USER MANUAL 600A AC Clamp Meter + NCV Model MA610

Similar documents
USER MANUAL. Model MA A AC Clamp Meter DMM Model MA445 True RMS 400A AC/DC Clamp Meter DMM

EX350 Series USER GUIDE. True RMS Digital Multimeters. EX350 True RMS Digital Multimeter EX355 True RMS Digital Multimeter with Temperature

EX360 Series USER MANUAL. True RMS Digital Multimeters. EX360 True RMS Digital Multimeter EX363 True RMS DMM with Temperature and µa AC/DC

USER MANUAL. Model MA A AC Mini Clamp-on Meter. Additional User Manual Translations available at

400Amp True RMS AC Clamp Meter + NCV

User s Guide. 400A AC/DC Clamp Meter. Model MA Washington Street Melrose, MA Phone Toll Free

400Amp True RMS AC/DC Clamp Meter Model EX613

User's Guide. 800 Amp AC/DC True RMS Clamp Meter. Model EX Washington Street Melrose, MA Phone Toll Free

200Amp AC Clamp Meter + NCV Model MA250

User s Guide. 400A AC/DC Clamp Meter. Model MA220

USER MANUAL. Mini Multimeter with Non-Contact Voltage Detector (NCV) Model EX330

AC/DC Clamp Meter. Owner's Manual. Model No Safety Operation Maintenance Español

Digital Clamp Meter Model: &

DL6508 User's Guide. 1500Amp True RMS AC/DC Clamp Meter

R/C SMD Tweezers Multimeter Model RC200

User s Guide. Digital AC/DC Clamp Meter Model 38394

User Guide. Digital AC/DC Clamp Meter Model 38394

Instruction Manual ICM 3091N Digital AC Clampmeter EN FR IT DE ES

Compact Autoranging Clamp Meters. Models (400 A AC), (400 A AC/DC)

User's Guide Extech EX Amp Clamp Meter with IR Thermometer

Compact MultiMeters + Voltage Detector

AC/DC CLAMP METER USER S MANUAL

User s Guide. Model MA A AC Mini Clamp-on Meter

User's Guide Mini Multimeter with Non-Contact Voltage Detector (NCV) Model EX330

CL900. True RMS 1000V 2000A 60MΩ ENGLISH. INSTRUCTION MANUAL 2000A Digital Clamp Meter. Measurement Technology

USER'S MANUAL DMR-6700

Mini Clamp Meter Model:

UT207A/208A/209A Operating Manual. Table of Contents

DM-45 Digital Multimeter

Model: &

400Amp True RMS AC/DC Clamp Meter with IR Thermometer Model EX623

99 Washington Street Melrose, MA Fax TestEquipmentDepot.com # # AAC Clamp Meter. Instruction Manual

Not for Reproduction

MS2030 CAT III 600 V A V AUTO RS232

ET-3888 True RMS Clamp Meter. User Manual

USER'S MANUAL ACDC-100 TRMS ACDC-100. Versatile AC/DC Clamp-on Multimeter Series

Safety. This symbol, adjacent to a terminal, indicates that, under normal use, hazardous voltages may be present.

CONTENTS MS2033A. 1.Introduction Safety Information...01

User Manual Digital Clamp Multimeter. model no.: MSR-C600

AMM-1022 Digital Multimeter USER`S MANUAL

User's Guide. Extech 800 Series 1000 Amp Clamp Meters with IR Thermometer

True RMS Digital Multimeter Model:

MM V 10A ENGLISH. INSTRUCTION MANUAL Auto-Ranging DATA HOLD AUDIBLE CONTINUITY MIN / MAX TEMPERATURE DIODE TEST CAPACITANCE

IDEAL INDUSTRIES, INC. TECHNICAL MANUAL MODEL: MODEL: Multimeter Service Information

User s Manual. MiniTec TM Series. Model MN26 (Model MN26T includes temperature probe) Mini Autoranging MultiMeter

Model True RMS AC/DC 30A Mini Clamp-on Meter. User Guide

NOTE: Fully read and understand this manual before using this Digital Multimeter.

INSTRUCTION MANUAL. Model Autoranging DMM ProbeMeter TM. Measures voltage, resistance, frequency, capacitance, temperature, and duty cycle.

User Guide. AC/DC Mini Clamp Meter. Model

OPERATOR S INSTRUCTION MANUAL M-2625 AUTO RANGING DIGITAL MULTIMETER

Electrical Multimeter

Autoranging Multimeter Extech EX503

MM700. True RMS ENGLISH. INSTRUCTION MANUAL Auto-Ranging. Measurement Technology

USER MANUAL. UV AB Light Meter. Model UV505. Additional User Manual Translations available at

DVM1190 DIGITAL MULTIMETER

IDEAL INDUSTRIES, INC. TECHNICAL MANUAL MODEL:

DIGITAL MULTIMETER OPERATOR'S INSTRUCTION MANUAL HOLD 10A COM LIGHT MS8265 ON/OFF. 200M KHz 2K 20K μ μ μ n.

AC/DC DIGITAL CLAMP METER OPERATION MANUAL

User Manual Digital Multimeter

1. SAFETY INFORMATION.1 2. DESCRIPTION SPECIFICATIONS.6 4. OPERATING INSTRUCTION Voltage measurement Current measurement 10

79/26 Series III Multimeter

CM605. User Manual AC/DC LOW CURRENT CLAMP-ON METER ENGLISH

MS8268 HANDHELD DIGITAL MULTIMETER OPERATOR S INSTRUCTION MANUAL

MS8250D DUAL DISPLAY DIGITAL MULTIMETER User s Manual

HANDHELD DIGITAL MULTIMETER OPERATOR S INSTRUCTION MANUAL

KMD-S04 Multímetro de bolsillo

ETHOS 5030 TRUE-RMS DIGITAL MULTIMETER OPERATION MANUAL

DIGITAL DUAL DISPLAY AC/DC CLAMP METER MODEL-860A OPERATION MANUAL

MM700. INSTRUCTION MANUAL Auto-Ranging Digital Multimeter True RMS

AM-510 Commercial / Residential Multimeter. AM-510-EUR Digital Multimeter. Users Manual

User Manual Digital Multimeter. model no.: MSR-U1000

MS8250A/B OPERATION MANUAL MS8250A. Hz% FUNC REL RANGE REL HOLD OFF 10A. Hz% A NCV. Hz% COM. A ma 10A FUSED 600V CAT IV.

User Manual. All rights reserved. Specifications are subject to change without notice.

Digital Multimeter, Pen Type

Thank you again for choosing AstroAI, if you have any questions or concerns regarding your product, please contact us at

Model UT201/202: OPERATING MANUAL. Table of Contents

INSTRUCTION MANUAL ACD-10 PRO & TRMS PRO

USER MANUAL. Extech EX850 True RMS 1000 Amp Clamp Meter. Bluetooth TM and Android TM ready. Patented

MODEL: D03128 CLAMP METER

PCMT20 PYLE C;",D J WWWPYLEAUDIO.COM

Model : OPERATING MANUAL Table of Contents (1)

312, 316, 318. Clamp Meter. Users Manual

Model 77 Series IV. Digital Multimeter. Users Manual

UT207/208. Digital Clamp Multimeter P/N:

IDM 98-III & IDM 99-III Digital Multimeters

Instruction Manual IDM 98-III & IDM 99-III Digital Multimeters

USER'S MANUAL. ACD-6 Pro. ACD-6 TRMS Pro. Versatile Clamp-on Multimeter Series

Sales: Technical: Fax:

User Manual. All rights reserved. Specifications are subject to change without notice.

MS8223A. CAT.IIi 600 V

Model: Pro95 TRUE RMS MILLIAMP CLAMP METER

Multifunction Digital

DCM730. Digital Clamp Meter User s Manual

BENNING. CM7 Electrical Tester. Service Information

600A Clamp Meters w/tightsight Display

Model UT10A: OPERATING MANUAL Table of Contents (1)

Handheld Digital Multimeter PRO-50A

OWNER S MANUAL HH0308C. AUTO-RANGING DC/True RMS AC DIGITAL MULTIMETER

OPERATOR S INSTRUCTION MANUAL

DVM98. True RMS Digital Multimeter. 1 Safety information. 1.1 Preliminary. 1.2 During use

Transcription:

USER MANUAL 600A AC Clamp Meter + NCV Model MA610 Additional User Manual Translations available at www.extech.com

Introduction Thank you for selecting the Extech MA610 Clamp Meter. This meter measures AC Current, AC/DC Voltage, Resistance, Capacitance, Frequency, Diode Test, Duty Cycle, Continuity and Non- Contact Voltage detection. This device is shipped fully tested and calibrated and, with proper use, will provide years of reliable service. Please visit our website (www.extech.com) to check for the latest version and translations of this User Manual, Product Updates, Product Registration, and Customer Support. Features Large backlit LED display 30mm (1.2") jaw size fits conductors up to 500MCM Relative and Zero mode functionality Auto Power OFF (APO) Non-Contact Voltage Detector Visual and audible continuity measurement alert Low battery indicator CAT III 600V Safety To ensure the safe operation and service of the meter, follow these instructions closely. Failure to observe warnings can result in severe injury. WARNINGS WARNINGS identify hazardous conditions and actions that could cause BODILY HARM or DEATH. When handling test leads or probes, keep hands and fingers behind the finger guards at all times. Remove test leads from the meter before opening the battery compartment or meter housing. Use the meter only as specified in this User Manual or accompanying Quick Start to avoid compromising the protections provided by the meter. Be sure to use the proper terminals, switch positions, and ranges when taking measurements. Verify the meter s operation by measuring a known voltage. Have the meter serviced if the meter responds unusually or if there are questions regarding the meter s functional integrity. Do not apply more than the rated voltage, as marked on the meter, between terminals or between any terminal and earth ground. Use caution working with voltages above 30 VAC RMS, 42 VAC peak, or 60 VDC. These voltages pose a shock hazard. To avoid misleading readings that could lead to electric shock and injury, replace the batteries as soon as the low battery indicator is displayed. Disconnect power to the circuit under test and discharge all high-voltage capacitors before testing resistance, continuity, diodes, or capacitance. 2 MA610-en-GB_V1.0 12/16

Do not use the meter in the presence of explosive gas or vapor. To reduce risk of fire or electric shock, do not use the meter if it is wet and do not expose the meter to moisture. Individual protective equipment should be used if HAZARDOUS LIVE parts in the installation where measurements are to be carried out could be accessible. CAUTIONS CAUTIONS identify conditions and actions that could cause DAMAGE to the meter or equipment under test. Do not expose the meter to extremes in temperature or high humidity. Disconnect the test leads from the test points before changing the position of the function (rotary) switch. Do not expose the meter to extremes in temperature or to high humidity. Never set the meter to the resistance, diode, capacitance, or amp functions when measuring the voltage of a power supply circuit; this could result in meter damage and damage to the equipment under test. Safety Symbols This symbol, adjacent to another symbol, indicates the user must refer to the manual for further information. Risk of electrical shock Equipment protected by double or reinforced insulation Diode symbol Capacitance Battery symbol Conforms to EU directives Complies with USA and Canada requirements AC measurement DC measurement Earth ground 3 MA610-en-GB_V1.0 12/16

PER IEC1010 OVERVOLTAGE INSTALLATION CATEGORY OVERVOLTAGE CATEGORY I Equipment of OVERVOLT AGE CATEGORY I is equipment for connection to circuits in which measures are taken to limit the transient over-voltages to an appropriate low level. Note Examples include protected electronic circuits. OVERVOLTAGE CATEGORY II Equipment of OVERVOLTAGE CATEGORY II is energy-consuming equipment to be supplied from the fixed installation. Note Examples include household, office, and laboratory appliances. OVERVOLTAGE CATEGORY III Equipment of OVERVOLTAGE CATEGORY III is equipment in fixed installations. Note Examples include switches in the fixed installation and some equipment for industrial use with permanent connection to the fixed installation. OVERVOLTAGE CATEGORY IV Equipment of OVERVOLTAGE CATEGORY IV is for use at the origin of the installation. Note Examples include electricity meters and primary over-current protection equipment Description Meter Description 1. Transformer current jaws 2. Jaw opening trigger 3. M (Mode) button 4. Backlit LCD 5. Control buttons (see descriptions below) 6. COM negative input terminal 7. Positive input terminal 8. Function selector 9. NCV alert lamp 10. Backlight button 11. NCV sensor Note: Battery compartment is located on back of meter Fig. 1 Meter Description 4 MA610-en-GB_V1.0 12/16

Display Description Relative mode icon Units of Frequency AC Alternating Current Units of Voltage DC Direct Current Units of Capacitance Negative readings Diode mode NCV Non-contact AC Voltage Detect Automatic range mode Continuity mode Display Hold Units of resistance Low Battery icon Duty Cycle Measurement overload Control Buttons Mode button: Short press to step through the mode options for the selected measurement function HOLD button: Short press to freeze/unfreeze reading Backlight button: Short press to turn backlight ON or OFF. Note that the backlight button is on the upper right side of the meter. For AC/DC voltage, AC current and Resistance modes: Short press to store the displayed reading as a reference value. Subsequent measurements will be displayed as measurement minus reference value. Short press to exit. For Capacitance mode, short press to zero the display; the LCD will show the delta symbol. Short press to exit this mode. Short press to step through frequency (Hz) and duty cycle (%) measurements for the Voltage and Hz switch positions. 5 MA610-en-GB_V1.0 12/16

Operation CAUTION: Read and understand all of the Safety statements listed in the safety section of this manual prior to use. Powering the Meter 1. Move the function switch to any position to power the meter. Check the batteries if the unit fails to power ON. 2. Move the function switch to the OFF position to remove power to the meter. 3. The meter has an Auto Power OFF feature (APO) where the meter switches OFF after 30 minutes of inactivity. Press any button to recover from an APO condition. Low battery indication When the icon appears in the display, the battery should be replaced. Refer to the battery replacement procedure in the maintenance section. 6 MA610-en-GB_V1.0 12/16

AC Current Measurements WARNING: Do not handle the meter above the finger/hand guard barrier. CAUTION: Observe CAT III 600V with respect to Earth Ground for the Jaw. 1. Rotate the function switch to the desired AC Current position (4A, 40A, or 600A). Start with the highest range setting (600A) and step down to lower ranges as needed, especially for signals that are of an unknown range. 2. The A and the AC symbols will appear on the display indicating AC Amperes (Amps). 3. Press the jaw trigger to open the clamp jaw. 4. Position the clamp around only one conductor. See Fig. 2 for correct and incorrect clamp technique. 5. Read the current in the display. The display will indicate the proper decimal point and value. NOTES: To ensure maximum accuracy, place the conductor at the center of the clamp head, otherwise additional error (± 1.0%) may apply. Fig. 2 Correct and Incorrect ACA Clamping 7 MA610-en-GB_V1.0 12/16

AC and DC Voltage Measurements WARNING: Do not apply > 600VAC/DC between the meter terminals and ground. CAUTION: When connecting the test leads to the circuit or device under test, connect the black lead before the red lead; when removing the test leads, remove the red lead before the black lead. 1. Set the function select switch to the Voltage position. 2. Use the M (Mode) button to select AC or DC Voltage. 3. Insert the black test lead banana plug into the negative (COM) jack and the red test lead banana plug into the red (V) jack. See Fig. 3. 4. Touch the test probe tips to the circuit or part under test. 5. Read the voltage in the LCD. The display will indicate the proper decimal point and value. 6. Relative (REL) mode can be used to set a reference reading from which subsequent readings will be offset (reference reading actual reading = displayed reading). Short press the REL button to store the displayed reading as a reference to which subsequent measurements will be compared. Short press the REL button to exit the relative mode. 7. The meter can display the frequency (Hz) or duty cycle (%) of the measured voltage. Short press the Hz % button to step through frequency and duty cycle readings. 8. Short press the H button to freeze/unfreeze the displayed reading. NOTES: The LCD displays OL when the input exceeds 1000V. Fig. 3 AC/DC Voltage Measurements 8 MA610-en-GB_V1.0 12/16

Resistance Measurements WARNING: Please remove power to the circuit under test and discharge all capacitors before taking resistance or continuity measurements. The meter will display OL if the circuit under test is an open circuit or if the measurement exceeds the maximum range of the meter. Do not input a voltage >30V AC or DC. 1. Turn the function switch to the Resistance Ω position. 2. Use the M (mode) button to select the ohm Ω display symbol. 3. Insert the black test lead banana plug into the negative (COM) jack. Insert the red test lead banana plug into the red (Ω) jack. See Fig. 4. 4. Touch the test probe tips across the circuit or part under test. It is best to disconnect one side of the part under test so that the rest of the circuit will not interfere with the resistance reading. 5. Read the resistance in the display. The display will indicate the proper decimal point and value. 6. Relative (REL) mode can be used to set a reference reading from which subsequent readings will be offset (reference reading actual reading = displayed reading). Short press the REL button to store the displayed reading. The Relative icon (triangle) appears when the Relative mode is active. Short press the REL button to exit the relative mode. NOTE: When measuring resistance >1MΩ the meter may require several seconds to obtain a stable reading. Fig. 4 Resistance Measurements 9 MA610-en-GB_V1.0 12/16

Continuity Measurements WARNING: Please remove power to the circuit under test and discharge all capacitors before taking resistance or continuity measurements. The meter will display OL if the circuit under test is an open circuit or if the measurement exceeds the maximum range of the meter. Do not input a voltage >30V AC or DC. 1. Turn the function switch to the Continuity position. 2. Use the M (mode) button to select the continuity display icon. 3. Insert the black test lead banana plug into the negative (COM) jack. Insert the red test lead banana plug into the red (Ω) jack. See Fig. 5. 4. Touch the test probe tips across the circuit or wire. 5. If the resistance is < 10Ω, the meter will beep. If the resistance is > 70Ω, the meter will not beep. If the resistance is between 10 and 70Ω, the meter will stop beeping at an unspecified point. Fig. 5 Continuity Measurements 10 MA610-en-GB_V1.0 12/16

Frequency Measurements WARNING: Do not input voltages > 30Vrms when measuring frequency. Turn the function switch to the Hz position. 1. Insert the black test lead banana plug into the negative (COM) jack. Insert the red test lead banana plug into the red jack. See Fig. 6. 2. Touch the test probe tips across the circuit or component. 3. Read the Frequency measurement on the meter display. 4. Use the Hz% button to view Duty Cycle %. Fig. 6 Frequency Measurements 11 MA610-en-GB_V1.0 12/16

Capacitance Measurements WARNING: Please remove power to the circuit under test and discharge all capacitors before taking capacitance measurements. 1. Turn the function switch to the position. 2. Use the M (mode) button to select the capacitor function if necessary. 3. Insert the black test lead banana plug into the negative (COM) jack. Insert the red test lead banana plug into the red jack. See Fig. 7. 4. Touch the test probe tips across the circuit or component. 5. Read the Capacitance measurement on the meter display. For readings > 400µF, several minutes may be required to obtain a stable reading. 6. Relative (REL) mode can be used to zero the display before taking a measurement. Short press the REL button to null the display, the relative symbol (triangle) will appear. Short press the REL button again to exit the REL mode. Fig. 7 Capacitance Measurements 12 MA610-en-GB_V1.0 12/16

Diode Test WARNING: Please remove power to the circuit under test and discharge all capacitors before taking diode measurements. Do not input voltages > 30V DC or AC to the meter. 1. Turn the function switch to the position. 2. Use the M button to select the diode icon. 3. Insert the black test lead banana plug into the negative (COM) jack and the red test lead banana plug into the red (V) jack. See Fig. 8. 4. Touch the test probes to the diode under test, in both polarity directions one at a time. 5. Forward voltage will indicate 0.5 to 0.8V. 6. Reverse voltage will indicate OL. 7. Shorted devices will indicate a reading close to 0 ohms in both directions. 8. An open device will indicate OL in both directions. Fig. 8 Diode Testing 13 MA610-en-GB_V1.0 12/16

Non-Contact Voltage-Detector (NCV) The area at the top of the clamp jaws is used for sensing AC voltage. When the electrical field is > 100V and the distance is < 10mm from the tip of the meter s clamp jaw, the beeper will sound and the red LED lamp will light. The NCV lamp flashes at the same rate as the beeper. The higher the field strength, the faster the beep rate and lamp flashing. When the sensed field is at highest levels, the meter s NCV lamp and beeper rate will become one continuous light and tone. If the meter does not react as described above to an AC voltage, there is still the possibility that a voltage is present. Please use caution. 1. Move the function switch to the NCV position. 2. In this mode, the meter will display OL and NCV. 3. Place the meter near a source of electrical energy. The tip of the clamp offers the highest sensitivity. 4. Note the beeping and the NCV lamp activation when an AC Voltage is sensed. Fig. 9 Non-Contact Voltage Detection 14 MA610-en-GB_V1.0 12/16

Maintenance WARNING: To avoid electrical shock, disconnect the meter from any circuit and turn OFF the meter before opening the case. Do not operate with an open case. Cleaning and Storage Periodically wipe the case with a damp cloth and mild detergent; do not use abrasives or solvents. If the meter is not to be used for 60 days or more, remove the batteries and store them separately. Battery Replacement 1. Remove the Phillips head screw at the back (near center) of the meter. See Fig. 10. 2. Open the battery compartment. 3. Replace the three (3) 1.5V AAA batteries observing correct polarity. 4. Re-assemble the meter before use. 5. Safety: Please dispose of batteries responsibly; never dispose of batteries in a fire, batteries may explode or leak; never mix battery types, install new batteries of the same type. Fig. 10 - BATTERY REPLACEMENT Never dispose of used batteries or rechargeable batteries in household waste. As consumers, users are legally required to take used batteries to appropriate collection sites, the retail store where the batteries were purchased, or wherever batteries are sold. Disposal: Do not dispose of this instrument in household waste. The user is obligated to take end-of-life devices to a designated collection point for the disposal of electrical and electronic equipment. Cleaning and Storage Periodically wipe the case with a damp cloth and mild detergent; do not use abrasives or solvents. 15 MA610-en-GB_V1.0 12/16

Specifications Electrical Specifications Accuracy is given as ± (% of reading + least significant digits) at 23C ±5C with relative humidity 75%. Accuracy is specified for a period of one year after calibration. Temperature Coefficient is 0.1 x specified accuracy / C, < 18C (64.5F), > 28C (82.4F) Function Range Resolution Accuracy (reading) OL Protection 4.000 A 0.001 A ± (2.5% + 30 digits) AC Current 40.00 A 0.01 A ± (2.5% + 5 digits) 600 A 1 A ± (2.0% + 9 digits) 4.000V 0.001V 600A AC Voltage 40.00V 0.01V 400.0V 0.1V ± (1.2% + 5 digits) 600V AC/DC 600V 1V ± (1.5% + 5 digits) 400.0mV 0.1mV ± (1.0% + 8 digits) 4.000V 0.001V ± (0.8% + 1 digit) DC Voltage 40.00V 0.01V 400.0V 0.1V ± (0.8% + 3 digits) 600V AC/DC 600V 1V ± (1.0% + 3 digits) Input Impedance: 10MΩ 400.0 Ω 0.1 Ω ± (1.2% + 2 digits) 4.000k Ω 0.001k Ω 40.00k Ω 0.01k Ω ± (1.0% + 2 digits) Resistance 400.0k Ω 0.1k Ω 4.000M Ω 0.001M Ω ± (1.2% + 3 digits) 40.00M Ω 0.01M Ω ± (2.0% + 5 digits) Open Circuit Voltage: Approx. 1.5V 600V AC/DC Continuity 400.0 Ω 0.1 Ω ± (1.2% + 2 digits) 600V AC/DC Continuity: Beeper ON < 10Ω. Beeper OFF >70Ω. Beeper unspecified >10Ω and <70Ω Diode 4.000V 0.001V Open Circuit Voltage: Approx. 1.5V Silicon PN junction 0.5 to 0.8V (typically) 600V AC/DC 16 MA610-en-GB_V1.0 12/16

50.00nF 0.01 nf ± (4.0% + 25 digits) Capacitance 500.0nF 0.1 nf 5.000 µf 0.001 µf 50.00 µf 0.01 µf ± (4.0% + 5 digits) 600V AC/DC 100.0 µf 0.1 µf Frequency (Hz) 10Hz~1MHz 0.01Hz~1kHz ± (0.1% + 4 digits) 600V AC/DC Sensitivity: (10Hz~1MHz): 200mVrms input amplitude 20Vrms Duty Cycle (%) 0.1 ~ 99.9% 0.1% ± (2.5%) 600V AC/DC Input amplitude: 500mVrms Input amplitude 20Vrms; Duty Cycle applies to 10kHz Square Wave Specified accuracy range: 10% ~ 90% range Non-Contact Voltage Detector (NCV) 100Vrms; 10mm (0.4 ) beeper sounds, and NCV lamp lights The tip of the meter offers optimum sensitivity 17 MA610-en-GB_V1.0 12/16

General Specifications Display Polarity Over-range indication Conversion rate Clamp Sensor Type Test position error Jaw Opening LCD 4000-count multi-function backlit LCD Automatic display of positive and negative polarity OL or -OL is displayed 3 updates per second Coil induction Additional error of ±1.0% of reading applies when the conductor under test is not positioned at the center of the clamp area 30mm diameter Electromagnetic field influence Unstable or inaccurate readings may be displayed if there is an electromagnetic field disturbance in the measurement environment Maximum Voltage 600V AC/DC maximum applied to any terminal Low battery indication is displayed Auto Power OFF After 30 minutes Operating Temperature and Humidity Storage Temperature and Humidity 0~30C (32~86F); 80%RH maximum 30~40C (86~104F); 75%RH maximum 40~50C (104~122F); 45%RH maximum -20~60C (-4~140F); 80%RH maximum (with battery removed) Operating Altitude 2000m (6562 ) Battery power 3 x 1.5V AAA alkaline batteries Weight 265g (9.3 oz.) Including batteries Dimensions (W x H x D) 77 x 228 x 41mm (3.0 x 9.0 x 1.6 ) Drop Protection 1m (approx. 3 ) Safety Standards Indoor use only; Complies with EN61010-1, CAT III 600V; Pollution Degree 2 Copyright 2016 FLIR Systems, Inc. All rights reserved including the right of reproduction in whole or in part in any form ISO-9001 Certified www.extech.com 18 MA610-en-GB_V1.0 12/16