COMPENSATION OF POWER QUALITY PROBLEMS USING ACTIVE POWER FILTER

Similar documents
Improvement of Power Quality by using Active Filter based on Vectorial Power Theory Control Strategy on the MATLAB-Simulink Platform

Shunt Active Power Filter based on SRF theory and Hysteresis Band Current Controller under different Load conditions

Modeling and Simulation of SRF and P-Q based Control DSTATCOM

Enhancement of Power Quality Using Advanced Series Active Power Filters

Reactive Power Compensation of LC Coupling Hybrid Active Power Filters by DC Link Voltage Controls

Simulation of Three Phase Cascaded H Bridge Inverter for Power Conditioning Using Solar Photovoltaic System

INTERNATIONAL JOURNAL OF PURE AND APPLIED RESEARCH IN ENGINEERING AND TECHNOLOGY

A Simple Control Algorithm for Three-Phase Shunt Active Power Filter for Reactive Power and Current Harmonic Compensation

SHUNT COMPENSATOR USED FOR POWER QUALITY IMPROVEMENT

Harmonics Reduction using 4-Leg Shunt Active Power Filters

Sinusoidal Current Control based Shunt Active Power Filter for Current Harmonics Reduction

Key-Words: - NARX Neural Network; Nonlinear Loads; Shunt Active Power Filter; Instantaneous Reactive Power Algorithm

IJSRD - International Journal for Scientific Research & Development Vol. 2, Issue 06, 2014 ISSN (online):

Power Quality Improvement of Distribution Network for Non-Linear Loads using Inductive Active Filtering Method Suresh Reddy D 1 Chidananda G Yajaman 2

Power Quality Improvement in Fourteen Bus System using UPQC

IJESR/Nov 2012/ Volume-2/Issue-11/Article No-21/ ISSN International Journal of Engineering & Science Research

Comparative Analysis of Harmonics with and Without Shunt Active Power Filter

Power Quality Improvement Using Hybrid Power Filter Based On Dual Instantaneous Reactive Power Theory With Hysteresis Current Controller

ISSN: ISO 9001:2008 Certified International Journal of Engineering Science and Innovative Technology (IJESIT) Volume 2, Issue 3, May 2013

Harmonics Elimination Using Shunt Active Filter

PERFORMANCE ANALYSIS OF SVPWM AND FUZZY CONTROLLED HYBRID ACTIVE POWER FILTER

A THREE PHASE SHUNT ACTIVE POWER FILTER FOR HARMONICS REDUCTION

Design and Simulation of Three Phase Shunt Active Power Filter Using SRF Theory

Three-Level Shunt Active Filter Compensating Harmonics and Reactive Power

IMPROVEMENT OF POWER QUALITY USING CUSTOM POWER DEVICES

Exploration in Power Quality Furtherance on Shunt Active Power Filter

IMPROVING THE OUTPUT OF CASCADED FIVE LEVEL MULTILEVEL INVERTER USING LOW PASS BROADNBAND FILTER

Simulation of Multi Converter Unified Power Quality Conditioner for Two Feeder Distribution System

POWER QUALITY IMPROVEMENT BY USING ACTIVE POWER FILTERS

2020 P a g e. Figure.2: Line diagram of series active power filter.

Harmonic Reduction in Five Level Inverter Based Dynamic Voltage Restorer

Neural Network Controlled Hybrid Active Power Filter with Distorted Mains for PMSM Drive

Power Quality Improvement using Active shunt Power filter using PI Controller

Power Quality Improvement in Distribution System Using D-STATCOM

Svpwm Technique to Eliminate Harmonics and Power Factor Improvement Using Hybrid Power Filter and By Using Dsp Tms 320lf2407

HYSTERESIS CONTROL FOR CURRENT HARMONICS SUPPRESSION USING SHUNT ACTIVE FILTER. Rajesh Kr. Ahuja

Design of UPQC with constant frequency controlled scheme for removal of Total Harmonic Distortion

Australian Journal of Basic and Applied Sciences. Simulation and Analysis of Closed loop Control of Multilevel Inverter fed AC Drives

Shunt Active Power Filter for Compensation of System Harmonics

Performance Comparison of DSTATCOM and Shunt Active Filter for Voltage Sag Improvement in Distribution System

DESIGN A D STATCOM FOR VOLTAGE HARMONIC SUPPRESSION IN DISTRIBUTION SYSTEM

STATCOM with FLC and Pi Controller for a Three-Phase SEIG Feeding Single-Phase Loads

Enhancement of Power Quality using active power filter in a Medium-Voltage Distribution Network switching loads

5DESIGN PARAMETERS OF SHUNT ACTIVE FILTER FOR HARMONICS CURRENT MITIGATION

IJSTE - International Journal of Science Technology & Engineering Volume 2 Issue 12 June 2016 ISSN (online): X

Improvement of Power Quality in Distribution System using D-STATCOM With PI and PID Controller

Power Quality improvement of a three phase four wire system using UPQC

Three Phase PFC and Harmonic Mitigation Using Buck Boost Converter Topology

Harmonics Reduction of 3 Phase Diode Bridge Rectifier by Implementing P-Q Theory with Active Filter

A Five Level DSTATCOM for Compensation of Reactive Power and Harmonics

POWER QUALITY IMPROVEMENT BY USING ACTIVE POWER FILTERS

A MATLAB-SIMULINK APPROACH TO SHUNT ACTIVE POWER FILTERS

Modified Three-Phase Four-Wire UPQC Topology with Reduced DC-Link Voltage Rating

HARMONIC ELIMINATION IN THREE PHASE SYSTEM BY MEANS OF A SHUNT ACTIVE FILTER

Power Quality Improvement using Shunt Passive Filter

Improvement of the Electric Power Quality Using Series Active and Shunt Passive Filters P. Salmerón and S. P. Litrán

A Hysteresis based Active Shunt, Passive Series Hybrid Filter for Power Quality Improvement

Multi Level Inverter Based Active Power Filter for Harmonic Reduction

ISSN Vol.03,Issue.42 November-2014, Pages:

Ripple Reduction Using Seven-Level Shunt Active Power Filter for High-Power Drives

CONCLUSIONS AND SUGGESTIONS FOR FUTURE WORK

Shunt active filter algorithms for a three phase system fed to adjustable speed drive

A Voltage Controlled DSTATCOM using Hybrid Renewable Energy DC Link VSI for Power Quality Improvement

Comparison of Reference Current Extraction Methods for Shunt Active Power Filters

SIMULATION AND COMPARISON OF SPWM AND SVPWM CONTROL FOR TWO LEVEL UPQC

Assessment of Different Compensation Strategies in Hybrid Active Power Filters

Unit Vector Theory based Unified Power Quality Conditioner for Power Quality Improvement

Application of Fuzzy Logic Controller in Shunt Active Power Filter

A Time Domain Reference-Algorithm for Shunt Active Power Filters

Reactive power compensation for linear and non linear loads by using active and passive filter for smart grid applications.

MMC based D-STATCOM for Different Loading Conditions

Performance Analysis of UPQC for Non-Linear Load by Using MATLAB

ISSN Vol.03,Issue.07, August-2015, Pages:

INTERLINE UNIFIED POWER QUALITY CONDITIONER: DESIGN AND SIMULATION

Current Control Technique for Three Phase Shunt Active Power Filter by Using Adaptive Hysteresis Current Controller

Volume I Issue VI 2012 September-2012 ISSN

ICCCES Application of D-STATCOM for load compensation with non-stiff sources

Multilevel Inverter Based Statcom For Power System Load Balancing System

ANALYSIS OF SYNCHRONOUS-REFERENCE-FRAME-BASED CONTROL METHOD FOR UPQC UNDER UNBALANCED AND DISTORTED LOAD CONDITIONS Salava Nagaraju* 1

Three Phase Active Shunt Power Filter with Simple Control in PSIM Simulation

Design of Shunt Active Filter to Improve Power Quality using Pq Theory

The Shunt Active Power Filter to Compensate Reactive Power and Harmonics Under Unbalanced Non-Linear Load Conditions

Hybrid Active Power Filters for Reactive Power Compensation with Adaptive DC-Link Voltage Control

Z-SOURCE INVERTER BASED DVR FOR VOLTAGE SAG/SWELL MITIGATION

Cascaded Multilevel Inverter based Active Filter for Power Line Conditioners using Instantaneous mitigates

A COMPARATIVE STUDY ON UPFC AND DPFC TOWARDS LOW HARMONIC DISTORTION

Analysis of Reference Current Generation for Shunt Active Power Filter Using SRF Algorithm to Compensate Harmonic Current

Reduction In Total Harmonic Distortion Using Active Power Filters

USING HYBRID POWER FILTER TO MITIGATE CURRENTS AND VOLTAGES HARMONICS IN THREE PHASE SYSTEM

World Journal of Engineering Research and Technology WJERT

Synchronous Reference Frame Control Algorithm Based Four -Leg Inverter DSTATCOM For Power Quality Improvement

Modeling & Simulation of Micro Grid Distribution System to reduce Harmonics Using Active Power Filters and PI controllers

PI-VPI Based Current Control Strategy to Improve the Performance of Shunt Active Power Filter

A NOVEL STRUCTURE FOR THREE-PHASE FOUR-WIRE DISTRIBUTION SYSTEM UPQC

Selective Harmonic Elimination Using Three Phase Shunt Active Power Filter

A Review on Simulation and Implementation of Thyristor controlled reactor and Shunt Hybrid Power Filter

Unit.2-Voltage Sag. D.Maharajan Ph.D Assistant Professor Department of Electrical and Electronics Engg., SRM University, Chennai-203

A Voltage Controlled Dstatcom for Power Quality Improvement

POWER QUALITY IMPROVEMENT FOR DISTRIBUTION NETWORK BY DESIGN OF TWO CONTROL STRATEGIES FOR ACTIVE POWER FILTER.

POWER QUALITY IMPROVEMENT BY HARMONIC REDUCTION USING THREE PHASE SHUNT ACTIVE POWER FILTER WITH p-q & d-q CURRENT CONTROL STRATEGY

Transcription:

International Journal of Engineering Science Invention ISSN (Online): 2319 6734, ISSN (Print): 2319 6726 Volume 2 Issue 3 ǁ March. 2013 ǁ PP.25-30 COMPENSATION OF POWER QUALITY PROBLEMS USING ACTIVE POWER FILTER *S. Kavaskar,M.Rajmal Joshi, S.Paneer Selvam, P.Kalaimani, A.Kalaimani, R.Bharat kumar, K.Narashkumar Panimalar Engineering College, Chennai-600123 ABSTRACT: Sensitive loads are greatly affected by power quality disturbances in the system. The increased reactive power, harmonics and unbalance cause in line losses, instability and voltage distortion. When harmonics travel upstream and produce drop across the line impedance. Passive filters do not provide any solution for unbalance and variable reactive power compensation. A shunt active power filter (APF) can realize the appropriate solution for all the above said problems. APF is used to compensate harmonics and reactive current drawn by nonlinear and linear loads. The system is examined with and without APF to minimize the power quality problems such as voltage sag and harmonic distortion for linear and non-linear loads. The FFT analysis is done to find the total harmonic distortion. The proposed scheme has a fast response and is able to maintain bar sinusoidal source current for harmonic compensation. The proposed scheme offers good solution to uncertainties in power system due to power quality problems. The circuit is simulated using MATLAB/SIMULINK. Keyword: Shunt active filters, Power quality disturbances, Harmonic distortion, Linear and Non linear load I. INTRODUCTION The AC power system has always been susceptible to problems regarding reactive power and unbalance from the very beginning. It has worsened with the increased used of power electronic converters as some of these converters not only increase reactive currents, but also generate harmonics in he source current. The increased reactive power harmonics and unbalance cause an increase in line losses, instability and voltage distortion when harmonics travel upstream and produce drop across the line impedance, which corrupts the power system. Conventionally shunt passive filters are used to suppress the harmonics and their application provides limited fixed reactive power compensation moreover passive filters do not provide any solution for unbalance variable reactive power compensation. Active power filters (APF) are power electronic devices operated in power systems for conditioning purposes. In most of the cases, APFs are primary designed for current or voltage harmonic compensation or isolation. Additional features, such as reactive power compensation or voltage regulation may be performed by some topologies. The APF compensation principles were proposed in 1970, and the significant development of power electronics technology has allowed engineers to make the APF a practical reality today [1]-[2]. Two fundamental configurations of stand-alone filters, either active or passive, have evolved: the series and the parallel filter. Combinations of one active and one passive filter in different configurations are known as hybrid filters [3]. A shunt active power filter can realize the appropriate solution for all the aforesaid problems. In [3] have discussed power quality problems in distribution systems and their solutions using power electronics equipments. The performances of the APF in distribution line under fault have also discussed. In [4] has discussed using both APF and passive filters for compensating current harmonic distribution and power factor improvement. The method propos is improved generalized integrator controller. II. SYSTEM STUDIED In this paper harmonic generated by linear and non linear loads are compensated using APF with and without transmission line. In this following cases are studied 2.1 Linear Load without APF 25 P a g e

Figure 1: Transmission line connected with load Figure 1 Shows 3 phase transmission line connected with linear load and performance of the system has been studied without APF. Figure 2: Voltage sag Figure 2: shows the voltage sag measured across the load after connecting the linear Load to the transmission line. It is found in the waveform due to the linear load there is voltage sag at the time 0.18(sec). Figure.3 RMS voltage Figure 4 FFT analysis 26 P a g e

Figure 3: Shows RMS voltage variation due to addition and load. Figure 4 shows the FFT analysis for the voltage measured across the load to determine the level of the harmonic distortion. The total harmonic distortion found using linear load with APF is 2.96%. 2.2 Linear Load with APF Figure.5 Circuit diagram with STATCOM Figure 5: shows transmission line is connected with both linear load and APF. Shunt active power filter has been connected across the three phase power generator to compensate the harmonic generated by the linear load. Figure.6 voltage measured across the load with APF Figure.6 voltage measured across the load with APF it is observed from the wave form after the instant 0.18(sec) in all the three phases voltage sag was completely eliminated due to the addition of STATCOM in the transmission line. RMS variation of three phase voltage has been given in the Figure.7 Figure 7: Three phase load current 27 P a g e

Figure.8 Real power Figure.9 Reactive power Figure. 10 FFT analyses for current Figure7: shows the variation of load current. Figure.8 and 9 shows the change in real and reactive power due to linear load. Figure 10: FFT analysis is applied to the voltage wave form of the linear load after the APF. It is observed that level of the harmonic is reduced to 1.70%. 2.3 Non Linear Loads without APF Figure.11 Circuit diagram 28 P a g e

Figure.11 shows a system consists non-linear load without APF. A bridge rectifier and a load is connected across the supply to ensure the performance of the transmission line without APF. Figure.12 Load voltage Figure. 13 FFT analysis The voltage measured across the bridge has been shown in the Figure 12: Here bridge rectifier is considered as non linear load. It is found from the Figure 12 voltage sag is found at the instant 0.18(sec) to 0.26(sec). Due to non-linear load voltage wave form measured across the load is highly distorted with harmonic. Figure. 14 Circuit diagram with STATCOM 29 P a g e

Figure.15 Three phase load voltage Figure.16 FFT analysis III. CONCLUSION In this paper current decomposition technique based on instantaneous power theory power for SAPF is studied, simulink model is designed and THD is calculated to determine the level of the harmonic distortion. APF used here monitors the load current constantly and continuously adapt to the changes in load harmonics. REFERENCE [1]. H. Akagi, New trends in active filters for power conditioning, IEEE Trans. Industry Applications,32(6)1996, 1312-1322. [2]. B. Singh, K. Al-Haddad, A. Chandra, A review of active filters for power quality improvement, IEEE Trans. Industrial Electronics, 46(5)1999,960-971. [3]. F.Z. Peng, D.J. Adams, Harmonic sources and filtering approaches series/parallel, active/passive and their combined power filters, IEEE IAS Ann. Meeting, 1999,vol. 1, 448-455. [4]. Morán, L.A., Dixon, J.W. & Wallace, R.R. A three-phase active power filter operating with fixed switching frequency for reactive power and current harmonic compensation. IEEE Transactions on Industrial Electronics, 42(4)1995,402-408. [5]. T.Mahalekshmi, Current Harmonic Compensation and Power Factor Improvement by Hybrid Shunt Active Power Filter International Journal of Computer Applications 4 (3),2010,9-13. 30 P a g e