Low Voltage Power Factor Correction Equipment Specifications Automatic, Automatic Detuned, Automatic Tuned

Similar documents
Design Specifications Low Voltage Active Harmonic Filter

POWER FACTOR CORRECTION. HARMONIC FILTERING. MEDIUM AND HIGH VOLTAGE SOLUTIONS.

Brown University Revised 2/1/2006 Facilities Design & Construction Requirements SECTION 16461C - DRY TYPE TRANSFORMERS

SECTION LOW VOLTAGE ACTIVE HARMONIC FILTER SYSTEM NEMA 1 ENCLOSED

SECTION 16483D ADJUSTABLE FREQUENCY DRIVE - MICRODRIVE (MVX <10-HP)

Power Processor - Series 700F 10KVA to 150KVA

SPECIFICATION FOR HORIZONTAL AIRFLOW OUTDOOR RESISTIVE LOAD BANK

SECTION DISTRIBUTION SWITCHBOARDS

PFCC-1000 series. Powerful Flexibility Durability - Quality. Medium Voltage Metal Enclose 5,15,25,35kV Power Factor Correction & Harmonic Filter

INTELLIMETER REGISTER

PRODUCT SPECIFICATION FOR A 15 AND 75 kva, THREE PHASE MODULAR POWER DISTRIBUTION SYSTEM WITH REGULATION AND CONDITIONING (Varian)

SECTION PANELBOARDS

DPM - Mesta Electronics, Inc. Low Voltage Active Harmonic Filters

The NOVA Recloser shall be designed and tested in accordance with the following standards as applicable:

MGM Transformer. Vacuum Pressure Impregnated (VPI) Dry-Type Substation Transformer Specification Guide

1. All electrical switches and outlets used shall be equal to Hubbell heavy duty, specification grade or equivalent quality.

SUGGESTED SPECIFICATION for Series 300 Automatic Transfer Switches

1. Institute of Electrical and Electronic Engineers (IEEE) a. Standard , IEEE Guide for Harmonic Content and Control.

INSTRUCTION MANUAL. Type SWF. Sine Wave Filters 690 Volts, 50Hz

APQline Active Harmonic Filters. N52 W13670 NORTHPARK DR. MENOMONEE FALLS, WI P. (262) F. (262)

Title: Southern States Type SLS Smart Sectionalizer Solid Dielectric Three Phase Sectionalizer. Product Specification Guide TABLE OF CONTENTS

SECTION AUTOMATIC TRANSFER SWITCH

Power Meter PQM (EnerSure Enkapsis) Guide Form Specification PART 1: GENERAL

SECTION 16322B SUBSTATION TRANSFORMERS DRY-TYPE

UNIVERSITY OF MISSOURI Liquid-Filled Utility Transformers 2016 Q1

LIFE LINE PRODUCT SPECIFICATION FOR A 1 TO 3 KVA, SINGLE PHASE, POWER DISTRIBUTION SYSTEM WITH REGULATION AND CONDITIONING

CONSULTANT PROCEDURES & DESIGN GUIDELINES Liquid-Filled Utility Transformers UNIVERSITY OF MISSOURI

S11 Adjustable Speed Drive Engineering Specification

ULTRA-K Series 600K - he

SWF DV/DT Solutions Sinewave Filters. N52 W13670 NORTHPARK DR. MENOMONEE FALLS, WI P. (262) F. (262)

Michigan State University Construction Standards SWITCHBOARDS, PANELBOARDS, AND CONTROL CENTERS PAGE

VF-nC1 Adjustable Speed Drive Engineering Specification

Power-Sure 700. Technical Data TD158001EN. Contents

SHARDA Make Harmonics Filter

Variable Frequency Drive Packages with Harmonic Mitigation. Low Harmonic Drive Packages Engineered by Rockwell Automation

2.2 American National Standards Institute Corporation and its applicable standards C39.1, C80.1, C89, C84.1.

SECTION DISTRIBUTION SWITCHBOARDS

E3 Adjustable Speed Drive Engineering Specification

SECTIONS , (15040, 15767, 15950, 16269) Guide Specification for VARIABLE SPEED DRIVES with Optional Bypass

B. Manufacturers: Square-D, G.E. or Westinghosue.

7. INSPECTION AND TEST PROCEDURES

MANUFACTURING GUIDELINES FOR PLC (LEVEL-1 AUTOMATION)

High Frequency Sinewave Guardian TM Filter

Liebert Datawave GUIDE SPECIFICATIONS kva Magnetic Synthesizer Power Conditioning System

EMI Installation Guidelines

Howard Smart Transformer Specification Guide

Dry Type Transformers Full Line Catalog. jeffersonelectric.com

SINGLE PHASE BUCK & BOOST TRANSFORMERS INSTRUCTION MANUAL

Liebert Datawave. GUIDE SPECIFICATIONS kva Magnetic Synthesizer Power Conditioning System 1.0 GENERAL

Low Pass Harmonic Filters

POWER DELEGATOR SERIES 7200A POWER DISTRIBUTION UNIT WITH POWER CONDITIONING GENERAL SPECIFICATIONS

UBC Technical Guidelines Section Edition Medium-Voltage Transformers Page 1 of 5

SECTION LOW-VOLTAGE ELECT. DIST. DESIGN AND CONSTRUCTION STANDARDS _ February 2015 PART I: GENERAL

MV ELECTRICAL TRANSMISSION DESIGN AND CONSTRUCTION STANDARD. PART 1: GENERAL 1.01 Transformer

High Frequency SineWave Guardian TM Filter

VARIABLE FREQUENCY DRIVE SPECIFICATION

TOSHIBA International Corp

GE Ventilated Dry-Type Transformers. Secondary Substation Transformers - 5 and 15kV Class

and cured to reduce hot spots and seal out moisture. The assembly shall be installed on vibration-absorbing pads.

Reactive Energy Management

NOsparc! MHXAC1F120! MHXAC1F240! MHXAC1F480 PATENTS AND PATENTS PENDING. Contact Arc Suppressor

Active Harmonic Filter

Distribution/Substation Transformer

CP /240-MC4 User Manual

Phoenix DX Clean Power (18 Pulse) AC Drive

P. O. BOX 269 HIGHLAND, ILLINOIS, U.S.A PHONE FAX

SECTION 16349B ADJUSTABLE FREQUENCY DRIVES MEDIUM VOLTAGE

SECTION 16496G CONTACTOR BASED AUTOMATIC TRANSFER SWITCHES LOW VOLTAGE

PANELMDP Main Distribution Panel. Descriptions Energy Efficient Transformer

LV Compensation & Filtering Products

NEO TELE-TRONIX PVT. LTD. 6/7 Bijoygarh, Kolkata , Tel : ; Fax :

P2 Power Solutions Pvt. Ltd. P2 Power Magnetics. Quality Power within your Reach. An ISO 9001:2008 Company

INSTALLATION, OPERATION AND MAINTENANCE GUIDE

C.P. SENTINEL AQUA-LINE

WAVEFORM CORRECTOR (WAVEFORM CORRECTORS) REPLACES SURGE PROTECTION DEVICES (SPD) PREVIOUSLY KNOWN AS (TVSS)

2.1. Product Description

GENERAL PURPOSE DRY-TYPE DISTRIBUTION TRANSFORMERS

INTERNATIONAL TRANSFORMERS. Acme Electric s broad selection of CSA energy efficient transformers

NSL-10 STANDARD LIFE MODULAR CAPACITORS

HPS Universal BUCK-BOOST TRANSFORMERS

Coil Products Beginnings 1960 State of the Art. Customer partnership around the globe. Continuous innovation since 1900

AC Resonant Test Systems Tank Type Up to 500 kv

2.4. Transformers. Contents Description General-Purpose Encapsulated Transformers Catalog Number Selection... Product Selection... Product Description

Compliant to DOE 10, CFR Part 431 (effective as of January 1 st, 2016)

ADJUSTABLE SPEED DRIVES. HX7 Series. 18 Pulse. Phone: Fax: Web: -

PowerFlex 400 Submittal

Varplus 2 capacitors installation guide

Power IT LV Active Filters PQFI PQFM PQFK. The ABB comprehensive solution for active filtering of harmonics

ADJUSTABLE SPEED DRIVES. HX7 Series. 18-Pulse

AC Resonant Test Systems Tank Type Up to 150 kv

High voltage shunt capacitor banks HIGH VOLTAGE COMPENSATION AND HARMONIC FILTERING PRODUCTS

SECTION THREE-PHASE UNINTERRUPTIBLE POWER SYSTEM

ACS 1000 Transformer Failure Investigation. Nathan Schachter, Peng

Commissioning and Maintenance of Power Factor Correction Systems

PowerGard Series C 18-Pulse Enclosed Drive Controllers

StatiVolt. Inverter UPS Systems. Features. Contents

Electrical IP Red Seal Practice Exam

Real Time Power Factor Correction Units (Transient Free Switching)

Rev.8.8 SSRMAN-1P SERIES USERS MANUAL SSR INTELLIGENT PHASE ANGLE CONTROL MODULE COPYRIGHT 2015 NUWAVE TECHNOLOGIES, INC.

PREFACE ********************************************************** IT IS NOT INTENDED THAT THESE STANDARDS BE COPIED AND USED AS A SPECIFICATION!

Transcription:

Low Voltage Power Factor Correction Equipment Specifications Automatic, Automatic Detuned, Automatic Tuned Part 1 - General Scope and Product Description 1.0 This specification contains the minimum design and manufacture requirements, standards, general equipment type, warranty and installation for power factor correction, detuned and tuned power factor correction equipment. Equipment shall be intended for the improvement of power factor, for low voltage AC electrical power distribution systems. Reference specification Section 26-263533 or Section 16 16280. 1.1 Exception to any part of this specification shall be indicated by reference to each item number, when providing a project bid. 1.2 Manufacturer of power factor correction equipment shall have been engaged in the application, design and production of such equipment for a minimum of twenty years. Manufacturer specified shall be ISO 9001 certified. The finished product shall be engineered, assembled, tested, and shipped by manufacturer. Equipment provided in any other manner is not acceptable. 1.3 Power factor correction equipment shall be suitable for indoor or outdoor (NEMA rated) environments. Finished design may be stand-alone type, or integrated with other electrical equipment. Equipment shall be provided for low voltage classifications, with a range from 240vac to 600vac, suitable for automatically switched configurations, with the compatibility to include fixed (non-automatic) power factor correction. In general, equipment shall be used on three phase, 3-wire, three phase 4-wire, grounded wye, ungrounded wye, or delta wire systems at 50 or 60 Hz. Equipment is designed for reliable, continuous operation in ambient temperatures of C to + C, up to 3300 feet (1000 meters) above sea level, with relative humidity of 70% at C or higher, when controlled by thermostats, conditioned air, heaters and/or fans, as required. 1.4 A power system analysis may be required to determine the harmonic content and requirement for filters, as part of the power factor correction equipment. It will be the responsibility of the owner, consultant, contractor or power quality service company to provide the manufacturer, at the time of request for quote, such data. 1.5 The finished power factor correction equipment shall be UL listed to 508A and cul. Part 2 - Standards and References Page 1

2.0 American National Standards Institute (ANSI) 2.1 Institute of Electrical and Electronic Engineers (IEEE) 2.2 National Electrical Manufacturers Association (NEMA) 2.3 Underwriters Laboratories, Inc. (UL) 2.4 National Electrical Code (NEC) 2.5 Canadian Standards Association (CSA) 2.6 International Electrotechnical Commission (IEC) 2.7 European Standards, EN Part 3 - System Ratings 3.0 The voltage rating of the power factor correction equipment shall be volts AC between phases. 3.1 The total capacity of the unit shall be kvar. 3.2 The total kvar shall be divided into # steps ; automatically switched kvar. 3.3 The fixed kvar non-switched. 3.4 The automatic capacitor bank shall have future provisions for expansion to kvar. Part 4 - Primary Component Description 4.0 The finished assembly shall provide a general design arrangement to accommodate an externally fused capacitor configuration as either switched, fixed and switched; and incorporating electro-mechanical contactors, filter reactors where applicable, copper bus work and control device, with all components mounted, wired and housed in a NEMA rated enclosure. 4.1 Power Capacitors, shall comply with applicable industry standards IEEE Std. 18, NEMA CP-1, CSA 22.2, IEC 831, and UL 810. Each capacitor housing shall be aluminum, with an internal self healing, metalized polypropylene film and resin encapsulation (dry type), or green, environmentally friendly liquid impregnation (wet type). Capacitors shall include a safety overpressure device and discharge resistors, which reduce residual voltage to 50VAC or less, within one minute from de-energization. Capacitors shall be designed for proper overcurrent, overvoltage, low watt loss, and long life capabilities. A THD of up to 10% shall not affect the life of the capacitors. Page 2

4.2 Current Limiting fuses shall be class J type rated at 200kaic, utilized for protection of major faults on all three phases of each switched step and each fixed step. Fuse mounting arrangement shall be in such a manner to provide convenience for inspection and servicing and shall include blown fuse indication. 4.3 Contactors shall be 3-pole electro-mechanical type, intended for capacitor switching duty and include a120vac coil, provide for positive open/close operation, while switching the low inductive, low loss capacitors. Each contactor shall include a means of suppression, capable of withstanding the full inrush capacitor switching current. Where detuned or tuned filters are used, separate inrush suppression shall not be incorporated. 4.4 Filter reactors (where applicable) shall be provided as protection for power factor correction equipment capacitors installed in a harmonically loaded environment. In general, reactors shall be detuned for the 4 th harmonic order and rated at 3.78 (227hz), to reduce harmonic amplification. Reactors for tuned systems shall be designed for mitigation for the 5 th order and rated at 4.7 (282hz). Reactors shall be three-phase, ironcore, C temperature rated, class H, air-cooled with Poly-Gap core and include a thermal switch. Reactors shall be provided to correct other specific harmonic orders, as required. 4.5 Control power transformer shall be rated for the supply of 120vac, with sufficient load capacity and include both primary and secondary fusing. 4.6 A three-phase zinc oxide arrester rated at 600vac shall be provided for voltage spike protection. 4.7 Optional components may be needed based upon application requirements: - Molded case type circuit breaker 3-pole, manually operated - Blown fuse lights, per step - Other Part 5 - Control and Monitoring 5.0 Power factor controller shall be door mounted and provide for automatic power factor regulation with a programmable target cosine. The microprocessor based device shall manage, measure, and display: - under- and overvoltage - harmonics - defective steps - maintenance (loss of power and amount of operations) - temperature measuring with fan control and switching off steps - digital input - number of steps in use - adjustable time settings of steps - voltage (phase/phase and phase/neutral) - current Page 3

- frequency - active power - reactive power - apparent power - THD voltage - THD current - harmonics for voltage (order 2nd 31st) - harmonics for current (order 2nd 31st) - counter active work import / export - counter reactive work inductive / capacitive - missing reactive power for target-cosphi - temperature, measuring the temperature in the enclosure by use of sensor - Controller shall be door mounted with a back-lighted, graphical LCD display and function keypad - Modbus 485 RTU option - SCADA management option 5.1 Supervision functions shall provide for reliable, safe operation of the compensation equipment and ensure a long life cycle of the components. 5.2 A current transformer shall be provided, split-core type, for controller measurement. 5.3 A CT (current transformer) shorting terminal block shall be provided for additional personnel safety. Part 6 - Equipment Construction 6.0 Power factor correction equipment design and manufacture shall follow the most recent applicable ANSI, IEEE and NEMA standards and guidelines; and be neatly constructed and finished, meeting all APQ,LLC. quality and production control standards. 6.1 The enclosure assembly shall be a rigid frame structure using a minimum 16- gauge formed sheet steel outer surface. Enclosure shall be a modular bolted design and allow for ease of expansion in the field. Top, bottom or side connection entry shall be provided. 6.2 Doors shall be hinged and equipped with a positive latch-close system and include a lockable feature. The entire assembly shall provide adequate personnel safety and component security. Removable lifting eyes located at the top of the equipment, shall be provided for transport and to facilitate ease of installation. 6.3 The complete assembly shall be painted using electrostatically applied powder coated paint, providing for enhanced durability and extended protection. Standard color shall be RAL 7034 (light grey), or color as specified. NEMA 1, 12, 3R and other ratings shall be available. 6.4 Fans shall be provided for force air cooling, convection cooling is not acceptable. Page 4

6.5 All internal power wiring shall have thermoplastic insulation rated for a minimum of 90 C at 600 volts. All wiring connections shall be mechanically fixed with a nut or screw. 6.6 Main bus shall be electrical grade cooper, fully rated and integral to the equipment. At a minimum, a 65ka brace rating shall be used, to withstand specified short circuit ratings, while providing adequate clearance. Bellevue hardware shall be utilized at connection points. A grounding connection point shall also be included. 6.7 On/Off switch for control power and dry contacts for remote/external disconnect means shall be provided. Internal circuit breaker (optional) shall include shunt trip and assembly shall include door interlock system. 6.8 The equipment shall be suitable to meet applicable seismic requirements. Part 7 - Testing, Safety and Documentation 7.0 Capacitors shall be tested at point of construction. The power factor correction equipment shall be production tested for proper operation, prior to shipment. This shall include, at a minimum: wire connections, torque connections, mechanical functional operation, controller operation, visual inspection. 7.1 Nameplates, labels, and other decals, providing safety, general operation instruction and manufacturer data, shall be included with the equipment. Such markings shall be visually accessible and conveniently located, both internally and externally on the equipment. 7.2 A manual for the purpose of operation, maintenance, and service instruction shall be included with the finished equipment. A general bill-of-material list, external and internal outline mechanical and electrical drawings shall be included with the equipment. Documentation shall be provided in a CAD format for approval or reference. Part 8 - Installation and Service 8.0 Installation and operation of equipment is intended for general business, commercial, industrial, government and energy service providers. 8.1 Correct installation is required for proper performance and function of the equipment. Physical inspection of equipment for damage is suggested, prior to any installation. Indoor storage shall be in a clean, dry environment. 8.2 National Electrical Code (NEC), electric utility company or service provider codes shall be adhered to during the installation. Electrical connections shall also be in compliance with required codes Page 5

8.3 Installer/Contractor shall inspect and verify proper alignment, anchorage, leveling and grounding, proper connections and tightness of connections, prior to any start-up procedures. 8.4 Appropriate personnel shall start-up and operate equipment upon installation approval. 8.5 All maintenance and inspection of the power factor correction equipment shall be done with the system disconnect device in the open position. 8.6 Routine maintenance and inspections should be limited to 15-30 minutes, as to not disrupt utility billing practices. 8.7 An annual inspection of the capacitors, fuses, contactors and reactors shall be performed. Part 9 - Equipment Warranty The manufacturer shall provide its standard warranty for equipment of this type. The warranty shall provide for repair or replacement of the equipment, should it be found to be defective within twelve months from the date of being first energized, or eighteen months from date of shipment, or whichever occurs first. Approved Manufacturer Power factor correction equipment designer and manufacturer shall be: APQ, LLC. N52 W13670 Northpark Drive Menomonee Falls, WI 53051 www.apqpower.com (262)754-3883 Page 6