Single Earthed Neutral and Multi Earthed Neutral. Single Earthed Neutral and Multi Earthed Neutral: Multi Grounded Neutral System (MEN):

Similar documents
Grounding for Power Quality

Overview of Grounding for Industrial and Commercial Power Systems Presented By Robert Schuerger, P.E.

Grounding Recommendations for On Site Power Systems

A DUMMIES GUIDE TO GROUND FAULT PROTECTION

Education & Training

Industrial and Commercial Power Systems Topic 7 EARTHING

SDCS-03 DISTRIBUTION NETWORK GROUNDING CONSTRUCTION STANDARD (PART-I) UNDERGROUND NETWORK GROUNDING. Rev. 01

Topic 6 Quiz, February 2017 Impedance and Fault Current Calculations For Radial Systems TLC ONLY!!!!! DUE DATE FOR TLC- February 14, 2017

2 Grounding of power supply system neutral

The Confusion Surrounding Stray Voltage

SDCS-03 DISTRIBUTION NETWORK GROUNDING CONSTRUCTION STANDARD (PART-II) OVERHEAD NETWORK GROUNDING. Rev. 01

The Variable Threshold Neutral Isolator (VTNI)

Need for grounding Codes and Standards for grounding Wind Turbine Generator grounding design Foundation + Horizontal Electrode grounding design

Section 6: System Grounding Bill Brown, P.E., Square D Engineering Services

Underground System Design TADP 547

Upgrading Your Electrical Distribution System To Resistance Grounding

CONTINUING EDUC ATION

Overvoltage Protection

EPG. by Chris C. Kleronomos

American Electrical Institute

Problems connected with Commissioning of Power Transformers

Safety through proper system Grounding and Ground Fault Protection

DP&L s Technical Requirements for Interconnection and Parallel Operation of Distributed Generation

SAFETY ASPECTS AND NOVEL TECHNICAL SOLUTIONS FOR EARTH FAULT MANAGEMENT IN MV ELECTRICITY DISTRIBUTION NETWORKS

TRANSMISSION ENGINEERING STANDARD TES-P , Rev. 0 TABLE OF CONTENTS 1.0 SCOPE 2.0 BONDING METHODS

R Distribution Transformers. Mineral Oil-Immersed, Self-Cooled, 60 Hertz Voltages and Connections. Reference Data

Product Classroom. Introduction. Grounding Systems. TN system. Title. Grounding System Introduction. Date October, 2016.

Earthing of Electrical Devices and Safety

Capstone Turbine Corporation Nordhoff Street Chatsworth CA USA Phone: (818) Fax: (818) Web:

UNITED STATES OF DEPARTMENT OF AGRICULTURE Rural Utilities Service BULLETIN 1751F-815. Electrical Protection of Outside Plant

Protection Basics Presented by John S. Levine, P.E. Levine Lectronics and Lectric, Inc GE Consumer & Industrial Multilin

PRACTICAL PROBLEMS WITH SUBSTATION EARTHING

Tech Talk (12) Down to Earth: A Discussion of the General Requirements for the Earthing of Control and Instrumentation Systems

Safety Issues Caused by High Earth Resistance and Identifying Them Using Instruments

Notes 1: Introduction to Distribution Systems

FERRORESONANCE SIMULATION STUDIES USING EMTP

High voltage engineering

ELECTRICAL SHOCK HAZARD DUE TO STRAY CURRENT THE SHOCKING SHOWER

Arc Flash Analysis Training

ECE 528 Understanding Power Quality

High Voltage Pylon Earth Measurements

Article 250 Grounding & Bonding

10. DISTURBANCE VOLTAGE WITHSTAND CAPABILITY

The Importance of the Neutral-Grounding Resistor. Presented by: Jeff Glenney, P.Eng. and Don Selkirk, E.I.T.

Appendix B to Working on Exposed Energized Parts

Power System Neutral/Ground Voltages Causes, Safety Concerns and Mitigation

INSTALLATION, OPERATION AND MAINTENANCE GUIDE

BED INTERCONNECTION TECHNICAL REQUIREMENTS

CONTENTS. 1. Introduction Generating Stations 9 40

Grounding and Lightning arrestors

CP Cu1. Advanced Test Equipment Rentals ATEC (2832) Multi-purpose coupling unit for CPC 100. Measurement System for

Busbars and lines are important elements

A Case Study on Selection and Application of Lightning Arrester and Designing its Suitable Grounding Grid

Grounding System Theory and Practice

CHAPTER 15 GROUNDING REQUIREMENTS FOR ELECTRICAL EQUIPMENT

Field Instruction. Induced voltages can occur in overhead lines, underground cables, or in switchyards.

SHUNT CAPACITOR BANK DESIGN AND PROTECTION BASICS

2/15/2015. Current will always try to return to its source. In order for there to be current, there must be a complete circuit

POWER FACTOR CORRECTION. HARMONIC FILTERING. MEDIUM AND HIGH VOLTAGE SOLUTIONS.

MV ELECTRICAL TRANSMISSION DESIGN AND CONSTRUCTION STANDARD. PART 1: GENERAL 1.01 Transformer

AN EXAMPLE OF A STANDARD ARC FLASH PPE LABELING STRATEGY

Arrester Disconnector

GROUNDED ELECTRICAL POWER DISTRIBUTION. Excerpt from Inverter Charger Series Manual BY: VIJAY SHARMA ENGINEER

Webinar: An Effective Arc Flash Safety Program

BE Semester- VI (Electrical Engineering) Question Bank (E 605 ELECTRICAL POWER SYSTEM - II) Y - Y transformer : 300 MVA, 33Y / 220Y kv, X = 15 %

High Voltage Pylon earth Measurements. Tycom (Pty) Ltd Frank Barnes Comtest (Pty) Ltd Presented by Gavin van Rooy

Wisconsin Contractors Institute Continuing Education

Tab 8 Surge Arresters

PC IEEE Guide for Grounding of Instrument Transformer Secondary Circuits and Cases

Summary of the Impacts of Grounding on System Protection

FAQ ON EARTHING STANDARDS 16/08/2018

Protection of Electrical Networks. Christophe Prévé

AC INTERFERENCE OF TRANSMISSION LINES ON RAILWAYS: INFLUENCE OF TRACK-CONNECTED EQUIPMENT I. ABSTRACT

Single Line Diagram of Substations

National Marine Manufacturers Association Compliance Specialist Examination A.C. Electrical (2018 Model Year) ABYC E-11 Supplement 56

To Float or Not to Float? Analysis of a floating vs. grounded output Associated Power Technologies

RAIDK, RAIDG, RAPDK and RACIK Phase overcurrent and earth-fault protection assemblies based on single phase measuring elements

SAFETY AND HEALTH STANDARD ELECTRICAL GROUNDING Effective Date: 07/17/10 Standard: Document Number: KUCSH0039 Rev: 4

UNIVERSITY OF MISSOURI Liquid-Filled Utility Transformers 2016 Q1

Application Note (Revision NEW) Original Instructions. EMI Control in Electronic Governing Systems

Guide for Conducting a Stray Voltage Evaluation Under the MPSC Stray Voltage Rule 1

Functional Range. IWE - Earth Fault Relay. C&S Protection & Control Ltd.

Grounding and Bonding of Service Equipment

A PARAMETRIC ANALYSIS OF AC INTERFERENCE CAUSED BY HIGH VOLTAGE POWER LINES ON NEIGHBORING RAILROAD TRACKS

Generator Protection GENERATOR CONTROL AND PROTECTION

Paul Dobrowsky Innovative Technology Services

ARC FLASH HAZARD ANALYSIS AND MITIGATION

Session Four: Practical Insulation Co-ordination for Lightning Induced Overvoltages

SECTION 5 TRANSFORMERS

6B.6 Substation Grounding

A practical viewpoint.

PJM Manual 07:: PJM Protection Standards Revision: 2 Effective Date: July 1, 2016

Testing the Ground Circuit

SINGLE PHASE BUCK & BOOST TRANSFORMERS INSTRUCTION MANUAL

Tertiary Winding Design in wye-wye Connected Transformers Restricted Siemens Energy 2013 All rights reserved.

AN EXAMPLE OF A STANDARD ARC FLASH PPE LABELING STRATEGY

Substation Design Volume VII

Generation Interconnection Requirements at Voltages 34.5 kv and Below

A Study on Lightning Overvoltage Characteristics of Grounding Systems in Underground Distribution Power Cables

Contact Voltage Detection

Transcription:

Single Earthed Neutral and Multi Earthed Neutral. SEPTEMBER 6, 2011 5 COMMENTS Single Earthed Neutral and Multi Earthed Neutral: In Distribution System Three Phase load is unbalance and non linear so The Neutral plays an important role in Distribution system. Generally, distribution networks are operated in an unbalanced configuration and also service to consumers. This causes current flowing through neutral conductor and voltage dropping on neutral wire. The unbalance load and excessive current in neutral wire is one of the issues in three phase four-wire distribution systems that causes voltage drop through neutral wire and makes tribulations for costumers. The existence of Neutral earth Voltage makes unbalance in three phase voltages for three phase customers and reduction of phase to neutral voltage for single phase customers. MULTI-GROUNDED three-phase four-wire service is widely adopted in modern power distribution systems due to having lower installation costs and higher sensitivity of fault protection than three-phase three-wire service. The neutrals play an important role in power quality and safety problems. The multi grounded neutral system is the predominant electrical distribution system used in the United States. It allow an uncontrolled amount of electric current to flow over the earth unrestrained, posing the potential of harm to the public and to animals causing electric shocks and is presumed responsible for undetected electrocutions. The protective grounding used in low voltage,600-volt and below, applications will be described and used to explain the hazards involved with the present day multi grounded neutral distribution System, used in the United States. This will allow the reader to see the parallels between the safe low voltage distribution system and the dangerous medium voltage multi grounded neutral distribution system. The reasons for the development of the three phase, four-wire, multi-grounded systems involve a combination of safety and economic considerations. The three-phase, four-wire multi-grounded design has been successfully used for many years and is well documented in the standards including the National Electrical Code (NEC). It is Crucial decisions to adopt Multi Grounded Neutral System save money by the adoption of the multi grounded neutral electrical distribution system in the cost of the public s safety. Multi Grounded Neutral System (MEN):

Fig shows the multi-grounded neutral systems commonly used by the electric utilities in North America. The neutral grounding reactor is used by some utilities to reduce the available ground fault current while at the same time still maintaining an effectively grounded system. The multiple earthed neutral (MEN) system of earthing is one in which the low voltage neutral conductor is used as the low resistance return path for fault currents and where its potential rise is kept low by having it connected to earth at a number of locations along its length. The neutral conductor is connected to earth at the distribution transformer, at each consumer s installation and at specified poles or underground pillars. The resistance between the neutral conductor of the distribution system and the earth must not exceed 10 ohms at any location. NEC Article 250 Part X Grounding of Systems and Circuits 1 kv and Over (High Voltage) (A) Multiple Grounding: The neutral of a solidly grounded neutral system shall be permitted to be grounded at more than one point. (B) Multi-grounded Neutral Conductor: Ground each transformer, Ground at 400 m intervals or less, Ground shielded cables where exposed to personnel contact. Single Grounded Neutral: Fig Show Single Grounded Neutral Which is different from Multi Grounded System.Figure shows the neutral also connected to earth, but the neutral conductor is extended along with the phase conductors. The configuration shown in figure allows electrical loads, transformers to be placed between any of the three phase conductors, phase-to-phase and/or phase-to-neutral. This connection, phase to neutral will force electric current to flow over the neutral back to the transformer. So far, this electrical connection is acceptable, as long as the neutral is insulated or treated as being potentially energized, but modifications will be made in the future that will negate safety for the public and animals. The ground connection would typically be located in the distribution substation. This may appear insignificant, but the differences are significant Advantages of Multiple Grounded Neutral Systems: (1) Optimize the Size of Surge Arrestor: Surge arresters are applied to a power system based on the line-to-ground voltage under normal condition and abnormal conditions. Under ground-fault conditions, the line-to-ground voltage can increase up to 1.73 per unit on the two, un faulted.

Application of surge arresters on a power system is dependent on the effectiveness of the system grounding. The over voltage condition that can occur during a ground fault can be minimized by keeping the zero sequence impedance low. Therefore, optimization in sizing the surge arresters on the system is dependent on the system grounding. An effectively grounded power system allows the use of a lower rated surge arrester. The lower rated surge arrester provides better surge protection at a lower cost. An effectively grounded system can only be accomplished using a properly sized, multi-grounded system neutral. With Single Grounded Neutral System require the use of full line-to-line voltage rated arresters. This increases the cost of the surge arresters while at the same time reduces the protection provided by the surge arrester. In addition, if the fourth wire neutral is not multi grounded, it would be good practice to place surge arresters at appropriate locations on that conductor. (2) The zero sequence impedance is lower for a multi grounded system than the single point grounded neutral system. (3) Freezing and arctic conditions have an adverse impact on the zero sequence impedance. A multi-grounded system neutral will still lower the zero sequence impedance over a single point ground. In fact, without the multigrounded system, it is more probable that insufficient fault current will flow to properly operate the ground fault protection. (4) Cost of Equipment for the multi-grounded system is lower. (5) Safety Concerns on Cable Shields. Medium voltage and high voltage cables typically have cable shields (NEC requirement above 5 kv) that need to be grounded. There are several reasons for this shield: To confine electric fields within the cable To obtain uniform radial distribution of the electric field To protect against induced voltages To reduce the hazard of shockif the shield is not grounded, the shock hazard can be increased. With the shield grounded at one point, induced voltage on the shield can be significant and create a shock hazard. Therefore, it is common practice to apply multiple grounds on the shield to keep the voltage limited to 25 volts. This practice of multi grounding cable shields includes the grounding of concentric neutrals on power cables thereby extending the need for multi grounding of neutrals on the power system. Disadvantages of Multiple Neutral Grounding: (1) Less Electrical Safety in Public and Private Property. With a multi grounded neutral distribution system it is necessary to have an electrical connection to earth at least 4 times per mile to keep the voltage on the multi grounded neutral from exceeding approximately 25 volts making it safe for the linemen should they come into contact with the neutral and the earth. As per NESC Rule 096 C in the section with the multi grounded neutral conductor connected to earth at least 4 times per mile and at each transformer and lightning arrester there are now multiple paths over and through the earth that the hazardous electric current can flow over continuously, uncontrolled. The path that this current flow takes through the earth cannot be determined. We cannot put an isotope on each electron and trace its path as it flows uncontrolled through the earth. It is irresponsible to permit stray uncontrolled electric current to flow into and over private property.

The National Electrical Code (NEC) requires the neutral in the service disconnect and over current panel board to be connected to the earth also. Now the secondary neutral is connected to earth a second time. A parallel connection of the neutral to earth now exists permitting hazardous electric current to flow continuously uncontrolled over the earth. (2) Earth Fault Protection Relay setting is complicated. Advantages of Single Grounded Neutral System: (1) More Reliable and Safe System. (2) Protection Relay Setting is more easy in Single Grounded Neutral: Protective relays need to sense abnormal conditions, especially those involving a ground fault. The single point grounded system, with or without a neutral conductor, current flowing into the ground should be considered abnormal (excluding normal charging current). For sensing of ground faults are: A current transformer in the location where the neutral is grounded can be used to sense the ground fault (zero sequence) current. A zero sequence CT enclosing the three phase and neutral conductors. Four CT residue circuit (Three CT residual with neutral CT cancellation). Protecting against ground faults on a multi-grounded neutral system is more difficult than the single point grounded system since both neutral and ground fault currents must be considered. Neutral current and likewise ground fault current can flow in both the neutral and the ground. So, We have must calculate both current as the amount of neutral current which may flow in the circuit, and the ground fault setting must be above this neutral current. This is self explanatory from Fig. (3) Sensing of Ground Fault current : While the sensing of the ground fault current in the single point grounded system is less complex than the multi grounded system, the amount of ground fault current on the single-point grounded system may be greatly limited

due to the fact that all ground fault current must return through the earth. This is especially true where the earth resistivity is high, the soil is frozen or the soil is extremely dry. Reference: John P. Nelson Fellow, IEEE ANSI/IEEE Std 142-1991 Westinghouse Electric Corporation, Electrical Transmission and Distribution Reference Book NFPA 70. Jeffery Leib, Train-Car Crashes on the Rise,Denver Post Newspaper, November 7, 2002 R.T. Beck and Luke Yu, Design Considerations for Grounding Systems. Source: http://electricalnotes.wordpress.com/2011/09/06/single-earthed-neutral-and-multiearthed-neutral/