Modeling and Validation of an Unbalanced LV Network Using Smart Meter and SCADA Inputs

Similar documents
Voltage Unbalance Reduction in Low Voltage Feeders by Dynamic Switching of Residential Customers among Three Phases

INVESTIGATING THE BENEFITS OF MESHING REAL UK LV NETWORKS

Voltage Level Management of Low Voltage Radial Distribution Networks with High Penetration of Rooftop PV Systems

Notes 1: Introduction to Distribution Systems

MODELING THE EFFECTIVENESS OF POWER ELECTRONICS BASED VOLTAGE REGULATORS ON DISTRIBUTION VOLTAGE DISTURBANCES

Modelling and Analysis of Practical Options to Improve the Hosting Capacity of Low Voltage Networks for Embedded Photo-Voltaic Generation

Harmonic Planning Levels for Australian Distribution Systems

A Practical Application of Low Voltage DC Distribution Network Within Buildings

ADVANCEMENT IN STATE GRASPING METHOD OF MV DISTRIBUTION NETWORK FOR SHORT-TERM AND MID-TERM PLANNING

Embedded Generation Connection Application Form

Harmonic impact of photovoltaic inverter systems on low and medium voltage distribution systems

Improving Power Quality in Low Voltage Networks Containing Distributed Energy Resources

ELF ELECTRIC AND MAGNETIC FIELDS MEASUREMENTS IN GREECE

UNBALANCED CURRENT BASED TARRIF

Network Monitoring and Visibility Summary

Determination of Smart Inverter Power Factor Control Settings for Distributed Energy Resources

Company Directive POLICY DOCUMENT: SD4/7. Relating to 11kV and 6.6kV System Design

HV Substation Earthing Design for Mines

Mapping the capacity and performance of the arterial road network in Adelaide

Maximum Allowable PV Penetration by Feeder Reconfiguration Considering Harmonic Distortion Limits

SAFETY ISSUES RELATED TO THE CONNECTION OF MV AND HV GROUNDING

Embedded Generation Connection Application Form

Accurate determination of distribution network losses

VOLTAGE CONTROL IN MEDIUM VOLTAGE LINES WITH HIGH PENETRATION OF DISTRIBUTED GENERATION

Assessing network compliance for power quality performance

NEW APPROACH TO REGULATE LOW VOLTAGE DISTRIBUTION NETWORK

Company Directive STANDARD TECHNIQUE: SD7F/2. Determination of Short Circuit Duty for Switchgear on the WPD Distribution System

EDS FAULT LEVELS

Table of Contents. Introduction... 1

Aggregated Rooftop PV Sizing in Distribution Feeder Considering Harmonic Distortion Limit

Understanding LV Network Voltage Distribution- UK Smart Grid Demonstration Experience

Distribution Network Capacitor Resonance A Case Study

VOLTAGE UNBALANCE DUE TO SINGLE-PHASE PHOTOVOLTAIC INVERTERS

When surge arres t ers are installed close to a power transformer, overvoltage TRANSFORMER IN GRID ABSTRACT KEYWORDS

VOLTAGE MANAGEMENT BY THE APPORTIONMENT OF TOTAL VOLTAGE DROP IN THE PLANNING AND OPERATION OF COMBINED MEDIUM AND LOW VOLTAGE DISTRIBUTION SYSTEMS

Embedded Generation Connection Application Form

Techniques for the Control of Steady State Voltage in MV and LV Networks

SOURCES OF ERROR IN UNBALANCE MEASUREMENTS. V.J. Gosbell, H.M.S.C. Herath, B.S.P. Perera, D.A. Robinson

Energex Smart Network Trials

The Effect of PV on Transformer Ageing: University of Queensland s Experience

VOLTAGE QUALITY PROVISION IN LOW VOLTAGE NETWORKS WITH HIGH PENETRATION OF RENEWABLE PRODUCTION

Coordinated voltage control scheme for Flemish LV distribution grids utilizing OLTC transformers and D-STATCOM s

Harmonics Issues that Limit Solar Photovoltaic Generation on Distribution Circuits

POWER QUALITY IMPACTS AND MITIGATION OF DISTRIBUTED SOLAR POWER

Voltage Control of Distribution Networks with Distributed Generation using Reactive Power Compensation

DC utilization of existing LVAC distribution cables

Power Quality of a Battery Energy Storage System (BESS) with Nonlinear Load Gabriel Haines

Aspects of Network Harmonic Impedance Modelling in High Voltage Distribution Networks

Network Equilibrium Balancing Act Conference Thursday 8th September 2016

THE IMPACT OF NETWORK SPLITTING ON FAULT LEVELS AND OTHER PERFORMANCE MEASURES

Distributed generation on 11kV voltage constrained feeders

Application of GridEye for Grid Analytics

INCREASING NETWORK CAPACITY BY OPTIMISING VOLTAGE REGULATION ON MEDIUM AND LOW VOLTAGE FEEDERS

D-UPFC Application as the Series Power Device in the Massive Roof-top PVs and Domestic Loads

Optimization of power transformers based on operative service conditions for improved performance

Click to edit Master title style. Click to edit Master title style. Northern Powergrid Asset Recording Guidance

Distribution Network Voltage Unbalance Control under High Penetration of Single-Phase Photovoltaic Microgeneration

APPENDIX A MATLAB CODE FOR CALCULATION OF MOTOR TORQUE

Some European experiences with renewable installations

POWER QUALITY AND ENERGY EFFICIENCY IN LOW VOLTAGE ELECTRICAL POWER SYSTEM OF THE TECHNICAL UNIVERSITY OF GABROVO

Update on the Australian National Network PQ Survey

Analysis of Voltage Rise Effect on Distribution Network with Distributed Generation

ADVANCED VECTOR SHIFT ALGORITHM FOR ISLANDING DETECTION

HARDWARE BASED CHARACTERISATION OF LV INVERTER FAULT RESPONSE

Dynamic Grid Edge Control

SOLID-STATE TRANSFORMERS

ISLANDED OPERATION OF MODULAR GRIDS

Impact Assessment Generator Form

Calculating AC Line Voltage Rise for IQ-Series Micros with Q Cable

Requirements for Offshore Grid Connections. in the. Grid of TenneT TSO GmbH

The Advantages and Application of Three Winding Transformers

MV ELECTRICAL TRANSMISSION DESIGN AND CONSTRUCTION STANDARD. PART 1: GENERAL 1.01 Transformer

Power quality report. A Manufacturing Plant

FRONIUS SMART METER APPLICATION GUIDE

Effectiveness of Reactive Power Capability of Photo Voltaic Inverters to Maintain Voltage Profile in a Residential Distribution Feeder

Network state estimation and optimal sensor placement

Improving High Voltage Power System Performance. Using Arc Suppression Coils

Harmonic filter design for IEC compliance

Optimal sizing of battery energy storage system in microgrid system considering load shedding scheme

Accuracy of Low Voltage Electricity Distribution Network Modelling

Power Quality Evaluation of Electrical Distribution Networks

The effect of data aggregation interval on voltage results

Publishing date: 23/07/2015 Document title: We appreciate your feedback. Share this document

The Impact of Connecting Distributed Generation to the Distribution System E. V. Mgaya, Z. Müller

J Project Methods. V (%) Network with high generation and low load. Network with low generation and high load

ASSESSMENT OF HARMONIC DISTORTION LEVELS IN LV NETWORKS WITH INCREASING PENETRATION LEVELS OF INVERTER CONNECTED EMBEDDED GENERATION

Sizing the neutral wire cross-section and minimization of neutral currents using microgeneration in low voltage networks

Power Quality Report. A Manufacturing Plant

Future. Ready. SM. Using Meters as Distribution Sensors for Capacitor Bank Monitoring. White Paper

Company Directive STANDARD TECHNIQUE: SD5R/2. Earth Fault Loop Impedances and Phase to Neutral Loop Impedances at LV Installations

VOLTAGE CONTROL FOR DISTRIBUTION NETWORKS and the 230V/400V Standard. Alex Baitch FIEAust, CPEng Manager Network Capability, Integral Energy

Master of Science thesis

Case Study Survey of Harmonic Pollution Generated by Railway Systems and Filtering Solutions

Low Voltage System State Estimation Using Smart Meters

Investigation of Earth Potential Rise on a typical single phase HV network

OPEN-PHASE DETECTION TECHNIQUES FOR CRITICAL STANDBY SUPPLIES

R10. III B.Tech. II Semester Supplementary Examinations, January POWER SYSTEM ANALYSIS (Electrical and Electronics Engineering) Time: 3 Hours

Electric Program Investment Charge (EPIC)

Landis+Gyr S650 Smart Grid Terminal. a smart grid innovation

My Electric Avenue (I 2 EV) Evaluation of Power Line Carrier communication for direct control of electric vehicle charging

Transcription:

Modeling and Validation of an Unbalanced LV Network Using Smart Meter and SCADA Inputs Derek C. Jayasuriya, Max Rankin, Terry Jones SP AusNet Melbourne, Australia Julian de Hoog, Doreen Thomas, Iven Mareels Electrical and Electronic Engineering & Mechanical Engineering University of Melbourne Abstract As new technologies such as Photovoltaics (PVs), Embedded Generators (EGs) and Electric Vehicles (EVs) penetrate Low Voltage (LV) distribution networks, the need to understand the constraints and real time system state of LV networks becomes essential for smart grid development. This paper demonstrates that, given household Smart Meter demand data combined with 66kV/22kV zone substation SCADA voltage data, it is possible to model LV networks on a per-phase basis to a high degree of accuracy in near real time. Our model is based on a real suburb in urban northern Melbourne consisting of 113 customers, and is populated with real conductor properties, route lengths and customer phase allocations to create a true unbalanced three-phase, four-wire model. Time stepped load flow simulations of the model are compared with data loggers installed on the LV network for validation, and on average simulated results differ from real measurements by less than 0.5% for phase voltages and less than 10% for phase currents. Such accuracy allows for evaluation of PV, EV and EG impact mitigation strategies and planning in reference to the Electricity Distribution Code with a strong degree of confidence. This LV model is unique as it has been validated and is the only bottom-up load model that utilizes near real time Smart Meter and SCADA inputs to analyse impacts on distribution assets on a per phase, unbalanced basis. I. INTRODUCTION Electricity distribution companies own and operate the infrastructure required to connect customers to the network. Distribution networks utilise different voltage levels: High Voltage (HV 66kV), Medium Voltage (MV 11kV to 22kV) and Low Voltage (LV 400V or 230V). The majority of residential and small business customers are connected to the LV network with single phase or three phase connections. Traditionally distribution companies had no requirement to model the LV network in great detail and only considered the overall aggregate load of each LV distribution transformer. Until recently, this level of granularity was sufficient for distribution network planning and analysis. However as disruptive technologies such as PVs, EGs and EVs are connected to LV networks [1][2][3], the need to understand the physical constraints and real-time system state have become crucial to designing a stable, efficient network facilitating smart grid development. The two key components required to better understand LV networks are accurate network models and smart meter consumption data to provide real inputs into the model. This work aims to do this by modeling a threephase, four-wire unbalanced model [4] of an urban network in northern Melbourne consisting of 113 customers (Fig. 1). By linking each customer s National Metering Identifier (NMI) to the smart meter consumption database, real load data per customer is integrated into the LV model. Combining an accurate LV model with real world and near real-time smart meter and SCADA data, a solid foundation for EV and EG optimisation and planning applications can be developed to better plan and manage LV networks. A. LV Model Layout II. LV MODEL CONFIGURATION The LV model was created using the load flow package DigSilent PowerFactory. 1 Conductor properties were entered into the model using conductor specification data sheets for the conductors used in the LV Network. In a similar manner, the distribution transformer was modeled according to the specification datasheet. Conductor route lengths for the LV backbone (conductors between distribution poles) and the service cables to each customer were determined via physical onsite inspection and using GIS software cross-referenced with satellite photos of the LV Network. The model also imports the 22kV conductor and zone substation data from available HV models. The infinite bus is defined at the 66kV bus into the zone substation. Each house (indicated by triangles in Fig. 2) is connected to a distribution pole via service cables. The colour of each service cable indicates the phase that 1 DIgSILENT PowerFactory http://www.digsilent.com.au/

This allows the model to access actual and near real time demand data at a granular level. Each smart meter provides voltage, current and consumption data at 30- minute intervals. The zone substation component of the model is fed with a SCADA voltage data stream from the 66kV/22kV transformers (Fig. 3). Fig. 3. Voltage as measured via SCADA from the 22kV conductors originating from the Zone Substation. Fig. 1. Model Topology (113 customers) - Red circles indicate locations of LV Data Loggers used as reference for validation. the customer is connected to. Phase allocation for each customer in the model reflects the actual connection to the LV network in order to establish a true unbalanced model. C. LV Data Loggers Two GridSense PowerMonic PM45 loggers (Fig. 4) were installed at two locations on the LV network as shown by red circles in Fig. 1. The loggers measure key parameters such as Voltage and Current at one-minute intervals for all three phases and neutral. This data serves as a reference point for the real state of the LV backbone. Fig. 4. Data loggers Records Voltage and Current parameters on the LV backbone Fig. 2. Phase allocation Red refers to Red Phase, Blue refers to Blue Phase and Green refers to White Phase B. Smart Meter / SCADA Data Integration Each house in the LV model is integrated with a data stream from the individual customer s smart meter. III. VALIDATION The LV model is said to be valid if the model outputs match the current and voltage measurements of each phase recorded via the loggers for each 30-minute time interval over a period of one day. This is achieved by importing the demand data from all 113 homes in the LV network into the model at time 00:00:00. Load flow analysis is conducted to determine the LV system state. The voltage and current model outputs are recorded at the two positions where the loggers are installed (Logger 2

Fig. 5. Voltage Validation at Distribution Transformer - Blue line voltage at the same point. 1 and Logger 2 in Fig. 1). This process is repeated for each 30-minute interval (for a total of 48 load flow calculations). The model outputs at the two positions are then compared with the data loggers at the same interval. Logger 1 in Fig. 1 is installed at the origin of the LV network, i.e. the distribution transformer. This location was selected as it will inform the starting voltage for the LV network before voltage drop occurs along the length of the LV network. By obtaining voltage at this point, the actual voltage of the HV side of the transformer can also be determined by using the tap setting of the transformer. This will contribute to analysis by providing validation reference points for the HV network. In addition, Logger 1 will also log the total current drawn by all the household loads attached to the transformer, a key performance metric for the LV model. Fig. 5 shows the voltage parameter at the distribution transformer. The blue line represents the measured voltage from Data Logger 1 for July 10th 2012. The Red line is the LV model estimation of the voltage for the same time period as the data logger measurement. It can be seen that the model estimation compared to the actual state has an error of approximately 0.5%. Fig. 6 shows the corresponding current measurement for current at the distribution transformer. The blue line represents the data measured from the data logger and the red line is the model estimation. The current in the network can vary rapidly at localised locations throughout the network depending on the current draw from each household. Despite this, load flow calculations using smart meter data at each home derived accurate results. On average, the model was able to estimate the Fig. 6. Current Validation at Distribution Transformer - Blue line voltage at the same point. current on each phase with an average error of 10%. The neutral has an expected higher error as this is a combination of the phase errors. Logger 2 in Fig. 1 is installed at the approximate half way point on the LV network. The primary reason for installation at this point is to observe the effects of voltage and current unbalance and to analyse the effect of voltage drop along the LV network. For example, the voltage data points here should indicate an overall voltage drop from the voltages recorded by Logger 1 due to conductor impedance (assuming low to no PV generation). Fig. 7 shows the voltage parameter at the midway point of the LV network at LV Logger 2 (network midpoint). The error at this point is under 1% for all cases. The green dotted line represents the voltage at the distribution transformer (Logger 1) for comparison purposes. It can be seen that the voltage for the red and white phases drop significantly down the LV network. The blue phase is not as heavily loaded hence the voltage drop is not as pronounced. Fig. 8 shows the current parameter at the midway point of the LV network at Logger 2. The percentage error for the white and blue phase is low. The error for the red phase is high (41.32%) however in absolute terms, the error is on average 1.53 Amps, an insignificant amount. This is due to a small number of houses 3

Fig. 7. Voltage Validation at LV Network Midpoint - Blue line voltage at the same point. Green dotted line represents the voltage at the transformer for comparison purposes Fig. 8. Current Validation at LV Network Midpoint - Blue line represents the current measured at the LV Network midpoint via the LV Data Loggers. The red line is the LV model estimation of the voltage at the same point. connected downstream from Logger 2 on the red phase. Again the neutral conductor has an expected high error due to the fact that it is a combination of all errors in the phases. The main source of error between model outputs and data obtained by the data loggers is believed to be due to 11 smart meters not yet configured to send data. The LV model compensates for this by assigning the average demand of all the houses with smart meter demand data in the LV network to houses with missing smart meter data. This will be amended in future publications once the missing data is available. percentage over positive sequence is an indicator of phase balance. The transformer is located at 0km and the last house in the network is approximately 0.5km away (x-axis). Traversing down the network increases negative sequence voltage for each house due to uneven allocation of loads between phases. The distribution code allows for negative sequence voltage up to 1% (light blue line) on average and a maximum of 2% (can go over 2% for a maximum period of 5mins within each 30min time period). Fig. 11 shows the transformer utilisation represented as a percentage over time. Ideally, this should be below 100% (light blue line) or on average and below 150% (purple line) at all times for safe operation. Fig. 12 shows the Current on a particular phase conductor. This parameter must be below 230A (purple line) to avoid conductor sag and ground clearance issues for the type of conductor used in the modelled LV network. Furthermore this parameter should be above 0A to avoid reverse power flow (light blue line). The voltage and negative sequence profile in Fig. 9 and Fig. 10 show the worst case time instant at 6:00pm while the phase current in Fig. 12 shows the white phase current which recorded the worst case highest current amongst the three active phases. It can be seen that all parameters in the modelled LV network, even under worst case instances are within Australian Standards and the Electricity Distribution Code on July 10th 2012 as IV. R ESULTS Validated LV model outputs are used to determine if key parameters including voltage range limits, negative sequence limits (phase voltage unbalance limits) conductor current limits and transformer capacity limits are within Australian Standards [5] and the Electricity Distribution Code [6] (Fig. 9-12). Fig.9 shows the voltage profile of the LV network. Three colours represent the phase voltages (red = red phase, green = white phase, blue = blue phase). Light blue lines represent the voltage limits. The transformer is located at 0km and the last house is located approximately 0.5km away from the transformer (x-axis). As houses draw more power, voltage begins to drop along the LV network. Nominal voltage is 1pu volt (230V). Distribution code allows voltage between 1.1pu and 0.94pu volts. Fig. 10 shows the negative sequence Voltage Profile of the LV network. Negative sequence expressed as a 4

Fig. 11. Transformer utilisation with limits Fig. 9. Voltage profile of the LV network with limits. Fig. 12. Phase current with limits and the Electricity Distribution code. The near real time input from smart meters and zone substation SCADA enhances this unbalanced per-phase LV model beyond assumption-based models often found in the literature. Using this as a baseline, the LV model can be used as an accurate, near real time platform to perform EV and EG optimization and planning strategies going forward. Fig. 10. limits. Negative sequence voltage profile of the LV network with estimated by the LV model. Although the modelled LV network performs to code under present conditions, the foreseen problem is the introduction of disruptive technologies such as solar PV and electric vehicles. High penetration of such technologies in LV networks are expected to exceed limits set out by Australian Standards and the Electricity Distribution Code. The next step in the LV model development is to simulate and estimate the impact of disruptive technologies over various penetration and phase unbalance scenarios. V. CONCLUSION The simulation model presented in this paper demonstrates strong correlation with the real network, with simulated outputs closely matching data logger reference measurements for current and voltage at different locations in the network, throughout the day. This shows that this LV model is sufficiently accurate to estimate the real state of LV networks in reference to Australian Standards ACKNOWLEDGEMENTS This work was supported by SP AusNet and The University of Melbourne. Special thanks to Luke Robinson from DigSilent Pacific for initial construction of LV components and support for the DigSilent PowerFactory software suite, Geoff Thorn for general guidance and Kenneth Chew for database assistance. BIBLIOGRAPHY [1] W. H. Kersting, A three-phase unbalanced line model with grounded neutrals through a resistance, in Power and Energy Society General Meeting - Conversion and Delivery of Electrical Energy in the 21st Century, 2008 IEEE, 2008, pp. 1 2, id: 1. [2] K. Poyan, Investigation of western powers low voltage operation limits with the integration of photovoltaic systems, no. Murdoch University, 2010. [3] P. Richardson, J. Taylor, D. Flynn, and A. C. Keane, Stochastic analysis of the impact of electric vehicles on distribution networks, 2011. [4] F. Shahnia, A. Ghosh, G. Ledwich, and F. Zare, Voltage unbalance reduction in low voltage distribution networks with rooftop pvs, in Universities Power Engineering Conference (AUPEC), 2010 20th Australasian, 2010, pp. 1 5, id: 1. [5] Australian Standard AS 2374.7-1997. Transformer Capacity Limits. [6] Electricity Distribution Code, Victoria, Australia. Version 6 (January 2011)., Online: http://www.esc.vic.gov.au/energy/ Distribution/Electricity-Distribution-code. 5