XT Technical Documentation. The magnetostrictive level sensor. Edition: Version: 1 Article no.:

Similar documents
Process Automation. Sensors and Systems: Level Sensors Level Switches Overfill Prevention Pressure Sensors Temperature Sensors

OPERATION AND MAINTENANCE INSTRUCTIONS AVK UNDERGROUND FIRE HYDRANT

Level sensor Magnetostrictive, high-resolution measuring principle For sanitary applications, model FLM-H

Process Automation. Sensors and Systems: Level Sensors Level Switches Overfill Prevention Pressure Sensors Temperature Sensors

Quill Stop V2 Installation Guide 11/16/2014

Installation instructions Dec. 2002

Operating Instructions K-POWERgrip EWL Always on the safe site.

KMS-2 Exd Magnetostrictive Level Transmitter

GWR2 Installation guide: Guided Wave Radar

TABLE OF CONTENTS REQUIRED TOOLS

QL55 Series Luminescence Sensor

Installation instructions for encoders. RM3xxx RM7xxx RN3xxx RN7xxx /02 08/2015

1. TABLE OF CONTENT 2. ASSEMBLY ATEX. PENCOflex Installation Instructions & Service Manual

Fisher 667 Diaphragm Actuators Size 80 and 100

Resistance Thermometers Model Series TR7X0, Sheathed Design

Operating Manual Multi-Spot M22AL CD Stud Welding Machine

Float Switches with Permanent Magnet For Vertical Installation Model RSM

INSTRUCTION MANUAL (ATEX / IECEx)

XXXX e. X d.. X X X a

Level and Pressure. Product Information. Vibrating level switches

Torque Sensor Series 3000 and Series 4000

KENCO Loop Powered Magnetostrictive Transmitter. KMD SERIES Operation and Installation Manual. Table of Contents

B Operating Instructions V1.00/EN/

INSTALLATION INSTRUCTIONS Y-Connector Accessory (For Multi-Dual Arm Mounting Systems) Model: KSA-1011

Digital flow transmitter for continuous flow measurement

SAM. Model: STV-C65 LCD Mobile Visualized Stand Instruction Manual. Weight Capacity: 1251bs / 56.7kg Suits LCD Flat Panel Display: 42"-55" Page 20

INSTRUCTION MANUAL LEG PRESS OPTION OF ELITE GYM

IRIS \ IRIS-I QUICK SET-UP GUIDE STEP 1 INSTALL

assembly instructions

7. Operating instructions: EFL 300

ph or ORP Transmitter

670K9 SORtrax Level Transmitter

Senior Swing. Caution

LPU-2127 User Manual

Assembly instructions

REPAIR INSTRUCTIONS: CABLE

Quick setup guide VEGAPULS 62. Radar sensor for continuous level measurement of liquids ma/hart - four-wire. Document ID: 51873

Control CONNECTOR. (AI500 Rev H 14Nov17) Hawke International UK Office, Oxford Street West, Ashton-under-Lyne, Lancashire. OL7 0NA.

Resistance thermometer Model TR30, compact design

Installation & Operating Manual. iwap202

Caution: Installation and Operation Instructions. Locking Mechanism (if supplied) Set Screws Backed Out. Mounting Orientation

KMS-2 Exia Magnetostrictive Level Transmitter

FMG90 Series Electromagnetic Flow Meter

Mx-D15 Intelligent Valve Actuator

MODEL T28173/T28174 ROLLER TABLES INSTRUCTIONS

RHE12. Hazardous Area Coriolis Mass Flow Transmitter. Features. Applications. Benefits

Composition of kit SC3140 SC3110 SC3100 SC3140 SC3120. KF-SC31-R0_EN PAGE 2 of 15. max mm. max. 100 kg. 10 mm

Durst Laborator 138 S

Operator s Guide. Sequin Device. Version 1.3. Published by: ZSK Stickmaschinen GmbH - Dokumentation - D Krefeld-Gartenstadt

3.2.3 Rear Door Window and Quarter Window Carrier Assembly

JARVIS. Model Brisket Scissor EQUIPMENT... TABLE OF

KMS305W. ManuFlo Page 1 MANU ELECTRONICS PTY LTD Flow Measurement Products. Electromagnetic Wafer Flowmeters with S300 display

Series GWL - Radar Level Transmitter for Liquids

Components made of special materials. Floor Elements for Profile St Profile KH. Fastening Elements for Profile KH

Page Type Resolution (mm) min. max. Output

25000 Series Lo-T TM Butterfly Control Valve Instructions

Resistance thermometer Model TR30, compact design

Assembly Instructions 10 X 10 Aluminum Frame Building

Merloni Elettrodomestici. Technical Fitting Manual FRIDGE. Language Issue/Edition Page GB /

Brochure Includes: Set-up Instructions Operating Instructions Parts List Fundamentals of Drill Sharpening. Patent 3,952,459

Installation and Operational Instructions for primeflex -couplings Types 933._33.1 / 933._35.1 / 933._66.1 / 933._67.1

Operating instructions Electronic level sensor LK / / 2008

Z07- SWING GATE HOME AUTOMATION. zero Z07 - SWING GATE MOTOR SUPPLY V HOME AUTOMATION IT EN FR Z07.REV USER MANUAL AND CONFIGURATION PG1

Door window. Front door window, assembly overview

Eolis io. Notice Instructions Anleitung Handleiding Manuale. Brugsanvisning Käyttöopas Bruksanvisning Veiledning FR EN DE NL IT DA FI SV NO

S6 User s Manual USER S MANUAL ver. 1.0

Temposonics. Magnetostrictive Linear Position Sensors. TH SSI Data Sheet

Magnetic Inductive Flow Sensor induq

Resistance thermometer Model TR30, compact design

Converting the MGL SERVO to a MGL CAPSTAN SERVO.

Installation guide 971 SmartRadar LTi

PRODUCT MANUAL. Flush Mount 1 mm Cavity TS FM01 K. Training and Technology for Injection Molding. Temperature Sensor

The transducer component converts the measured signal and displays the actual value.

Hydraulic Clamp Carrier. Installation & Operation Manual

installation guide

ABM International, Inc. Navigator Assembly Manual

Fisher 667 Diaphragm Actuator Sizes 30/30i 76/76i and 87

Ricochet Alphasonic Level Transmitter Model LA15/20 Owner s Manual

FABA. Installation Instructions. Conductor Bar System. Publication #FABA-03 3/1/04 Part Number: Copyright 2004 Electromotive Systems

Javelin Integra Inspired Design Precision Engineering

Pharma Temperature Sensor G3/8"

D25122(K) D25123(K) D25124(K) D25213(K)

Assembly instructions

Insolroll Clutch Operated Shades Installation Instructions Installation Instructions

MSR/MSB Mechanical Setting Tool

WPS crew Doors Installation instructions

DS 400 DS 400. Intelligent Electronic Pressure Switch Completely in Stainless Steel. piezoresistive stainless steel sensor

OPERATING INSTRUCTIONS

FBX-PA-2AC. Third edition : April No

KMS101W. ManuFlo Page 1 MANU ELECTRONICS PTY LTD Flow Measurement Products. Electromagnetic Wafer Flowmeters with S100 display

TIDALFLUX 2300 F Technical Datasheet

HANDHOLE SEAT GRINDER

Level transmitters Series LTDR TDR guided radar level transmitter for liquids and solids

Operator Manual. Transmitters Series KAT-... Analog transmitters in 2-wire technique

Tube Facing Tool.

MANUAL SEALLESS STEEL STRAPPING TOOL MODEL A335

1 of 2 3/3/2017 4:49 PM

HD installation guide

INSTALLATION INSTRUCTIONS TRI-ROOF. energy for a better world

The Phoenix. Professional Quilting Frame. Copyright January 1, 2016 Jim M. Bagley, GraceWood, Inc (Reproduction Prohibited) Version 2.

Transcription:

Technical Documentation The magnetostrictive level sensor Edition: 11-2010 Version: 1 Article no.: 233571 Gems Sensors & Controls One Cowles Rd Plainville CT Telephone 800-378-1600

Page 2/19

Table of contents 1 Properties...4 2 Safety instructions...5 3 Design and mode of operation...6 4 Installation...8 4.1 Installation with screw-in unit...9 4.2 Installation with flange...10 4.3 Installation on the bypass...10 5 Electrical connection...12 6 User configuration...14 6.1 Measuring span at the level sensor...14 6.2 Current consumption in failure mode...16 7 Technical data...17 7.1 Sensor...17 7.2 Floats...19 Copyright: Reproduction and translation only with the written consent of GEMS Sensors & Controls. GEMS Sensors & Controls reserves the right to carry out product alterations without prior notice. Page 3/19

1 Properties The high-precision and robust level sensor is designed to provide continuous gauging of liquid media levels in tanks. The measuring principle used by the sensor exploits the physical effect of magnetostriction and is largely unaffected by temperature. Magnetostriction is particularly ideal where level measurements are required to be extremely accurate, e.g. in the chemical industry. The level sensor outputs measuring signals in the range 4 to 20 ma. Available in lengths of 8 to 19 it is compatible with a variety of tank dimensions. It also comes in the following versions: Version for installation on a bypass with magnetic float Version with flange Version with screw-in unit for infinitely variable positioning of the level sensor The Ex-approved version of the level sensor can be installed in potentially explosive atmospheres in which electrical equipment of category 1 (zone 0) or category 1/2 (zone 0/1) are required. Operating on the digital HART protocol, the HART level sensor is able to output the position of the first, second or both floats (refer to the HART documentation). Page 4/19

2 Safety instructions The purpose of the level sensor is to gauge liquid levels in tanks. Use the level sensor for this purpose only. The manufacturer accepts no liability for any form of damage resulting from improper use! The level sensor has been developed, manufactured and tested in accordance with stateof-the-art technology and with recognized safety rules and regulations. Nevertheless, hazards may arise from its use. For this reason, the following safety information must be observed: Do not change or modify the level sensor or add any equipment without the prior consent of the manufacturer. The installation, operation and maintenance of the level sensor must be carried out only by expert, authorized personnel. Specialized knowledge must be obtained by undergoing regular training. Operators, installers and service technicians must comply with all applicable safety regulations. This also applies to any local safety regulations and accident prevention regulations which are not stated in these operating instructions. The safety instructions in this manual are labelled as follows: Failure to observe these safety instructions will result in a risk of an accident or of damage to the level sensor. Useful information designed to ensure continued and correct operation of the level sensor or helpful advice to make your work easier. Page 5/19

3 Design and mode of operation The design of the level sensor has been illustrated using the version with screwin unit (see Figure 1). Inside sensor head (1) of the level sensor, concealed by cap (2), are the protected terminal clamps and configuration buttons. The electrical connection is established by an M16 x 1.5 screwed cable gland (3) or M12 plug-in connection at the top of the sensor head and by ground connector (4) at the bottom of the sensor head (see Installation and User configuration ). Probe tube (5) features a screw-in unit (6) (cutting ring or sealing gland coupling) for height adjustment capability or a flange (not shown) for fixed installation. Float (7) is the key component for continuous gauging of the product filling level or boundary layer and is held on the probe tube by a collar (8). The B version is supplied without a process connection and float. Figure 1: level sensor Page 6/19

The measuring principle illustrated in Figure 2 exploits the physical effect of magnetostriction and is largely unaffected by temperature. The probe tube contains a tensioned wire (1) made of magnetostrictive material. The sensor electronics transmit current pulses (2) through the wire, which generate a circular magnetic field (3). A magnet (4) contained in the float acts as the level sensor. Its magnetic field applies an axial magnetic field to the wire. The superposition of the two magnetic fields produces a torsional wave (5) at the float position, which then propagates along the wire in both directions. One wave propagates directly to the sensor head, the other propagates down to the bottom of the probe tube and is reflected. The time between the current pulse being transmitted and the wave arriving at the sensor head is measured. From these propagation times, it is possible to determine the current position of the float. Figure 2: operating principle of the level sensor Page 7/19

4 Installation This product should not be installed in a potentially explosive application. Also observe any local safety regulations and accident prevention regulations which are not stated in these operating instructions. This section describes how to install the level sensor. The procedures for each version are described separately (see Figure 3). Figure 3: versions Page 8/19

During installation, take great care not to bend the probe tube, and protect the float from shock and impact loads. Installing a level sensor in areas exposed to a powerful external magnetic field is not recommended because this could impair gauging. The level sensor can also be fitted into the tank from underneath. If the float is removed during installation, it must be slid back onto the probe tube afterwards with the TOP marking oriented towards the sensor head end, to enable correct measurements to be made. 4.1 Installation with screw-in unit 2 3 1 4 5 Figure 4: installation with screw-in unit Removal of the float is necessary only if the float does not fit through the installation opening in the tank. Otherwise, please proceed directly to steps 3, 6 and, if applicable, 7. Insert the level sensor into the tank (see Figure 4): (1) Loosen both set screws, remove collar (1) and remove float (2) from probe tube (3). (2) If necessary, slot screw-in unit (4) onto the probe tube. (3) Insert the level sensor into the tank, provide screw-in unit thread (4) with a suitable sealing material, screw it in and tighten. (4) Slide float (2) back onto probe tube (3). Page 9/19

For correct gauging, the float must be slid onto the probe tube with the TOP marking oriented towards the sensor head end, to enable correct measurements to be made. (5) Refit collar (1) to hold float (2) on the tube, align the set screws with the groove and tighten. (6) Adjust the height of the process connection and secure it in position by tightening union nut (5). (7) If applicable, tighten the lock screw (not shown) on union nut (5). In the case of installation with a cutting ring coupling, it is no longer possible to alter the position of the level sensor after the union nut has been tightened. In this event, it would be necessary to return the level sensor to the factory to have the probe tube replaced. 4.2 Installation with flange The probe tube is permanently welded to the flange, which means that the installation length cannot be altered. Secure the flange using the flange screws. If the float does not fit through the installation opening, refer to the related installation instructions in section 4.1. 4.3 Installation on the bypass The level sensor is installed on the bypass tube using suitable fasteners (nonmagnetic). To ensure reliable gauging, the probe tube must be fitted with no deformation on the outside. The distance between the probe and bypass tubes must be as small as possible. Only floats approved by GEMS Sensors & Contr0ls can be used. Page 10/19

-B Distance between probe tube and float center: max. distance from the SureSite float SureSite float Probe tube fitted without tension (undeformed) SureSite housing Magnet position Spacer bracket Probe fixture (nonmagnetic) min. 2.76 Measuring range min. 1.97 max. magnet position min. magnet position Probe length SECTION A-A Figure 5: installation with SureSite Page 11/19

5 Electrical connection It is essential that the correct minimum wire gauge be selected: the supply voltage at the level sensor must not fall below 8 V in the event of maximum current draw (21.5 ma). The sensor head and probe tube of Standard are made of stainless steel. The level sensor without Ex approval is installed in accordance with the following wiring diagram: Voltage supply Emax DC DC Line resistors Load Figure 6: wiring diagram for To connect the level sensor, see Figures 7: Unscrew sensor head cap (1) using an open-ended spanner. Loosen union nut (2) of screwed cable gland (3). Figure 7: connecting the level sensor Page 12/19

Feed the two conductor cable (4) into the union nut and retighten the union nut. The external diameter must be 0.2 to 0.4. Connect the two conductor cable to the screw terminals on the sensor head marked (+) and ( ). Observe the proper polarity. Configuration of reference points if necessary (see section 6.1) Screw the sensor head cap (1) back on. The ground connector on the underside of the sensor head can be used for grounding or equipotential bonding. Protect the sensor head against the ingress of water. An external cable diameter of 0.2 to 0.4 mm ensures reliable sealing of the cable entry. Make sure that the cable gland is screwed tight, and close the sensor head cap firmly. Page 13/19

6 User configuration Versions that support the HART protocol enable the adjustments described below to be carried out remotely without the sensor head having to be opened. 6.1 Measuring span at the level sensor To enable configuration of the 4 ma and 20 ma points at the level sensor, two buttons and an LED (light emitting diode) are provided near the terminals inside the sensor head. By default, the level sensor is set to maximum measuring span with 4 ma at the sensor base and 20 ma at the sensor head. The measuring span is configurable for adaptation to the tank concerned. However, a minimum clearance of 0.4 must be observed. If this minimum clearance is not observed, the display direction of the level sensor will be reversed automatically (ullage measurement). Through configuration, it is also possible to have the measured value output inverted: e.g. the level sensor can be set to maximum measuring span with 4 ma at the sensor head and 20 ma at the sensor base. Figure 8: configuring the measuring span Unscrew sensor head cap (1) using an open-ended spanner. Press and hold 4 ma button (2) or 20 ma button (3) for at least 3 seconds. The green LED begins to flash. Page 14/19

The level sensor is now in configuration mode. The current consumption of the level sensor is 12 ma. If no button is pressed again, the level sensor remains in configuration mode for 20 seconds before reverting to measuring mode and discarding any changes. In configuration mode, the 4 ma or 20 ma reference point, or both, can be modified in any order. To define a reference point: Move the float to the desired reference point briefly press (0.1 to 2 seconds) 4 ma button (2) to define a current consumption of 4 ma at this position briefly press (0.1 to 2 seconds) 20 ma button (3) to define a current consumption of 20 ma at this position When the 4 ma button is pressed, the LED goes out for 5 seconds. When the 20 ma button is pressed, the LED lights up permanently for 5 seconds. The sensor then remains in configuration mode for a further 15 seconds before storing the change and reverting to measuring mode. The new measuring range configuration is not stored until the level sensor reverts from adjustment mode to configuration mode automatically and the LED goes out. The new configuration is retained even if the level sensor is subsequently disconnected from the power supply. For dry settings to be possible in the case of bypass sensors, a magnetic system with spacer bracket will need to be obtained from the manufacturer of the bypass. Configuration can then be carried out even with the sensor removed. Page 15/19

6.2 Current consumption in failure mode If a malfunction is preventing the level sensor from recording a plausible float position, i.e. the measured level is incorrect, the sensor will enter failure mode after a short time. Failure mode signalling conforms to the NAMUR NE43 recommendation. The failure current is set by default to 21.5 ma but this value can also be set to 3.6 ma. To configure current consumption in failure mode (see Figure 8) Unscrew sensor head cap (1) using an open-ended spanner. Press and hold both the 4 ma (2) and 20 ma (3) simultaneously for at least 3 seconds. Green LED (4) Cal/Err flashes rapidly. The current consumption of the level sensor is 16 ma. After 5 seconds, the LED stops flashing and indicates the current consumption value for failure mode for 2.5 seconds: if the LED lights up permanently, I failure = 21.5 ma; if the LED goes out, I failure = 3.6 ma. If no button is pressed again, the level sensor remains in failure mode for a further 2.5 seconds before reverting to measuring mode and discarding the change. To set a current consumption of 3.6 ma during the dwell period (10 s) in failure mode briefly press 4 ma button (2) (0.1 to 2 seconds). To set a current consumption of 21.5 ma during the dwell period (10 s) in failure mode briefly press 20 ma button (3) (0.1 to 2 seconds). The new measuring range configuration is not stored until the level sensor reverts from adjustment mode to configuration mode automatically and the LED goes out. The new configuration is retained even if the level sensor is subsequently disconnected from the power supply. Screw sensor head cap (1) back on. If, during operation, the level sensor detects that the level cannot be output correctly due to an insufficient supply voltage, it enters failure mode and sets current consumption to 3.6 ma (regardless of any failure current settings). Page 16/19

7 Technical data 7.1 Sensor Electrical connection Two-line terminal 4 to 20 ma (3.8 to 20.5 ma) current consumption for level display 21.5 ma (3.6 ma) current consumption in failure mode Supply voltage: 8 to 30 V DC Process connection Screw-in unit with the option of infinitely variable height adjustment Standard G ½ (cutting ring coupling) 3 Ansi Flange 2 NPT screw-in unit Sensor head Height 4.53 Diameter 1.97 Index of protection IP 68 Material: stainless steel Cable diameter 0.2 to 0.4 Temperature 40 F to +185 F Probe tube Communication Length 8 to 19 (to order) Diameter.47 Material: 1.4571 standard (titanium, Hastelloy C, or other materials on request) Measuring range freely configurable (> 0.4 ) Normal temperature (NT) -40 F to +250 F High temperature (HT) -40 F to +450 F Ultra high temperature (HHT) -40 F to +840 F Low temperature (LT) -85 F to +250 F HART protocol (optional) Page 17/19

Accuracy Digital component Accuracy NT/LT Bypass digital component Accuracy Bypass HT/HHT digital component Accuracy Analog component Linearity better than ± 0.04 or ±0.025 %, better than ±0.001 % per K, Repetition accuracy better than 0.004 Resolution better than 0.002 Linearity better than ±0.04 mm or ±0.025 %, better than ±0.001 % per K, Repetition accuracy better than 0.004 Resolution better than 0.002 Linearity better than ±0.08 or ±0.1 %, better than ±0.001 % per K, Repetition accuracy better than 0.02 Resolution better than 0.002 Linearity better than ±0.01 % Temperature drift better than ±0.01 % per K Resolution better than 0.5 μa (16 bit) Page 18/19

7.2 Floats The float is a key component of the level sensor that must be matched to the medium in respect of density, pressure resistance and material durability. The following floats are exchangeable and are available to order separately. Other float types and materials are available on request. The density and magnet position of floats of the same type may vary slightly, in which case readjustment may be required. All floats are also suitable for use at a pressure of 1 bar (vacuum). Excerpt from available float range: min. density of Material medium [g/cm³] max. operating pressure [bar] at 68 F *) Shape 0.5 0.6 0.7 0.7 0.85 0.95 Titanium 1.4571 / 316 Ti 1.4571 / 316 Ti C276 1.4571 / 316 Ti 1.4571 / 316 Ti 20 20 16 10 20 50 Ball ø 50 Ball ø 52 Cylinder ø 43 Cylinder ø 46 Ball ø 43 Ball ø 43 *) above 120 F the maximum operating pressure decreases Pressure resistance is guaranteed for undamaged floats only. Even the most minor and invisible dents, which can occur if, for example, the float is dropped from a bench onto a stone floor, are sufficient to cause a significant deterioration in pressure resistance. Page 19/19