Study on closed loop operation of low voltage distribution network under three-phase unbalanced condition

Similar documents
Computer Control System Application for Electrical Engineering and Electrical Automation

Optimization of unipolar magnetic couplers for EV wireless power chargers

A Research of Single Phase Grounding Fault Location Method Based on the Component of Zero Sequence Current in Distribution Network

C I R E D 21 st International Conference on Electricity Distribution Frankfurt, 6-9 June 2011

RESEARCH ON CLASSIFICATION OF VOLTAGE SAG SOURCES BASED ON RECORDED EVENTS

Optimal Reactive Power Dispatch Considering Power Loss of Transformer

Simulation Analysis of Ferromagnetic Resonance of Low Magnetic Flux Density-Type PT under Single-Phase Earth Fault of 10kV Power Grid

Double Criteria Feeder-Selection Method for Single-Phase Ground Fault of Resonant Grounding System Based on Multi-State Components

Research on Parallel Three Phase PWM Converters base on RTDS

The Application of Visual Illusion in the Visual Communication Design

Inductive Power Supply for On-line Monitoring Device

The Pitch Control Algorithm of Wind Turbine Based on Fuzzy Control and PID Control

A Measuring Method about the Bus Insulation Resistance of Power Battery Pack

Mitigation of Negative Sequence Currents and Effect of Magnetic Inrush Currents in Indian Railway Traction System

Statistical analysis of low frequency vibrations in variable speed wind turbines

Current limiting characteristic of saturated iron core SFCLs

Enhanced RF to DC converter with LC resonant circuit

Study on New Type Magnetic Saturation Transformer Based on PDF Theory

Hybrid Simulation of ±500 kv HVDC Power Transmission Project Based on Advanced Digital Power System Simulator

An Improved Method of Adaptive Under Voltage Load Shedding

Busbar Differential Relaying Method Based on Combined Amplitude and Phase Information of High Frequency Transient Currents

The Simulation Experiments on Impulse Characteristics of Tower Grounding Devices in Layered Soil

Notes 1: Introduction to Distribution Systems

Research on HF Radio Propagation on the Sea by Machine Learning Optimized Model

SHORT CIRCUIT ANALYSIS OF 220/132 KV SUBSTATION BY USING ETAP

Analysis on exciting winding electromagnetic force of Turbogenerator under rotor interturn short circuit fault

Research on Parallel Interleaved Inverters with Discontinuous Space-Vector Modulation *

Research on the modeling of the impedance match bond at station track circuit in Chinese high-speed railway

Intelligent traffic control system using PLC

A compact ultra wideband antenna with WiMax band rejection for energy scavenging

Analysis of Temporal Logarithmic Perspective Phenomenon Based on Changing Density of Information

Research on State Estimation and Information Processing Method for Intelligent Substation

New ENT Laser Micromanipulator Design

Study on the Technology of Leakage Protection

MMC based D-STATCOM for Different Loading Conditions

The Beam Characteristics of High Power Diode Laser Stack

DESIGN OF OMNIDIRECTIONAL HIGH-GAIN AN- TENNA WITH BROADBAND RADIANT LOAD IN C WAVE BAND

Published in: IECON 2016: The 42nd Annual Conference of IEEE Industrial Electronics Society

Research on the smart measuring system for DC resistance box

UNBALANCED CURRENT BASED TARRIF

Analysis of the effect on propagation of voltage sag considering different winding connection modes of transformer

Airborne Wireless Optical Communication System in Low Altitude Using an Unmanned Aerial Vehicle and LEDs

Distribution system security region: definition, model and security assessment

A variable step-size LMS adaptive filtering algorithm for speech denoising in VoIP

Design of a 212 GHz LO Source Used in the Terahertz Radiometer Front-End

Response characteristic of high-speed on/off valve with double voltage driving circuit

High Power 12-Element Triangular-Grid Rectangular Radial Line Helical Array Antenna

TABLE OF CONTENT

Photovoltaic Cells Mppt Algorithm and Design of Controller Monitoring System

Modelling and Simulation of PQ Disturbance Based on Matlab

Classification of Voltage Sag Using Multi-resolution Analysis and Support Vector Machine

Applicability of a Hall Sensor in Directional Ground Fault Protections of MV Cable Networks with No-Effective Earthing

10kV XLPE cable ampacity improvement research in Guangzhou area

Reducing the Fault Current and Overvoltage in a Distribution System with an Active Type SFCL Employed PV System

A Calibration Method of Absolute Time Delay for Phased Array Antenna

Application Analysis of Electronic Power Transformer in Photovoltaic Power System

Frequency Control Method of Isolated Micro-grid Based on Thermostatically Controlled Load Qingzhu Wan1, a, Yuan Bian1, b and Yalan Chen1, c

Open Access Parallel Resonant DC Link Inverter for Thermoacoustic Power Generation

The relationship between operating maintenance and lightning overvoltage in distribution networks based on PSCAD/EMTDC

System grounding of wind farm medium voltage cable grids

IMAGE TYPE WATER METER CHARACTER RECOGNITION BASED ON EMBEDDED DSP

MV network design & devices selection EXERCISE BOOK

Discussion on the Deterministic Approaches for Evaluating the Voltage Deviation due to Distributed Generation

THE DESIGN OF RURAL POWER NETWORK POWER QUALITY MONITORING AND ANALYSIS PLATFORM ON LABVIEW

, ,54 A

The Coupling of Voltage and Frequecncy Response in Splitting Island and Its Effects on Load-shedding Relays *

Open Access On Improving the Time Synchronization Precision in the Electric Power System. Qiang Song * and Weifeng Jia

The Research on Neutral Grounding Scheme of Fengxian 35 kv and 10 kv Power Grid

Single Image Haze Removal with Improved Atmospheric Light Estimation

A Modified Gysel Power Divider With Arbitrary Power Dividing Ratio

Comparison and Research on Insulation Monitoring Methods For Marine Power System Wanxuan Zhu1, a, Zhiliang Wu2, b

Solution to Harmonics Interference on Track Circuit Based on ZFFT Algorithm with Multiple Modulation

Noise Removal of Spaceborne SAR Image Based on the FIR Digital Filter

On-Line Monitoring Analysis of Aeolian Vibration of Jiangmen-Tongtangjia 220kV Transmission Line

The Principle and Simulation of Moving-coil Velocity Detector. Yong-hui ZHAO, Li-ming WANG and Xiao-ling YAN

Hyperband Bi-Conical Antenna Design Using 3D Printing Technique

Australian Journal of Basic and Applied Sciences. Simulation and Analysis of Closed loop Control of Multilevel Inverter fed AC Drives

New Residual Current Compensation Method for Single-Phase Grounding Fault in Power Network Based on Capacitive Current Detection and Analysis

A HIGH-POWER LOW-LOSS MULTIPORT RADIAL WAVEGUIDE POWER DIVIDER

3rd International Conference on Machinery, Materials and Information Technology Applications (ICMMITA 2015)

Distance Protection for Distribution Feeders. Presented By: Yordan Kyosev, P.Eng. & Curtis Ruff, P.Eng.

Extraction of Gear Fault Feature Based on the Envelope and Time-Frequency Image of S Transformation

Design of high precision current signal source on DDS Han Ya Kun1, a, Suo Xue Song*,1, b

Impact of Distributed Generation on Voltage Regulation by ULTC Transformer using Various Existing Methods

International Journal of Current Research and Modern Education (IJCRME) ISSN (Online): & Impact Factor: Special Issue, NCFTCCPS -

A Study on Retrieval Algorithm of Black Water Aggregation in Taihu Lake Based on HJ-1 Satellite Images

Analysis of Computer IoT technology in Multiple Fields

Sound pressure level calculation methodology investigation of corona noise in AC substations

Effect of Frequency and Migration Aperture on Seismic Diffraction Imaging

A Study on Staggered Parallel DC/DC Converter Applied to Energy Storage System

Extensive LV cable network. Figure 1: Simplified SLD of the transformer and associated LV network

Open Access Application of Partial Discharge Online Monitoring Technology in ± 660kV Converter Transformer

Reliability Improvement Strategies for HVDC Transmission System

CHAPTER 4 POWER QUALITY AND VAR COMPENSATION IN DISTRIBUTION SYSTEMS

Hybrid Power Quality Compensator for Traction Power System with Photovoltaic Array

AS the power distribution networks become more and more

SUPERCONDUCTING MAGNETIC ENERGY

Statistical Characteristics of Partial Discharge Caused by Typical Defects in Cable Joint under Oscillating Voltage

SAMPLE EXAM PROBLEM PROTECTION (6 OF 80 PROBLEMS)

The Spatial Distribution Characteristics of IT Enterprises in Shanghai Caohejing Hi-Tech Park: Take the 24 Buildings as Example

Transcription:

IOP Conference Series: Earth and Environmental Science PAPER OPEN ACCESS Study on closed loop operation of low voltage distribution network under three-phase unbalanced condition To cite this article: Jing Zhang et al 2018 IOP Conf. Ser.: Earth Environ. Sci. 108 052124 View the article online for updates and enhancements. This content was downloaded from IP address 148.251.232.83 on 16/09/2018 at 00:45

Study on closed loop operation of low voltage distribution network under three-phase unbalanced condition Jing Zhang 1, Ming Jin 1, Yunguo Cheng 1, Dejun Wang 1, Kang Zhou 1, Xin Yan 2,* 1 Yuhang Power Supply Bureau, Hangzhou, China; 2 Wuhan University, Wuhan, China; *Corresponding author e-mail: whu_yx@163.com Abstract. The closed loop operation to achieve power load can greatly improve the power supply reliability of low-voltage distribution network, but because of the low voltage distribution network asymmetry and the difference of voltage loop, closed loop operation will not change the balance of system, generating loop impulse current, affect the safe operation of power grid. So this paper considers the low voltage distribution network closed loop current in the load transfer method, and through the simulation and analysis of the distribution network load rate and the unbalance of the loop current and loop distribution after unbalance effect, verify the closed loop operation of distribution network considering the unbalanced degree of necessity. 1. Introduction Low voltage power distribution network, as the end of the power grid, takes the important responsibility of providing safe and reliable electricity to the end users [1]. Due to the load types tending to diversification, it is more common that the low voltage distribution network works asymmetrically because of asymmetric line parameters, asymmetric three-phase load operation, access of single phase load [2]. At the same time, the user has higher requirement for power supply service quality. In order to improve the reliability of power supply, at present, China s power grid construction type adopts the model of "construction with closed loop and operation with open loop " [3]. The grid structure can not only improve the efficiency of the power configuration, but also down load without power cut which ensures power supply to the users by the closed loop operation when it is in fault, maintenance, engineering reform and load transfer. Comparing to exchange distribution equipment in short time, expanding the conductor cross section, increasing variable volume and other methods which can improve the reliability of power supply have the advantages of shorter time, less spend and high efficiency [4]. However, when making closed loop operation without power cut, because of the presence of voltage amplitude and phase angle difference on both ends of the closed loop, impulse current and steady-state current after through switch will produce impact on the grid at the moment when the loop is closing. So we need to check whether steady-state current can meet the requirements of equipment when operating closed loop. In the literature [5], the closed loop steady-state current is equivalent to the superposition between the open loop steady-state current and the equivalent current caused by the Content from this work may be used under the terms of the Creative Commons Attribution 3.0 licence. Any further distribution of this work must maintain attribution to the author(s) and the title of the work, journal citation and DOI. Published under licence by Ltd 1

voltage difference on both sides of the loopback point. The method does not take into account the load transfer caused by the loop operation, and the result compared to actual closed loop current has deviation; Literature [6] proposed the closed loop current affected by the closed loop feeder load distribution, and set up three kinds of typical load model, increasing, decreasing, uniform distribution and calculated the closed loop current to verify the load distribution has impact on closed loop current. But it did not put forward how to apply this method to the actual; in combination with the actual situation, literature [7] researched the impact that the voltage of closed loop point had on the closed loop current, and summed up the closed loop conditions and determination methods. But it did not give the calculation method of closed loop point voltage difference. At present, the criterions in view of closed loop current calculation and closed operation are most based on the study of medium voltage distribution network closed loop. The calculation of closed loop current are most based on the situation that the source voltage, the line impedance and the loads do not change before the loop closes. Besides, it does not consider the actual situation that the 380 voltage three-phase four-wire and low voltage distribution system works asymmetrically. The tide will redistribute while the network is making the loop closed. And it maybe cause the current in some lines over the limitation and the transformer imbalanced degree is more than allowance. For this defect, this paper proposed a method which could be applied to the practical situation, taking into account the load transformation, the calculation of simple closed loop current and closed loop point s voltage difference. Considering the asymmetry of low voltage distribution network running status and the national requirements of imbalanced degree, it also proposed the judgment basis of low voltage distribution network closing operation and verified the accuracy of the closed loop current s calculation by simulation. Otherwise, it analyzed the impact that the low voltage distribution transformer s load rate and the imbalanced degree had on the closed loop current and the imbalanced degree of distribution network after closing loop. 2. The calculation of closed loop 2.1. Closed loop steady-state current In low voltage distribution network, in order to meet the different electrical requirements of singlephase or three-phase loads, the distribution transformers are neutral-point solid ground system [8], so we can calculate in single phase when calculating the closed loop current. Due to wide distribution of low voltage distribution network, a single distribution transformer capacity is limited, short transmission distance, small load, small power loss, if we model and calculate according to the actual load distribution, it will be heavy work, time consuming and cannot be promoted in the practical application [9]. So it adopted the double end power network model to simplify the equivalent. Figure 1 is the typical closed loop grid of low voltage distribution network. ' ' Respectively, S T1, S T 2, S T1, S T 2 are two closed loop distribution transformers output power in low voltage side. U H is the bus voltage of the distribution transformer in high voltage side(if the closed loop grid does not belong to the same superior feeder, closed loop switch voltage difference on both ends is affected by the superior power grid operation state. Because the voltage difference and the risk of closing loop are huge, at present, there is the same superior feeder s low voltage distribution network closing loop when in the same area), S 1, S 2 are load power of the distribution transformer s main line, L 1, L 2 are load power of the unclosed loop distribution transformer s line, Z T 1, Z T 2 are the two distribution transformers resistance, U 2N is the distribution transformer s rated voltage in low voltage side, U is the both ends voltage difference in the closed loop point, k is the distribution transformer ratio. 2

10kV BUS U H Z T1 10kV/380V Transformer Z T2 S T1 380V Distribution line S T2 L 1 Contact switch L 2 S 1 I CB S 2 Before closing loop, the network power meet S S L S S L T1 1 1, T 2 2 2 Figure 1. Typical closed loop networks We calculate closed loop line s steady-state current ICB by using the way closed network power flow calculation. Now we assume the contact switch s power is S CB after closing loop, the line s resistance and the distribution transformer s voltage in high voltage side are not change. Then S CB ( S L ) Z ( S L) Z U U Z Z Z Z 2 2 T2 1 1 T1 L T1 T2 T1 T2 (1) ' T1 1 1 S S L S (2) CB So the closed loop steady-state current is ' T2 2 2 S S L S (3) CB I S ( S L ) Z ( S L) Z U CB 2 2 T2 1 1 T1 CB UL ( ZT1ZT2) UL ZT1ZT2 (4) Choosing the maximum of closed loop steady-state current is I m. We can see that the magnitude of the steady-state current value of the closed loop is mainly affected by the network current distribution, the distribution transformer s impedance, the closed loop point voltage difference from formula (4).With the difference of closed loop point s voltage, distribution transformer s load and distribution transformer s impendence increasing, the closed loop steady-state current will increase and it will decrease with distribution transformer s impendence increasing. 2.2. The difference of the closed loop point s voltage In the case of grid parameters and load determination, the key to obtaining circulation is to find the voltage difference. The losses calculated by converting distribution transformer s resistance in low voltage side into it in high voltage side are U T 1, U T 2.Then P' R Q' X P' X Q' R U (5) 1 1 1 1 1 1 1 1 T1= T T T T T T T T UH UH 3

P' R Q' X P' X Q' R U T2 T2 T2 T2 T2 T2 T2 T2 T2 (6) UH UH The voltage of distribution transformer in low voltage areu L1, U L2.Then U U L1 L2 U U H H U k U k T1 T 2 (7) The difference of closed loop s voltage is U U L1U L2. 2.3. The closed loop impact current Under normal circumstances, closed loop contact switch is normally open state. The distribution transformers independently supply their respective loads. When distribution transformer does not work or need repaired, it will need switching operation by closing contact switch and at the moment it will produce impact current [10].The maximum instantaneous value i M and the maximum effective value I M of closed loop can be calculated by using the calculation formula of short-circuit impulse current. They are 0.01/ T (1 a M ) m M m i e I k I (8) 2 2 2 M ( 1) 2 1 ( 1) CB M CB M CB I I k I k I (9) In the two formulas, k M is impact coefficient, T a is decay time constant, andt a L R L R T1 T2 T1 T2 3. Simulation Study This paper chooses a two 380V low voltage distribution network in Yuhang area of Hangzhou city to simulate and analyze, In the example, the distribution transformer on both sides of the loop is the same type. Its capacity is 400kVA. the connection mode is Dyn11. the impedance voltage is 4%. When the two distribution transformers three-phase load are balanced, the load rate in distribution transformer 1 is constant, but it in distribution transformer 2 varies from 0 to 100%. Its closed loop current calculation value changes as shown in Figure 2 solid line, the closed loop current simulation value changes as shown in Figure 2 dotted line. The figure on the right shows the transformer 1 load rate. Due to ignore line impendence when calculating, there is certain error between the calculation value and the simulation value, but the error can be accepted. It verifies the accuracy of the loop current calculation method. We can know when the two models with the same type closing, the closed loop current will increase with the two transformers load rate increasing and the closed loop current is minimum when the two distribution transformer rate is the same.. 4

Figure 2 Relationship between loop current and load rate of distribution transformer When the two distribution transformers loads are imbalanced, we assume the transformer 1 load s imbalanced degree is constant and A, B, C three-phase load rate from large to small is arranged as A> B> C; The transformer 2 load s imbalanced degree varies from 0 to 15% and A, B, C three-phase load rate from large to small is also arranged as A> B> C. When the total load rates of the transformer 1 and 2 remain unchanged and are 30%, The maximum change in the closed loop current in the three phases is shown in the solid line in Fig3. The distribution network s imbalance degree after closing loop is shown in the solid line in Fig4; When the total load rates of the transformer 1 and 2 remain unchanged and the total load rates are respectively 30% and 90%, The maximum change in the closed loop current in the three phases is shown in the dotted line in Fig3. The distribution network s imbalance degree after closing loop is shown in the dotted line in Fig4. We can know that the distribution transformer s imbalanced degree has slight impact on closed loop current by analyzing the curve in Fig3 and the closed loop current affected mainly by the closed loop load rate difference; The smaller the load rate difference in the closed loop, the smaller the variation range of the closed loop maximum current with the load imbalance. When the closed loop distribution transformer has the same load rate and the same direction of imbalance, the difference of imbalanced degree and the closed loop maximum current will be smaller. We can know that closing loop operation will change the distribution network s imbalanced degree by analyzing the solid line in Fig4. When the two distribution transformers have the same load rate and load s imbalanced degree, the imbalanced degree of the distribution network after closing loop is changed relative to that before the loop, its imbalanced degree is affected by the two distribution networks imbalanced degree before closing loop and bigger than the average of the two distribution networks imbalanced degree; We can know that the network's imbalanced degree after closing loop is mainly affected by the higher load's imbalanced degree before closing loop when the two closed loop distribution transformers' load rates are different and the difference is large by analyzing the dotted line in Fig4. When the distribution transformers imbalanced degree is 15% (The distribution transformer allows the maximum degree of imbalance) before closing loop, the distribution network s imbalanced degree is more than 15% after closing loop. So it is necessary to consider load shift caused by closing loop operation and calculate weather network s imbalanced degree can meet the requirement in the closed loop operation judgment condition. 5

Figure 3 Relationship between current and unbalance of distribution transformer loop Figure. 4 unbalance degree of distribution network after loop closing 4. Conclusion This paper mentioned the closed loop simplified calculation method in low voltage distribution network with considering load shift situation which improved the closed loop current calculation s accuracy. And for three-phase asymmetrical operation of low-voltage distribution network, it analyzed the impact that closing loop operation had on distribution network s imbalanced degree, improving the operation judgement conditions and safety. In the end, this paper verified the calculation method s accuracy and the correctness of theoretical analysis by simulation. References [1] LI Peng, Li Huisheng, Wang Rui, et al. Simulation of low voltage loop current based on PSCAD/EMTDC [J]. China electric power, 2016, 49 (12): 21-25. [2] SHEN Zhongwei. Application of 10kV single bus bar ring connection mode automatic switch over device[j].electric power science and technology journal, 2011, 26 (1): 114-117. [3] KANG Qingping, Lu Jinling, Yang Guowang. A method for determining the optimal segment number of urban 10kV distribution network [J]. automation of electric power systems, 2000, 24 (13): 57-59. 6

[4] Ji Y, Zhao J. Research on the loop closing operation analysis system in radial medium voltage distribution network[c]// China International Conference on Electricity Distribution. IEEE, 2008:1-5. [5] WANG Sai Yi, Wang Chengshan. Optimal segmentation of radiation lines in distribution networks [J]. automation of electric power systems, 2005, 29 (8): 50-54. [6] Sepasian M S, Seifi H, Foroud A A, et al. A new approach for substation expansion planning[j]. IEEE Transactions on Power Systems, 2006, 21(2):997-1004. [7] Xiang W, Zhang J, Luo G, et al. Fast loop closing-opening operation of two lines with 30 degree phase difference[c]// Chinese Control Conference. 2016:9957-9962. [8] Ji Y F, Zhao J H. Design and research on the loop closing operation analysis system medium voltage in radial distribution network[j]. Power System Protection & Control, 2009:1-5. [9] WU Zhenhui, Peng Xiaotao, Shenyang Wu, et al. Research on a loop power supply model and its closed loop operation mode of distribution network [J]. proceedings of the Chinese society of electrical engineering, 2013, 33 (10): 57-63. [10] Gan G, Wang Z, Zhou Y, et al. Reliability and Economy Based Closed-loop Operation Modes for Medium Voltage Distribution Networks[J]. Automation of Electric Power Systems, 2015, 39(16):144-150. [11] Xiao B, Zhao L A, Zhang Y, et al. Analysis and decision of loop closing operation in urban mid-voltage distribution network[j]. Power System Protection & Control, 2014. [12] Li Peng. Research on closed loop power supply technology for Tianhe District Guangzhou low voltage distribution network [D]. South China University of Technology, 2015. 7