FRIENDS Devices and their Coordination

Similar documents
Compensation of Distribution Feeder Loading With Power Factor Correction by Using D-STATCOM

INSTANTANEOUS POWER CONTROL OF D-STATCOM FOR ENHANCEMENT OF THE STEADY-STATE PERFORMANCE

International Journal of Scientific & Engineering Research, Volume 6, Issue 8, August ISSN

Power Control Scheme of D-Statcom

Unit.2-Voltage Sag. D.Maharajan Ph.D Assistant Professor Department of Electrical and Electronics Engg., SRM University, Chennai-203

Protection from Voltage Sags and Swells by Using FACTS Controller

OVERVIEW OF SVC AND STATCOM FOR INSTANTANEOUS POWER CONTROL AND POWER FACTOR IMPROVEMENT

CHAPTER 4 POWER QUALITY AND VAR COMPENSATION IN DISTRIBUTION SYSTEMS

Power Quality enhancement of a distribution line with DSTATCOM

Reducing the Effects of Short Circuit Faults on Sensitive Loads in Distribution Systems

ISSN Vol.07,Issue.21, December-2015, Pages:

Simulation and Comparison of DVR and DSTATCOM Used For Voltage Sag Mitigation at Distribution Side

Thyristor Based Static Transfer Switch: Theory, Modeling and Analysis

Mitigation of voltage disturbances (Sag/Swell) utilizing dynamic voltage restorer (DVR)

MITIGATION OF VOLTAGE SAGS/SWELLS USING DYNAMIC VOLTAGE RESTORER (DVR)

Harmonic Immunity And Power Factor Correction By Instantaneous Power Control Of D-STATCOM

Closed Loop Single Phase Bidirectional AC to AC Buck Boost Converter for Power Quality Improvement

Chapter -3 ANALYSIS OF HVDC SYSTEM MODEL. Basically the HVDC transmission consists in the basic case of two

Voltage Sag and Swell Mitigation Using Dynamic Voltage Restore (DVR)

Power Quality Basics. Presented by. Scott Peele PE

Poornima G P. IJECS Volume 3 Issue 6 June, 2014 Page No Page 6453

Module 3. DC to DC Converters. Version 2 EE IIT, Kharagpur 1

Design and Control of Interline Unified Power Quality Conditioner for Power Quality Disturbances

Voltage Sag and Mitigation Using Dynamic Voltage Restorer (DVR) System

A NOVEL APPROACH ON INSTANTANEOUS POWER CONTROL OF D-STATCOM WITH CONSIDERATION OF POWER FACTOR CORRECTION

Simulation of Multi Converter Unified Power Quality Conditioner for Two Feeder Distribution System

UPGRADING SUBSTATION RELAYS TO DIGITAL RECLOSERS AND THEIR COORDINATION WITH SECTIONALIZERS

ARC FLASH PPE GUIDELINES FOR INDUSTRIAL POWER SYSTEMS

Design of Interline Dynamic Voltage Restorer for Voltage Sag Compensation

Volume I Issue VI 2012 September-2012 ISSN

Power Quality Improvement using Hysteresis Voltage Control of DVR

Keywords: Forward Boost Converter, SMPS, Power Factor Correction, Power Quality, Efficiency.

Analysis, Modeling and Simulation of Dynamic Voltage Restorer (DVR)for Compensation of Voltage for sag-swell Disturbances

Performance of DVR & Distribution STATCOM in Power Systems

Design and Simulation of superconducting fault current limiter

Power Quality Improvement by DVR

UNIFIED POWER QUALITY CONDITIONER IN DISTRIBUTION SYSTEM FOR ENHANCING POWER QUALITY

ISSN Vol.03,Issue.11, December-2015, Pages:

A Pyrotechnic Fault Current Limiter Model for Transient Calculations in Industrial Power Systems

Busbars and lines are important elements

ICCCES Application of D-STATCOM for load compensation with non-stiff sources

EFFECT OF SFCL ON DISTRIBUTION POWER QUALITY

Design Strategy for Optimum Rating Selection of Interline D-STATCOM

Tab 2 Voltage Stresses Switching Transients

Relay Coordination in the Protection of Radially- Connected Power System Network

SIMULATION OF D-STATCOM IN POWER SYSTEM

Arvind Pahade and Nitin Saxena Department of Electrical Engineering, Jabalpur Engineering College, Jabalpur, (MP), India

A Versatile Control Scheme for UPQC for Power Quality Improvement using fuzzy controller

A DYNAMIC VOLTAGE RESTORER (DVR) BASED MITIGATION SCHEME FOR VOLTAGE SAG AND SWELL

Bhavin Gondaliya 1st Head, Electrical Engineering Department Dr. Subhash Technical Campus, Junagadh, Gujarat (India)

INTERLINE UNIFIED POWER QUALITY CONDITIONER: DESIGN AND SIMULATION

International Journal of Research (IJR) e-issn: , p- ISSN: X Volume 2, Issue 09, September 2015

ANFIS based 48-Pulse STATCOM Controller for Enhancement of Power System Stability

REDUCTION OF TRANSFORMER INRUSH CURRENT BY CONTROLLED SWITCHING METHOD. Trivandrum

CHAPTER 5 POWER QUALITY IMPROVEMENT BY USING POWER ACTIVE FILTERS

Dr.Arkan A.Hussein Power Electronics Fourth Class. Commutation of Thyristor-Based Circuits Part-I

PRC Generator Relay Loadability. Guidelines and Technical Basis Draft 5: (August 2, 2013) Page 1 of 76

Simulation and Implementation of DVR for Voltage Sag Compensation

A HIGH RELIABILITY SINGLE-PHASE BOOST RECTIFIER SYSTEM FOR DIFFERENT LOAD VARIATIONS. Prasanna Srikanth Polisetty

Protection Basics Presented by John S. Levine, P.E. Levine Lectronics and Lectric, Inc GE Consumer & Industrial Multilin

Z-SOURCE INVERTER BASED DVR FOR VOLTAGE SAG/SWELL MITIGATION

Mitigating Voltage Sag Using Dynamic Voltage Restorer

PQ for Industrial Benchmarking with various methods to improve. Tushar Mogre.

PRC Generator Relay Loadability. Guidelines and Technical Basis Draft 4: (June 10, 2013) Page 1 of 75

MODERN switching power converters require many features

Interline Power Quality Conditioner for Power Quality Improvement

Neutral Reactor Optimization in order to Reduce Arc Extinction Time during Three-Phase Tripping

Transient stability improvement by using shunt FACT device (STATCOM) with Reference Voltage Compensation (RVC) control scheme

IJSRD - International Journal for Scientific Research & Development Vol. 3, Issue 03, 2015 ISSN (online):

DOWNLOAD PDF POWER ELECTRONICS DEVICES DRIVERS AND APPLICATIONS

POWER QUALITY ENHANCEMENT BY DC LINK SUPPLIED INDUSTRIAL SYSTEM

Adaptive Relaying of Radial Distribution system with Distributed Generation

Performance of Indirectly Controlled STATCOM with IEEE 30-bus System

SIMULATION OF D-STATCOM AND DVR IN POWER SYSTEMS

PRECISION SIMULATION OF PWM CONTROLLERS

In power system, transients have bad impact on its

Improvement of Power Quality in Distribution System using D-STATCOM With PI and PID Controller

Impact of Distributed Generation on Network Voltage Levels

DESIGN A D STATCOM FOR VOLTAGE HARMONIC SUPPRESSION IN DISTRIBUTION SYSTEM

Implementation of D-STACTOM for Improvement of Power Quality in Radial Distribution System

Power Quality and Circuit Imbalances Northwest Electric Meter School Presented by: Chris Lindsay-Smith McAvoy & Markham Engineering/Itron

FERRORESONANCE SIMULATION STUDIES USING EMTP

Voltage Unbalance Reduction in Low Voltage Feeders by Dynamic Switching of Residential Customers among Three Phases

Solving Customer Power Quality Problems Due to Voltage Magnification

Application of Dynamic Voltage Restorer for Voltage Balancing with ASD Load Using DQO Transformation

SOFT SWITCHING TECHNIQUE USING RESONANT CONVERTER FOR CONSTANT SPEED DRIVE

SHORT CIRCUIT ANALYSIS OF 220/132 KV SUBSTATION BY USING ETAP

Reduction of Voltage Imbalance in a Two Feeder Distribution System Using Iupqc

Improvement in Power Quality of Distribution System Using STATCOM

Improvement of Voltage Profile using D- STATCOM Simulation under sag and swell condition

Design And Analysis Of Control Circuit For TCSC FACTS Controller

Voltage Quality Enhancement in an Isolated Power System through Series Compensator

Enhancing Power Quality in Transmission System Using Fc-Tcr

Enhancement of Power Quality in Distribution System Using D-Statcom for Different Faults

CHAPTER 2 A SERIES PARALLEL RESONANT CONVERTER WITH OPEN LOOP CONTROL

Enhancement of Power Quality in Distribution System Using D-Statcom

Ferroresonance Conditions Associated With a 13 kv Voltage Regulator During Back-feed Conditions

AORC Technical meeting 2014

Analysis and modeling of thyristor controlled series capacitor for the reduction of voltage sag Manisha Chadar

Mitigation of Voltage Sag and Swell Using Dynamic Voltage Restorer

Transcription:

INDIAN INSTITUTE OF TECHNOLOGY, KHARAGPUR 721302, DECEMBER 27-29, 2002 425 FRIENDS Devices and their Coordination R. L. Meena, Arindam Ghosh and Avinash Joshi Abstract-- The paper discusses various aspects of Flexible, Reliable and Intelligent Electrical energy Delivery System (FRIENDS) devices and their coordination to improve power quality by using power electronics based semiconductor devices. Static Current Limiter (SCL) and Static Circuit Breaker (SCB) are protecting devices while Static Transfer Switch (STS) is a network controlling device. Static Switch is the basic building block of all protecting and control FRIENDS devices. The SCL and SCB are simulated for an 11 radial distribution system. Coordination issues for protection using FRIENDS Devices are simulated for 11 generic distribution system. The single phase STS is simulated for both SCR and GTO based topologies and results are compared. Digital simulations for FRIENDS devices are performed using PSCAD/EMTDC software package (version 3.1.7) on a personal computer. Index Terms FRIENDS, Power Quality, PSCAD/EMTDC Simulation, SCB, SCL, STS. P I. INTRODUCTION OWER QUALITY issues are currently receiving a great deal of attention in the light of distribution generation, deregulation, liberalization and privatization of the electrical energy market. For AC transmission and distribution system, power quality broadly refers to maintaining a near sinusoidal bus voltage at rated magnitude and frequency. The power quality of a supply voltage can deteriorate due to very highspeed events such as voltage impulses/transients, high frequency noise, waveshape distortion, voltage swells and sags or due to simple total power loss. Each type of electrical equipment will be affected differently by the power quality issues. Problem of poor power quality can be solved by power electronics based FRIENDS devices. The word FRIENDS stands for Flexible Reliable and Intelligent Electrical energy Delivery System [1]. With FRIENDS, the power system can be operated without interrupting the power supply by flexibly changing the distribution systems configurations after the occurrence of a fault. Power electronics based static switch shown in Fig. 1 is the building block for all FRIENDS devices. Static current limiting and breaking devices protects the distribution system fast and efficiently. STS transfers supply between two or more ac sources when applied at critical facilities. GTOs are used for Static Current Limiter (SCL) and Static Circuit Breaker (SCB) where instantaneous current has to be interrupted [2]. SCRs are used for Static Transfer Switch (STS) where transfer of power from one source to another is performed. GTOs can be used for STS instead of SCRs to make them faster. The protective devices must switch off the smallest portion of network without affecting the majority of loads. This objective is accomplished through primary and back up protection using inverse time overcurrent relays [3]. This basic principle of coordination must be kept in mind while placing SCL and SCB. For power quality related problems caused by voltage sags and swells, lightening strikes and other system related disturbances, in many instances, the use of a STS can be one of the most cost effective solutions. The objective of the paper is to simulate FRIENDS devices in PSCAD/EMTDC software package and study their coordination aspects to determine their placement location in a generic distribution system. Also operating parameters are calculated for providing a fast and reliable protection. II. STATIC SWITCH This is the combination of two anti-parallel thyristors as shown in Fig. 1. Assume that an alternating current flows from the left to the right of the static switch. The positive half cycle current is passed by the thyristor that is in forward biased condition. Similarly the negative half cycle current is passed by the other thyristor. Thus each thyristor conducts for half cycle and remains in the off state for another half cycle. The current flowing through static switch can be interrupted by blocking the firing signal. The current will then be interrupted at its next zero crossing. When thyristors are replaced by GTOs, the operation will be faster because current can be forced to zero at any instant, therefore eliminating the need to wait till the next zero crossing. This characteristic is mandatory for current limiting and breaking devices. For load transferring thyristors are sufficient but GTOs may transfer faster than thyristors. Ramjee Lal Meena is with Electrical Engineering Department at Indian Institute of Technology, Kanpur, 208016 INDIA (telephone: 0512-597801, e-mail: meenarl@iitk.ac.in). Arindam Ghosh is with Electrical Engineering Department at Indian Institute of Technology, Kanpur, 208016 INDIA (telephone: 0512-597179, e- mail: aghosh@iitk.ac.in). Avinash Joshi is with Electrical Engineering Department at Indian Institute of Technology, Kanpur, 208016 INDIA (telephone: 0512-598342, e-mail: ajoshi@iitk.ac.in). (+) (+) (-) (-)

426 NATIONAL POWER SYSTEMS CONFERENCE, NPSC 2002 Fig. 1 A static switch. III. STATIC CURRENT LIMITER Topology of SCL is shown in Fig.2. GTO based static switch and let-through reactor are connected in parallel. Snubber circuit is used to protect the GTOs from large dv/dt. ZnO arrester limits the peak voltage appearing across the switch during turn-off. Under normal load conditions, the GTOs are gated continuously and maintained in full conduction. When a fault occurs on the load side of SCL, a control circuit, activated by the instantaneous magnitude of the fault current, initiates a turn-off for the GTOs. Because GTOs respond within a few microseconds of the control signal and are capable of turning off current considerably higher in magnitude than the maximum continuous current, fault current is quickly limited before it reaches a destructive level. Immediately after GTO turn off, the V. STATIC TRANSFER SWITCH The thyristor based single phase STS is illustrated in the Fig. 4. The success of the device is mainly due to its low cost and fast response due to the phenomenon of fast switching, usually referred to as make before break switching (MBB). The name refers to the possibility of firing the thyristors of the static switch that is not conducting (alternative source), thus initiating the transfer, before the current on the corresponding switch in the preferred source has become zero. It is possible to gate the thyristors such that, a current will start flowing in the thyristor that has just been fired in such a direction that it forces the thyristor that was conducting to turn off very quickly. Fig. 4 Thyristor based STS topology. The transfer time depends on the type of disturbance and Preferred Source Alternative Source ZnO Arrester Zf ZnO ZnO Zf Supply Side Let-Through Reactor Inductor current will be diverted in to current limiting reactor and arrester. Fig. 2 GTO based SCL topology. IV. STATIC CIRCUIT BREAKER The schematic diagram for SCB is shown in Fig.3.The main components of this equipment are a high-speed vacuum circuit breaker (VCB) and a GTO based static switch connected in parallel. The usual load current is carried out by the VCB. In case of system fault, the fault current is commutated to and interrupted by the GTO based static switch by opening the vacuum switch. This equipment does not require a large cooling system and is compact compared with conventional solid state equipment. Fig. 3 GTO and VCB based SCB topology. I i I sw GTO based Static Switch ZnO Arrester High-Speed VCB I b I sw Load Side I sp Fault ipp i pn Sw1 Critical Load Sw2 on actual operating conditions of the power system when transfer is initiated. The nature of the transfer however will depend on many factors. Some of these factors are: relative magnitude of the source voltages, phase angle difference between the preferred and alternate sources, feeder impedances, load impedance, fault detection time, whether load is passive or active etc. The nature of the load current will depend on the combination of these parameters. The design of the transfer control must take into account all these factors for satisfactory operation. VI. COORDINATION A generic distribution system is shown in Fig. 5 in which the SCL and SCB are to be placed at positions labeled with numerals. This distribution system has two incoming transformers, each connected to one main bus. These two buses are connected by a bus tie-breaker. Devices below the buses are referred to as down stream devices. The best position of a static current limiter is at the output of the main incoming transformers, i.e. location 1 and 2. This will limit the current for fault in any part of the network. Furthermore, such an arrangement will not cause any serious i an i ap I sa Supply Side GTO based Static Switch Load Side

INDIAN INSTITUTE OF TECHNOLOGY, KHARAGPUR 721302, DECEMBER 27-29, 2002 427 coordination problem. The main SCL/SCB features for protection coordination are 4 1 T 1 Bus-tie Down Stream Feeders Fig. 5 A generic distribution system It must limit the short circuit current such that it does not exceed the interrupting rating of any down stream protecting devices It must allow sufficient fault current to flow such that it can clear the fault any down stream over current protection device. It must maintain the fault current with in a specified limit till a down streams device clear the fault. The limiter must reset automatically after the fault is cleared. It must relatively free from maintenance. VII. SIMULATION STUDIES Load Digital simulations for static protection and control devices are performed using PSCAD/EMTDC software package (version 3.1.7) on a personal computer. For SCL and SCB we have considered a simple radial distribution system (test system) that is supplying an R-L load as shown in Fig.6. The line to neutral voltage is 6.35 (rms) and the system frequency is 50 Hz. The feeder has a resistance of 3.025 Ω and a let-through inductor of 38.5 mh while the load resistance and inductance are given by 60.5 Ω and 770.3 mh respectively. This implies that for a base voltage of 11 (L-L) and a base MVA of 1.0, the feeder impedance is 0.025 + j0.1 per unit and the load impedance is 0.5 +j 2.0 per unit. The pre fault current in the steady state is 24.25 A (rms), i.e., 0.462 per unit. For a short circuit fault (V l = 0), only the feeder impedance limits the load current, which has the peak of about 1200 A, i.e., more than 20 per unit. Vs 3.025 Ω 38.5mH 3 T 2 5 6 7 V t SCL/SCB i f Vl 2 60.5 Ω 770.3mH Fig.6 Radial distribution protected by SCL/SCB. The simulation for single-phase STS is done similarly using the topology shown in Fig 4. In this case the short circuit fault is assumed to occur at the input of SW 1 as shown in the above mentioned figure. The test system for the study of protection coordination is shown in Fig. 8. Generators G1 and G2 are supplying power at 19.05 (line-to-neutral, rms) to the incoming feeder via 19.05 /6.35 (line-to-neutral, rms) transformers to the bus 1 and bus 2 respectively. These buses are connected by a Bus-tie SCB 3. The system frequency is 50 Hz. The each incoming feeder has a resistance of 27.225 Ω and an inductance of 346.5 mh while the transformer has leakage inductance of 346.5 mh referred to the primary side. Down stream feeders 4, 5 and 6 each have the sum of feeder and load resistance of 60.5 Ω and inductance of 770.3 mh. The load supplied through SCB 7 has resistance of 30.25 Ω and inductance of 385.15 mh. This implies that for a base voltage 33 (L-L) and a base MVA of 1.0, the incoming feeder impedance is 0.025 + j0.1 pu and the leakage inductance of the transformer is j0.1 pu. The impedance of each of the downstream feeders 4, 5 and 6 is 0.5 + j2.0 pu and the load labeled 7 impedance is 0.25 + j1.0 pu. The steady state current in the feeders 4, 5 and 6 is 24.30 A (rms), i.e., 0.463 pu. Load 7 draws 48.60 A (rms) i.e. 0.926 pu. If the bus-tie is in closed position, the same amount of current will be supplied by the both sources which is 60.625 A (rms), i.e., 1.1575 pu. By the network topology 12.15 A, i.e., 0.2315 pu current is passing through bus-tie. This power delivery system is simulated in PSCAD/EMTDC software package and proper coordination is achieved. G 1 19.05 19.05 G 2 27.225 W 27.225 W 346.5 mh Outgoing Feeder 4, 5 and 6 346.5 mh T 2 19.05/6.35 19.05/6.35 SCL1 Bus-tie SCL2 Bus 1 I 1 I 3 I 2 Bus 2 I 4 I SCB3 F1 5 I F 6 I F2 7 SCB4 SCB5 SCB6 SCB7 F4 F5 F6 F7 F F30.25 Ω F 60.5 Ω 60.5 Ω 60.5 Ω 385.15 mh 770.3 mh 770.3 mh 770.3 mh Fig.7 Test distribution system. T 2 Lo Load 7

428 NATIONAL POWER SYSTEMS CONFERENCE, NPSC 2002 VIII. SIMULATION RESULT AND DISCUSSION The simulation studies have been divided into following four cases 1. Case-a: Static Current Limiter (SCL) 2. Case-b: Static Circuit Breaker (SCB) 3. Case-c: Static Transfer Switch (STS) 4. Case-d: Coordination Issues In all cases the operation of the protective devices and their coordination issues has been studied using the per phase equivalent circuit for a short circuit fault at or near the load terminal. Successful operation of the protective devices has been illustrated by waveforms of voltages and currents in the test system. Case-a: Static Current Limiter (SCL) The SCL is connected in line to limit the fault current. The value of the let-through inductor is chosen as 500 mh and the clipping voltage level of the ZnO arrester is chosen as 6.9. The system response to a short circuit at the load terminal at time t=0.21 sec is shown in Fig. 8.The load voltage falls to zero immediately and the load current free wheels to zero in local loop. The feeder current magnitude is sensed and the GTO based static switch is commutated as soon as the current reaches 40 A (0.76 pu). The current through the let-through inductor can not rise instantaneously. Therefore initially the feeder current passes through the ZnO arrester. Later the feeder current flows through the let through inductor and the arrester in parallel. As seen in figure the feeder current has to a peak of about 105 A (2 pu). Thus the fault level is reduced from the value of about 20 pu to 2 pu by the use of SCL. The voltage across the Static Switch is limited to 6.9 by the arrester. Again the fault current is the sum of the current I i and. The arrester current dominates this current. V l V z +8-8 I i -0.2-0.12 I sw 0 0.1 0.2 0.3 0.4 0.5 Time Fig.8. SCL protected system response for an arrester clipping voltage level 6.9. If the arrester voltage level is increased to 13.8, the system response is shown in Fig.9. Now the let through inductor current is predominantly the fault current. It may be noted that increasing the voltage level reduces the arrester current. This will however increase the voltage across the Static Switch. In Fig.9 it is 9 which is the about the peak of the system voltage because the arrester clipping voltage level is higher than the peak of the system voltage. V l V z Il I i -0.12-0.12 +0.001-0.001 I sw 0 0.1 0.2 0.3 0.4 0.5 Fig.9. SCL protected system response for an arrester clipping voltage level 13.8. Case-b: Static Circuit Breaker Time The SCB is simulated for the same feeder as in case-a above Simulated result is shown in Fig 10.The fault is created at t = 41 ms. The fault current flowing to feeder through VCB is sensed and compared with a specific limit. I b I sw +0.25 +0.1-0.04 +0.25 +0.07-0.01 0 0.02 0.04 0.06 0.08 0.1 Fig.10 System response with SCB.

+6-6 -2 2 +0.07-0.042-0.014-0.03 +0.03 INDIAN INSTITUTE OF TECHNOLOGY, KHARAGPUR 721302, DECEMBER 27-29, 2002 429 The GTO based Static Switch is turned on when the feeder current crosses the limit. At the same time a trip signal is given to the VCB and it is assumed to turn off on its own. The turn off time is very small and may be neglected. The GTO based Switch is kept on for a short fixed time interval (1.25 ms) as there is no current limiting inductor in this topology. At the end of this interval the switch is commutated. The total time interval to interrupt the fault current depends upon the time instant when the fault occurs and the value of the current limit. The total interrupting time for the fault at time t = 41 ms is observed to be 4 ms, which is much smaller than that of the mechanical circuit breaker. In this topology the arrester current is smaller than SCL topology as GTO is used to interrupt the fault current. Case-c: Static Transfer Switch The system topology for this case is shown in Fig. 4 and it is assumed that a fault occurs on the preferred feeder. Simulation result for thyristor based STS switch is shown in Fig.11 with make-before break strategy The typical transfer time is observed to be 8 ms but this is not a constant for all the conditions. It varies from 7 ms to 12 ms and depends on many factors. Some of these factors are: relative magnitude of source voltages and their phase difference, feeder impedance, load impedance, fault detection time, whether the load is passive or active etc. I ps I as -0.06-0.04-0.06 0 0.04 0.08 0.12 0.16 0.2 Fig.11 Make-before-break switching with thyristor based STS. to flow through STS components This is shown in Fig.12. This may damage the STS and destroy the power quality of the sensitive load. To eliminate the possibility of such large current flowing in switches, the transfer in that case has to break before make. This implies that the switching of S w2 has to be delayed till the current through out going switch to became zero. (ka I ps (ka I as (ka -0.04 0.2 0.3 0.4 0.5 3-0.039-0.04 0.2 0.3 0.4 0.5 0 0.04 0.08 0.12 0.16 0.2 Fig. 13 Make -before -break switching with GTO based STS. Simulation result when GTOs are used instead of SCR is shown in Fig. 13. The operation is independent of fault instant and other operating conditions. The load transfer time is 6ms, which is almost constant for all the switching conditions. This is 2 to 6 ms less than that of the SCR case discussed above Case-d: Coordination Issues The simulated Steady State response of the Test System is shown in Fig. 14 The system is examined for various unhealthy conditions, which are summarized in Table 1 and results are discussed. The SCL 1 and 2 provide primary protection for the fault at the bus and back up protection to the down stream feeders and load. Similarly SCB 3 functions differently for bus fault and fault at feeders. For the fault at bus it is compulsory for this to isolate the healthy section from unhealthy section within a short time. But in case of fault at the feeders, which +5 () ( a ) Bus 1 voltage : Vb1 +0-5 Ips I as +0.8 0.0-0.8 +0.2-1.2 0.0 ) ( +2 +0.014 0 ( b ) Bus 2 Voltage: Vb2 0 c ) Current Through Bus-Tie : I3 ( 0-0.07 (sec) Time Upper Stream Feeder Current Upper Stream Feeder Current d ) Feeder 1 Current : I1 +0.25 ( e ) Feeder 2 Current : I2 +0.25 ( -0.06 0 0.04 0.08 0.12 0.16 0.2 Fig.12 Current during incorrect transfer for a fault in the preferred feeder. MBB strategy is also not applicable for all the operating conditions as this may lead to temporary transfer of the fault from unhealthy side to healthy side witch cause large current Currents Down Stream Feeder Feeder 4 Current : I4 ( +0.075 f ) 5 0.24 0.32 0.4 0 0.08 0.16 (sec) Time Stream Feeder currents Down Current : I6 ( +0.075 h 6 Feeder ) 5-0.045 0-0.045 0 g ) Feeder 5 Current : I5 +0.075 ( i ) Feeder 7 Current : I7 ( 5 +0.09-0.045 0-0.09 0

+6-6 -2 2 +0.07-0.042-0.014 Stream Feeder Current Upper d ) Feeder 1 Current : I1 ( -0.03 +0.03 ( a ) Bus 1 voltage : Vb1 430 +5 () +0 NATIONAL POWER SYSTEMS CONFERENCE, NPSC 2002-5 0 are primarily protected by the SCBs connected to the concerned feeder, SCB 3 provides back protection. ) ( +2 ( b ) Bus 2 Voltage: Vb2 Fig 14 Steady state response of the test system. 0 ( c ) Current Through Bus-Tie : I3 Table I. Various Faults and Coordination of Protection Devices. +0.014 0-0.07 Upper Stream Feeder Current e ) Feeder 2 Current : I2 +0.25 ( +0.25 0 Down Stream Feeder Currents Down Stream Feeder currents +0.075 +0.075 ( h ) Feeder 6 Current : I6 ( f ) Feeder 4 Current : I4 5 5-0.045-0.045 0 0 +0.075 ( i ) Feeder 7 Current : I7 ( g ) Feeder 5 Current : I5 5 +0.09 To achieve the goal, the current settings of SCL 1 are chosen to be 120 A (i.e. 2 pu) of the normal rms value of the current I 1 as primary protection. For the back up protection of down stream feeders 4 and 5, the current settings are taken as 144 A (i.e. 6 pu) of their normal rms values. The SCLs operate for 5 cycles of the supply. The current setting of SCB 3 are 30 A (2.5 pu) for primary protection and 6 pu of the normal rms current of the corresponding feeder and load for back up protection. The current setting of SCB 4, 5, 6 and 7 are fixed at 2 pu of the normal values of rms currents of the respective feeders and load. The detailed simulation results for the fault at feeder 4 are shown in Fig. 15. Similar results have also been obtained for faults at other locations given in Table I [4]. 0-0.045 0-0.09 [2] Smith R. K., Slade P.G., Sakozi M., Stacey E. J., Bonk J. J., Mehta H. Solid State distribution current Limiter and Circuit Breaker: Application Requirements and Control strategies. IEEE Trans. Power Delivery, Vol.8, No.3, July 1993, pp 1155-1164. [3] A. Ghosh and G. Ledwich, Power quality enhancement using custom power devices, Kluwer Academic Publishers, Boston, 2002. [4] R. L. Meena, FRIENDS Devices and Their Coordination, M.Tech thesis, Electrical Engg. Deptt., IIT Kanpur, July 2002. Fig 15 System response for fault at feeder 4. IX. CONCLUSION The topologies of the various FRIENDS devices; SCL, SCB and STS have been described and their operation has been simulated. The clipping voltage of the ZnO arrester influences the current sharing between the ZnO arrester and the let-through inductor of the SCL. A higher clipping voltage increases the current through the let through inductor. In the SCB, the static switch is normally off, thus reducing the conduction losses. The current is shown to be interrupted within 4 ms which is much faster than the mechanical circuit breakers. In the STS, the GTO based static switch is shown to be faster than the thyristor based switch. It further simplifies the control strategy. The simulation results demonstrate the coordination of test system for various faults. I X. REFERENCES [1] Masakazu Takami, Toshifumi Ise and Kiichiro Tsuji, Studies toward a Faster, Stabler and Lower Losses Transfer Switch, IEEE Power Engg. Society Winter Meeting 2000, Vol. 4, pp 2729-2734.