Active Harmonic Filter (AF3)

Similar documents
CHAPTER 5 POWER QUALITY IMPROVEMENT BY USING POWER ACTIVE FILTERS

Harmonic Filters and Reactors

ARE HARMONICS STILL A PROBLEM IN DATA CENTERS? by Mohammad Al Rawashdeh, Lead Consultant, Data Center Engineering Services

Thyristorised Automatic Power Factor

Harmonic Solutions in Electrical Systems. Raed Odeh Application Specialist - Power Quality & Electrical Distribution

PQ01. Harmonic Solutions for VFD s. Review of Power Control Harmonics, Power Factor, Distortion & Displacement

CASE STUDY. Implementation of Active Harmonic Filters at Ford Motor Company SA Silverton Plant

22.0 Harmonics in Industrial Power Systems

Effective Harmonic Mitigation with Active Filters

Understanding Harmonics

Technical Paper. Harmonic Distortion in Data Centers

SHUNT ACTIVE POWER FILTER

Harmonics and Their Impact on Power Quality. Wayne Walcott Application Engineering Manager June, 2017

HARMONICS THE BASICS H A R M O N I C M I T I G A T I O N A N D D I S P L A C E M E N T P O W E R F A C T O R C O R R E C T I O N

Guide to Harmonics. Reactive Power and Harmonic Compensation POWER QUALITY. The Basics of Harmonics

Harmonics, its Mitigation & Result of Case study of Spinning Mill

7/15/2002 PP.AFD.08 1 of 28

CHAPTER 4 HARMONICS AND POWER FACTOR

APQline Active Harmonic Filters. N52 W13670 NORTHPARK DR. MENOMONEE FALLS, WI P. (262) F. (262)

A PQ Case Study CS 36 HOSP 14. A Case Study OF Harmonics Mitigation in a Hospital and its Benefits

P2 Power Solutions Pvt. Ltd. P2 Power Magnetics. Quality Power within your Reach. An ISO 9001:2008 Company

Emicon Engineering Consultants L.L.C.

Low Pass Harmonic Filters

Harmonic Mitigation for Variable Frequency Drives. HWEA Conference February 15, Kelvin J. Hurdle Rockwell Bus. Dev. Mgr.

Welcome to the rd. Annual Northern Ohio. 3 rd Energy Management Conference September 30, 2008

Fluke 40/41 Power Harmonics Analysers

Power Quality Solutions

NJWA - Harmonics and Drives Proper System Design

McGill Power Sales & Engineering, INC.

ENERGY SAVING WITH OPTIMIZATION OF VOLTAGE AND CURRENT QUALITY

PQ for Industrial Benchmarking with various methods to improve. Tushar Mogre.

HARMONICS CAUSES AND EFFECTS

Understanding Input Harmonics and Techniques to Mitigate Them

How Harmonics have led to 6 Power Factor Misconceptions

3/29/2012 MAIN TOPICS DISCUSSED ELECTRICAL SYSTEMS AND ELECTRIC ENERGY MANAGEMENT SECTION K ELECTRIC RATES POWER COMPUTATION FORMULAS.

PRUDENT PRACTICES TO IMPROVE POWER FACTOR AND REDUCE POWER LOSS.

Power Factor. Power Factor Correction.

Analysis of Harmonic Distortion in Non-linear Loads

PF Correction Techniques in highly varying load

Reduction Of Harmonics By Using Active Harmonic Filter

PQ Synergy Effective Harmonic Filter Designs for Commercial Implementation. Team Power Matrix, Sony Jacob.

Active Harmonic Filter (AHF)

Generator Advanced Concepts

DSP-BASED CURRENT SHARING OF AVERAGE CURRENT CONTROLLED TWO-CELL INTERLEAVED BOOST POWER FACTOR CORRECTION CONVERTER

P2 Power Solutions Pvt. Ltd.

World Academy of Science, Engineering and Technology International Journal of Electrical and Computer Engineering Vol:7, No:6, 2013

Drives 101 Lesson 5. Power Input Terminology for a VFD

E S C R I P T I V E B U L L E T I N .,.,.,. Bulletin DB-106. October, Square D Company Power System Studies ---1 I SQU ARED COMPANY --

International Journal of Advance Engineering and Research Development ANALYSIS AND MITIGATION OF HARMONICS IN MEDICAL FIELD

HARMONIC MITIGATIONCASE STUDY

Active Harmonic Filters IPC150 AHF Series

Liebert AF2 Next Generation Active Harmonic Filter. Power Protection for Business-Critical Continuity TM

Reducing Total Harmonic Distortion with Variable Frequency Drives

Electromagnetic Harmonic Filters Technical Guide

Tuningintobetter power quality

Economical Solutions to Meet Harmonic Distortion Limits[4]

Three Phase PFC and Harmonic Mitigation Using Buck Boost Converter Topology

Chapter M Harmonic management

Harmonic Mitigating Transformer - Technical Guide

Technical News. Part 2: Harmonics. The link between harmonics and power factor. Industrial Electrical and Automation Products, Systems and Solutions

An easy-to-use Precision Power Analyser. The touch of a button gives direct readout of true power and a host of other useful measurements.

Voltage and Current Waveforms Enhancement using Harmonic Filters

Harmonic Power. A VFDs.com Whitepaper Written by Ernesto Jimenez

Understanding Power Quality

Power factor correction and harmonic filtering. Harmonic filters and EMI

Power Factor improved by Variable Speed AC Drives By Mauri Peltola, ABB Oy, Drives

ISSN: X Impact factor: (Volume 3, Issue 6) Available online at Modeling and Analysis of Transformer

Power Quality Monitoring:

Harmonic distortion from induction furnace loads in a steel production plant

ASSOCIATION OF ENERGY ENGINEERS NORTHERN OHIO CHAPTER APRIL 21, 2005

R. W. Erickson. Department of Electrical, Computer, and Energy Engineering University of Colorado, Boulder

POWER QUALITY A N D Y O U R B U S I N E S S THE CENTRE FOR ENERGY ADVANCEMENT THROUGH TECHNOLOGICAL I NNOVATION

ENERGY SAVINGS THROUGH POWER CONDITIONING WITH THE PowerGUARD SYSTEM

ECET Modern Power

16th NATIONAL POWER SYSTEMS CONFERENCE, 15th-17th DECEMBER,

There s Gold in Those Waveforms Richard P. Bingham, Dranetz-BMI

Power IT LV Active Filters PQFA - PQFL - PQFT

The Occurrence of Faults in Permanent Magnet Synchronous Motor Drives and its Effects on the Power Supply Quality

Impact Assessment Generator Form

ABB DRIVES Technical guide No. 6 Guide to harmonics with AC drives

Power Quality Analysis in Power System with Non Linear Load

Case Study 38 Reduction in Break Down and Specific Energy Consumption by Reducing Harmonics at Usha Martin Wire Rope Plant.

INVESTIGATION INTO THE POWER QUALITY AND RELIABILITY OF SUPPLY IN THE INDUSTRIAL NETWORKS WITH DISTRIBUTED GENERATION

Peteris Spels, ABB Inc., WMEA, November 18, 2011 HARMONICS. ABB Group December 14, 2011 Slide 1

Power Quality Analysis: A Study on Off-Line UPS Based System

Active Harmonic Filter

Harmonic control devices

ABB n.v. Power Quality Products, October 2014

IGBT Induction Heater Profiles

Est Static Frequency Converter. SFX 10kVA - 10MVA

Introduction to Rectifiers and their Performance Parameters

Power Analysis Summary

VFDs and Harmonics in HVAC Applications

A. Harmonics. non-linear loads. are. required)

Harmonic Filters for Power Conversion Equipment (Drives, rectifiers, etc) Effects of Harmonics IEEE Solutions

MIRUS International Inc.

Power Quality Monitoring and Power Metering Tutorial

Harmonic Analysis and Its Mitigation Using Different Passive Filters

Simulation of Three Phase Cascaded H Bridge Inverter for Power Conditioning Using Solar Photovoltaic System

Use only for doing work with or for BC Hydro. Complete Legal Acknowledgement is at

Transcription:

Active Harmonic Filter (AF3)

Active Harmonic Filter Improving the Efficiency and Life of System by use of Digital Active Power Conditioner

HARMONICS 50 Hz, fundamental 100 Hz, 2nd Harmonic 150 Hz, 3rd Harmonic

Sources of Harmonics Main sources of voltage and current harmonics are Computers & Electronic ballasts Rectifiers - AC & DC drives - UPS systems - Arc furnaces & SCR temperature controllers - Battery chargers & Rectifiers 4

Computer & Electronic Ballast (IT Loads) Discontinuous current. Presence of large amount of third and higher order Harmonics THDi = 80 to 140% 5

Rectifiers / Chargers Six-pulse Rectifier Twelve Pulse Rectifier Variable Speed Drives UPS Battery Chargers & Rectifiers THDi = 30 to 60% 6

Common Problem caused by Harmonic Problems caused by harmonic currents Overloading of neutrals Overheating of transformers Nuisance tripping of circuit breakers Over stressing of power factor correction capacitors Skin effect Problems caused by harmonic voltages Voltage distortion Zero-crossing noise 7

Over Loading of Neutral Conductor In a three-phase system, With Linear load the fundamental currents cancel out. With Non-Linear load the harmonic currents do not cancel. In fact, being an odd multiple of three times the fundamental, the triplen harmonics, add in the neutral. The Neutral current goes upto 2.5 to 3 times than the phase current for Non-linear loads. Neutral conductors gets heated. 8

Cable De-rating If we refer the standards, the cable de-rating is about 60% since due to harmonic phenomena. 9

Overheating of Transformers Transformers are affected in two ways by harmonics. Eddy current losses - 10 % normal value at full load. Results in high temperature rise. Increases the square of the harmonic number. With Non-Linear Load Transformer losses would be twice as high as for an equivalent linear load. Harmonics in Neutral increases THREE times. 10

Nuisance Tripping of Circuit Breakers Nuisance tripping can occur with presence of harmonics for ; The RCCB may not sum the higher frequency components correctly and therefore trips erroneously. Noise suppression capacitor, to suppress noise line, generated due to harmonics, can be sufficient to trip the RCCB. Nuisance tripping of RCCB is usually cause due to non-consideration of non-sinusoidal nature of current, during calculations. RCCB : Residual Current Circuit Breaker 11

Over Stressing of Power Factor Correction Capacitors The impedance of the PFC capacitor reduces as frequency rises, while the source impedance is generally inductive and increases with frequency. The capacitor and the stray inductance of the supply system can resonate at or near one of the harmonic frequencies. When this happens very large voltages and currents can be generated, often leading to the catastrophic failure of the capacitor bank system. 12

Skin Effect Alternating current tends to flow on the outer surface of a conductor at higher frequencies. It has very little effect at Power supply frequencies. But above 350 Hz skin effect will become significant causing additional loss and heating. Where harmonic currents are present, designers should take skin effect into account and de-rate cables accordingly. 13

Problems caused by Harmonic voltages Because the supply has source impedance, harmonic load currents give rise to harmonic voltage distortion on the voltage waveform Voltage distortion by non linear load 14

Problems caused by Harmonic voltages The non-linear load causes a voltage drop in the cable impedance. The resultant distorted voltage waveform is applied to all other loads connected to the same circuit, causing harmonic currents to flow in them - even if they are linear loads. 15

Harmonic Effects and Causes Overheating and failure of electric motors Overloading, overheating and failure of power factor correction capacitors, distribution transformers and neutral conductors. Reduction of efficiency of power generation, transmission and utilization Aging of the installation of electrical plant components and shortening of their useful life Malfunctioning and failure of electronic equipment

Contd... Harmonic Effects and Causes High measurement errors in metering equipment Spurious operation of fuses, circuit-breakers and other protective equipment Voltage glitches in computers systems resulting in lost data Electromagnetic interference with TV, radio, communication & telephone Damage and disruption to standby generators and associated AVR control equipment

Components Damaged due to Harmonics

Conclusion : Harmonic currents cause problems both on the supply and within the distribution system. The effects and the solutions are very different and need to be addressed separately. The measures that are appropriate to control the effects of harmonics within the installation may not necessarily reduce the distortion caused on the supply and vice versa. 19

EFFECT OF HARMONICS ON POWER FACTOR

For Non linear load Distortion Factor pfdisp = is a displacement power factor pfdist = is a distortion power factor or Harmonic Power factor 21

M a x im u m T r u e P o w e r F a c t o r v s T H D i M a x T ru e P F 1 0.9 0.8 0.7 0.6 0.5 20 40 60 80 100 120 140 T H D o f C u rre n t 22

ACTIVE HARMONIC FILTER (AHF)

Working Principle of AHF Input source current is sensed by DSP Fundamental only idistortion Supply Load DSP calculates harmonic components of the input current and reactive input power. Counter harmonics and reactive power control is generated by DSP and fed to power circuit icompensation Active Filter With this harmonics and reactive power is compensated by Active filter 24

Features of Active Harmonic Filter Closed loop active filter with source current sensing High attenuation up to 96% of individual harmonics Programmable selective harmonic elimination PF compensation, leading as well as lagging Selection between PF and harmonic compensation IGBT based inverter design Multiple paralleling Shunt Operation, Self current limiting. 25

Performance Results of AHF Test results taken for 6 pulse UPS with 100A filter Without Active Filter Input Current 164 A Voltage 217 V VTHD 4.8 % ITHD 27.4 % PF 0.87 Power KVA 106.5 Power kw 92.7 26

With filter only Harmonic compensation Input Current 146A Filter Current 48A VTHD 3.7 % Voltage PF 0.92 ITHD 4.0 % Power KVA 96.79 Power kw 90 221 V 27

Input Current 135 A Filter current VTHD 2.2 % Voltage 223V PF 1.00 ITHD 3.9 % Power KVA 90.30 16.20 Power kw 90.30 2.4 With filter Harmonic and PF correction 95 A 28

CASE STUDY 1 Industrial Application CASE STUDY 2 IT Application

CASE STUDY - I Jindal Steel & Power Ltd. DRI-II, Raigarh (MP) 4 Nos.150 Amp AHF at KILN 8 DY 1

Existing Set - up at DRI - II Plant The major loads in DRI : DC Thyristor Drives UPSs AC Drives

The existing power Distribution in DRI - No. of KILNs - 4 Nos. - No. of Power Supply Transformer 4 Nos. - Transformer rating 1.7MVA - Load Distribution- One Transformer for per KILN. - Spare Transformer 1 No. - Transformer efficiency (@ PF-1, assumed) 98%

Schematic of Power Distribution at Site

Initial Recorded Parameters Phase R Y B Load Current (A) 640 A 680 A 615 A Current T.H.D. % 51 % 49 % 47 % Power Factor 0.56

Comments on Observations High Input current Harmonic Distortion around 51% Input Current waveform distorted Low power factor High Input currents

Objectives of Load Study To reduce input current harmonic to less than 10%. To improve power factor from 0.52 to better than 0.9 To observe the effect of the solution on the existing problems of - Cable heating - Spurious tripping of breakers etc. To record power saving

Problems observed by user (due to Harmonics) - Cable Over heating - Transformer over heating - Frequent failure of electronic PCB s - Frequent tripping of breakers process for unknown reasons resulting into interruption in

Tested at JSPL DRI-II 4 Nos.150 Amp AHF At KILN 8

Performance Results of AHF Sr. No. 1 2 3 4 Test Condition With One AHF Connected With Two AHF Connected With Three AHF Connected With Four AHF Connected Phase R Y B Load Current (Amp) 558 A 612 A 560 A Current T.H.D. % 27.60% 29.40% 28.50% Power Factor 0.63 Load Current (Amp) 540 A 590 A 540 A Current T.H.D. % 7% 10% 10% Power Factor 0.72 Load Current (Amp) 480 A 487 A 482 A Current T.H.D. % 8% 7.90% 6.90% Power Factor 0.8 Load Current (Amp) 340 A 350A 344 A Current T.H.D. % 7.80% 8% 6% Power Factor 0.92

Summary of AHF Test Results Input currents reduced from 680 A to average 350 A per phase. Input PF is improved from 0.57 to 0.92 Input current distortion reduced from 57% to 7-8% Input KVA reduced from 489 to 252 KVA KVA Released - 237KVA (direct reduction) Existing transformer of 1.7 MVA was supporting 0.97 MW load earlier Now, it can support 1.56 MW load, if Harmonics & PF are controlled.

MVAH Measurement after connecting 4 Nos. AHF Condition Date Time MVAH Recorded Without AHF 2 Feb 08 13 hrs 3871.4 Without AHF 4 Feb '08 13 hrs 3888.3 With AHF - 4 Nos. 4 Feb '08 13 hrs 3888.3 With AHF - 4 Nos. 6 Feb '08 13 hrs 3901.3 MVAH Consumption in 48 Hours 16.9 13

MVAH Savings achieved MVAH saved in 48 hrs when AHF was used 16.9-13 = 3.9 MVAH MVAH Saving = 1.95 MVAH / per Day = 58.5 MVAH / per Month = 711.75 MVAH / per Year

MVAH Savings per KILN Load MVAH per Day No of Days Total MVAH Rate Rs. / MVAH Total Savings in Rs. 1.95 1 1.95 6,000 11,700 1.95 7 13.65 6,000 81,900 1.95 30 58.5 6,000 3,51,000 1.95 365 711.75 6,000 42,70,500 Savings at ONE KILN = Rs. 42,70,500 Savings at FOUR KILN = Rs.1,70,82,000

Distribution Transformer Loss Calculation (without AHF) Transformer Rating 1.7 MVA = 17,00 KVA Load connected without AHF = 650 A / phase = 467 KVA Power in KVA Percentage of Load connect = 28 % Efficiency of Transformer at full Load (given) = 98% Copper Loss = 19.5 KW Iron Loss = 2.2 KW Loss Calculation at existing load of 28% = 3.73 KW TRANSFORMER LOSS with Filter connected = 2.5 KW KW Saved = 1.23 KW

KVA Savings in Transformer Direct Saving / Day No. of Days Total Kwh Rate in Rs. Per KWH Total Savings with Commercial Rate in Rs. 1.15 KW 1 27.6 4.5 124.20 1.15 KW 7 193.2 4.5 1.15 KW 30 828 4.5 1.15 KW 365 10074 4.5 869.40 3,726.00 45,333.00 KW Savings in 1 No. X MER = Rs. 45,333 KW Savings in 4 Nos. X MERS = Rs. 1,81,332

Distribution Transformer Loss Calculation - Conclusion The Copper losses reduced to half, as the current dropped from 640 to 340 A Core loss decreased due to decrease in harmonics. Considering this total transformer loss will be much more than actual figure, and hence the savings will go up to not less than 1.8 kw The temperature has gone down drastically

Benefits Direct 1) Savings in KVA 2) Savings in Transformer losses (KW) Indirect 1) With AHF two distribution transformers freed for future expansion 2) Cable temperature reduced 3) Stopped frequent & spurious tripping of MCCBs 4) Spurious blowing of fuses in distribution controlled 5) Due to improvement in power quality, the electronic control systems and logics are well protected 6) KVA demand is made free for additional usage

Case Study: Cooper Foundries Ltd., Satara Sr.No. Load study point Input Source Existing Suggested DAPC only with Existing load KW PF THD Per phase Current AMP Only for Harmonics correction Factor correction 1 Furnace /Melting Furnace -800KW 3PH 2100 0.95 23-25% 725 150AMP +60 AMP Passive Filter 2 CD Furnace -500KW 3PH 1800 0.94 12% 600 150AMP Passive Filter 3 175KW Power Track Furnace (H1) 3PH 625 0.95 25% 275 60 AMP Passive Filter 4 LT PANEL (Furnace 125kw,RT, PFC,Core Shooter,H4 F/C Omega Compressor-75kw) 750 0.54 11% 197 60AMP Passive Filter 5 500KW Panel -Pump House, Foundry Crane AU M/C Office Load,AMH6 01.03 800 0.96 52% 450 2*150AMP Passive Filter Extremely high vthd Levels at the plant

Load Analysis with 150 A Harmonic Filter System Sr. No. I II III IV V VI VII VIII IX Parameter Frequency Vrms Phase 1 Phase 2 Phase 3 Arms Neutral Phase 1 Phase 2 Phase 3 THD vthd Phase 1 Phase 2 Phase 3 ithd Phase 1 Phase 2 Phase 3 p.f. Phase1 Phase 2 Phase 3 V Unbalance A Unbalance kw Phase 1 Phase 2 Phase 3 TOTAL kva Phase 1 Phase 2 Phase 3 TOTAL Unit Hz V ** Average Values Withour AHF With AHF 49.4 % Change 49.4 238.19 238.96 230.11 231.54 234.15 233.95 2.8% 2.0% -1.7% 49.6 549.31 558.16 575.11 52.47 494.27 497.43 515.78-5.8% 10.0% 10.9% 10.3% A Improvements in % 12.66 12.04 11.8 3.65 3.59 3.7 36.14 34.98 31.61 9.89 9.75 9.7 0.931 0.936 0.942 0.24 2.61 0.993 0.988 0.993 0.71 2.68-6.7% -5.6% -5.4% 121.96 124.91 129.57 376.45 113.73 115.19 119.88 348.81 6.7% 7.8% 7.5% 7.3% 130.88 133.415 137.56 401.85 114.48 116.5 120.705 351.69 12.5% 12.7% 12.3% 12.5% vthd / ithd % % % KW & KW/KVA kva

CASE STUDY 2 For Software Development Company Sutherland Global Service, Chennai Audit Done with : Manaco Power Analyser

Problems Experienced - Frequent failure of Electronic Boards in Servers and Work Station areas - Slow down of Network for reason unknown - Tripping of Generator - Distribution Transformer getting overheated

Site Condition Installed Power = 640 KVA Generator Capacity = 300 KVA

Load Current and VTHD measured in UPS panel Phases Load Current without AHF Load Current with AHF R Y B 237 A 208 A 187 A 182 A 168 A 150 A Phases VTHD without AHF VTHD with AHF R Y B 7.8% 8.3% 7.6% 2.6% 2.5% 2.5%

ithd measured in UPS panel Phases ithd without AHF ithd with AHF R 62% 12.7% Y 62.8% 14.5% B 64.8% 16.5%

PF Correction due to Harmonic Reduction Phases Power Factor without AHF Power Factor with AHF R 0.65 0.81 Y 0.59 0.74 B 0.63 0.84

Summary of Audit Input current reduced from 237 to 182 A / phase KVA demand reduced from 50.51 to 43.18 VA Due to current reduction copper losses (i²r losses) in the cables & transformers will be substantially reduced which we could not measure.

Summary of Audit Input Voltage distortion is reduced from 8.3% to 2.5% Input current distortion reduced from 64 % to 16 % Input PF is improved from 0.65 to 0.81 Harmonic Level in MV Panel before connecting AHF is 27% ithd After connecting AHF it was 3% ithd

Effect in kvar Initial value of PF capacitor was 370 KVAR in MV Panel. PF value = 0.97 With AHF connected required PF capacitor value is 230 KVAR @ 0.99 PF Due to this the circulating current in capacitors is reduced from 137 to 119 A Difference is around 18 A per phase

Results Substantial KVA DEMAND reductions to 32.16 KVA Issues related with the NOICE, EMI and RFI in the facility was ELIMINATED FAILURE OF ELECTRONIC BOARDS in the Server STOPPED completely GENERATOR AND EB TRANSFORMER HEATING issues resolved Generator CAPACITY REQUIREMENT REDUCED TO HALF

Thank you for your attention for further details Email : -------------@emerson.com Mobile #