference current for APF. IRP has advantage that obtained fundamental components of active and reactive power are DC quantities. As these signals are DC quantities, αβ reference frame is unaffected by any phase shift introduced by low pass filter. Figure 6 Source current before compensation in SRF 609 International Journal of Current Engineering and Technology, Vol.6, No.2 (April 2016)

Before compensation the total harmonic distortion in the source current is 28.17 IN SRF and 25.03 % in IRP. But after compensation, the total harmonic distortion in SRF is 6.00% and in IRP is 3.42%. These results are shown in following figures. Figure7 Source current before compensation in IRP Figure 8 Source current after compensation in SRF Figure12 % THD in source current before compensation in SRF Figure 9 Source current after compensation in IRP Figure 13 % THD in source current before compensation in IRP Figure10 Filter current injected at PCC by inverter in SRF Figure11 Filter current injected at PCC by inverter in IRP Figure 14 % THD in source current after compensation in SRF 610 International Journal of Current Engineering and Technology, Vol.6, No.2 (April 2016)

Acknowledgement Figure 15 % THD in source current after compensation in IRP 5. Comparison of SRF and IRP methods Sr.No. Method Before Compensation in % After Compensation in % 1 SRF 28.17 6.00 2 IRP 25.03 3.42 Thus from above comparison it is clear that with help of SRF method more harmonics are eliminated. Conclusion In this paper two different reference current generation techniques are studied for performance analysis of shunt active power filter. The harmonic content in the power system are also studied before and after shunt active power filter is connected. The results are analyzed considering the %THD. In IRP the % THD is reduced from 25.03 % to 3.42 %. The advantage of this is that in this case there is no requirement of filter for elimination of ac component and this can be used in steady state and transient state. Similarly, in SRF the harmonics are reduced from 28.17 % to 6.00 %. Therefore from above analysis we can see that the instantaneous SRF is most efficient and can reduce more harmonic distortion from the system. I express my sincere thanks to my guide Mr.Santhosh Kumar Rayarao Asst. Prof. Department of Electrical Engineering, MSS S College of Engineering and Technology, Jalna for his continuous encouragement, support, ideas, most constructive suggestions, valuable advice and confidence in me. I express my gratitude and sincere thanks to Mr. Kompelli Santhosh, Head, Department of Electrical Engineering, MSS s College of Engineering and Technology, Jalna for his constant motivation and support. I sincerely thank Dr. C.M.Sedani, Principal, MSS S College of Engineering and Technology, Jalna for their continuous encouragement and active interest in my progress that they gave throughout the work References R.Dugan, M.Mc Granaghan and H.Beaty (1996), Electrical Power System Quality,New York,McGraw-Hill. Naresh K. Kummari, Asheesh K. Singh, Member, IEEE, and Pradeep Kumar, Member, IEEE (2012), Comparative Evaluation of DSTATCOM Control Algorithms for Load Compensation. Maurício Aredes, Member, IEEE, Hirofumi Akagi, Fellow, IEEE, Edson HirokazuWatanabe, Senior Member, IEEE, Eumir Vergara Salgado, Student Member, IEEE, and Lucas Frizera Encarnação (April 2009), Comparisons Between the p-q and p-q-r Theories in Three-Phase Four-Wire Systems, Vol. 24, No. 4. Hirofumi, Akagi, fellow, IEEE (Nov/Dec 1996), New trend in active power filter for power conditioning, IEEE,Transaction on industry application,vol 32,No.6 Hyosung Kim,Frede Blaabjerg,Birgitte Bak-Jensen Jlaeho Choi (2001),Instantaneous Power Compensation in Three-phase Systems by IJsing p-q-r Theory,IEEE 611 International Journal of Current Engineering and Technology, Vol.6, No.2 (April 2016)