High voltage engineering

Similar documents
Tab 8 Surge Arresters

Tab 2 Voltage Stresses Switching Transients

Power Quality and Reliablity Centre

Insulation Co-ordination For HVDC Station

Computer Based Model for Design Selection of Lightning Arrester for 132/33kV Substation

Utility System Lightning Protection

Transformers connected via a cable Overvoltage protection

Insulation Coordination Fundamentals Where Arrester and Insulator Characteristics Meet

Disclosure to Promote the Right To Information

MODIFICATION OF THE ARRESTER ARRANGEMENT WHEN CONVERTING THE METHOD OF NEUTRAL TREATMENT

HIGH VOLTAGE Insulation Coordination

10. DISTURBANCE VOLTAGE WITHSTAND CAPABILITY

LIGHTNING OVERVOLTAGES AND THE QUALITY OF SUPPLY: A CASE STUDY OF A SUBSTATION

EE 1402 HIGH VOLTAGE ENGINEERING

TECHNICAL NOTE 2.0. Overvoltages origin and magnitudes Overvoltage protection

Calculation of Transient Overvoltages by using EMTP software in a 2-Phase 132KV GIS

Session Four: Practical Insulation Co-ordination for Lightning Induced Overvoltages

PREVENTING FLASHOVER NEAR A SUBSTATION BY INSTALLING LINE SURGE ARRESTERS

OVERVOLTAGE PROTECTION OF POLE MOUNTED DISTRIBUTION TRANSFORMERS

Shunt Reactor Switching

OVERVOLTAGE PROTECTION. Dimensioning, testing and application of metal oxide surge arresters in low-voltage power distribution systems

A Study on Lightning Overvoltage Characteristics of Grounding Systems in Underground Distribution Power Cables

ABSTRACTS of SESSION 6

In power system, transients have bad impact on its

DIFFERENCE BETWEEN SWITCHING OF MOTORS & GENERATORS WITH VACUUM TECHNOLOGY

Analysis of lightning performance of 132KV transmission line by application of surge arresters

Electric Stresses on Surge Arrester Insulation under Standard and

A Case Study on Selection and Application of Lightning Arrester and Designing its Suitable Grounding Grid

APPLICATION OF LONG FLASHOVER ARRESTERS FOR IMPROVEMENT OF LIGHTNING PROTECTION AND OPERATING VOLTAGE RELIABILITY OF DISTRIBUTION LINES

CHOICE OF MV FEEDER BIL TO MAXIMIZE QOS AND MINIMIZE EQUIPMENT FAILURE

Protection against unacceptable voltages in railway systems

X International Symposium on Lightning Protection

2. Current interruption transients

Chapter 1. Overvoltage Surges and their Effects

CONTENTS. 1. Introduction Generating Stations 9 40

Simulation and Analysis of Lightning on 345-kV Arrester Platform Ground-Leading Line Models

Lightning Protection of Distribution Substations by Using Metal Oxide Gapless Surge Arresters Connected in Parallel

Switching Restrikes in HVAC Cable Lines and Hybrid HVAC Cable/OHL Lines

The impact of distributed generation to the lightning protection of modern distribution lines

Modeling insulation in high-voltage substations

GIS Disconnector Switching Operation VFTO Study

Lightning performance of a HV/MV substation

In order to minimise distribution (11 and 22 kv) feeder breaker

SAFETY ASPECTS AND NOVEL TECHNICAL SOLUTIONS FOR EARTH FAULT MANAGEMENT IN MV ELECTRICITY DISTRIBUTION NETWORKS

n 151 overvoltages and insulation coordination in MV and HV D. Fulchiron

EVALUATION OF DIFFERENT SOLUTIONS OF FAULTED PHASE EARTHING TECHNIQUE FOR AN EARTH FAULT CURRENT LIMITATION

When surge arres t ers are installed close to a power transformer, overvoltage TRANSFORMER IN GRID ABSTRACT KEYWORDS

FGJTCFWP"KPUVKVWVG"QH"VGEJPQNQI[" FGRCTVOGPV"QH"GNGEVTKECN"GPIKPGGTKPI" VGG"246"JKIJ"XQNVCIG"GPIKPGGTKPI

Lightning overvoltage and protection of power substations

Topic 6 Quiz, February 2017 Impedance and Fault Current Calculations For Radial Systems TLC ONLY!!!!! DUE DATE FOR TLC- February 14, 2017

Roll No. :... Invigilator s Signature :.. CS/B.TECH(EE)/SEM-5/EE-502/ POWER SYSTEM-I. Time Allotted : 3 Hours Full Marks : 70

Exercises. 6 Exercises

Substation Design Volume VII

Fixed Series Compensation

Modeling of overhead transmission lines with line surge arresters for lightning overvoltages. Poland

Vacuum Interrupters for Medium Voltage

I. INTRODUCTION II. MULTICHAMBER SYSTEM (MCS) A. MCS Principle

DEPARTMENT OF EEE QUESTION BANK

Electrical Power and Energy Systems

PANIMALAR ENGINEERING COLLEGE Department of Electrical and Electronics Engineering

Hazard of Induced Overvoltage to Power Distribution Lines Jiang Jun, Zhao Rui, Chen Jingyang, Tian Hua, Han Lin

SUBJECT CODE : EE6702 SUBJECT NAME: Protection & switchgear STAFF NAME : Ms.J.C.Vinitha

VFTO STUDIES DUO TO THE SWITCHING OPERATION IN GIS 132KV SUBSTATION AND EFFECTIVE FACTORS IN REDUCING THESE OVER VOLTAGES

Overvoltage Protection

The Many Uses of Transmission Line Arresters

Great Northern Transmission Line: Behind the (Electrical) Design

CHAPTER 2. v-t CHARACTERISTICS FOR STANDARD IMPULSE VOLTAGES

Energy Division. Bowthorpe LV/MV Surge Arresters

This is a preview - click here to buy the full publication

POWER FACTOR CORRECTION. HARMONIC FILTERING. MEDIUM AND HIGH VOLTAGE SOLUTIONS.

Estimation of Re-striking Transient Over voltages in a 132KV Gas insulated Substation

A Simple Simulation Model for Analyzing Very Fast Transient Overvoltage in Gas Insulated Switchgear

POWER TRANSFORMER SPECIFICATION, DESIGN, QUALITY CONTROL AND TESTING 18 MARCH 2009

Modeling for the Calculation of Overvoltages Stressing the Electronic Equipment of High Voltage Substations due to Lightning

POWER SYSTEM TRANSIENTS - Switching Overvoltages in Power Systems - Juan A. Martinez-Velasco, Jacinto Martin-Arnedo

A TECHNICAL REVIEW ON CAPACITOR BANK SWITCHING WITH VACUUM CIRCUIT BREAKERS

Transmission of Electrical Energy

Protection of Electrical Networks. Christophe Prévé

Transient Recovery Voltage (TRV) and Rate of Rise of Recovery Voltage (RRRV) of Line Circuit Breakers in Over Compensated Transmission Lines

INSTALLATION OF LSA ON A 400 KV DOUBLE-CIRCUIT LINE IN RUSSIA

Medium voltage circuit breaker technical guide

Precautions to be considered for use of surge arresters tested according to Class 1 of IEC

Our experience. Our products

MAHALAKSHMI ENGINEERING COLLEGE

Single Line Diagram of Substations

INTERNATIONAL STANDARD

ROEVER ENGINEERING COLLEGE ELAMBALUR, PERAMBALUR DEPARTMENT OF ELECTRICAL & ELECTRONICS ENGINEERING

High-Voltage Test Techniques

Effect of High Frequency Cable Attenuation on Lightning-Induced Overvoltages at Transformers

Selection of MO surge arresters Overvoltage protection

Secondary Arresters. Figure 1. Type L secondary surge arrester rated 175 Vac, 125 Vdc.

Estimation of Re-striking Transient Overvoltages in a 3-Phase 132KV Gas insulated Substation

AORC Technical meeting 2014

(2) New Standard IEEE P (3) Core : (4) Windings :

A SIMPLIFIED LIGHTNING MODEL FOR METAL OXIDE SURGE ARRESTER. K. P. Mardira and T. K. Saha s: and

GIS Instrument Transformers: EMC Conformity Tests for a Reliable Operation in an Upgraded Substation

A3-308 HIGH SPEED GROUNDING SWITCH FOR EXTRA-HIGH VOLTAGE LINES

ABSTRACT 1.0 INTRODUCTION LIST OF SYMBOLS

TECHNICAL SPECIFICATION

Substation Insulation Coordination Study

Transcription:

High voltage engineering Overvoltages power frequency switching surges lightning surges Overvoltage protection earth wires spark gaps surge arresters Insulation coordination

Overvoltages power frequency switching - lightning - Short time ( > U m ) 2 Ylijännitelajit

Power frequency overvoltages earth faults in unearthed & compensated neutral systems Þ maximum phase voltage» 1,05 3 U V U v is the normal phase voltage Flow of fault current in an earth fault in unearthed power system. U v = phase voltage before fault. R f = fault resistance. Voltages during an earth fault in unearthed power system. a) R f = 0, b) R f ¹ 0, U max» 1,05 Ö3 U v

Limiting the earth fault voltages Solid earthing; earth fault factor k 1,4 U k = T = U k ì í î X R V 1,4 0 0 / / X X 1 1 if Highest phase voltage (fault) Normal phase voltage 4,5 1,0 In Finland the 420 kv system is solid earthed Values of k, when R 1 = R 2 = 0,1 X 1

Power frequency overvoltages Ferranti-phenomenon: in no-load state the voltage of a line rises towards the end l r l r g c g c s ds s+ds U U U 2 = voltage in the line end U 1 = voltage in the line beginning 2 1 = 1 cos b s b = r << (r + l ; jwl) (g + & g s b = = << line length phase constant jwc) c Example: s/km U 2 /U 1 100 1,006 200 1,022 300 1,05 400 1,09 500 1,15 Þ b» w lc = 6 / 100 km (regardless the voltage!!!)

Energising a capacitively loaded network S k = short circuit power Q c = capacitive var production - compensation reactor absorption 420 kv system voltages (U) as a function of feeding point short circuit power (S k ) and undercompensation degree (Q c ).

Switching overvoltages: Interrupting capacitive current i t 2 t 3 t 1) current of C is cut off at time t 1 ; in C it remains a Ö2U voltage u t 1 2) half 50 Hz cycle later the voltage across k is 2Ö2U (t 2 ); restriking with frequency w =1/ÖLC t Ö2 U 3) if current interrupted 1. half cycle later (t 3 ), voltage in is C -3 Ö2U -3Ö2 U L k u(t) ~ C u(t) ( wl = << 2 U sin wt 1 wc )

Interrupting a small inductive current L k k i u i ~ u(t) C k C s u L s u(t) = 2 U cos wt After interruption the circuit behind k starts to oscillate with frequency: W w S = 1/ L S C Þ over voltage S Energy stored in L and C : = 1 2 C S u 2 0 + 1 2 L S i 2 0 = 1 2 C S u 2 L, max Means of limitation : breaker selection (restriking is Ok) opening resistors in CB increasing capacitance C s surge arresters

Switching an unloaded line Travelling wave phenomenon Of importance for lines over 300 kv High speed reclosing & residual charge Highest overvoltages even 3.5 p.u. Mitigation : closing resistors Þ 2 p.u. Voltage in line end when switching an unloaded line live a) one-line diagram of the circuit, b) voltages: graph 1: residual charge = 0 graph 2: residual charge = -1,0 p.u. Voltage in line end when switching an unloaded line in a strong transmission system. graph 1: no residual charge graph 2: residual charge -1,0 p.u.

Lightning surges thunder cloud and the lightning stroke Thunder cloud cross section Phases of a lightning stroke

Direct stroke to the conductor 1 2 2 u = 1 2 i Z 0 i = lightning current, Ex. 20 ka Z 0 = surge impedance, Ex. 450 W Þ u» 4,5 MV Þ always causes flashover Cross-arm unearthed (wood pole) Lightning stroke causes 3-ph fault Cross-arm earthed Bach flashover Earthed pole with shielding wires

Induced overvoltages stroke to the line vicinity 3-pole travelling wave created U < 200 300 kv problem mainly in MV networks Number of faults caused by lightning strokes for lines without shielding wires. 1 direct strokes, 2 induced overvoltages.

Means for limiting the overvoltages Voltage withstand curve of a 123 kv transformer. 1: steep surges, 2: slow surges, 3: short switching and, 4: long switching over voltages, 5: 50 Hz voltage, (1 min) circuit breaker selection closing / opening resistors parallel reactors protection capacitors shielding wires spark gaps surge arresters

Shielding wires used for 110 kv, 220 kv, 400 kv lines In 110 kv lines the number of lightning faults 7-fold in no shielding wires shielding angle q selected such that the currents with stroke distance higher than r s can not reach the phase conductors (r s ~ lightning current) r s» 6,7 i s 0,8 Ex. 20 ka Þ 74 m The dependence of shielding angle on the line geometry. r s ^ stroke distance The shielding angle q

Spark gaps a: s=80 mm or 100 mm b: s=60 mm or 80 mm Sparks gaps used for pole mounted secondary transformers used for < 200 kv pole transformers operation causes an earth fault Þ reclosing when operates, the surge voltage collapses Þ transformer must be tested for a cut surge large variation in the flashover voltage with steep surges, the flashover voltage strongly increased Voltage-time characteristics for lightning surges. a) estimation method, b) results for a 30 inch spark gap (positive polarity)

Surge arresters Two types: spark gaps in series with SiC-resistors ZnO - surge arresters Voltage - current characteristics of SiC and ZnO resistors Surge arrester types. (a) spark gap type, (b) active spark gap type, (c) ZnO - type. 1 = resistor, 2 = spark gap, 3 = active spark gap, 4 = blowing coil, 5 = by-pass resistor.

The operation of a surge arrester SiC û 1 = peak value of the incoming voltage û 2 = insulation level of the equipment u s = break down voltage (SiC only) û r = remaining voltage of the arrester û = peak value of 50 Hz voltage î s = peak value of the surge current î j1 = 50 Hz current in the spark gap î j2 = 50 Hz current in the active spark gap t 1 = time of break down ZnO

Transformer protection using spark gap or surge arrester A ^ a transformer, voltage strength for surges 550 kv, B ^ spark gap S = 79 cm, C ^ spark gap S = 66 cm, D ^ surge arrester U N = 120 kv, 1,2 ^ test voltage crest values Surge arrester location a) transformer connected in overhead line b) transformer connected in underground cable

Rated data of a surge arrester Protective level: highest voltage over the surge arrester. Withstand level voltage of the power system equipment must be 1,2-1,4 * protective level. Nominal voltage: highest voltage that the surge arrester can take without break down. Must be 5 10 % higher than maximum expected operation voltage of the power system considered. Nominal discharge current: current surge amplitude, that corresponds to the protective level. Standard values: 20, 10, 5, 2.5 ka Rated current: the capacity to discharge energy

Insulation coordination Fitting the insulation level and the protective level together Protective level U s margin Withstand level U w Max operation voltage U m U w vs. U m U w = withstand level = margin - lightning surges 1.2-1.4 - switching overvoltages 1.1-1.2 the ratio of protective level and operation voltage - in conventional surge arresters about 2.4 margin for surge arrester operation 10 % earth fault factor k highest normal operation voltage as phase voltage

Example. Unearthed system U m = 24 kv - earth fault factor k = 1.05 3» 1.82 - margin for surge arrester operation 1.1 - protective level / operation voltage 2.4 - margin between insulation level and protection level 1.4 Insulation withstand level: U w Um = 1.82 1.1 2.4 1.4 3 = 93.2 kv (Std IEC-71: 95 kv)

Example: Solid earthed system U m = 420 kv - earth fault factor k = 1.4 - margin for surge arrester operation 10 % - protection level / operation voltage 2.4 - margin between insulation level and protection level 1.2 Insulation withstand voltage: Um U w = 1.4 1.1 2.4 1.2 3 = 1075 kv (Std IEC-71: 1050 kv tai 1175 kv)

Statistical methods Failure risk : R = U U max ò min p(u) F(U) du - p(u) is the distribution of the voltage stresses - F(U) is the probability function of insulation strength Statistical insulation coordination. a) the risk of failure, b) the minimum of costs 1= insulation costs, 2=failure costs, 3=total costs

Statistical safety factor g g = U U W10 S2 -U W10 is the voltage level with a 10 % break down probability -U S2 is the voltage stress having a 2 % exceeding probability The definition of the variables in statistical safety factor definition