The Upgradabilty of Conventional Three Phase Delta/Star Networks

Similar documents
MV network design & devices selection EXERCISE BOOK

The Variable Threshold Neutral Isolator (VTNI)

TN, TT & IT Earthing Arrangements

SDCS-03 DISTRIBUTION NETWORK GROUNDING CONSTRUCTION STANDARD (PART-I) UNDERGROUND NETWORK GROUNDING. Rev. 01

Electrical Switchgear & Power Transformer Testing. H.H. Sheik Sultan Tower (0) Floor Corniche Street Abu Dhabi U.A.E

SDCS-03 DISTRIBUTION NETWORK GROUNDING CONSTRUCTION STANDARD (PART-II) OVERHEAD NETWORK GROUNDING. Rev. 01

QUESTIONNAIRE for Wind Farm Power Stations only

ET 51 - Electrician Theory Examination Marking Schedule

Embedded Generation Connection Application Form

EDS LV WAVEFORM MAINS CABLE RATINGS

Education & Training

Power Voltage Transformers for Air Insulated Substations. THE PROVEN POWER.

Experience with VQM in Italy

MAJOR ADVANCES IN MV/LV SUBSTATIONS. Th.Grima et JF.Faltermeier. Groupe CAHORS, France SUMMARY

Low Voltage Products. Enclosed Third Harmonic Filter THF and THF star Enclosed units. Brochure THFS1GB 03_04 1SCC330003C0201

Problems connected with Commissioning of Power Transformers

Collection of standards in electronic format (PDF) 1. Copyright

Embedded Generation Connection Application Form

Remotes Case 2&3 Form REINDEER Cases 2&3 -Connection Impact Assessment (CIA) Application

Emicon Engineering Consultants L.L.C.

2kVA EARTH TESTING CURRENT INJECTION SYSTEM 4046 / 4047 DATASHEET REDPHASE INSTRUMENTS

Utility Interconnection and System Protection

POWER SERVICE DETAILS

LIGHTNING OVERVOLTAGES AND THE QUALITY OF SUPPLY: A CASE STUDY OF A SUBSTATION

VI 3 - i TABLE OF CONTENTS

UBC Technical Guidelines Section Edition Medium-Voltage Transformers Page 1 of 5

1. All electrical switches and outlets used shall be equal to Hubbell heavy duty, specification grade or equivalent quality.

Michigan State University Construction Standards SWITCHBOARDS, PANELBOARDS, AND CONTROL CENTERS PAGE

Need for grounding Codes and Standards for grounding Wind Turbine Generator grounding design Foundation + Horizontal Electrode grounding design

Protection of Electrical Networks. Christophe Prévé

FAQ ON EARTHING STANDARDS 16/08/2018

IVE(TY) Department of Engineering. Electrical Machines 1. Electrical Machines 1. Hour 13. slide 1

GROUNDED ELECTRICAL POWER DISTRIBUTION. Excerpt from Inverter Charger Series Manual BY: VIJAY SHARMA ENGINEER

SAFETY ISSUES RELATED TO THE CONNECTION OF MV AND HV GROUNDING

SECTION PANELBOARDS

MV ELECTRICAL TRANSMISSION DESIGN AND CONSTRUCTION STANDARD. PART 1: GENERAL 1.01 Transformer

BE Semester- VI (Electrical Engineering) Question Bank (E 605 ELECTRICAL POWER SYSTEM - II) Y - Y transformer : 300 MVA, 33Y / 220Y kv, X = 15 %

Topic 6 Quiz, February 2017 Impedance and Fault Current Calculations For Radial Systems TLC ONLY!!!!! DUE DATE FOR TLC- February 14, 2017

Capstone Turbine Corporation Nordhoff Street Chatsworth CA USA Phone: (818) Fax: (818) Web:

Substation Preventive Maintenance

Low Voltage Products. Third Harmonic Filter THF and THF star System components for assembly and retrofitting. Catalogue THFS2GB 03_05 1SCC330004C0201

Section L5: PRE-ENERGIZATION TEST PROCEDURES FOR LOAD-ONLY ENTITIES AND TRANSMISSION-ONLY ENTITIES

2/15/2015. Current will always try to return to its source. In order for there to be current, there must be a complete circuit

POWER DELEGATOR SERIES 7200A POWER DISTRIBUTION UNIT WITH POWER CONDITIONING GENERAL SPECIFICATIONS

Power Quality. Case Study. Conrad Bottu Laborelec January 2008

SECTION LOW-VOLTAGE ELECT. DIST. DESIGN AND CONSTRUCTION STANDARDS _ February 2015 PART I: GENERAL

Embedded Generation Connection Application Form

POWER FACTOR CORRECTION. HARMONIC FILTERING. MEDIUM AND HIGH VOLTAGE SOLUTIONS.

SPECIFICATION FOR STEP UP TRANSFORMER 0.415/11Kv and (630KVA & 1000KVA)

Upgrading Your Electrical Distribution System To Resistance Grounding

HVDC High Voltage Direct Current

Report on investigation of failure of 315 MVA Auto transformer at 400 kv Bawana Substation of Delhi Transco Ltd.(DTL)

PRACTICAL PROBLEMS WITH SUBSTATION EARTHING

OPTIMIZING MAINS IMPEDANCE: REAL WORLD EXAMPLES by Judith M. Russell Consulting Electrical Engineer PowerLines

Basic Principles and Operation of Transformer

Impact Assessment Generator Form

GSC57 Rel of 257/10/05

Integration between the MV protection and control unit REF542 and the LV protection trip unit PR123: selectivity and earth fault 1SDC007402G0201

thepower to protect the power to protect i-gard LITERATURE Low and medium voltage

SECTION - 3 EARTHING CLAMPS & FITTINGS

CONTENTS. 1. Introduction Generating Stations 9 40

Installation requirements

PREFACE ********************************************************** IT IS NOT INTENDED THAT THESE STANDARDS BE COPIED AND USED AS A SPECIFICATION!

Power Processor - Series 700F 10KVA to 150KVA

Shunt Reactors. Global Top Energy, Machinery & Plant Solution Provider

Company Directive STANDARD TECHNIQUE: TP21D/2. 11kV, 6.6kV and LV Earthing

Protective earthing, protective conductor and automatic disconnection in case of a fault (Fault protection)

Single-Phase Transformation Review

Positive-guided relay outputs: 8 safety contacts (N/O), instantaneous. 1 auxiliary contact (N/C), instantaneous


MV, HV AND EHV SWITCHGEAR TESTING & COMMISSIONING

GRID CODE COMPATIBLE PROTECTION SCHEME FOR SMART GRIDS

PRE COMMISSIONING TESTS ON EQUIPMENT AT 33/11 KV SUB STATIONS. IR Values are to be read on the megger by meggering the Power transformer

EARTH FAULT PROTECTION VIS-A-VIS GENERATOR GROUNDING SYSTEM

Chapter 12 Electric Circuits

Form-IV. Form of Inspection/Test Report. (Under Regulation 43)

Primary Metering. What is Primary Metering?

Design Approaches for Hospital Distribution Systems With Considerations for Future Expansion, Operator Safety, and Cost

The 50plus. 50plus technical support lighting circuits

CONTINUING EDUC ATION

Simulations of open phase conditions on the high voltage side of YNd05-power plant transformers

Specialists in HV and MV test and diagnostics. Testing in Substations

System Components and Accessories

Grounding Recommendations for On Site Power Systems

Module 9. Fault Type Form 4.X RELIABILITY ACCOUNTABILITY

ECP GROUND-MOUNTED SWITCHGEAR WITH PROTECTION RELAYS COMMISSIONING PROCEDURE

~=E.i!=h. Pre-certification Transformers

CHAPTER 5 POWER QUALITY IMPROVEMENT BY USING POWER ACTIVE FILTERS

, Power Industries and Communications Industry Training Board

ENERGY SAVINGS THROUGH POWER CONDITIONING WITH THE PowerGUARD SYSTEM

Course ELEC Introduction to electric power and energy systems. Additional exercises with answers December reactive power compensation

Company Directive STANDARD TECHNIQUE: SD5F. Relating to connecting multiple small low voltage connections with limited network analysis

6B.6 Substation Grounding

POWER SYSTEM ANALYSIS TADP 641 SETTING OF OVERCURRENT RELAYS

Document Type: DPL EARTHING OF ELECTRICAL Revision: 0 NETWORKS Published date: AUGUST 2010 Total pages: 15 Review date: AUGUST 2015

DM-III Multitest & DM-III Multitest F Power Quality Recorders

OPEN-PHASE DETECTION TECHNIQUES FOR CRITICAL STANDBY SUPPLIES

148 Electric Machines

ELECTRICIAN S THEORY EXAMINATION 20 November 2010 QUESTION AND ANSWER BOOKLET

Variation in SFRA plot due to design and external parameter

Transcription:

The Upgradabilty of Conventional Three Phase Delta/Star Networks

WHY NEW STANDARDS? CAPITAL COSTS Initial Final OPERATIONAL COSTS UPGRADABILITY SAFETY MAINTAINANCE

CONVENTIONAL CONFIGURATION Electrification Area 1-ph. MV/LV transformer HV/MV Substation SEF Protection MV 3-Wire line Single Phase MV Lines Single Phase LV Lines Electrification Area

Losses under Imbalanced Conditions The Delta Systems balances the loads and no losses are accumulated in the neutral conductor The following is a comparison for equal loading on the LV side Losses are displayed for a 1 km section of MV line only

Diagrammatic Demonstration-STAR Losses under imbalanced conditions Ph Red Ph Blue Ph Yellow Ph Neutr. Loss W Resistance 1 1 1 1 Amp 35 52 17 26 Loss 1200 2700 300 675 4875

Diagrammatic Demonstration-DELTA Losses under imbalanced conditions Ph Red Ph Blue Ph Yellow Ph Neutr. Loss W Resistance 1 1 1 1 Amp 20 20 20 0 Loss 400 400 400 0 1200

Comparison of Voltage drop and Losses for two system using same conductors sizes The system simulates six villages 30km apart & 30km away from the 3 ph lines. Saturation load is 1000W per household A 2.5 MVar Cap Bank is needed for the Delta System A 3.5 MVar Cap Bank is needed for the Star System

Delta 2.5MVA Cap Bank - Losses 353 kw (3 000 kw )

DELTA System with 2.5 Mvar Cap Bank

Star 2.5MVA Cap Bank - Losses 591 kw (3000kW )

STAR System with 3.5 Mvar Cap Bank

Conductor fixing position Stay assembly, complete with pre-form, stay insulator, turn-buckle and base plate. Three phase transformers mounted on transformer platform, surge arresters mounted on transformer Transformer surge arresters and tank earthed at transformer stations. Min 10 ohm earth resistance to be obtained Neutral to be earthed, every first and last pole from transformer. No LV earthing at Transformer Stations Three Phase General Arrangement Drawing

Single Phase General Arrangement Drawing Neutral to be earthed, every first and last pole from transformer. No LV earthing at Transformer Stations Single phase transformers pole mounted, surge arresters mounted on transformer Transformer surge arresters and tank earthed at transformer stations. Min 10 ohm earth resistance to be obtained Stay assembly, complete with pre-form, stay insulator, turn-buckle and base plate.

IDENTIFIED ISSUES Connectivity of 3 ph plant Existing MV lines conversion Substations revamp The MV 73% less capacity lighter poles, insulators and conductors earth fault protection (safer)

CONTINUED. Low voltage reticulation upgradable System imbalances and harmonics transfers Earth wires vulnerable to theft Compatibility with regional standards Alternative systems offer no visible cost savings Proper comparisons should be made.

Thank You!

Connectivity of Pole Mounted Split Meters and Ready Boards M M M M M Pole Mounted Meter Box, containing split meter & circuit breaker, 20A Service cable, two core copper conductor 6-10 sq mm, with integrated twin comms. meter cable, 1 sq mm. Poles to be earthed, every first and last pole from transformer. No LV earthing at Transformer Stations All customers to be provided with earthed installations No neutral to be earthed after the E/L unit to ensure save operation of E/L breakers 123 456 789 Ready Board, containing circuit breakers, light fitting, SSO s, meter key pad, neutral and earth terminals

REVISED STANDARDS WHY NEW STANDARDS MEDIUM VOLTAGE LOW VOLTAGE SERVICE LINES TRANSFORMERS COST SAVING

SERVICE LINE 6 sq mm SINGLE CORE CONDUCTOR Lower cost Lighter weight on structure CONDUCTOR FROM POLE TO METER Anchor to pole with pole lug No joints required No D-Irons & isolators required on pole ANCHOR SERVICE LINE TO HOUSE ROOF STRUCTURE No Service Bracket required FLY FUSE Protect network from service cable faults Cut-off position INSTALLATION TIME 50%

TRANSFORMERS GALVANIZED DISTRIBUTION BOX MAIN LV CIRCUIT BREAKER TO PROTECT TRANSFORMER No fuse to bypass with wire Transformer is protected against overload Phase balance can be checked if breaker trips Transformer can be replaced with bigger one RATED CIRCUIT BREAKERS ON CABLE CIRCUITS

POTENTIAL SAVINGS Time, cost, maintenance MEDIUM VOLTAGE Less components, less failure, less maintenance LOW VOLTAGE 40 % saving on material cost Saving per km LV line (average) Time saving easier construction SERVICE CONNECTION LINE 23% Saving on material cost 50% saving on installation time 50% less components to procure, transport & manage

ACCELERATED ELECRIFICATION Procurement process (Material, Contractors) Labour Contracts (Material by Utility) Turnkey Contracts Readyboards Increase distance 30m > 50m

REVISED STANDARDS WHY NEW STANDARDS MEDIUM VOLTAGE LOW VOLTAGE SERVICE LINES TRANSFORMERS COST SAVING

WHY NEW STANDARDS? ECONOMY TECHNOLOGY SAFETY OPERATION MAINTAINANCE

MEDIUM VOLTAGE VERTICAL CONFIGURATION

LOW VOLATGE REFURBISHMENT PROJECTS Use existing standards NEW PROJECTS Use ABC technology

SERVICE LINE 6 sq mm SINGLE CORE CONDUCTOR Lower cost Lighter weight on structure CONDUCTOR FROM POLE TO METER Anchor to pole with pole lug No joints required No D-Irons & isolators required on pole ANCHOR SERVICE LINE TO HOUSE ROOF STRUCTURE No Service Bracket required FLY FUSE Protect network from service cable faults Cut-off position INSTALLATION TIME 50%

TRANSFORMERS GALVANIZED DISTRIBUTION BOX MAIN LV CIRCUIT BREAKER TO PROTECT TRANSFORMER No fuse to bypass with wire Transformer is protected against overload Phase balance can be checked if breaker trips Transformer can be replaced with bigger one RATED CIRCUIT BREAKERS ON CABLE CIRCUITS

POTENTIAL SAVINGS Time, cost, maintenance MEDIUM VOLTAGE Less components, less failure, less maintenance LOW VOLTAGE 40 % saving on material cost Saving per km LV line (average) Time saving easier construction SERVICE CONNECTION LINE 23% Saving on material cost 50% saving on installation time 50% less components to procure, transport & manage

ACCELERATED ELECRIFICATION Procurement process (Material, Contractors) Labour Contracts (Material by ELGZ) Turnkey Contracts Readyboards Increase distance 30m > 50m