STABILITY IMPROVEMENT OF POWER SYSTEM BY USING PSS WITH PID AVR CONTROLLER IN THE HIGH DAM POWER STATION ASWAN EGYPT

Similar documents
Introduction to PID Control

Figure 1: Unity Feedback System. The transfer function of the PID controller looks like the following:

Load Frequency and Voltage Control of Two Area Interconnected Power System using PID Controller. Kavita Goswami 1 and Lata Mishra 2

EXPERIMENTAL INVESTIGATION OF THE ROLE OF STABILIZERS IN THE ENHANCEMENT OF AUTOMATIC VOLTAGE REGULATORS PERFORMANCE

Performance Analysis of Conventional Controllers for Automatic Voltage Regulator (AVR)

DEPARTMENT OF ELECTRICAL AND ELECTRONIC ENGINEERING BANGLADESH UNIVERSITY OF ENGINEERING & TECHNOLOGY EEE 402 : CONTROL SYSTEMS SESSIONAL

VECTOR CONTROL SCHEME FOR INDUCTION MOTOR WITH DIFFERENT CONTROLLERS FOR NEGLECTING THE END EFFECTS IN HEV APPLICATIONS

Automatic Voltage Control For Power System Stability Using Pid And Fuzzy Logic Controller

CHAPTER 2 PID CONTROLLER BASED CLOSED LOOP CONTROL OF DC DRIVE

ROBUST TECHNIQUE LFC OF TWO-AREA POWER SYSTEM WITH DYNAMIC PERFORMANCE OF COMBINED SMES AND SSSC CONTROL

Transient stability improvement by using shunt FACT device (STATCOM) with Reference Voltage Compensation (RVC) control scheme

6545(Print), ISSN (Online) Volume 4, Issue 1, January- February (2013), IAEME & TECHNOLOGY (IJEET)

MATLAB Simulink Based Load Frequency Control Using Conventional Techniques

Frequency Response Analysis and Design Tutorial

Design Of PID Controller In Automatic Voltage Regulator (AVR) System Using PSO Technique

Position Control of DC Motor by Compensating Strategies

Comparative Analysis of a PID Controller using Ziegler- Nichols and Auto Turning Method

PID TUNING WITH INPUT CONSTRAINT: APPLICATION ON FOOD PROCESSING

PYKC 7 March 2019 EA2.3 Electronics 2 Lecture 18-1

EXCITATION SYSTEM MODELS OF GENERATORS OF BALTI AND EESTI POWER PLANTS

Generator Operation with Speed and Voltage Regulation

GE420 Laboratory Assignment 8 Positioning Control of a Motor Using PD, PID, and Hybrid Control

2.4 Modeling on reactive power or voltage control. Saadat s Chapters Kundur s Chapters 5.4, 8 and 11.2 EPRI Tutorial s Chapter 5

EVALUATION ALGORITHM- BASED ON PID CONTROLLER DESIGN FOR THE UNSTABLE SYSTEMS

Analysis of Effect on Transient Stability of Interconnected Power System by Introduction of HVDC Link.

SECTION 6: ROOT LOCUS DESIGN

Excitation systems and automatic voltage regulators

AUTOMATIC VOLTAGE REGULATOR AND AUTOMATIC LOAD FREQUENCY CONTROL IN TWO-AREA POWER SYSTEM

Comparative Study of PID and Fuzzy Controllers for Speed Control of DC Motor

Control of Load Frequency of Power System by PID Controller using PSO

Governor with dynamics: Gg(s)= 1 Turbine with dynamics: Gt(s) = 1 Load and machine with dynamics: Gp(s) = 1

Comparative Study of PID and FOPID Controller Response for Automatic Voltage Regulation

The Effect of Fuzzy Logic Controller on Power System Stability; a Comparison between Fuzzy Logic Gain Scheduling PID and Conventional PID Controller

COMPUTATION OF STABILIZING PI/PID CONTROLLER FOR LOAD FREQUENCY CONTROL

International Journal of Research in Advent Technology Available Online at:

Transient Stability Improvement Of IEEE 9 Bus System With Shunt FACTS Device STATCOM

Arvind Pahade and Nitin Saxena Department of Electrical Engineering, Jabalpur Engineering College, Jabalpur, (MP), India

Cantonment, Dhaka-1216, BANGLADESH

P Shrikant Rao and Indraneel Sen

Simulation of Synchronous Machine in Stability Study for Power System: Garri Station as a Case Study

Hacettepe University, Ankara, Turkey. 2 Chemical Engineering Department,

Fundamentals of Servo Motion Control

Embedded Control Project -Iterative learning control for

Brushless excitation of synchronous generators: study of models and control optimization

ECE 422/522 Power System Operations & Planning/Power Systems Analysis II 5 - Reactive Power and Voltage Control

QuickBuilder PID Reference

CHAPTER 3 WAVELET TRANSFORM BASED CONTROLLER FOR INDUCTION MOTOR DRIVES

Simulation and Numerical Analysis and Comparative Study of a PID Controller Based on Ziegler-Nichols and Auto Turning Method

IJESRT. Scientific Journal Impact Factor: (ISRA), Impact Factor: 1.852

A Novel PSS Design for Single Machine Infinite Bus System Based on Artificial Bee Colony

Design of Fractional Order Proportionalintegrator-derivative. Loop of Permanent Magnet Synchronous Motor

Application Of Power System Stabilizer At Serir Power Plant

Hands-on Lab. PID Closed-Loop Control

DC MOTOR SPEED CONTROL USING PID CONTROLLER. Fatiha Loucif

Different Controller Terms

Voltage Control and Power System Stability Enhancement using UPFC

A Comparative Study on Speed Control of D.C. Motor using Intelligence Techniques

TWO AREA CONTROL OF AGC USING PI & PID CONTROL BY FUZZY LOGIC

Digital Control of MS-150 Modular Position Servo System

CHAPTER 4 PID CONTROLLER BASED SPEED CONTROL OF THREE PHASE INDUCTION MOTOR

1. Governor with dynamics: Gg(s)= 1 2. Turbine with dynamics: Gt(s) = 1 3. Load and machine with dynamics: Gp(s) = 1

Load frequency control in Single area with traditional Ziegler-Nichols PID Tuning controller

Design of an Intelligent Pressure Control System Based on the Fuzzy Self-tuning PID Controller

CHAPTER 6 UNIT VECTOR GENERATION FOR DETECTING VOLTAGE ANGLE

Dr Ian R. Manchester Dr Ian R. Manchester Amme 3500 : Root Locus Design

DC Motor Speed Control: A Case between PID Controller and Fuzzy Logic Controller

Design, Implementation, and Dynamic Behavior of a Power Plant Model

Modelling to stability analysis of brushless excitation systems on synchronous generator

Motor Modeling and Position Control Lab 3 MAE 334

Some Tuning Methods of PID Controller For Different Processes

Design and Simulation of Fuzzy Logic controller for DSTATCOM In Power System

A PID Controller Design for an Air Blower System

Figure 1.1: Quanser Driving Simulator

ME 5281 Fall Homework 8 Due: Wed. Nov. 4th; start of class.

Review of Pole Placement & Pole Zero Cancellation Method for Tuning PID Controller of A Digital Excitation Control System

Development of an Experimental Rig for Doubly-Fed Induction Generator based Wind Turbine

Getting the Best Performance from Challenging Control Loops

Design of Different Controller for Cruise Control System

TUNING OF PID CONTROLLERS USING PARTICLE SWARM OPTIMIZATION

II. PROPOSED CLOSED LOOP SPEED CONTROL OF PMSM BLOCK DIAGRAM

CDS 101/110: Lecture 8.2 PID Control

Design and Implementation of Self-Tuning Fuzzy-PID Controller for Process Liquid Level Control

-binary sensors and actuators (such as an on/off controller) are generally more reliable and less expensive

BINARY DISTILLATION COLUMN CONTROL TECHNIQUES: A COMPARATIVE STUDY

One-degree-of-freedom PID controlled Helicopter. PDE 2420 Control Systems

AN EXPERIMENTAL INVESTIGATION OF THE PERFORMANCE OF A PID CONTROLLED VOLTAGE STABILIZER

Chapter 10: Compensation of Power Transmission Systems


DC Motor Speed Control for a Plant Based On PID Controller

Tuning Of Conventional Pid And Fuzzy Logic Controller Using Different Defuzzification Techniques

PID-CONTROL FUNCTION AND APPLICATION

The Discussion of this exercise covers the following points: Angular position control block diagram and fundamentals. Power amplifier 0.

LARGE-SCALE WIND POWER INTEGRATION, VOLTAGE STABILITY LIMITS AND MODAL ANALYSIS

Position Control of AC Servomotor Using Internal Model Control Strategy

A Brushless DC Motor Speed Control By Fuzzy PID Controller

COMPARISON OF TUNING METHODS OF PID CONTROLLER USING VARIOUS TUNING TECHNIQUES WITH GENETIC ALGORITHM

Level control drain valve tuning. Walter Bischoff PE Brunswick Nuclear Plant

An Introduction to Proportional- Integral-Derivative (PID) Controllers

TUNING OF PID CONTROLLER USING PSO AND ITS PERFORMANCES ON ELECTRO-HYDRAULIC SERVO SYSTEM

A Fuzzy Controlled PWM Current Source Inverter for Wind Energy Conversion System

Transcription:

3 rd International Conference on Energy Systems and Technologies 16 19 Feb. 2015, Cairo, Egypt STABILITY IMPROVEMENT OF POWER SYSTEM BY USING PSS WITH PID AVR CONTROLLER IN THE HIGH DAM POWER STATION ASWAN EGYPT Elhussein A. Ibrahim¹, Abdel-Moamen M. A.², G. Shabib 2, A.M. El- Noby 2 1) The High-dam Power Station, Aswan, EGYPT 2) Faculty of Energy Engineering, Aswan, EGYPT The main objective of an automatic voltage regulator (AVR) is the accurate control and regulation of the terminal voltage and the reactive power flow of a synchronous machine. In order to fulfill these requirements, the field voltage must react quickly to changes of the operating conditions, i.e. with a response time that does not exceed a few milliseconds. To accomplish this, a high-speed controller is required. It continuously compares the actual values with the set point values and changes the final control element (firing angle for the converter) with an insignificant delay. The main control device calculates the controlled variable from the measured values in very short time intervals. The result is a quasi-continuous behavior with a negligible time delay. In recent years, the scale of power systems has been expanding, and with that expansion smooth power operation is becoming increasingly important. One of the solutions is to realize a practical high speed, highly reliable exciter system that is suitable for stable operation of a power system. In this work, a model of a static excitation system of an alternator connected to a network via a transformer have been built using MATLAB- SIMULINK.The parameters of the machine has been obtained from the high dam power station taking into account saturation effects. A PID controller is used to control the output voltage of the synchronous generator for static excitation systems. A method based on step response has been proposed and verified for tuning the parameters of the controller. In order to validate the simulated results of the system with AVR, the results have been compared with practical results of the hugh dam and a good agreement has been realized. However, in large generating units, undesirable oscillations in the active power and speed result as a side effect of the AVR control or due to outside disturbances. Keywords: Static Excitation, PID controller 1. INTRODUCTION In the last three decades, static excitation systems are introduced. The exciters used in alternators were DC generators driven by either the steam -203-

turbine on the same shaft of the generator or by an induction motor. Old systems are being replaced by new system for many advantages (such as quick response, online maintenance and high field current). The static systems consist of some form of controlled rectifiers or choppers supplied by the ac bus of the alternator or from an auxiliary bus. A static excitation system regulates the terminal voltage and the reactive power flow of the synchronous machine by direct control of the field current using thyristor converters. The figure below shows an overview of the excitation system and its typical environment. The voltage regulator controls the output of the exciter so that the generated voltage and reactive power can be controlled. The excitation system must contribute to the effective voltage control and therefore enhance the system stability. It must be able to respond quickly to a disturbance, thereby enhancing the transient stability as well as the small signal stability. In most modern systems the automatic voltage regulator (AVR) is a controller that senses the generator output voltage and the current or reactive power then it initiates corrective action by changing the exciter control to the desired value. The excitation system controls the generated EMF of the generator and therefore controls not only the output voltage but the reactive power as well. The response of the AVR is of great interest in studying stability. It is difficult to make rapid changes in field current, because of the high inductance in the generator field winding. This introduces a considerable lag in the control function and is one of the major obstacles to be overcome in designing a regulating system. The AVR must keep track of the generator output reactive power all the time and under any working load conditions in order to keep the voltage within pre-established limits. Based on this, it can be said that the AVR also controls power factor of the machine once these variables are related to the generator excitation level. The AVR quality influences the voltage level during steady state operation and also reduces the voltage oscillations during transient periods, affecting the overall system stability. Most researchers on modeling and simulation of generating systems did not use detailed models for the generating units with their detailed excitation system. Moreover researchers who implemented PI and PID controller for AVR in their models ignored a detailed procedure for determining controller parameters. Fig. (1) gives the block diagram of synchronous generator and excitation system with AVR and PSS while Fig. (2) shows the automatic voltage regulator of the high dam power station with PSS using IEEE 2B PSS type. A model representing the AVR and PSS and High-dam Power Station on MATLAB SIMULINK was done, and the actual data of the high dam power station units are introduced and as shown in Fig. (3), This system is two area making a comparison between this system using AVR of the High Dam power station and the AVR of the Simulink model, Comparing the output voltage, we shall consider the following unity feedback system Fig. (4). The transfer function of the PID controller looks like the following: where Kp is the proportional gain, Ki is the integral gain, and Kd is the derivative gain. First, let's take a look at the effect of a PID controller on the closed-loop system using the schematic above. To begin, the variable (e) is the tracking error or the difference between the desired reference value (r) and the actual output (y). The controller takes this error signal and computes both its derivative and its integral. The signal which is sent to the actuator -204-

(u) is now equal to the proportional gain (Kp) times the magnitude of the error plus the integral gain (Ki) times the integral of the error plus the derivative gain (Kd) times the derivative of the error. A large Kp will have the effect of reducing the rise time and will reduce (but never eliminate) the steady-state error. Integral control (Ki) will have the effect of eliminating the steady-state error, but it will make the transient response worse. If integral control is to be used, a small Ki should always be tried first. Derivative control will have the effect of increasing the stability of the system, reducing the overshoot, and improving the transient response. The effects on the closed-loop response of adding to the controller terms Kp, Ki and Kd are listed in Table (1). Note that these correlations are not exactly accurate, because Kp, Ki, Kd are related to each other. Changing one of these variables can change the effect of the other two. For this reason, the table should only be used as a reference as the values for Ki, Kp and Kd are determined by trial and error approach. Figure 1. Block diagram of synchronous generator and excitation system with AVR and PSS. Figure 2. Transfer function of the High Dam AVR -205-

Figure 3. Unity feedback system Figure 4. AVR Simiulink representation Table 1. Effects on the closed-loop response RISE TIME OVERSHOOT SETTLING TIME S-S ERROR Kp Decreases Increases No Change Decreases Ki Decreases Increases Increases Eliminates Kd No Change Decreases Decreases No Change -206-

2. ADJUSTING CONTROLS 2.1 Proportional Control From the discussion above we see that Kp will help to reduce the steady-state error. Let's first add a proportional controller into the system, by changing the m-file to look like the following: num=1; den=[1 10 20]; Kp=10; [numcl,dencl]=cloop(kp*num,den, -1); t=0:0.01:2; step(numcl, dencl,t) The "cloop" command in Matlab is used to convert the open loop transfer function into a closed-loop one. Since the "cloop" command only accepts one transfer function, the plant and controller transfer functions have to be multiplied together before the loop is closed. It should also be noted that it is not a good idea to use proportional control to reduce the steady-state error, because you will never be able to eliminate the error completely. This fact will become evident below. If you rerun your m-file, you should get the form shown in Plot no (1). Now, the rise time has been reduced and the steady-state error is smaller, if we use a greater Kp, the rise time and steady-state error will become even smaller. Change the Kp value in the m-file: Kp=500; Rerun the m-file and the Plot no (2) emerges. Plot no. 1 Plot no. 2 This time we see that the rise time is now about 0.1 second and the steadystate error is much smaller. But the overshoot has gotten very large. From this example we see a large proportional gain will reduce the steady-state error but at the same time, worsen the transient response. If we want a small -207-

overshoot and a small steady-state error, a proportional gain alone is not enough. 2.2 PD Control The rise time is now probably satisfactory (rise time is about 0.1 second). Now let's add a derivative controller to the system to see if the overshoot can be reduced. Add another variable, Kd, to the m-file, set it equal to 10 and rerun the m-file: Kp=500; Kd=10; numc=[kd Kp]; [numcl, dencl]=cloop(conv(num,numc),den); step(numcl, dencl,t) The overshoot is much less then before. It is now only twenty percent instead of almost forty-five percent. We can now try to improve that even more. Try increasing Kd to 100, you will see the overshoot eliminated completely as we see in Plot no. (3). We now have a system with a fast rise time and no overshoot. Unfortunately, there is still about a 5 percent steady-state error. It would seem that a PD controller is not satisfactory for this system. Let's try a PI controller instead. 2.3 PI Control As we have seen, proportional control will reduce the steady-state error, but at the cost of a larger overshoot. Furthermore, proportional gain will never completely eliminate the steady-state error. For that we need to try integral control. Let's implement a PI controller and start with a small Ki. Go back to the m-file and change it so it looks like the following (note the t input is removed from the "step" command so more of the response can be seen in Plot no. (4). Kp=500; Ki=1; Kd=0; numc=[kd Kp Ki]; denc=[1 0]; [numcl, dencl]=cloop(conv(num,numc),conv(den,denc)); step(numcl, dencl) Plot no. 3 Plot no. 4-208-

The Ki controller really slows down the response. The settling time becomes more than 500 seconds. To reduce the settling time, we can increase Ki, but by doing this, the transient response will get worse (e.g. large overshoot). Try Ki=10, by changing the Ki variable. The plot can be seen better if an "axis" command is added after the step response. Your m-file should now look like the following: Kp=500; Ki=10; Kd=0; numc=[kd Kp Ki]; denc=[1 0]; [numcl, dencl]=cloop(conv(num,numc),conv(den,denc)); step(numcl, dencl) axis([0 100 0 1.5]) Now we have a large overshoot again, while the settling time is still long. To reduce both settling time and overshoot, a PI controller by itself is not enough as we see in Plot no. (5). Plot no. 5 Plot no. 6 2.4 PID Control From the two controllers above, we see that if we want a fast response, small overshoot, and no steady-state error, neither a PI nor a PD controller will suffice. Let's implement both controllers and design a PID controller to see if combining the two controllers will yield the desired response. Recalling that our PD controller gave us a pretty good response, except for a little steady-state error. Let's start from there, and add a small Ki (=1). Change the m-file to the following to implement the PID controller and plot the closed-loop response: KP=500; KI=1; KD=100; numc=[kd KP KI]; denc=[1 0]; [numcl, dencl]=cloop(conv(num,numc),conv(den,denc)); step(numcl, dencl) -209-

The settling time is still very long. Increase Ki to 100. The settling time is much shorter, but still not small enough. Increase Ki to 500 and change the "step" command to "step(numcl, dencl,t)". Now the settling time reduces to only 1.5 seconds. This is probably an acceptable response for this system as is seen in Plot no (7). To design a PID controller, the general rule is to add proportional control to get the desired rise time, add derivative control to get the desired overshoot, and then add integral control (if needed) to eliminate the steady-state error. You may have to go back and readjust all three variables to fine-tune the response. Plot no. 7 3. ADJUSTING THE PARAMETER OF THE AVR There is many ways to adjust the PID parameters one of them an efficient MA (Memetic Algorithm) for determining optimal proportional integralderivative (PID) controller parameters of an AVR and the method Ziegler_ Nichols method is famous also in finding the parameters of the AVR controller and PSS. In this paper use is made of the actual parameters of the High Dam power station units and using Matlab simulink for representing the result of the High Dam generators tests. Simulation of the AVR on simulink is done after changing it to S domain functions, and compare the simulation result with the actual commissioning result which applied on the High Dam units. The PID Filter is the heart of the AVR and is built as a D-I-P-Structure. As soon as one of the time constants is set to 0, the respective LEAD/LAG is bypassed. All PID-Filters typically share the same configuration. Only when problems occur during the commissioning, some of the filter values will be changed. The PSS uses the same PID Filter structure. As mentioned before the controller in the high dam is PID controller with PID filters. We use a transfer function with high/low value gates as a suitable technique for representing the control operation in the AVR. As is seen from Fig. (2), the PID Controller and Filter for AVR and PSS are before the HIGH/LOW value gates. This transfer function named as TRF_OUT is preferable for static excitation system after simulating the same transfer functions for AVR, PSS, Limiter, High Dam Excitation System, and Exciter and using the same parameter in the actual High Dam units -210-

In our simulink representation for the AVR of the High Dam, we are changing the parameter to improve the response of the AVR to reach to the fast response and low rise time after the step response test this will clear in this test. Figure 5. Two area system with High Dam units representation -211-

Figure 6. The voltage response after changing reference value -+2%step response for the practical system and for the simiulink system for the High Dam generator. 3. REFERENCE VALUE +-2% STEP RESPONSE Increasing the reference value by step +-2% and as we see results in actual test and our simulink program. In the simulink program the result of step response test is fast response and small overshoot and no steady state error if compared with the actual result of the actual reference value step response for the high dam units as shown in Fig. ( 6 ). 4. CONCLUSION The simulation results obtained are compared with the practical results obtained from The High Dam power station. This comparison shows that the simulation result is more stable and has fast response than the practical results. This is achieved because of changing the parameters on a try and error basis to find the best parameters. This way is very good if we already make the true computer representation of the system with the AVR as was described in this paper, so we can change parameters and cases of operation until we reach the best parameter that make the system stable. The experience gained will give us the chance in future to change the PID controller which is already used in the High Dam power station by fuzzy controller or any new controller and make a new study to find the effect of this controller compared with the actual or practical controller. The program and experience gained have the advantage in saving money and effort spent on practical search, and keep the units from the damage caused by errors during practical tests. REFERENCES [1] ABB Company, Standard Simplified Computer Representation for Power System Stability Studies. [2] Dhiya Ali Al-Nimma, Reactive Power Control of an Alternator with Static Excitation System Connected to a Network. [3] A.S. Ibrahim, "Self tuning voltage regulators for a synchronous machine", IEE Proceedings, Vol. 136, Pt. D. No. 5, September 1989. -212-

[4] Shigeyuki Funabiki and Atsumi Histsumoto, "Automatic voltage regulator for a synchronous generator with pole-assignment self-tuning regulator", Industrial Electronics, Control and Instrumentation, 1991, Proceedings IEE on industrial conference, pp. 1807-1811. [5] Vinko Casic and Zvonko Jurin, "Excitation system with microprocessor based twin-channel voltage regulator for synchronous machines", EPE-PEMC 2002 Dubrovnik & Cavtat. [6] Y. Kitauchi, etal, Simulation Experiments on a Multi-input PSS Prototype for Suppression of Long-period Perturbation, in Proceedings of the National Convention of the Institute of Electrical Engineers of Japan, 6-276 (1999), in Japanese. [7] Control tutorials for PID tutorial (1996) [8] A.H.M.S. Ula and Abul R. Hasan, "Design and implementation of a personal computer based automatic voltage regulator for a synchronous machine", IEEE Transaction on Energy Conversion, Vol. 7, No.1, March 1992 [9] P. Kundur, Power System Stability and Control, New York: McGraw- Hill, 1994. [10] P.M. Anderson, A.A. Fouad, Power System Control and Stability. APPENDIX Block parameters of the high dam unit in actual and matlab simulink. -213-