Improvement of Power Quality by using Active Filter based on Vectorial Power Theory Control Strategy on the MATLAB-Simulink Platform

Similar documents
Power Quality Improvement Using Hybrid Power Filter Based On Dual Instantaneous Reactive Power Theory With Hysteresis Current Controller

COMPENSATION OF POWER QUALITY PROBLEMS USING ACTIVE POWER FILTER

Improvement of the Electric Power Quality Using Series Active and Shunt Passive Filters P. Salmerón and S. P. Litrán

Sinusoidal Current Control based Shunt Active Power Filter for Current Harmonics Reduction

Current Control Technique for Three Phase Shunt Active Power Filter by Using Adaptive Hysteresis Current Controller

Power Quality Improvement of Distribution Network for Non-Linear Loads using Inductive Active Filtering Method Suresh Reddy D 1 Chidananda G Yajaman 2

Improving Passive Filter Compensation Performance With Active Techniques

Reactive Power Compensation of LC Coupling Hybrid Active Power Filters by DC Link Voltage Controls

Enhancement of Power Quality using active power filter in a Medium-Voltage Distribution Network switching loads

Three Phase Active Shunt Power Filter with Simple Control in PSIM Simulation

INTERNATIONAL JOURNAL OF PURE AND APPLIED RESEARCH IN ENGINEERING AND TECHNOLOGY

A THREE PHASE SHUNT ACTIVE POWER FILTER FOR HARMONICS REDUCTION

Power Quality Improvement using Shunt Passive Filter

ISSN: ISO 9001:2008 Certified International Journal of Engineering Science and Innovative Technology (IJESIT) Volume 2, Issue 3, May 2013

Assessment of Different Compensation Strategies in Hybrid Active Power Filters

CURRENT HARMONICS REDUCTION IN 3 PHASES 4 WIRE SYSTEM USING HYBRID FILTERS R.Saravanakumar 1#, S.Amritha 2#

POWER QUALITY IMPROVEMENT BY USING ACTIVE POWER FILTERS

HARMONIC ELIMINATION IN THREE PHASE SYSTEM BY MEANS OF A SHUNT ACTIVE FILTER

IJSTE - International Journal of Science Technology & Engineering Volume 2 Issue 12 June 2016 ISSN (online): X

A Study of Various Filters for Power Quality Improvement

ISSN Vol.04,Issue.16, October-2016, Pages:

A Simple Control Algorithm for Three-Phase Shunt Active Power Filter for Reactive Power and Current Harmonic Compensation

Load Compensation at a Reduced DC Link Voltage by Using DSTATCOM with Non-Stiff Source

Shunt Active Power Filter based on SRF theory and Hysteresis Band Current Controller under different Load conditions

Three Phase PFC and Harmonic Mitigation Using Buck Boost Converter Topology

Key-Words: - NARX Neural Network; Nonlinear Loads; Shunt Active Power Filter; Instantaneous Reactive Power Algorithm

USING HYBRID POWER FILTER TO MITIGATE CURRENTS AND VOLTAGES HARMONICS IN THREE PHASE SYSTEM

A Review on Simulation and Implementation of Thyristor controlled reactor and Shunt Hybrid Power Filter

A Novel FPGA based PWM Active Power Filter for Harmonics Elimination in Power System

Simulation of Three Phase Cascaded H Bridge Inverter for Power Conditioning Using Solar Photovoltaic System

Modeling & Simulation of Micro Grid Distribution System to reduce Harmonics Using Active Power Filters and PI controllers

Analysis of Hybrid Power Conditioner in Three-Phase Four-Wire Distribution Power Systems for Suppressing Harmonics and Neutral-Line Current

Harmonics Reduction using 4-Leg Shunt Active Power Filters

Power Quality improvement of a three phase four wire system using UPQC

Design and Simulation of Three Phase Shunt Active Power Filter Using SRF Theory

A HYBRID ACTIVE FILTER FOR A DIODE RECTIFIER USED AS THE FRONT END OF AN INDUCTION MOTOR DRIVE

POWER QUALITY IMPROVEMENT BY USING ACTIVE POWER FILTERS

TRANSFORMER LESS H6-BRIDGE CASCADED STATCOM WITH STAR CONFIGURATION FOR REAL AND REACTIVE POWER COMPENSATION

Review on Shunt Active Power Filter for Three Phase Four Wire System

ICCCES Application of D-STATCOM for load compensation with non-stiff sources

Harmonics Elimination Using Shunt Active Filter

Hybrid Active Power Filters for Reactive Power Compensation with Adaptive DC-Link Voltage Control

Multi Level Inverter Based Active Power Filter for Harmonic Reduction

Power Quality Improvement in Fourteen Bus System using UPQC

Selective Harmonic Elimination Using Three Phase Shunt Active Power Filter

Comparison of Reference Current Extraction Methods for Shunt Active Power Filters

Analysis of Advanced Techniques to Eliminate Harmonics in AC Drives

Design and Simulation of Fuzzy Logic controller for DSTATCOM In Power System

2020 P a g e. Figure.2: Line diagram of series active power filter.

PI Controller Based Shunt Active Power Filter with Cascaded Multilevel Inverter

Harmonic Analysis in Non-linear Load by using Hybrid UPQC

Svpwm Technique to Eliminate Harmonics and Power Factor Improvement Using Hybrid Power Filter and By Using Dsp Tms 320lf2407

Design of Shunt Active Filter to Improve Power Quality using Pq Theory

Z-SOURCE INVERTER BASED DVR FOR VOLTAGE SAG/SWELL MITIGATION

Available online at ScienceDirect. Procedia Technology 21 (2015 ) SMART GRID Technologies, August 6-8, 2015

PERFORMANCE ANALYSIS OF SVPWM AND FUZZY CONTROLLED HYBRID ACTIVE POWER FILTER

PI-VPI Based Current Control Strategy to Improve the Performance of Shunt Active Power Filter

A Voltage Controlled DSTATCOM using Hybrid Renewable Energy DC Link VSI for Power Quality Improvement

SHUNT COMPENSATOR USED FOR POWER QUALITY IMPROVEMENT

Indirect Current Control of LCL Based Shunt Active Power Filter

ISSN: ISO 9001:2008 Certified International Journal of Engineering Science and Innovative Technology (IJESIT) Volume 2, Issue 3, May 2013

Application of Fuzzy Logic Controller in Shunt Active Power Filter

Ripple Reduction Using Seven-Level Shunt Active Power Filter for High-Power Drives

DESIGN AND DEVELOPMENT OF ACTIVE POWER FILTER FOR HARMONIC MINIMIZATION USING SYNCHRONOUS REFERENCE FRAME (SRF)

DC Link Capacitor Voltage of D-Statcom With Fuzzy Logic Supervision

Control Of Shunt Active Filter Based On Instantaneous Power Theory

Harmonics Reduction of a Single Phase Half Bridge Inverter

IJSRD - International Journal for Scientific Research & Development Vol. 2, Issue 06, 2014 ISSN (online):

Simulation Study of PWM Techniques for Voltage Source Converters

MODELLING & SIMULATION OF ACTIVE SHUNT FILTER FOR COMPENSATION OF SYSTEM HARMONICS

Power Quality Improvement using Active shunt Power filter using PI Controller

Efficient Hybrid Shunt Active Power Filter for Improvement of Power Factor and Harmonic Suppression using MATLAB

Enhancement of Power Quality Using Advanced Series Active Power Filters

Shunt active filter algorithms for a three phase system fed to adjustable speed drive

POWER QUALITY IMPROVEMENT IN MATRIX CONVERTER USING HYBRID FILTER

Design of Hybrid Active Filter for Power Quality Improvement of Electrical Distribution System Using Fuzzy Logic Controller

Reactive power compensation for linear and non linear loads by using active and passive filter for smart grid applications.

Mitigating Voltage Sag Using Dynamic Voltage Restorer

shunt (parallel series

Harmonic Reduction and Power Factor improvement in three phase three wire system by using Passive Filters

A MATLAB-SIMULINK APPROACH TO SHUNT ACTIVE POWER FILTERS

P.CHAITHANYAKUMAR, T.VARAPRASAD/

Power Quality Improvement of Unified Power Quality Conditioner Using Reference Signal Generation Method

Design of UPQC with constant frequency controlled scheme for removal of Total Harmonic Distortion

CHAPTER 6 UNIT VECTOR GENERATION FOR DETECTING VOLTAGE ANGLE

MODELING AND ANALYSIS OF IMPEDANCE NETWORK VOLTAGE SOURCE CONVERTER FED TO INDUSTRIAL DRIVES

Shunt Active Power Filter for Compensation of System Harmonics

ISSN Vol.03,Issue.42 November-2014, Pages:

Modified Three-Phase Four-Wire UPQC Topology with Reduced DC-Link Voltage Rating

INVESTIGATION OF HARMONIC DETECTION TECHNIQUES FOR SHUNT ACTIVE POWER FILTER

Cascaded Multilevel Inverter based Active Filter for Power Line Conditioners using Instantaneous mitigates

Harmonic Reduction in Five Level Inverter Based Dynamic Voltage Restorer

POWER QUALITY IMPROVEMENT BY HARMONIC REDUCTION USING THREE PHASE SHUNT ACTIVE POWER FILTER WITH p-q & d-q CURRENT CONTROL STRATEGY

Power Quality Improvement of Non-Linear Load by Using Instantaneous P-Q Theory

Hybrid Matrix Converter Based on Instantaneous Reactive Power Theory

Improvement of Power Quality Using a Hybrid Interline UPQC

Kanuru; Krishna (Dt); A.P, India. DOI: / Page. 1 G. Aruna Jyothi, 2 DR. P. V. R. L.

Field Programmable Gate Array (FPGA) Based Pulse Width Modulation for Single Phase Hybrid Active Power Filters U. Krishna Reddy 1 Ch.

CUCKOO SEARCH ALGORITHM BASED CURRENT CONTROL TECHNIQUE FOR HARMONIC REDUCTION IN NON-LINEAR LOADS

[Mahagaonkar*, 4.(8): August, 2015] ISSN: (I2OR), Publication Impact Factor: 3.785

Transcription:

Improvement of Power Quality by using Active Filter based on Vectorial Power Theory Control Strategy on the MATLAB-Simulink Platform Metkari Archana Subhash ElectricalEngg., Government college of engg., Karad / ShivajiUniversity,India Prof.S.H.Pawar ElectricalEngg., Government college of engg., Karad / ShivajiUniversity,India Abstract: Harmonic current drawn from a supply by the nonlinear load results in the distortion of the supply voltage waveform. Both distorted current and voltage may cause conductors to overheat and may reduce the efficiency and life expectancy of the equipment. So that reduction of harmonics is very important in day today life. For that purpose used filtersactive power filters are used to improve power quality by compensating harmonics and reactive power required by a non-linear load. In this paper a Series active and passive shunt filter is discussed. The control strategy based on vectorial theory of instantaneous reactive power, so that the voltage waveform injected by the active filter is able to compensate the reactive power. Keywords Active power filter, current harmonics, instantaneous reactive power, power filter, power quality I. INTRODUCTION In recent years both power engineers and consumers have been giving focus on the electrical power quality i.e. degradation of voltage and current due to harmonics, low power factor etc. A power quality problem exists if any voltage, current or frequency deviation results in a failure or in a bad operation of customer s equipment. So, for the better performance of the system it should be free from harmonics. For that purpose filters are used. There are so many types of filters such as active filter, passive filter, high pass filter, low pass filter etc. In that high-pass filters present disadvantages due to the resistance connected in parallel to the inductor, which increases the filter losses and reduces the filtering effectiveness at the tuned frequency. Conventionally, Passive LC filters were used to compensation of current harmonics. But, there are some limitations of using only passive filters such as fixed compensation, large size, bulkiness, occurring series and /or parallel resonance problem etc. To overcome these limitations combination of active and passive filters are used. In this paper a Series active with passive shunt filter is discussed. Series active with passive shunt filter topology is implemented with three phase PWM inverter connected in series with power lines and resonant LC passive filter are connected in parallel with power lines [1]. Power quality II. PROPOSED ALGORITHM Power quality means the physical characteristics of the electrical supply provided under normal operating conditions that do not disturb the customer s processes. 2.1 Power quality problems Power quality problem exists if any voltage, current or frequency deviation results in a failure or in a bad operation of customer s equipment.one more problem is harmonics. Harmonics are produced due to non linear load 2.2 Solution to power quality problems A flexible and versatile solution to power quality problems are offered by active power filters. There are also three types of active power filter such as series active power filter, shunt active power filter& hybrid active

power filter. In that the cost of shunt active power filter is relatively high and they are not preferable for a large scale system. The series active power filters works as a kind of harmonic isolator rather than a harmonic voltage generator. Series active power filters are used to eliminate voltage harmonics, to balance and regulate the terminal voltage of the load or line. Also, it has been used to reduce negative-sequence voltage [2].A new control algorithm is hybrid filter, which is a combination of an active series filter and passive shunt filter is quite popular because of the solid-state devices are used in the active series part can be of reduced size and cost. Also the major part of the hybrid filter is made of the passive shunt LC filters are used to eliminate lower order harmonics [2]. It has the capability of reducing voltage and current harmonics at a reasonable cost, and allows the use of active power filters in high-power applications at a relatively low cost. Moreover, compensation characteristics of passive filters can be significantly improved by connecting a series active power filter at its terminals, giving more flexibility to the compensation scheme and avoid possibility of the generation of series and /or parallel resonance [3]. 3.Series active filter and parallel passive filter Series active filter and parallel passive filter topology shown in fig. 3,An active power filter is implemented with a three-phase pulse width modulation (PWM) voltage-source inverter operating at fixed switching frequency. When this equipment is connected in series to the ac sourceimpedance it is possible to improve the compensation characteristicsof the passive filters in parallel connection.in order to allow current harmonic compensation, a parallel LC filter must be connected between the nonlinear loads and the series transformers. It is well known that series active power filters compensate current system distortion caused by non-linear loads by imposing a high impedance path to the current harmonics which forces the high frequency currents to flow through the LC passive filter connected in parallel to the load. The high impedance imposed by the series active power filter is created by generating a voltage of the same frequency that the current harmonic component that needs to be eliminated. Current harmonic and voltage unbalance compensation are achieved by generating the appropriate voltage waveforms with the three phase PWM voltage-source inverter (Fig.3). Active power filter is used with passive filters to improve the compensation characteristic of passive filter, also it avoid the possibility of generation of series or parallel resonance [4]. 4. Instantaneous reactive power theory- Vectorial The instantaneous reactive power theory is the most widely used as a control strategy for the active power filter. There are five formulationsof the instantaneous reactive power theory: p-q original theory, d-q transformation, modified or cross product formulation, p-q-r reference frame and vectorial theory.from the five formulations, only the vectorial one allows balanced and sinusoidal source currents after compensation. The main difference between vectorial power theory and rest of the formulations is that, vectorial formulation need not do any kindof coordinates translation. It uses the same power variables as the original theor[5]. Defining now the instantaneous real and imaginarypower in phase coordinates as follows: With

III. EXPERIMENT AND RESULT Fig.No.1 Three phase source before using filter Fig.No.2 Current Waveform before using filter

Fig. No. 3 Series active and shunt passive filter topology Fig.No.4 Current Waveform after using filter The system shown in Fig. 1 & Fig.3 has been simulated in the Matlab-Simulink platform. Each powerdevice has been modeled using the SimPowerSystem toolbox library. Fig.1 shows the system without using filter.fig.2 shows the current waveform without using filter. From distorted current waveform 5th& 7th order harmonics are found by using FFT analysis.fig.3 shows the series active and shunt passive filter topology, in that the PWM

voltage source inverter consists of an Insulated Gate Bipolar Transistor (IGBT) bridge. With 200V dc supply are connected. An LC filter has been included to eliminate the high frequency components at the output of the inverter. This set is connected to the power system by means of three single-phase transformers with a turn ratio of 1:1. Also passive LC filter are connected in parallel with load to eliminate the 5th& 7th order harmonics. IV.CONCLUSION Harmonic distortion is a main cause of power quality degradation. For elimination of harmonics active filters are used. Because there is are some disadvantages of passive filter. Improve the compensation characteristic of passive filter. It eliminates the problems of using only a shunt passive filter. Also it improve the behavior of passive filter.it allows the use of active power filter in high power application at relatively low cost.compensation characteristic of series active and shunt passive filter do not depend upon system impedance. It is achieve due to using vectorial power theory. REFERENCES [1] P. Salmerón and S. P. Litrán, Improvement of the electric power quality using series active andshunt passive filters, IEEE Trans. Power Del., vol.25, no. 2, Apr. 2010 [2] Bhim Singh, Kamal Al-Haddad, and Ambrish Chandra, A review of active filters for power quality improvement, IEEE Trans. Ind. Electronics, vol. 46, no. 5, Oct. 1999. [3] Darwin Rivas, Luis Morán, Juan W. Dixonand José R. Espinoza, Improving passive filter compensation performance with active techniques, IEEE Trans. Ind. Electronics,vol. 50, no. 1, Feb 2003. [4] Darwin Rivas, Luis Morán, Juan W. Dixonand José R. Espinoza, Improving passive filter compensation performance with active techniques, IEEE Trans. Ind. Electronics,vol. 50, no. 1, Feb 2003. [5] R.S.Herrera and P. Salmerón, Instantaneous reactive power theory: A comparative evaluation of different formulations, IEEE Trans. Power Del., vol. 22, no. 1, pp. 595 604, Jan. 2007..