Single-Phase Mini Pad-Mounted Transformer Specification: Energy+ MPDL

Similar documents
WESTERN UNDERGROUND COMMITTEE GUIDE 2.6 (2.6/00/0868)

CONSULTANT PROCEDURES & DESIGN GUIDELINES Liquid-Filled Utility Transformers UNIVERSITY OF MISSOURI

S. C. Electric Cooperative s Specification for a Single-Phase, Single Bushing Overhead Distribution Transformer (Revised 10/2013)

UNIVERSITY OF MISSOURI Liquid-Filled Utility Transformers 2016 Q1

50-SDMS-01 SPECIFICATIONS FOR

MESP TECHNICAL SPECIFICATION FOR AN ESSENTIAL SERVICES SUPPLY STEP UP TRANSFORMER

SPECIFICATION FOR STEP UP TRANSFORMER 0.415/11Kv and (630KVA & 1000KVA)

SECTION TRANSFORMERS

ELECTRICAL NETWORKS SPECIFICATION TECHNICAL SPECIFICATION FOR A 230V/110V AND 400V/110V TRANSFORMER

THE KENYA POWER AND LIGHTING CO. LTD. SPECIFICATIONS for IMPULSE VOLTAGE TEST EQUIPMENT

51-SDMS-04 SPECIFICATIONS FOR. DISTRIBUTION TRANSFORMERS UP TO 36 kv WITH ALUMINUM WINDINGS FOR DUAL SECONDARY 400/230 V AND 230/133 V

MESP TECHNICAL SPECIFICATION FOR AN AUXILIARY OR ESSENTIAL SERVICES AND AUXILIARY TRANSFORMER FOR USE IN A RAILWAY SUBSTATION

Howard Smart Transformer Specification Guide

51-SDMS-02 SPECIFICATIONS FOR DISTRIBUTION TRANSFORMERS UP TO 36KV 400/230 VOLTS

شركة كهرباء محافظة القدس المساهمة المحدودة JERUSALEM DISTRICT ELECTRICITY CO. LTD.

Distribution Transformers

36kV VOLTAGE TRANSFORMERS (OUTDOOR TYPE)

CITY OF TACOMA Transmission & Distribution

COMBINED METERING TRANSFORMERS (OUT DOOR TYPE) FOR 11kV & 33kV SYSTEMS

DATA SHEET FOR LIGHTING TRANSFORMER APPD. BY VDV PROJECT NO

MV ELECTRICAL TRANSMISSION DESIGN AND CONSTRUCTION STANDARD. PART 1: GENERAL 1.01 Transformer

All the standards referred to the most current issue, including all amendment supplements. as of the date of the bid.

DMRC ELECTRICAL STANDARDS & DESIGN WING (DESDW)

DISTRIBUTION TRANSFORMER kv

DISTRIBUTION TRANSFORMER 11 / kv

PURCHASE SPECIFICATIONS 500KVA DRY TYPE TRANSFORMER FOR OIL RIG APPLICATIONS

012: 2015 CEB SPECIFICATION GALVANIZED STEEL WIRE (EXCEPT SHIELDING WIRE FOR TOWER LINE APPLICATION)

Group F : Sl. No. - 1) 33/0.403 KV, 100 KVA Station Transformer GUARANTEED & OTHER TECHNICAL PARTICULARS. Table : A

Transformer Factory Testing

INSTALLATION & TESTING OF UNDERGROUND PRIMARY AND SECONDARY POWER CABLES PRIOR TO ENERGIZATION

Compliant to DOE 10, CFR Part 431 (effective as of January 1 st, 2016)

CONDITIONS FOR A TENTATIVE APROVAL FOR CONNECTION OF TRANSFORMERS

.2 Accompany all submissions with a transmittal letter, in duplicate, containing:.4 Specification Section number for each submittal

SPECIFICATION SS-140/9. 0.6/1 (1.2) kv CONTROL AND POWER UNDERGROUND CABLES WITH PVC OR XLPE INSULATION AND PVC JACKET

Table of Contents. Introduction... 1

VI 3 - i TABLE OF CONTENTS

PPC TECHNICAL SPECIFICATION D/ NCMD / THREE-PHASE DISTRIBUTION TRANSFORMERS

Company Directive STANDARD TECHNIQUE: SD1E/2. Technical Requirements for Customer Export Limiting Schemes

SOUTHERN ELECTRICITY SUPPLY COMPANY OF ODISHA LIMITED (SOUTHCO UTILITY)

CUSTOMER SUPPLIED HIGH VOLTAGE METERING UNIT SPECIFICATION FOR 11, 22 & 33 kv

APDRP SCHEME, WESCO. Technical Specification for Distribution Transformers ( 11/0.4KV ) PART 1: GENERAL

MESP TECHNICAL SPECIFICATION FOR A 1500V DC RECTIFIER TRANSFORMER

PUBLIC POWER CORPORATION ENGINEERING & CONSTRUCTION OF TRANSMISSION PROJECTS DEPARTMENT

PRESENTATION ON IS 1180 (Part 1): 2014 DISTRIBUTION TRANSFORMERS SHYAM KUMAR SCIENTIST B ELECTROTECHNICAL BUREAU OF INDIAN STANDARDS

11-SDMS-03 REV. 02 SPECIFICATIONS FOR

JMAA-1800HR15. Installation and Operation Instructions. 180w Performance Series Amplifier Kit For Harley RoadGlide/ Ultra

7. INSPECTION AND TEST PROCEDURES

TECHNICAL SPECIFICATION

Reference Number PPS 05 - (RIC Standard: EP SP)

Title: Southern States Type SLS Smart Sectionalizer Solid Dielectric Three Phase Sectionalizer. Product Specification Guide TABLE OF CONTENTS

Company Directive ENGINEERING SPECIFICATION EE SPEC: 5/5. Relating to 11kV Distribution Transformers

JMAA-3600HR16-UL. Installation and Operation Instructions. Performance Series 360w RMS 4-Channel Amplifier Kit For Harley RoadGlide Ultra

No. COA/BHL/2018/293 Dated: REQUEST FOR QUOTATIONS

SYRIAN ARAB REPUBLIC MINISTRY OF ELECTRICITY PUBLIC ESTABLISHMENT FOR DISTRIBUTION THE ELECTRICITY (PEDE) SPECIFICATIONS FOR

KNOW MORE ABOUT THE TRANSFORMERS. Glossary Transformers

STATE OF OHIO DEPARTMENT OF TRANSPORTATION SUPPLEMENT 1073 PRECAST CONCRETE CERTIFICATION PROGRAM JULY 20, 2018

001: 2007 CEB STANDARD

TECHNICAL SPECIFICATION OF ELECTRICAL MATERIALS CT & PT GROUP C

Section Meetings Section Material and Equipment. None Required

Brown University Revised 2/1/2006 Facilities Design & Construction Requirements SECTION 16461C - DRY TYPE TRANSFORMERS

MGM Transformer. Vacuum Pressure Impregnated (VPI) Dry-Type Substation Transformer Specification Guide

ECP COMPACT AND MICRO SUBSTATION COMMISSIONING PROCEDURE

Title Substation Auxiliary Transformer from Rectifier Transformer Secondary. Reference Number PDS 01 (RIC Standard: EP SP)

380 SERIES REPAIR PARTS INDEX. NOTE! Read and understand the pump and motor instructions before attempting to install, disassemble or repair the pump.

Performance Series 360w Amplifier Kit For Harley RoadGlide with Lower/Rear Speakers JMAA-3600HR15-RC

Embedded Generation Connection Application Form

SPECIFICATION FOR 11 KV CLASS, 24/15.7, 30/19.7 & 45/29.5 AMPS SPECIAL DESIGN TRANSFORMERS.

Embedded Generation Connection Application Form

General Electricity Company of Libya

Mechanical Design. Brian Brinson Mechanical Design Manager.

Plant Client Contract Code Document ID Contract No. TECHNICAL SPECIFICATIONS DC SHUNT Rev 00 Page 1 of 2

Eaton s Cooper Power Series DEADFRONT ARRESTERS

Substation transformers

Figure 1. Two- and Three-phase MagneX Interrupter.

SINGLE-PHASE VSV SWITCH

Introduction. Centrado leading-edge transformer. Introduction

Power transformers for Network, Rectifiers, Furnace

UBC Technical Guidelines Section Edition Medium-Voltage Transformers Page 1 of 5

Pre-Filter. Brushless/ Sparkless Blower. HEPA Filter. Fluorescent Light

Liquid-Filled Transformers

TERMS OF SALE. Quotations & Orders

420 SERIES. TWO Stage Vertical and

Distribution transformers Part 2 Ground mounted transformers not closecoupled

RHODE ISLAND TURNPIKE AND BRIDGE AUTHORITY P.O. Box East Shore Road Jamestown, Rhode Island Invitation to Bid Request for Proposals

1. All electrical switches and outlets used shall be equal to Hubbell heavy duty, specification grade or equivalent quality.

JULY Standards are finally approved by the Standards High Council of Iranian Ministry of Petroleum.

OUR MISSION: TO PROVIDE HIGH QUALITY PRODUCTS, TECHNICAL EXCELLENCE & PRACTICAL ENGINEERING AT AN ECONOMICAL PRICE

EMR CORPORATION N. 25th Avenue Phoenix, Arizona Toll Free: Tel: (623) Fax: (623)

TABLE OF CONTENTS. 1.0 Scope. 2.0 References. 3.0 Definitions. 4.0 Submission and Design Requirements. 5.0 Materials 5.1 General 5.

GE Ventilated Dry-Type Transformers. Secondary Substation Transformers - 5 and 15kV Class

SMS4. Compact Two-Way Loudspeaker INSTRUCTION MANUAL

Master Reference Unit

Distribution/Substation Transformer

SPECIFICATIONS FOR TENDER # SUPPLY OF ONE WIRELESS CLOCK SYSTEM & ASSOCIATED COMPONENTS FOR WESTERN HEALTH

JAMP-700HR15-RCP. Installation and Operation Instructions. ROKKER XXRP 700w Amplifier Kit For Harley RoadGlide with Lower/Rear Speakers

HPS Universal BUCK-BOOST TRANSFORMERS

POTENTIAL TRANSFORMER

SECTION 16322B SUBSTATION TRANSFORMERS DRY-TYPE

Annexure - V. Specifications, Typical Drawing & Data Sheet for Split TEE (Hot Tapping Material)

Installation Instructions

Transcription:

Single-Phase Mini Pad-Mounted Transformer Specification: Energy+ MPDL Issued by: Approved by: Engineering Department Energy+ Inc. September 2016 Shawn Jackson, P.Eng. Approval is given in accordance with Ontario Regulation 22/04

i. Scope This specification includes Energy+ Inc. (ENERGY+) requirements for distribution transformers purchased by ENERGY+ and by developers or contractors purchasing on behalf of ENERGY+. The requirements of CSA Specification C227.3-06 (Reaffirmed 2011) apply in addition to specific requirements in this document. Where conflicting information exists, this document shall supersede the CSA specification. Clause numbering is identical to that used in C227.3-06. Additional or modifying statements to existing clauses contained in this specification shall govern and, where no reference is made, C227.3-06 shall apply as written. New clauses have been assigned new numbers based on the existing CSA numbering of the appropriate sections. ii. Latest Revisions a) Section 4.4 - Removed requirement for tap changer switch for 16kV transformers. The tap changer is still required for transformers specified with other primary voltages. b) Section 4.10 Added a minimum impedance of 4.25% for 167 kva transformers to reduce the available fault current at service entrance locations. c) Section 5.3 Updated transformer fusing requirements. d) Section 6.3.1.1 Added maximum secondary bushing thickness. e) Section 8.3.2.7 Increased allowable load losses for 167 kva transformers to allow for the higher impedance from Section 4.10. f) Section 11.1 h) added requirement for bail tabs on both HV bushing wells. g) 03-Jun-16: Changed supplemented CEA document to CSA. Changed tank steel to stainless. Changed corporate name. h) Included stainless steel construction requirement. i) Updated CSA spec number. Updated fusing part numbers (Table 6). 4. Electrical Characteristics 4.4.1 Off-Circuit Voltage Taps Voltage taps are not required for transformers with a primary voltage of 16 kv. For transformers with other primary voltages, off circuit voltage taps shall be included and shall meet Clauses 4.4.2 and 7.1. In addition, taps shall be hot stick operable and transformers shall be shipped with the tap switch in the 100% or neutral position. 4.10 Impedance September 2016 Page 2 of 11

Minimum impedances to limit the available short circuit current at service entrances shall be as follows: 50 kva 1.5% 75 kva 2.0% 100 kva 2.5% 167 kva 4.25% 5. Electrical Connection and Mechanical Features 5.2.1 Dimensions - Minimum Transformer Width Transformers shall have a minimum width of 915mm and a maximum dimension of 965mm. Therefore the width dimension shown in Figure 2 shall be revised to 940mm 25 mm. 5.2.5 Drain / Filler Plugs Transformers shall not include a drain plug. A filler plug is required and shall consist of a 1 IPS pipe connection with a threaded brass plug. 5.3 Fusing Specific transformer fusing requirements have been updated to include the latest manufacturer s recommendations. See Table 6. Fusing other than that specified must be approved prior to transformer manufacture. 5.3.2 Fusing Bayonet Assembly The fuse assembly shall be designed such that repeated fuse insertions and removals do not result in loosening or detachment of any contacts or other parts of the assembly. Copper press on contact clips shall be used for connection onto the fuse studs. Wire connections to the contact clips shall be made using appropriate nuts and bolts. 5.3.6 Fusing Interrupting Current Ratings The fuse assemblies shall have an interrupting capability as shown below, and provide safe energization and de-energization within any load range of the transformer: HV Rating Interrupting Capability (RMS Symmetrical) 4160GrdY/2400 12000 A, asymmetrical factor 1.2 8320GrdY/4800 12000 A, asymmetrical factor 1.2 27600GrdY/16000 12000 A, asymmetrical factor 1.6 September 2016 Page 3 of 11

5.3.7 Fusing Assembly Loadbreak Capability The load break device including leads, connectors, contacts, etc. shall be capable of carrying 200% of nominal transformer primary current both continuously and for load breaking at 40 C ambient. 5.4 Stainless Steel Construction Stainless steel shall meet the requirements of American Iron and steel Institute (AISI) Type 304L. The transformer tank, hood and sill shall be constructed from Stainless Steel Type 304L. 6. Bushings, Terminals, and Grounding 6.2 High Voltage Bushings 6.2.4 The H2 ground spade terminal shall be located between 350 mm and 400 mm from the left side of the transformer when facing the front wall. 6.2.5 The internal connection between the two bushings shall have a fault withstand rating according to clause 5.3.6. 6.3 Low Voltage Bushings 6.3.1 Low voltage bushings shall be as per Figure 9 a) for all transformer sizes including 167kVA. 6.3.1.1 The thickness of the bushing spade shall not exceed 10mm. 6.4 Grounding 6.4.1 A grounding bracket to facilitate the attachment of temporary working grounds is not required and therefore shall not be provided. 7. Switch and Tap Changers 7.2 Loadbreak Switch All transformers shall be supplied with a loadbreak transformer winding switch meeting the requirements of Section 7.2. The make and catalogue number of the switch shall be identified in transformer drawings for approval prior to manufacture. September 2016 Page 4 of 11

8. Tests 8.2 Routine Tests h) The leak detection test shall be performed with a minimum internal pressure of 50kPa. In addition to CSA C2.1-06 and C227.3-06, the following routine tests shall be performed for each transformer supplied: i) A RIV Test shall be performed for transformers having a high-voltage rating of 27600 GrdY/16000. j) An impulse test, modified from the ANSI C57.12.90 requirements to include only 2 full waves, shall be applied to transformers having a high-voltage rating of 27.6/16 kv. k) Resistance shall be measured on high-voltage and low-voltage windings at the transformer production rate of 1 per 25, or one per batch for quantities below 25. 8.3.2 Losses and Exciting Current 8.3.2.1 No Load Losses Transformer no-load loss and exciting current shall be quoted and measured at 100% of rated voltage and corrected to 85 C. 8.3.2.4 Assessment of Loss Penalty If the measured average No-Load loss or Load loss on a stock item of a given purchase order exceeds the guaranteed value, the evaluation formula from clause 8.3.2.1 shall be applied to obtain the actual cost of losses (a). The guaranteed cost of losses (b) shall then be calculated using the same formula. If (a) - (b) is a positive value, a penalty shall be assessed using ((a) - (b)) the number of units on the stock item. 8.3.2.5 Evaluation of Losses - Installation by ENERGY+ Quoted No-Load (N) and Load (L) losses in Watts will be evaluated in accordance with the following formula: Present Value of Cost of Losses = $8.30N + $4.10L. For evaluating competitive bids on a tender, the evaluated losses will be added to the quoted no-tax price to produce the "Total Owning Cost" (TOC). Tender award will not necessarily depend on the lowest TOC, but will also include other considerations such as September 2016 Page 5 of 11

first cost, delivery, manufacturing quality, and historical quality of contract performance. 8.3.2.6 Maximum Losses - Installation by ENERGY+ Losses shall be equal or less than those maximum values given in CSA Standard C802, Maximum Losses for Distribution, Power, and Dry-Type Transformers. 8.3.2.7 Maximum Losses - Installation by Developers Maximum values shall be as follows: Rating, kva No Load Loss, W Load Loss, W 50 105 300 75 145 440 100 210 525 167 255 1080 8.5.4 Impulse Tests In addition, the chopped waves, as required by CSA Standard C2.1-06, shall be replaced by two negative full waves and must be performed in addition to the requirements of CSA Standard C227.3-06. 9. Workmanship and Finish 9.2 Colour The standard exterior finish shall be equipment green, Munsell 9GY 1.5/2.6. 10. Markings 10.2.3 Information on Nameplate s) The purchase order number 10.5.1 Tank Markings h) The kva rating and high voltage shall be clearly stencilled on the inside of the hood. These designations shall consist of the numbers without kva or voltage wording, and shall be legible with the hood in an opened position. The numbers shall have a uniform minimum height of 60 mm. September 2016 Page 6 of 11

10.5.3 Information on the exterior of the Transformer 10.5.3.1 Information Tag c) The manufacturer s logo shall not appear on the exterior of the pad-mounted assembly d) The purchase order number 11. Accessories and Features 11.1 Optional Items The following optional accessories shall be included for all purchases meeting this specification: b) Filler plug (Section 5.2.5). c) Loadbreak transformer winding switch (Section 7.2). h) Bail tabs on each HV bushing well to connect a bleeder wire between the well and the insert. k) HV taps for transformers with primary voltages of other than 16 kv (Section 4.4). n) Impedance - Minimum impedances to limit the short circuit current at service entrance locations shall be as per Clause 4.10. s) Stainless Steel Construction the transformer shall be constructed with stainless steel (Section 5.4). 13. Witnessing 13.1 The manufacturer shall advise ENERGY+ s Engineering Department (or designated representative) a minimum of four production days in advance of scheduled testing. The notice will allow in-plant witnessing of the tests plus inspection of the transformers on order. Where the testing location is beyond 200 km from ENERGY+, a minimum of seven days notice shall be required. 13.2 A sampling, or the full quantity, of transformers of each rating ordered may be testwitnessed at the discretion of ENERGY+ s inspectors. 14. Quotation Data In addition to price and delivery, tenders shall include the following information in duplicate: September 2016 Page 7 of 11

Guaranteed No-load and Load losses at 100% voltage and 85 C. Guaranteed impedance at 85 C. (Where a design has been changed or the specific rating is infrequent, an approximation will suffice. Doubtful cases should be discussed with the Purchaser). Acknowledgement of specified fuse ratings. Make and catalogue number of the loadbreak switch. Location of manufacturing plant. 15. Contract Drawings Nameplate and Outline drawings, specific to the rating ordered, shall be submitted in two copies for approval prior to the commencement of production. Any deviations from this specification shall be clearly noted on the drawings. Signature by ENERGY+ on the approval drawings shall not waive the manufacturer s responsibility to supply the transformer(s) to this specification. Once the outline and nameplate drawings are approved by ENERGY+, new drawings are not required on future orders unless the manufacturer makes a change. 16. Certified Test Reports The manufacturer shall submit two copies of a Certified Test Report reflecting all Routine and Type Test results as outlined in this specification. The reporting of the Routine Tests should be similar to Figure 1 Sample Test Report. 17. Failure to Comply If the manufactured equipment does not comply with all the requirements of this specification, ENERGY+ reserves the right to reject all, or part of, the equipment under this contract. Such right will apply whether the equipment is in the manufacturing plant or in ENERGY+ s stores. 18. Shipment Shipment shall be made only when authorization is given by CNHDI. At such time, the shipment will be FOB Utility Stores. 19. Late Delivery September 2016 Page 8 of 11

ENERGY+ has the right to cancel a given order without cost to ENERGY+ if a late delivery is deemed unacceptable. 20. Warranty Approval, by ENERGY+ or its appointed agent, of the factory tests shall not relieve the manufacturer from its responsibilities with respect to Warranty. If a transformer is defective upon arrival or malfunctions in normal service, for causes other than an accident, misapplication, or abuse, during a period of one year after the unit is placed in service, or two years after delivery, whichever occurs first, the defective transformer will be returned to the manufacturer by common carrier at its own expense. The manufacturer shall make good all defects or shall provide a new transformer to replace the defective one without cost to ENERGY+. If the manufacturer fails to repair or replace the returned transformer within a time period agreed upon, the manufacturer shall reimburse ENERGY+ for the purchase price of the transformer. Transformers returned under Warranty shall include a Certified Test Report and a report on the cause of the failure. September 2016 Page 9 of 11

Table 6 Transformer Fusing (Section 5.3) kva PRIMARY V %IZ BAYONET FUSE ELSP FUSE 50 4160 Grd Y/2400 1.5 4000358C12M CBUC08180D100 8320 Grd Y/4800 1.5 4000358C08M CBUC08080C100 27600 Grd Y/16000 1.5 4000358C05M CBUC17030C100 75 4160 Grd Y/2400 2 4000358C14M CBUC08150D100 (2/ph) 8320 Grd Y/4800 2 4000358C10M CBUC08125C100 27600 Grd Y/16000 2 4000358C08M CBUC15080C100 100 4160 Grd Y/2400 2.5 4000358C16M CBUC08165D100 (2/ph) 8320 Grd Y/4800 2.5 4000358C12M CBUC08150D100 27600 Grd Y/16000 2.5 4000358C08M CBUC15080C100 167 4160 Grd Y/2400 4.25 4000358C18M CBUC08180D100 (2/ph) 8320 Grd Y/4800 4.25 4000358C14M CBUC08250D100 27600 Grd Y/16000 4.25 4000358C10M CBUC15080C100 September 2016 Page 10 of 11

Figure 1 Sample Test Report (See Section 16) XYZ Company DISTRIBUTION TRANSFORMER TEST REPORT* Customer: Energy+ Customer Code: P.O. No. Specification No.: MPDL September 2016 Work Order Number: Order Quantity: 5 Description: Low Profile Pad-Mounted Transformer 100kVA 27600GrdY/16000-240/120 V Tested By: Date: 05-07-22 Signature: Certified By: Witnessed By: Title: The following tests were successfully performed on each unit in accordance with the above specification: Ratio: Within 0.5% Yes Polarity: Additive Yes Applied Potential: HV to LV and Ground at: n/a L V to HV and Ground at: 10 kv for 1 min. Yes Induced Potential: 40/ 180/40 kv, Hz, sec respectively Yes Routine Impulse: On HV, 2-Full Waves at 125 kv Yes Radio Influence V: 100 V maximum Yes Oil Leak Test: At 50kPa Yes The following performance values were obtained: Resistance: Ser. No. 26219 HV: 6.130 ohms @ 85 C LV: 0.001043 ohms @ 85 C No Load % Exciting Load Loss Impedance Loss, W Current @ 85 C,W @85 C, % 100% V 110% V Guarantee 210 1.8 3.5 525 2.5 Ave. of 5 units 208.6 0.9 3.2 520.5 2.55 Serial No. Tested 26217 209.6 0.94 3.25 521.2 2.60 26218 208.3 0.92 3.14 518.7 2.52 26219 208.7 0.89 3.38 519.6 2.59 26220 207.6 0.80 3.15 520.8 2.51 26221 209.0 0.84 3.31 522.3 2.54 * - EXAMPLE ONLY September 2016 Page 11 of 11