Harmonic Correction Unit NEMA 1 Enclosure

Similar documents
SECTION LOW VOLTAGE ACTIVE HARMONIC FILTER SYSTEM NEMA 1 ENCLOSED

DPM - Mesta Electronics, Inc. Low Voltage Active Harmonic Filters

APQline Active Harmonic Filters. N52 W13670 NORTHPARK DR. MENOMONEE FALLS, WI P. (262) F. (262)

TOSHIBA International Corp

POWER DELEGATOR SERIES 7200A POWER DISTRIBUTION UNIT WITH POWER CONDITIONING GENERAL SPECIFICATIONS

AF91 Adjustable Frequency Drives Series B

SECTION 16483D ADJUSTABLE FREQUENCY DRIVE - MICRODRIVE (MVX <10-HP)

Design Specifications Low Voltage Active Harmonic Filter

INPUT VOLTAGE STARTING MINIMUM NORMAL MAXIMUM MAXIMUM INPUT RANGE VOLTAFE VOLTAGE VOLTAGE VOLTAGE CURRENT

Liebert Datawave. GUIDE SPECIFICATIONS kva Magnetic Synthesizer Power Conditioning System 1.0 GENERAL

Utility Systems Technologies, Inc. Sag Fighter. Deep Voltage Sag Protection:

SECTION THREE-PHASE UNINTERRUPTIBLE POWER SYSTEM

Phoenix DX Clean Power (18 Pulse) AC Drive

150 C 30 F B D 8L 152H C 30 F BD 43 8L

1. All electrical switches and outlets used shall be equal to Hubbell heavy duty, specification grade or equivalent quality.

2.1 Performance Standards The UPS is designed with the applicable sections of UL, CUL, and ISO The UPS has UL and CUL listing.

GUIDE SPECIFICATIONS 40-80kVA, kVA and kVA Scalable Three-Phase Uninterruptible Power System 1.0 GENERAL

These true on-line inverters incorporate pulse width modulation (PWM) control combined with high frequency igbt power transistors.

Liebert Datawave GUIDE SPECIFICATIONS kva Magnetic Synthesizer Power Conditioning System

SECTIONS , (15040, 15767, 15950, 16269) Guide Specification for VARIABLE SPEED DRIVES with Optional Bypass

MITSUBISHI ELECTRIC 2033A DDC SERIES SPECIFICATIONS

S11 Adjustable Speed Drive Engineering Specification

Power IT LV Active Filters PQFA - PQFL - PQFT

DSA150 Series. xxx Series. 150 Watts. AC-DC Power Supplies. Models & Ratings. Mechanical Details 3.92 (99.8) 2.18 (55.5) 4.92 (125.

ReactiVar AT6000/AT7000 transient-free reactive compensation system

HARMONICS THE BASICS H A R M O N I C M I T I G A T I O N A N D D I S P L A C E M E N T P O W E R F A C T O R C O R R E C T I O N

LCL Series. SIngle Output Industrial Supplies. High Efficiency. Low Cost. 150 W Convection Cooled. 300 W & 500 W with Internal Fans

Low Voltage Power Factor Correction Equipment Specifications Automatic, Automatic Detuned, Automatic Tuned

Data Sheet. RISH Master Record %THD

High Frequency Sinewave Guardian TM Filter

High Frequency SineWave Guardian TM Filter

BED INTERCONNECTION TECHNICAL REQUIREMENTS

Power Processor - Series 700F 10KVA to 150KVA

STATIC UNINTERRUPTIBLE POWER SYSTEM Revised 4/30/ Electrical Systems

Power Meter PQM (EnerSure Enkapsis) Guide Form Specification PART 1: GENERAL

Power IT LV Active Filters PQFI PQFM PQFK. The ABB comprehensive solution for active filtering of harmonics

DP&L s Technical Requirements for Interconnection and Parallel Operation of Distributed Generation

Installation and Operating Instructions

RISH EM 3490 DS Dual Source Energy Meter (With All Display Parameters) RISH EM 3490 DS. Application : Product Features:

PowerFlex 400 Submittal

DSR120 Series. xxx Series. 120 Watts. AC-DC Power Supplies. Models & Ratings. Mechanical Details

Michigan State University Construction Standards SWITCHBOARDS, PANELBOARDS, AND CONTROL CENTERS PAGE

PowerGard Series C 18-Pulse Enclosed Drive Controllers

1. Institute of Electrical and Electronic Engineers (IEEE) a. Standard , IEEE Guide for Harmonic Content and Control.

Digital Multifunction Instrument - Rish Master 3440

RI-F200 Series. Single and Three Phase Multifunction Energy Meter. Telephone : +44 (0) Displayed Parameters

SECTION LOW-VOLTAGE ELECT. DIST. DESIGN AND CONSTRUCTION STANDARDS _ February 2015 PART I: GENERAL

Medical Safety Approvals (-M versions) Industrial Heavy Duty Terminals. Output Power up to 1500 W. High Power Density - 18W/in 3

NEWPCC VARIABLE FREQUENCY DRIVES Section LAB RENOVATION BID OPPORTUNITY NO PAGE 1 OF SCOPE

Ambient Conditions Storage Conditions Installation Minimum Clearances and Air Flow...2 3

NLP65 SERIES 75 Watt Open Frame Power Supply Measures: 5.00 x 3.00 x 1.26

Original operating instructions Fail-safe inductive sensor GM504S / / 2010

Protective Relays Digitrip 3000

AccuSine PCS Active Harmonic Filter. Cruise through rough waves in your electrical network

SECTION AUTOMATIC TRANSFER SWITCH

Design Characteristics. FlexDrive II. Series

Title: YALE OFFICE OF FACILITIES PROCEDURE MANUAL Chapter: 01 - Yale Design Standard Division: Electrical Standards

CROSS Chassis from 160 A to 450 A

ACH550 HVAC Drive Submittal

Variable Frequency Drive Packages with Harmonic Mitigation. Low Harmonic Drive Packages Engineered by Rockwell Automation

ECC100 Series. -40 ºC to +75 ºC Operation. 100 W - Baseplate Cooled. High Efficiency Resonant Topology. Screw Terminals Available.

Metering Devices, Protective Relays, Software and Connectivity

Type AHF Active Harmonic Filter

Table G. INPUT/OUTPUT Ratings & External Wiring Requirements for the /160 Rating 50/60 Hz. kva kw VOLTS VOLTS / /220

Output Voltage* (nom.)(adjustable)

The power to work. Power conditioning products. Harmonic correction unit Sag ride-through power conditioner

PowerFlex 400 AC Drive Guide Specification

NGS INVERTER REPLACEMENT SCOPE OF WORK & SPECIFICATIONS

TECHNICAL DATA SHEET B9600FXS kva

Installation and Operating Instructions. Power IT Power Factor Controller RVC

INTERIM ARRANGEMENTS FOR GRID TIED DISTRIBUTED ENERGY RESOURCES. Technical Requirements for Grid-Tied DERs

SC1000 DGPS USCG Dual Transmitter

PREFACE ********************************************************** IT IS NOT INTENDED THAT THESE STANDARDS BE COPIED AND USED AS A SPECIFICATION!

SAMSUNG ELECTRO-MECHANICS CO., LTD

AccuSine PCS Active Harmonic Filter. Cruising through rough waves in your electrical network

Multimeter 500CVD21 RTU500 series

Protection components

Active Harmonic Filter

PRODUCT SPECIFICATION FOR A 15 AND 75 kva, THREE PHASE MODULAR POWER DISTRIBUTION SYSTEM WITH REGULATION AND CONDITIONING (Varian)

UNINTERRUPTIBLE POWER SUPPLY SPECIFICATIONS MODEL 1100B SERIES

Manual Overview...1 2

VF-nC1 Adjustable Speed Drive Engineering Specification

G8000MM Series IGBT. 100 to 750 KVA UPS UNINTERRUPTIBLE POWER SYSTEMS. 94% Efficiency. Input PF >0.98 DESIGN

Addendum to Instructions for Installation, Operation and Maintenance of Digitrip 3000 Protective Relays

Metal Case Power Supplies

ISO Rules Part 500 Facilities Division 502 Technical Requirements Section Wind Aggregated Generating Facilities Technical Requirements

Electromagnetic Harmonic Filters Technical Guide

SECTION 16496G CONTACTOR BASED AUTOMATIC TRANSFER SWITCHES LOW VOLTAGE

SPECIFICATION SWITCHING POWER SUPPLY SINGLE POWER 250W BEST POWER SOLUTIONS, INC. 9F, NO.196-7, SEC.3, TA-TUNG RD SHI CHIH, TAIPEI, TAIWAN, R.O.C.

SUGGESTED SPECIFICATION DUAL OPERATOR OPEN TRANSITION AUTOMATIC TRANSFER SWITCH WITH RPTCS MICROPROCESSOR CONTROL

SPECIFICATION SWITCHING POWER SUPPLY BPS-300SP/2U 6-OUTPUT WITH ACTIVE PFC FUNCTION SINGLE POWER 300W BEST POWER SOLUTIONS, INC.

UNINTERRUPTIBLE POWER SUPPLY SINGLE MODULE SYSTEM SPECIFICATIONS MODEL 9800AE

ATV12HU22M2. Main. Range of product Altivar 12. Component name Quantity per set Set of 1. Built-in fan. Motor power hp Communication port protocol

Harmonics, its Mitigation & Result of Case study of Spinning Mill

This Chapter contains:

ALPHA 50 MULTIFUNCTION METER (ALPHA SERIES)

ECL03B1AAA 20A 120V Lighting Contactor

UNITY/I TM. Installation Manual. UT3K, UT4K, UT5K and UT8K. Single-Phase Uninterruptible Power Systems

Altivar 28 drive Altivar 28 enclosed drive

IC800SSD Hardware Manual Pub 348R5. for models. A publication of

Transcription:

ffective: June 2001 Page 1 New Information Harmonic orrection Unit ontents Description Page Harmonic orrection Unit Specifications.......... 2 Sizing and Selection............................................. 3 Installation and Power ircuit Diagrams............................. 3 HU050 Layout Dimensions....................................... 4 HU100 Layout Dimensions....................................... 5 HU300 Layout Dimensions....................................... 6 Harmonic orrection Units For more information contact utler-hammer at: www.ch.cutler-hammer.com

Page 2 ffective: June 2001 Harmonic orrection Unit Harmonic orrection Unit Specifications The harmonic correction unit is an integrated power electronic product which senses and injects current to cancel harmonics and provide reactive power. Harmonic cancellation is installed directly on the A line in parallel to harmonic producing loads such as A drives. Table 1. Harmonic orrection Unit Specifications Safety Agency lectrical nvironment UL: SA: Voltage: Frequency: Ambient Temperature: Storage Temperature: Relative Humidity: Altitude: Vibration: Pending Approved 208 480V +/- 10% 50/60 Hz, +/- 3 Hz 0º to 40º nclosed -40º to 65º to 95% Non-condensing to 2000 Meters Seismic Zone 4 Packaging Standard nclosure: NMA 1 Wall Mount (50/100A) Floor Standing (300A) Protection Input Fuses Surge Withstand apacity: Logic Ride-Through: Output apacity: 600V, 200,000 AI, lass T I 62.41-1991 30 Seconds Upon Full Loss of Input Voltage Self-limited to 100% Rated Performance orrective apability: <5% TDD and Near Unity Displacement Power Factor Information/ontrol Display: Operators: Indicator LD: Information Diagnostics: Output ontacts: ommunications: Requires series input line reactor or D bus choke in each A drive for optimum performance. 2 Line, 20 haracter/line Alphanumeric Run, Stop, Setup, nter Up and Down Scroll Run (green) nglish Power On, Run, Fault, at Maximum apacity RS-485 Port For more information contact utler-hammer at: www.ch.cutler-hammer.com

Harmonic orrection Unit Technical Data ffective: June 2001 Page 3 Sizing and Selection Table 2. Harmonic ontrol Units Ratings NMA 1 nclosed Model Voltage Frequency Total urrent Amperes (rms) Watt Losses (kw) xterior Dimensions in Inches (H x W x D) Unit Weight Lbs. nclosure Type Disconnect HU050D5N1 208 480 50/60 50 1.8 51.8 x 20.7 x 18.5 250 Wall-Mount/NMA 1 HU100D5N1 208 480 50/60 100 3.0 68.7 x 20.7 x 18.5 350 Wall-Mount/NMA 1 HU300D5N1 208 480 50/60 300 8.0 74.9 x 32.2 x 19.5 775 Free-Standing/NMA 1 X Table 3. urrent transformer Ratings Dimensions in Inches (mm) Model Type A Line urrent Rating Type T500S 500 Split 2.25 T1000S 1000 Split 4.65 T3000S 3000 Split 6.50 T5000S 5000 Split 7.50 Internal Diameter Table 4. Digital Interface Specifications Model DIMBL03 7.6 DIMBL05 12.7 DIMBL10 25.4 able Length Feet Note: urrent transformers are rated for 400 Hz. Two current transformers are required for 3-phase loads. Three current transformers are required when single-phase loads are present. Load(s) Source XFMR Typical T Placement A Lines Fuse Fuse Fuse Line Inductor Pre-charge ontactor Inductor S1 S3 S5 + Alternate T Placement HU Filter Board S2 S4 S6 Figure 1. Installation Diagram Figure 2. Power ircuit Diagram For more information contact utler-hammer at: www.ch.cutler-hammer.com

Page 4 ffective: June 2001 Harmonic orrection Unit Drawings HU050 Layout Dimensions The HU050 series offers 50 amperes of corrective current in a convenient package. The enclosed model comes standard with a digital interface panel for control diagnostics and programming. Input fuses are included. The enclosed unit includes a removable panel for bottom conduit entry. 4.57 (116.1) 8.73 (221.6) 16.67 (423.5) 16.06 (408.0) 4.69 (119.2) 6.00 (152.4) 7.46 (189.5) 50.33 (1278.3) 48.00 (1219.2) onduit Plate 20.67 (525.1) 6.25 (158.8).53 (13.4) 7.70 (195.7) 3.17 (80.6) 5.25 (133.4) 2.17 (55.2) 9.98 (253.6) 1.63 (41.3).85 (21.5) 4.63 (117.6) 2.75 (69.9) 6.25 (158.8) Figure 3. HU050 50 Amperes Dimensions in Inches (mm) For more information contact utler-hammer at: www.ch.cutler-hammer.com

Harmonic orrection Unit Technical Data ffective: June 2001 Page 5 HU100 Layout Dimensions The HU100 series offers 100 amperes of corrective current in a wall-mounted NMA 1 enclosure. The enclosed model comes standard with a digital interface module for control, diagnostics and programming. Input fuses are included. The enclosed unit includes a removable panel for bottom conduit entry. 9.79 (248.7) 4.62 (117.4) 20.67 (525.1) 16.67 (423.5) 8.81 (223.8) 19.94 (506.5) 67.19 (1706.5) 3.75 (95.3) 5.00 (127.0) 65.23 (1656.9) 16.67 (423.5) onduit Plate 5.25 (133.4) 6.25 (158.8) 2.55 (64.7).51 (12.9) 3.05 (77.6) 7.70 (195.7) 1.38 (34.9) 1.10 (27.9) 5.25 (133.4) 11.08 (281.5) 6.25 (158.8) 2.38 (60.3) Figure 4. HU100 100 Amperes Dimensions in Inches (mm) For more information contact utler-hammer at: www.ch.cutler-hammer.com

Page 6 ffective: June 2001 Harmonic orrection Unit HU300 Layout Dimensions The HU300 series offers 300 amperes of corrective current for large capacity applications. It is available in a floor-standing NMA 1 enclosure (including a door-interlocking disconnect). The enclosed model comes standard with digital interface module for control, diagnostics and programming. Input fuses are included. The enclosed unit includes a removable panel for top conduit entry. 6.50 (165.1) 23.10 (586.7) 76.2 (3.00) onduit Plate 7.00 (177.8) 5.02 (127.4) 31.50 (800.0) 8.00 (203.2) 22.08 (560.7) 19.23 (488.5) 13.62 (345.9) 17.38 (441.6) 5.00 (127.0) 3.63 (92.1) 70.95 (1802.2) 74.71 (1897.6) 12.22 (310.3) 2.72 (69.1) 13.98 (355.2) 4.32 (109.8).55 TYP (14.0) 27.13 (689.0).55 TYP (14.0) 15.31 (389.0) Figure 5. HU300 300 Amperes Dimensions in Inches (mm) For more information contact utler-hammer at: www.ch.cutler-hammer.com

Harmonic orrection Unit Technical Data ffective: June 2001 Page 7 Harmonic orrection Unit () Guide Specification To reduce current harmonics and correct power factor on low voltage electrical systems. 1.0 General 1.1 Summary This specification defines the electrical and mechanical characteristics and requirements for harmonic correction units in order to meet 5% total harmonic current distortion [THD(I)], 5% total demand distortion [TDD], and <5% total harmonic voltage distortion [THD(V)] levels at selected points within the electrical system. 1.2 Standards The harmonic correction unit shall be designed in accordance with the applicable sections of the following documents. Where a conflict arises between these documents and statements made herein, the statements made in this specification shall govern. ANSI I standard 62.41-1991 [surge withstand capacity] SA 22.2, No. 14 and 66 [SA requirements for power electronics] F Part 15, Sub Part J, lass A [RFI/MI emission standards] ANSI I standard 519-1992 [Harmonic limits] UL 508 [UL requirements for power conversion equipment] N 50178 [uropean Union requirements for power assemblies] N 60439 [uropean Union requirements for low voltage assemblies] N 55011 [uropean Union requirements for electromagnetic compatibility] I 529, IP20 (NMA 1) [type of enclosure] IBO Building ode, Section 16, Seismic Zone 4 [vibration standard] The products shall include third party approvals by UL or SA. 1.3 System Description 1.3.1 System Description A. Voltage: 480V, 3-phase, 3-wire, plus ground. B. Output Load apacity: Rated capacity shall be the specified current capacity at the voltage required as indicated within this specification and shown on the respective electrical drawings included within this document.. Field Installable apacity Upgrade: Additional power correction capacity shall be added by installing additional units in parallel to previously installed power correction systems. A maximum of 3 units shall be installed in parallel per set of current transformers. D. urrent Transformers: 1. Split core type current transformers shall be installed as defined herein and shown in the electrical drawings contained in these documents. 2. Two current transformers per power correction system location are required and mounted on phases A and B. 3. A third current transformer is required if single- or 3-phase line to neutral connected loads are present downstream from the location of the Ts. 4. urrent ratings of the current transformers shall be according to full load current of the circuit on which installed. 5. urrent transformers rated for 400 Hz shall be used. 1.3.2 Modes of Operation A. The harmonic correction unit shall be designed to electronically inject harmonic current to cancel load produced harmonic current such that the upstream power harmonic current and voltage are reduced to below 5% TDD and 5% THD(V) as defined by ANSI I standard 519-1992 for load demand and voltage distortion limits. TDD as used herein refers to the total load demand of the applied circuit. The applied circuit may be a single nonlinear load, an entire distribution bus load, or the facility load at the point-of-common coupling (P). B. Reactive current compensation (aka displacement power factor correction) shall be activated via a digital keypad/display mounted on the door of the enclosure. When reactive current compensation is activated, the harmonic correction unit shall first perform harmonic current correction and then use the remaining capacity to inject reactive current compensation to the specified level herein defined. 1.3.3 Performance Requirements A. Input Power: 1. Voltage: 480V, 3-phase, plus ground 2. Voltage Tolerance: +/- 10% of nominal 3. Frequency: 60 Hz, +/- 5% 4. urrent Limit: 100% of rating 5. Surge Withstand apability: ANSI/I standard 62.41-1991 without damage 6. Input Fuses: Rated at 200,000 AI (amperes interrupting capacity), lass T B. Output Performance 1. Performance of the harmonic correction unit shall be independent of the impedance of the power source. All performance levels shall be attained whether on the A lines or backup generator or output of UPS. 2. Harmonic orrection: a. Limit 2nd through 50th order harmonic current to <5% TDD as defined in ANSI/I standard 519-1992 at each installed location. Harmonic levels for individual harmonic orders shall comply with respective levels established in ANSI/I standard 519-1992. b. Limit the THD(V) added to the electrical system immediately upstream of the power correction system location(s) to less than or equal to 5% as defined in ANSI/I standard 519-1992. The power correction system shall not correct for utility supplied voltage distortion levels. 3. Reactive urrent ompensation: to.90 lagging displacement power factor. Leading power factor is not permitted. For more information contact utler-hammer at: www.ch.cutler-hammer.com

Page 8 ffective: June 2001 Harmonic orrection Unit. urrent transformers 1. urrent transformers shall be rated for the total rated rms current of the total load at each installed location. 2. Two current transformers, mounted on phases A and B, are to be installed per location. 3. A third current transformer is required if single- or 3-phase line to neutral connected loads are present downstream from the location of the Ts. 4. ach current transformer shall have a current output of 5 amperes. urrent capacity of each current transformer shall be 5000, 3000, 1000 or 500, as required for the electrical system where installed. No other ratings are acceptable. 5. ach current transformer shall be rated for 400 Hz. 1.4 nvironmental onditions The harmonic correction unit shall be able to withstand the following environmental conditions without damage or degradation of operating characteristics or life. 1. Operating Ambient Temperature: 0º (32ºF) to 40º (104ºF). 2. Storage Temperature: -40º (-40ºF) to 65º (149ºF). 3. Relative Humidity: 0 to 95%, non-condensing. 4. Altitude: Operating to 2000 meters (6,500 feet). Derated for higher elevations. 5. Audible Noise: Generated by power correction system not to exceed 65 dba measured 1 meter (3 feet) from surface of unit. 6. Vibration: Seismic Zone 4. 2.0 Product 2.1 nclosure A. ach harmonic correction unit shall be provided in a NMA Type 1 enclosure. B. All units shall meet Seismic Zone 4 vibration requirements when installed according to installation requirements defined herein.. Freestanding units shall include a door-interlocked disconnect that provides power interruption when the door is opened. Disconnect shall be lockable in the power-off position. Wall mount units shall be disconnected from the power source by a disconnect device or circuit breaker contained in the power distribution center. D. NMA 1 nclosed units shall include lifting provisions by forklift truck and lifting lugs.. All units shall include 200,000 AI rated fuses with lass T actuation. F. All units shall be provided with a grounding lug. Grounding by the contractor is to be performed according to local and national standards. G. The paint shall be ASA61 2.2 Operator ontrols and Interface A. All units shall include a digital interface model (DIM) that includes an alphanumeric display consisting of 2-lines with 20 characters per line. All information shall be in nglish. Operators include run, stop, setup, enter, and up/down scroll. B. The display shall provide operating data while functioning. Standard operating parameters available for display are A line voltage, total rms load current, harmonic current of load, reactive current of load, output harmonic and reactive current of power correction system.. When the output of the power correction unit is at full rated capacity, the display shall indicate at-maximum capacity and actuate an atmaximum capacity relay. D. All fault conditions shall be displayed as they occur. Diagnostic information shall be provided in nglish and clearly indicate the nature of the fault.. The run pushbutton shall include a green LD. LD shall be lighted when unit is running. F. ontacts shall be provided for operator information for poweron, run, fault and at-maximum capacity. ach contact shall be rated for 1 ampere at 120/240 volts. One form contact shall be provided for each relay. G. An RS485 serial communication port shall be provided for remote control and diagnostic information. 2.3 Design A. ach unit of the harmonic correction units shall meet F Part 15, Sub Part J, lass A requirements for both radiated and conducted MI. B. ach unit shall be designed with a current limiting function to protect the semiconductors. When this level is attained, a message shall be displayed indicating the output capacity is at-maximum capacity and actuate the at-maximum capacity relay. Operation shall continue indefinitely at this level without tripoff or destruction of the power correction unit.. Two distinct levels of faults shall be employed. Non-critical level faults will provide automatic restart and a return to normal operation upon automatic fault clearance. ritical level faults stop the function of the unit and await operator action. 1. Faults such as A line overvoltage, A line undervoltage, A line power loss, and A line phase imbalance shall be automatically restarted. Upon removal of these fault conditions, the power correction system shall restart without user action. Automatic restart will not occur if 5 faults have occurred in less than 5 minutes. During the fault condition, except line loss, the display shall state the type of fault and indicate that automatic restart will occur. The run relay and run LD shall be disabled. The fault relay shall not be enabled unless time out occurs. Upon A line loss, the power-on relay shall be disabled and no display shall be provided. 2. All other types of faults shall be considered critical and stop the power correction system. The display shall indicate the fault condition and stop. The run LD and relay shall be disabled and the fault relay enabled. User shall be required to initiate a power reset (turn power off and on) to restart the power correction system. 2001 aton orporation, All Rights Reserved TD03A03T Printed in U.S.A. / Z01841