Modeling of Shunt Active Filter Using P-Q Theory

Similar documents
Simulation Results of a Shunt Active Power Filter with Control Based on p-q Theory

Harmonics Elimination Using Shunt Active Filter

Harmonics Reduction using 4-Leg Shunt Active Power Filters

POWER QUALITY IMPROVEMENT USING SHUNT ACTIVE FILTER

Current Control Technique for Three Phase Shunt Active Power Filter by Using Adaptive Hysteresis Current Controller

Control Of Shunt Active Filter Based On Instantaneous Power Theory

A MATLAB-SIMULINK APPROACH TO SHUNT ACTIVE POWER FILTERS

Kanuru; Krishna (Dt); A.P, India. DOI: / Page. 1 G. Aruna Jyothi, 2 DR. P. V. R. L.

Harmonics Reduction of 3 Phase Diode Bridge Rectifier by Implementing P-Q Theory with Active Filter

INTERNATIONAL JOURNAL OF PURE AND APPLIED RESEARCH IN ENGINEERING AND TECHNOLOGY

Power Quality improvement with Shunt Active Power filter using p-q control technique

SHUNT COMPENSATOR USED FOR POWER QUALITY IMPROVEMENT

Sinusoidal Current Control based Shunt Active Power Filter for Current Harmonics Reduction

PERFORMANCE ANALYSIS OF SVPWM AND FUZZY CONTROLLED HYBRID ACTIVE POWER FILTER

ISSN: Page 20. International Journal of Engineering Trends and Technology- Volume2Issue3-2011

Simulation of Three Phase Cascaded H Bridge Inverter for Power Conditioning Using Solar Photovoltaic System

Synchronous Reference Frame Theory For Nonlinear Loads using Mat-lab Simulink

Power Quality Improvement using Shunt Passive Filter

A THREE PHASE SHUNT ACTIVE POWER FILTER FOR HARMONICS REDUCTION

Three Phase Active Shunt Power Filter with Simple Control in PSIM Simulation

A Time Domain Reference-Algorithm for Shunt Active Power Filters

ABSTRACT I. INTRODUCTION

2020 P a g e. Figure.2: Line diagram of series active power filter.

Comparison of Reference Current Extraction Methods for Shunt Active Power Filters

Modeling and Simulation of SRF and P-Q based Control DSTATCOM

Power Quality Improvement of Non-Linear Load by Using Instantaneous P-Q Theory

Cascaded Multilevel Inverter based Active Filter for Power Line Conditioners using Instantaneous mitigates

Three-Level Shunt Active Filter Compensating Harmonics and Reactive Power

KKR &KSR institute of Technology and sciences,vinjanampadu(v),vatticherukuru(m) Guntur(D) , Andhra Pradesh,India. I.

A Novel FPGA based PWM Active Power Filter for Harmonics Elimination in Power System

Control Strategy for Shunt Active Power Filters

IJSTE - International Journal of Science Technology & Engineering Volume 2 Issue 12 June 2016 ISSN (online): X

5DESIGN PARAMETERS OF SHUNT ACTIVE FILTER FOR HARMONICS CURRENT MITIGATION

Power Quality Improvement Using Hybrid Power Filter Based On Dual Instantaneous Reactive Power Theory With Hysteresis Current Controller

Power Quality Improvement in Fourteen Bus System using UPQC

HYSTERESIS CONTROL FOR CURRENT HARMONICS SUPPRESSION USING SHUNT ACTIVE FILTER. Rajesh Kr. Ahuja

Experimental Results of a Single-Phase Shunt Active Filter Prototype with Different Switching Techniques

Analysis of Reference Current Generation for Shunt Active Power Filter Using SRF Algorithm to Compensate Harmonic Current

A Novel Control Strategy of Shunt Active Filters

COMPENSATION OF POWER QUALITY PROBLEMS USING ACTIVE POWER FILTER

A Simple Control Algorithm for Three-Phase Shunt Active Power Filter for Reactive Power and Current Harmonic Compensation

Single Phase Shunt Active Filter Simulation Based On P-Q Technique Using PID and Fuzzy Logic Controllers for THD Reduction

NEUTRAL CURRENT COMPENSATION USING FOUR LEG SHUNT ACTIVE POWER FILTER

Power Quality Improvement using Active shunt Power filter using PI Controller

Hardware Implementation of SPWM Based Diode Clamped Multilevel Invertr

PI Controller Based Shunt Active Power Filter with Cascaded Multilevel Inverter

Performance Improvement of Active Power Filter using a New Control Strategy under Unbalanced Grid Voltage

CHAPTER 5 POWER QUALITY IMPROVEMENT BY USING POWER ACTIVE FILTERS

INSTANTANEOUS POWER CONTROL OF D-STATCOM FOR ENHANCEMENT OF THE STEADY-STATE PERFORMANCE

Application of Fuzzy Logic Controller in Shunt Active Power Filter

MITIGATION OF POWER QUALITY DISTURBANCES USING DISCRETE WAVELET TRANSFORMS AND ACTIVE POWER FILTERS

Assessment of Different Compensation Strategies in Hybrid Active Power Filters

Harmonic Analysis in Non-linear Load by using Hybrid UPQC

Simulation Study of PWM Techniques for Voltage Source Converters

IJSRD - International Journal for Scientific Research & Development Vol. 2, Issue 06, 2014 ISSN (online):

Comparative Analysis of Harmonics with and Without Shunt Active Power Filter

Shunt Active Power Filter based on SRF theory and Hysteresis Band Current Controller under different Load conditions

PI-VPI Based Current Control Strategy to Improve the Performance of Shunt Active Power Filter

CHAPTER 7 CONCLUSIONS AND FUTURE SCOPE

Mitigation of Current Harmonics with Combined p-q and Id-IqControl Strategies for Fuzzy Controller Based 3Phase 4Wire Shunt Active Filter

Key-Words: - NARX Neural Network; Nonlinear Loads; Shunt Active Power Filter; Instantaneous Reactive Power Algorithm

A Comparative Study on Four Time-Domain Harmonic Detection Methods for Active Power Filters Serving in Distorted Supply

Review on Shunt Active Power Filter for Three Phase Four Wire System

ISSN Vol.03,Issue.07, August-2015, Pages:

Design and Simulation of Three Phase Shunt Active Power Filter Using SRF Theory

Neural Network Controlled Hybrid Active Power Filter with Distorted Mains for PMSM Drive

Three Phase PFC and Harmonic Mitigation Using Buck Boost Converter Topology

MODELLING AND SIMULATION OF DIODE CLAMP MULTILEVEL INVERTER FED THREE PHASE INDUCTION MOTOR FOR CMV ANALYSIS USING FILTER

PLL Synchronization with PID Controller Based Shunt Active Power Line Conditioners

Hybrid Matrix Converter Based on Instantaneous Reactive Power Theory

ANALYSIS OF SYNCHRONOUS-REFERENCE-FRAME-BASED CONTROL METHOD FOR UPQC UNDER UNBALANCED AND DISTORTED LOAD CONDITIONS Salava Nagaraju* 1

MODELLING & SIMULATION OF ACTIVE SHUNT FILTER FOR COMPENSATION OF SYSTEM HARMONICS

Power Control and Quality Management in DG Grid Interfaced Systems

Power Quality improvement of a three phase four wire system using UPQC

Power Quality Improvement of Distribution Network for Non-Linear Loads using Inductive Active Filtering Method Suresh Reddy D 1 Chidananda G Yajaman 2

Improvement of Power Quality by using Active Filter based on Vectorial Power Theory Control Strategy on the MATLAB-Simulink Platform

STATCOM with FLC and Pi Controller for a Three-Phase SEIG Feeding Single-Phase Loads

Analysis of Hybrid Power Conditioner in Three-Phase Four-Wire Distribution Power Systems for Suppressing Harmonics and Neutral-Line Current

Fig. 1 Schematic Diagram Showing Connections to the Active Filter With Non-Linear Load

P.CHAITHANYAKUMAR, T.VARAPRASAD/

REDUCED COMMON MODE NOISE AND LOWER ORDER HARMONIC IN PUSH PULL CONVERTER BY ACTIVE FILTER

Development and Simulation of Dynamic Voltage Restorer for Voltage SAG Mitigation using Matrix Converter

Modeling & Simulation of Micro Grid Distribution System to reduce Harmonics Using Active Power Filters and PI controllers

POWER QUALITY IMPROVEMENT BY USING ACTIVE POWER FILTERS

Modified Three-Phase Four-Wire UPQC Topology with Reduced DC-Link Voltage Rating

DESIGN AND DEVELOPMENT OF ACTIVE POWER FILTER FOR HARMONIC MINIMIZATION USING SYNCHRONOUS REFERENCE FRAME (SRF)

Improvement of Power Quality Using Hybrid Active Power Filter in Three- Phase Three- Wire System Applied to Induction Drive

ISSN: ISO 9001:2008 Certified International Journal of Engineering Science and Innovative Technology (IJESIT) Volume 2, Issue 3, May 2013

Mitigating Voltage Sag Using Dynamic Voltage Restorer

DC Link Capacitor Voltage of D-Statcom With Fuzzy Logic Supervision

Simulation of Multi Converter Unified Power Quality Conditioner for Two Feeder Distribution System

Design of Shunt Active Power Filter by using An Advanced Current Control Strategy

Universal power quality conditioner

Literature Review for Shunt Active Power Filters

HARMONIC ELIMINATION IN THREE PHASE SYSTEM BY MEANS OF A SHUNT ACTIVE FILTER

DESIGN AND IMPLEMENTATION OF THREE PHASE SHUNT APF CURRENT CONTROLLER WITH ANN TECHNIQUE

Improvement of the Electric Power Quality Using Series Active and Shunt Passive Filters P. Salmerón and S. P. Litrán

Mitigation of Line Current Harmonics Using Shunt Active Filter With Instantaneous Real and Reactive Power Theory

Multi Level Inverter Based Active Power Filter for Harmonic Reduction


Transcription:

Modeling of Shunt Active Filter Using P-Q Theory Kirti Vibhute Assistant Professor, Shri Dadaji Institute of Technology & Science, Khandwa (M.P.), India Abstract: APF's are known to cancels the reactive and harmonic currents drawn by the load so as to make supply current sinusoidal and have been explored for executing different power conditioning functions simultaneously, along with harmonic elimination due to increase in Non-linear & unbalanced loads at the point of common coupling. The paper presents a study of different control strategies for APF's with an emphasis on instantaneous real power theory based Shunt APF, which is predominantly used in present scenario. The filter topologies are investigated through Matlab / Simulink and the design issues of APF for Non-linear load conditions are also discussed. Keywords: Active Power Filter (APF), Harmonics, Non-linear load, P-Q Theory, Reactive Power. 1.Introduction The intensive use of powers converters and other nonlinear loads in industry, domestic consumers in general has increased the deterioration of voltages and currents waveforms of power networks. The harmonics present in the power lines results in varied problems, like: greater power losses in distribution, problems of electromagnetic interference in communication systems, operation failures of protection devices, electronic equipments and industrial processes [3-4]. These problems result in high costs for industry and commercial activities, since they can lead to a decreasing in productivity and to a reduction of quality in the products or services duly delivered to consumers end more than ever. An object of great concern, being obligatory to solve the problem of the harmonics caused by polluting equipments such as adjustable speed drivers, static converters, UPS's, PC's, and electronic equipments in general. Passive filters have been used as a conventional solution to solve harmonic currents problems, but they present some challenges such as they only filter the frequencies they are pre-tuned for, their operation cannot be limited to a certain load or group of loads, resonance can occur due to the interaction between the passive filters and others loads, with unexpected results. To cope with these disadvantages continuous efforts have been concentrated on the development of active power filters [10-13]. In this paper the development of a shunt & series active filter is proposed, with a control system based on the p-q theory. The filter described effectively compensates the harmonic currents and the reactive power and also balances the power supply currents. and current waveforms as well. It involves an algebraic transformation of the three-phase voltages and currents in the a-b-c coordinates to the á-â-0 coordinates, followed by the calculation of the p-q theory instantaneous power components. A summary of these transformations is given under Where:- P0 =instantaneous zero sequence power p =instantaneous real power q =instantaneous imaginary power The power components p and q are related to the same á-â voltages and currents, and can be written together: 2.Proposed Instantaneous Power Theory (P-Q Theory) In 1983, Akagi et al. [6] proposed "The Generalized Theory of the Instantaneous Reactive Power in Three-Phase Circuits", also known as instantaneous power theory or p-q theory. Based on instantaneous values in three-phase power systems with or without neutral wire, the theory is valid for steady-state or transitory operations and for generic voltage These quantities are illustrated in Fig.1 for an electrical system represented in a-b-c coordinates and have the following physical meaning: Paper ID: SEP14548 1900

p0 = mean value of the instantaneous zero-sequence power corresponds to the energy per unit time transferred from the power supply to the load through the zero-sequence components of voltage and current. p0 ~ =alternated value of the instantaneous zero-sequence power, which is energy per unit time that is exchanged between the power supply and the load through the zero-sequence components. Furthermore, the systems must have unbalanced voltages and currents in both voltage and current of at least one phase. q = instantaneous imaginary power, corresponding to the power that is exchanged between phases of the load. This component is responsible for the existence of undesirable currents which circulates between the system phases. In the case of a balanced sinusoidal voltage supply and a balanced load, with or without harmonics, q is equal to the conventional reactive power p = mean value of instantaneous real power, corresponds to the energy per unit time which is transferred from the power supply to the load, through the a-b-c coordinates, for a balanced condition. p~ =alternated value of the instantaneous real power It is the energy per time unity that is exchanged between the power supply and the load, through the a-b-c coordinates. Figure 1: Power components in p-q theory An important aspect is that only the mean values of the instantaneous real power (p) and of the instantaneous zerosequence power (p0) must come from the power supply, as they effectively transfer energy to the load. Figure 2: p-q theory power components in a generic three phase power system with shunt active filter The active filter also permits the power supply to deliver a magnitude p0 to the load from the phases, without the using the neutral wire. All the other power components (p0,~p,pand q ) can be compensated with the use of shunt active power filter, as presented in Fig 2. The p-q controller allows systematic information, to verify the requirement of compensation currents by the active filter. It receives the information of phase voltages, load currents and DC voltage, and proceeds to the calculations based on its control algorithm generating necessary reference compensation currents, which is indicated in Fig.3. The objective of this algorithm is to compensate all undesirable power components. Besides, the source will see the load as if it was a balanced resistive load and the RMS value of the supply currents will be the lower possible to deliver the energy the load needs to work. 3.Reference Current Calculation The control scheme of the Shunt and Series active power filters must calculate the current reference signals from each phase of the inverter using instantaneous real power compensator. The block diagram is shown in fig. 4. In this case a P-Q controller is applied to the System in generating the switching signals. The Power stage is basically a VSI, controlled similar to a current source. Reference currents calculated by the controller (ica *,icb*,icc*,icn*) is used by the inverter to Paper ID: SEP14548 1901

produce the compensation currents (ica, icb, icc, icn) to compensate harmonics. The basic algorithm commonly used for the calculation of the compensating currents is shown in Fig. 5. In this figure, pc and qc are the compensation reference powers. The p-q theory is a suitable tool to the analysis of non-linear threephase systems and for the control of active filters. The implementation of active filters based on the p-q theory are cost-effective solutions, allowing the use of a large number of low-power active filters in the same facility, close to each problematic load (or group of loads), avoiding the circulation of current harmonics, reactive currents and neutral currents through the facility power lines. 4.Simulation Design The P-Q Theory based with and without Shunt Active Power Filter is implemented for harmonic compensation and the various models used for simulating and validating its performance are given under in Fig.6 & Fig7. 5.Simulation Results The filter topologies discussed in the previous sections were investigated through Matlab / Simulink V-2009b and the results obtained are shown below for an electric network voltage and current responses without Fig.7 & Fig.9 and with an APF in Fig.10 & Fig 11. Paper ID: SEP14548 1902

As the source current & Voltage are in phase, also the source current is almost sinusoidal (very low THD), it can be said that source is providing only active power required by the circuit. In P-Q theory view, source current is providing only average real power component (P ), while remaining components i.e. real oscillating power P +,q + &q is being provided by APF. From load current and Non linear load RL, it can be said that the effectiveness of APF in compensating of harmonic components of load current depends on the specific load current waveform involved. Two different waveforms have the same rms harmonic content, but APF may do a better job of compensating for one of the waveforms because of the wave shapes involved. In general the limiting factor for increasing the DC voltage is the voltage withstands capability of the IGBT devices. From harmonic analysis of source current, it can be seen due to uneven switching of compensator large No. of interharmonics are introduced. But it should be noted that these components have very less magnitude. It is worth to also to note that P-Q based APFs can be used for complete harmonic elimination not selective harmonic elimination. compensated and are very effective for voltage source inverter type loads, even when the distortion is high. By comparing reference current & source waveforms, it can be conducted that this controller compensation at the cost of high switching frequency, which can result in high switching losses in practical high power applications. In p-q theory has some short comings which need to be addressed like mathematical expression of instantaneous power does not follow power conservation and real & imaginary power needed to be more accurately defined as zero sequence instantaneous power cannot be defined by the theory. In practical approach also it can be noted that p-q theory is unable of providing selective harmonic elimination and specific power factor compensation. 7.Acknowledgement The authors would like to thank to all referees for their useful remarks, which helped to improve the work. And would also like to express cordial thankfulness to the entire Department of Electrical Engineering, NIIST, Bhopal (M.P.), INDIA for providing all necessary and due help for successful attainment of the research objectives. References 6.Conclusion The validity in terms of eliminating p-q theory in terms of eliminating harmonics and Power Factor improvement is conformed from low THD source current which is in phase with source voltage. But p-q theory utilizes large No. of calculation & demands higher processing power resulting in utility to be complex & expensive. They are predominantly utilized in three phase circuits, thus cannot be used at remote single phase customer. From source currents of both cases, it can be inferred that APF is most effective when the load current waveform does not have abrupt changes. The overall filtering effectiveness depending significantly on the types of loads being [1] T. Mahalalekshami, Current harmonic compensation and power factor improvement by hybrid shunt active power filter, International journal of computer applications (0975-8887) Vol-04, No.3,july 2010. [2] Vaibhav Purwar,Sanjiv Kr., Simulation of Shunt Active power line conditioner (APLC) for three phase AC/DC converters, VSRD-IJEECE Vol.1,No.9, 2011,504-513 [3] H. Akagi, New trends in active power filters for power conditioning, IEEE Trans. Ind. Appli.,vol.IAvol 32, no 6, pp.1312-1322.1996. [4] H. Akagi, Y. Kanazawa and A.Nabae, Instantaneous reactive power compensators comprising switching devices without energy storage compenents, IEEE Trans. Ind Appli.,vol. IA-20, pp.625-630.1984. Paper ID: SEP14548 1903

[5] Edson H.Watanabe,Maurício Aredes,Hirofumi Akagi The P-Q Theory For Active Filter Control : Some Problems And Solutions,review & automatic control. Vol.15 No.1, 2004. [6] Akagi, H., Kanazawa, Y. and Nabae, A. (1983) "Generalized Theory of the Instantaneous Reactive Power in Three-Phase Circuits," IPEC 83. Int. Power Electronics Conf., Tokyo, Japan, pp. 1375-1386. [7] N. Mohan, T. M. Undeland, W. P. Robbins, "Power Electronics:Converters, Applications, and Design," New York, NY, USA, John Wiley & Sons, Inc., 1995. [8] Handbook of Power Electronics Circuits,Devices and applications by M. H.Rashid,,pearson Education,Singapore 1993 [9] Handbook of Power Electronics by M.D. Singh, K.B. Khanchandani., Tata McGraw Hill Publication,Delhi 2001 [10] Karrupanan P. and Kamalakanta Mahapatra Cascaded Multilevel inverter based Active Filters for Power line Conditioners using Instantaneous Real PowerTheory IEEE-IICPE2010, International conference on Power Electronics, NSIT-NEW Delhi, January 28-30 2011. [11] Leszek S. Czarnecki, Fellow IEEE Instantaneous Reactive Power p-q Theory and Power Properties of Three-Phase Systems, IEEE transaction on Power Delivery,Vol.21 No.1,Jan 2006, 362-367. [12] G. Jayakrishna and K.S.R.Anjaneyulu, Fuzzy Logic Control based Three Phase Shunt Active Filter for Voltage Regulation and Harmonic Reduction,,International journal of computer applications(0975-8887)vol-10, No.5,Nov. 2010. [13] Musa Yusup Lada,Ismadi Bugis, Md Hairul Nizam Talib Simulation Shunt Active Power Filter using Matlab/Simulink, The 4th International Power Engineering and Optimization Conf. (PEOCO2010), Shah Alam, Selangor, MALAYSIA: 23-24 June 2010 [14] HandBook of Electrical Power Systems Quality by R.C. Dugan, Tata McGraw Hill Publication, Delhi Second Edition. Author Profile Mrs. Kirti Vibhute was completing her B.Tech (Electrical Engg) degree from Amravati University, (M.S) INDIA and M.Tech (Power Electronics) from Rajiv Gandhi Prodyogiki Vishwavidyalaya, Bhopal (M.P.) India. Presently she is working as a Assistant Prof. at Shri Dadaji Institute of tech. & Science, Khandwa (M.P.), India Paper ID: SEP14548 1904