TD-106. HAEFELY HIPOTRONICS Technical Document. Partial Discharge Pulse Shape Analysis to Discriminate Near and Far End Failures for Cable Location

Similar documents
TD-100. HAEFELY HIPOTRONICS Technical Document

Evaluation and Limitations of Corona Discharge Measurements An Application Point of View

GENERATOR TESTING APPLICATION GUIDE. reliable. precision.

700 Series AC Dielectric Test Sets

EFFECT OF INTEGRATION ERROR ON PARTIAL DISCHARGE MEASUREMENTS ON CAST RESIN TRANSFORMERS. C. Ceretta, R. Gobbo, G. Pesavento

KIT 4.0 HIGH VOLTAGE CONSTRUCTION KIT. reliable. precision. HIGH V O L T A G E T E S T S OLUTION S

Modular Partial Discharge (PD) & Radio Interference Voltage (RIV) Detector

Mitigating Murphy s Law While Test. Frédéric Dollinger

THE PROPAGATION OF PARTIAL DISCHARGE PULSES IN A HIGH VOLTAGE CABLE

Practical aspects of PD localization for long length Power Cables

TMS 580. Transformer Loss Measuring System FEATURES BENEFITS APPLICATIONS

Chapter 12: Transmission Lines. EET-223: RF Communication Circuits Walter Lara

CABLE FAULT LOCATING APPLICATION GUIDE. HIGH V O L T A G E T E S T S OLUTION S. reliable. precision.

Effect of Shielded Distribution Cable on Very Fast Transients

HiAS TM 744 HIGHEST RESOLUTION IMPULSE ANALYZING SYSTEM

Investigation of PD Detection on XLPE Cables

TTR2796. Fully Automated Three Phase 250V Transformer Turns Ratio Meter FEATURES AND BENEFITS APPLICATIONS

Online Localisation of Partial Discharge Using Pulse Propagation Parameters in Medium Voltage Cable Network

4. Digital Measurement of Electrical Quantities

Improving CDM Measurements With Frequency Domain Specifications

NEW MV CABLE ACCESSORY WITH EMBEDDED SENSOR TO CHECK PARTIAL DISCHARGE ACTIVITY

TRAINING OVERVIEW EDUCATION IS POWER. HIGH V O L T A G E T E S T S OLUTION S. reliable. precision.

Automatic Transformer Winding Analyser

UNIT 2. Q.1) Describe the functioning of standard signal generator. Ans. Electronic Measurements & Instrumentation

Design and Construction of a150kv/300a/1µs Blumlein Pulser

Long lengths transmission power cables on-site testing up to 500 kv by damped AC voltages

Fully automated three phase 250V Transformer Turns Ratio Meter

New Features of IEEE Std Digitizing Waveform Recorders

Partial Discharge Measurement and Monitoring on High Voltage XLPE Cables

Standing Waves and Voltage Standing Wave Ratio (VSWR)

AC Dielectric Test Sets

Time Domain Reflectometry (TDR) and Time Domain Transmission (TDT) Measurement Fundamentals

The University of New South Wales. School of Electrical Engineering and Telecommunications. High Voltage Systems ELEC9712. Appendix Partial Discharge

Statistical Characteristics of Partial Discharge Caused by Typical Defects in Cable Joint under Oscillating Voltage

Sirindhorn International Institute of Technology Thammasat University

PULSE-SEQUENCE ANALYSIS OF PARTIAL DISCHARGES IN POWER TRANSFORMERS

Experiment 2: Transients and Oscillations in RLC Circuits

Measurement of Surge Propagation in Induction Machines

Analysis of Propagation Paths of Partial Discharge Acoustic Emission Signals

ON-LINE PARTIAL DISCHARGE TESTING OF SOME OF THE WORST PERFORMING CIRCUITS ON A UTILITY DISTRIBUTION SYSTEM

A Reflectometer for Cable Fault Location with Multiple Pulse Reflection Method

SG A. Impulse Voltage Test System, kv / kj APPLICATION

The Amazing MFJ 269 Author Jack Tiley AD7FO

P a g e 1 ST985. TDR Cable Analyzer Instruction Manual. Analog Arts Inc.

Exercise 1-2. Velocity of Propagation EXERCISE OBJECTIVE

IEC Electrical fast transient / Burst immunity test

The Principle V(SWR) The Result. Mirror, Mirror, Darkly, Darkly

Application Note 5525

Prediction of Transient Transfer Functions at Cable-Transformer Interfaces

Lab 1. Resonance and Wireless Energy Transfer Physics Enhancement Programme Department of Physics, Hong Kong Baptist University

For the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary and the secondary circuit.

The quality of the transmission signal The characteristics of the transmission medium. Some type of transmission medium is required for transmission:

Comparison of IC Conducted Emission Measurement Methods

Lecture Fundamentals of Data and signals

FREQUENCY RESPONSE OF R, L AND C ELEMENTS

RCTrms Technical Notes

Ref: HO 50-S/SP33, HO 100-S/SP33, HO 150-S/SP33, HO 200-S/SP33, HO 250-S/SP33

Implementation of Orthogonal Frequency Coded SAW Devices Using Apodized Reflectors

Lecture 16 Microwave Detector and Switching Diodes

Bill Ham Martin Ogbuokiri. This clause specifies the electrical performance requirements for shielded and unshielded cables.

Study of Inductive and Capacitive Reactance and RLC Resonance

High voltage amplifiers and the ubiquitous 50 Ohm: Caveats and benefits. Falco Systems application note, version 1.0,

A New TEM Horn Antenna Designing Based on Plexiglass Antenna Cap

CHAPTER 5 CONCEPT OF PD SIGNAL AND PRPD PATTERN

University of Jordan School of Engineering Electrical Engineering Department. EE 219 Electrical Circuits Lab

Model 310H Fast 800V Pulse Generator

Custom Interconnects Fuzz Button with Hardhat Test Socket/Interposer 1.00 mm pitch

a) Basic unit of an ideal transmission line b) an ideal transmission line

HO 50-S/SP30, HO 100-S/SP30, HO 150-S/SP30, HO 200-S/SP30, HO 250-S/SP30 and HO 200-S/SP31

I PN. Ref: HO 50-S, HO 100-S, HO 150-S, HO 200-S, HO 240-S, HO 250-S

CH85CH2202-0/85/ $1.00

Trees, vegetation, buildings etc.

CHAPTER 4 MEASUREMENT OF NOISE SOURCE IMPEDANCE

For the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary circuit and the secondary circuit.

New Technique Accurately Measures Low-Frequency Distortion To <-130 dbc Levels by Xavier Ramus, Applications Engineer, Texas Instruments Incorporated

HAMEG EMI measurement tools

User s Manual for Integrator Short Pulse ISP16 10JUN2016

University of New Hampshire InterOperability Laboratory Gigabit Ethernet Consortium

How to Analyze and Test the Location of Partial. Discharge of Single-winding Transformer Model

Design and experimental realization of the chirped microstrip line

Novità sulla IEC ; -10; -12

A Walk Through the MSA Software Vector Network Analyzer Reflection Mode 12/12/09

Effect of High Frequency Cable Attenuation on Lightning-Induced Overvoltages at Transformers

INVESTIGATION ON THE TECHNOLOGIES FOR DEFECT LOCALIZATION AND CHARACTERIZATION ON MEDIUM VOLTAGE UNDERGROUND LINES

10 Mb/s Single Twisted Pair Ethernet Evaluation Board Noise Measurements Marcel Medina Steffen Graber Pepperl+Fuchs

Transmission Line Transient Overvoltages (Travelling Waves on Power Systems)

Lab 1: Pulse Propagation and Dispersion

Power Frequency Withstand Voltage On-site testing of 400 kv GIS

Measurement Notes. Note 53. Design and Fabrication of an Ultra-Wideband High-Power Zipper Balun and Antenna. Everett G. Farr Farr Research, Inc.

Effect of Shielded Distribution Cables on Lightning-Induced Overvoltages in a Distribution System

Voltage Probe Manual and Data North Star High Voltage, Inc. Rev January 2016

Signal Characteristics

Specification. CTR 2 ESD calibration target

High Voltage Diagnostics Sarl 4, Rue de Lac CH 1897 Le Bouveret Switzerland

Alternative Coupling Method for Immunity Testing of Power Grid Protection Equipment

Power supplies are one of the last holdouts of true. The Purpose of Loop Gain DESIGNER SERIES

Power Quality Measurements the Importance of Traceable Calibration

University of Pennsylvania Department of Electrical and Systems Engineering ESE319

Insulation Level and Test Technology of. 1000kV Power Transformer

D D X. Digital Partial Discharge Detector

Transcription:

HAEFELY HIPOTRONICS Technical Document Partial Discharge Pulse Shape Analysis to Discriminate Near and Far End Failures for Cable Location P. Treyer, P. Mraz, U. Hammer Haefely Hipotronics, Tettex Instruments Division TD-106

The 20 th International Symposium on High Voltage Engineering, Buenos Aires, Argentina, August 27 September 01, 2017 PARTIAL DISCHARGE PULSE SHAPE ANALYSIS TO DISCRIMINATE NEAR AND FAR END FAILURES FOR CABLE TESTING Patrick Treyer 1*, Petr Mraz 1 and Urs Hammer 1 1 Haefely Hipotronics, Birsstrasse 300, 4052 Basel, Switzerland *Email: <treyer.patrick@haefely.com> Abstract: Apparent charge measurement according to IEC 60270 is performed during high-voltage cable routine test. In case the partial discharge (PD) level exceeds the specified acceptance limits, PD cable site location functionality enables the operator to locate the position of the failure. Due to various types of cable construction, different insulating materials and insulation wall thicknesses, and variable background noise levels it is difficult to determine an absolute value for the required accuracy of PD site location. However, experience has shown that an accuracy of 1% of the full cable length is achievable. Using commercially available PD site location analyzing systems it is more difficult or even impossible to locate faults closer than 20 meters from the cable far end. This issue is caused by pulse superposition resulting from the limited PD bandwidth of the test arrangement. An increase of the PD measurement bandwidth will lead to augmented noise levels and sensitivity to high-voltage connection lengths and local reflections. In this paper, the theory of PD site location on high-voltage cables is described and discussed. We present a novel approach for site location enabling the user to accurately discriminate between near and far end cable faults. The method is based on the recording and comparison of pulse widths and shapes at the time of calibration and during measurement in order to determine whether the failure is located at the near or far end of the cable. The influence of the coupling capacitor, cable termination and coupling impedance is assessed to provide recommendations for a successful test setup. 1 INTRODUCTION This paper revisits the theory related to cable fault location, investigates near/far end calibration characteristics and explores optimizations of the test setup and pulse processing using techniques such as matched filtering, derivative or autocorrelation for pulse width measurement. The paper concludes by an example and method to discriminate near and far end failures. Rather than finding an accurate model of a particular setup the purpose of this work is to propose a method that can be directly exploited in most situations. 2 THEORY Cable fault location mainly consists of measuring the time between partial discharge pulses. This section covers the basic theory to characterize the relevant parameters for faults located close to the cable ends. 2.1 Bandwidth and Pulse Separation The Nyquist theorem defines the main relationship between bandwidth (BW) and the maximum pulse rate which can be transmitted on a cable. The most well-known application of this theorem is the Nyquist filter, a digital filter used to transmit data in a limited BW reaching the theoretical limit of Equation 1. This limit applies as well to pulses that can be separated and detected in PD site location applications without (positive) superposition.!" =2#$% (1) BW = available BW in Hertz (Hz) PRF = Pulse repetition frequency in Hertz The optimum BW in time domain PD measurement for distribution cables is up to 20 MHz (but can be less depending on the cable length) which allows to separate pulses as close as 25 ns resulting in a spatial resolution of. 2.5 m [1,2,3]. Increased cable attenuation at higher frequencies as well as the influence of the coupling capacitor are the main limiting factors. PD pulses are generated in short burst sequences after each PD event, which leads to the possibility of using the pulse width to further detect superimposed pulses. 2.2 Sampling Rate and Time Resolution The sampling rate of the analog-to-digital converter (ADC) is the basic parameter defining the time resolution of the measuring system but the ultimate boundary for the time resolution is limited by the ADC sample and hold aperture jitter as well as ADC clock jitter and linearity. By means of signal processing the time and amplitude resolution can be increased to the limit determined by these additional parameters. An increase of the resolution by a factor of ten or more can be easily achieved.

2.3 Cable Characteristic Impedance and Reflection Coefficient The cable characteristic impedance can be either calculated from the insulation characteristics and the conductor sizes or from two impedance measurements with a short circuit and open termination of the cable [4].!(")=#!$%& (")' *+!,- (") (2) f = frequency (Hz) Z o = characteristic impedance Ω Z open = open end cable impedance in Ω Z short = shorted end cable impedance in Ω The reflection coefficient is given as follows [4]:.= / 01/ 2 / 0 3/ 2 = 4 5678 4 9:; (3) G = reflection coefficient Z L = load impedance in Ω E refl = reflected voltage wave E inc = incident voltage wave When the fault is close to one of the cable ends the pair of pulses appears as a single pulse due to superposition. 3 CALIBRATION 3.1 Calibration Pulse in Frequency Domain The test object C a according to IEC 60270 is supposed to be capacitive or to behave as a capacitor which is mostly the case for small test objects. However, the test object can also behave as a pure inductor [5] or as an LC network [6] - both cases allow equally valid calibration according to IEC 60270. In case of high-voltage cables the test object mostly behaves as an ideal resistor. This leads to a calibration pulse spectrum with lower cut-off frequency as per Equation 4.!"#($6%&)= ' *+,+-.+(/ 0 12 3 )+4 5 (4) F low = lower cut off frequency (Hz) R M = measuring impedance (Ω) Z o = cable characteristic impedance (Ω) C k = coupling capacitance (F) 2.4 Near and Far End Pulse Patterns Depending on the PD event location the recorded pulse sequence starts with a single isolated pulse or a pair of pulses. End A End B Figure 2 shows the schematic of a cable with 5 µs transmission delay which is terminated with its characteristic impedance of 30 Ω to avoid reflections. The calibrator model is an ideal swept current generator according to the method described in [5]. Transmission delay 5u Ck 20n RLoad 30 V Calibrator Model 200 Fault at far end Fault at near end Detector connected at End A Detector connected at End B Figure 1: Near end vs. far end pulse patterns. The subsequent pulses always appear as a pair of pulses. The time between the two pulses of a pair of pulses is proportional to the distance of the fault from the cable end. Figure 2: Calibration setup. This simple setup is used to confirm the flat pulse spectrum which is the first requirement to validate the calibration principle. 3.2 Calibration Pulse in Time Domain For the time domain, an ideal step generator V i combined with an ideal capacitor C i was used for simulation.

Ci 100p Transmission delay 1u Open/Load Ci Near End Transmission delay 100n + Vi Ck 20n V Rinf. + Vi Ck Near Rinf. R1 30 Ci T 1.00 Transmission delay 100n Far End Ck Far Rinf 690.22m Output 380.44m V 200 V 50 V 600 Ci PD Event Transmission delay 55n Transmission delay 45n 70.67m Ck PD Event Rinf -239.11m 0.00 10.00n 20.00n 30.00n Time (s) Figure 3: Time domain signal of the calibration pulse. Provided that C i << C k T 2.00 1.50 Far FiltFar FiltNear FiltPDevent Near PD Event PD Event Far End =! " #$ " and % &' = ( )#( * ( ) +( * (5) Output 1.00 Near End $ (, -./ = $ " #0 12 345#6 7 (6) 500.00m? 8 9 = : ; $ ( (, -.<</#>. * @ = ( ) ( ) +( * # (7) With Q m proportional to the injected charge q, the second requirement to validate the calibration principle is fulfilled. Here, no C i /C a requirements apply as for pure capacitive test objects since the cable behaves as a resistive load transmission line. In the case of cable test objects the important requirement is to keep C i small enough to avoid any variations of the reflection coefficient between calibration and measurement as well as to keep the BW of the calibration pulse higher than the system BW. 3.3 Near and Far End Calibration The circuit simulations shown in Figure 4 compare the pulse shape and magnitude for near end and far end calibration as well as for a PD event along the cable. The diagram shows both full bandwidth PD pulses (Far, Near, PD Event) and also 20 MHz low-pass (LP) filtered signals (FiltFar, FiltNear, FiltPDevent) which reveals the fact that the near end calibration pulse has the same charge magnitude as the PD event along the cable. On the other hand, the far end calibration pulse exhibits twice the magnitude (in fact the LP filter results in an integration of the pulse waveform hence reflecting the PD level). 0.00 0.00 37.50n 75.00n 112.50n 150.00n Time (s) Figure 4: Near end vs. far end calibration. The PD event signal is always measured equally by the PD detector. However, a difference is observed in the calibration factor which changes by a factor of two when calibrating at the near or far end. In the case of far end calibration, the full charge is entering the cable. In case of the PD event the charge is split into two pulses both carrying half of the full charge. The near end pulse has a magnitude of V i (PD Calibrator) whereas the far end and PD event pulses have a magnitude of 2*V i because of the reflection coefficient at the near end. The near end calibration signal is proportional to R eq /Z o while the far end calibration is proportional to 1+G. Since 2! "# $ % = &1 + ' (8) the charge reading for near end and far end calibration differs by a factor of two. Table 1 summarizes the calibration and measurement parameters when calibrating at the cable near or far end.

Table 1: Near and far end calibration parameters. Parameter Near End Far End V cal(t) &!"# '( ") *!"# Calibrator Load -./ = 0 1"- 2 0 0 1 3-1 2 V,cal(t) Q m,cal Q PD,inj Q m,pdevent PD Reading 8 $% $% $% +, ") * $% +, ") * &!"# '( ") *!"45367"# 0 1 9"0 1 "8 "8 0 1 3-2 0 1 3-2 5 9 ":!"! = 8 5 9 9 ":!"! = 8 9 0 1 0 1 "8 "8 0 1 3-2 0 1 3-2 8 9 V cal (t) = PD calibrator output voltage (V) V,cal (t) = R M voltage at calibration (V) Q m,cal = Q measured at calibration (C) Q PD,inj = PD event injected charge in one cable direction (C) Q m,pdevent = Q measured for PD event along the cable (C) PD Reading = Q m,pdevent / Q m,cal (C) The PD event charge splits into two pulses traveling in opposite direction but the measuring equipment only measures one of them, i.e. q/2. For near end calibration, the measuring equipment still measures q/2 but displays q due to the calibration factor. Far end calibration utilizes a reference pulse which has travelled along the cable; hence integrating the cable attenuation characteristics which is not the case for near end calibration. This is probably one reason for previous standards and papers to require that calibration in terms of charge be accomplished by injecting a known charge at the end of the cable remote from the detector [7]. The latest IEC 60885-3 standard requires now near end calibration in case of long cables without termination. Table 1 is therefore very useful to compare PD measurement results. Issues and discussions will mostly arise for long cable lengths in comparison of the measurement BW. 4 OPTIMIZED SETUP AND PROCESSING 4.1 Coupling Capacitor Model Matching R M to C k Their physical extension (1 m or more) indicates that coupling capacitors be modeled as a transmission line. We can consider the characteristic impedance to be close to 300 Ω (usual impedance of a connection wire in highvoltage impulse applications). This model leads to matching R M with the 300 Ω impedance of the capacitor instead of the characteristic impedance of the cable. Simulation in Figure 5 compares full response and 20 MHz limited BW for R M = 30 Ω and R M = 300 Ω. A 10 ns propagation delay is used to represent the typical height of a 2 m coupling capacitor, filtering should already be below 20 MHz to avoid oscillations and distortions of the measured PD pulse. C k Model T V30 + V300 V300Filt V30FIlt Vi 30.00m Ci 10p -10.00m 30.00m -10.00m 10.00m -4.00m 3.00m -1.00m Ck 20n Ra 30 Figure 5: Modeling and simulation of the coupling capacitor C k. 4.2 Matched Filtering Transmission delay 10n 0 Rstray 1 Cstray 50p V 0.00 100.00n 200.00n 300.00n 400.00n Time (s) A matched filter is a filter which optimizes the signal-to-noise ratio of the filtered signal. The samples of a reference pulse shape h(n) of duration T reversed in time directly serve as the filter coefficients as expressed in Equation 9. The filter output is maximized when the signal correlates with the reference pulse. (!)="(#$!) 0%!%# (9) For cable fault location, the reference pulse can be recorded during PD calibration. Assuming the PD calibrator connection leads are kept shorter than the expected length/time resolution and the injection capacitance is small enough in comparison to other stray elements connected at the cable end, the pulse will almost have the same shape as a single PD event. The shape is close to the real PD event including the attenuation and BW limitation of the overall system. Calibration can be performed at a higher discharge level or signal

averaging can be applied to ensure that the reference pulse is noise-free. The calibrator pulse must be short enough (i.e. C i small enough) such that the BW of the calibration pulse is larger than the available bandwidth of the system. BW limitation is necessary because the cable itself has a limited bandwidth. Noise in the higher frequency range is more likely to enter the measuring system because the coupling capacitor and the circuit wiring both act as antenna. Fault location at cable ends requires to detect and eventually separate superimposed pulses. 4.3 Pulse Width Measurement The pulse width can be measured from the matched filtered signal using the difference between two positive and negative maxima of the derivative. This method requires low processing power and is, in our example, almost as accurate as measuring the full width at half maximum (FWHM) of the auto-correlation of the pulse [7]. Figure 7: Detectable pulse resolution for far end calibration. 5 CABLE FACTORY TEST The figures in the present section are based on cable factory test data for a 12/20 kv XLPE cable. Figure 8 shows the PD detector measurement using the time between the first and second peak, the cable fault location is calculated at 5 m. Figure 6: Pulse width derived from derivative Figure 8: PD measurement, near end fault. Whatever method is used for the pulse width measurement, the pulse shape is the very limiting factor. The width of superimposed ideal exponential pulses as shown in Figure 3, can be measured with the matched filtered/derivative method from 1 sample delay. The sharp peaks are even more visible after matched filtering. For far end calibration, the recorded reference pulse has a limited BW and is very smooth at the peak value. As a result, the pulse width measurement is almost identical for superimposed pulses up to a shift of ten samples (one sample each 10 ns, which is equivalent to one meter in this example) as shown in Figure 7. This implies that for this case it is impossible to clearly distinguish and hence detect PD pulses originating from faults less than 10m from the far end. The same limitation is observed for the auto-correlation method. The graph from Figure 7 allows to assess the minimum pulse separation of the overall system, just by recording the calibration pulse. Figure 9: Far end calibration post processing.

- the ratio of the first pulse is < 1 - the ratio of the 2 nd pulse is ³ 1 - the ratio of the 3 rd pulse is ³ 1 7 CONCLUSION To verify the detection method, we have used a 200 m RG-58 coaxial cable and we have simulated faults at 2, 3 and 5 m with an SMA connector directly coupling to the inner conductor. The near end fault was correctly located in all of the three cases. For the far end the fault distance could not be exactly determined but the correct cable end was identified in all cases. Figure 10: Near end fault PD post-processing. Figure 9 and Figure 10 display post-processed calibration and measurement data using matched filtering. When using the matched filtered pulse, the distance between pulse #1 and #2 is increased to 7 m. The real fault was located at approx. 8 m. 6 RECOGNITION OF SUPERIMPOSED PULSES When the time between pulses #1-#2 and #2-#3 is close to the propagation time of a single cable length, this is an indication for superimposed pulses. The magnitude pattern shown in Figure 11 can give some hints to the location of the fault. Far End Pulse #1 #2 #3 #4 #5 Near End Figure 11: Near and far end patterns. Case 1) The first pulse is lower than the second pulse. In that case, the fault is most probably at the near end. Case 2) The first pulse is higher than the second pulse. In that case, the fault is most probably at the far end. Case 1) can also occur for far end failures, which depends on how the superimposed pulses combine and are being reflected at the cable end. An open far end always has some stray capacitance and stub caused by removing the cable shielding. This means that the termination cannot be considered as an ideal open circuit. It is a complex impedance, unmatched stub with either negative or positive reflection coefficients depending on the signal frequency. The ratio between measured pulse and far end calibration pulse can be used to distinguish a near end fault when: We have covered the influence of measuring impedance R M, coupling capacitor C k and near or far end calibration on cable fault location measurements. This reveals R M should be close to the coupling capacitor characteristic impedance, calibration should be performed at far end. The cable model for calibration is a resistor R a =Z o which comes in parallel with R M in case of near end calibration. The time between pulses can be measured even in case of superimposed pulses. Matched filtering allows to reduce noise in an optimal way and to correctly detect the pulse position to measure time differences. The PD pulse shape determines the limits of pulse width measurements. REFERENCES [1] C. Knapp et al., Signal Processing Techniques for Partial Discharge Site Location in Shielded Cables, IEEE Transactions on Power Delivery, Vol 5, No 2, April 1990. [2] S. Boggs, The Case for Frequency Domain PD Testing in the Context of Distribution Cable, IEEE Electrical Insulation Magazine, Vol 19, No 4, July/August 2003. [3] IEEE Std 400.3-2006, IEEE Guide for Partial Discharge Testing of Shielded Power Cable Systems in a Field Environment", February 2007 [4] R. Anderson et al., S-Parameter Techniques for Faster, More Accurate Network Design, Test & Measurement Application Note 95-1, Hewlett Packard, 1997. [5] P. Treyer et al., Breaking the Limit of Power Capacitor Resonance Frequency with Help of PD Pulse Spectrum to Check and Setup PD Measurement, ISH Pilsen, August 2015. [6] P. Treyer et al., Innovative Application of Frequency Response Analysis for Partial Discharge Measurement, ISH Pilsen, August 2015 [7] S. Boggs, G. Stone, Fundamental Limitations in the Measurement of Corona and Partial Discharge, IEEE Transactions on Electrical Insulation, Vol 7, No 2, April 1982.

The original version of this article was published in ISH 2017 proceedings: 20th International Symposium on High Voltage Engineering, Buenos Aires, Argentina, 2017 Locate our local sales representative at www.haefely-hipotronics.com OFFICES: Europe Haefely Test AG Birsstrasse 300 4052 Basel Switzerland ( + 41 61 373 4111 6 + 41 61 373 4912 š sales@haefely.com China Haefely Test AG Representative Beijing Office 8-1-602, Fortune Street No. 67, Chaoyang Road, Chaoyang District Beijing, China 100025 ( + 86 10 8578 8099 6 + 86 10 8578 9908 š sales@haefely.com.cn North America Hipotronics, Inc. 1650 Route 22 N Brewster, NY 10509 United States ( + 1 845 279 3644 6 + 1 845 279 2467 š sales@hipotronics.com HAEFELY HIPOTRONICS has a policy of continuous product improvement. Therefore we reserve the right to change design and specification without notice.