Study of High Voltage AC Underground Cable Systems Silva, Filipe Miguel Faria da; Bak, Claus Leth; Wiechowski, Wojciech T.

Similar documents
Published in: Proceedings of the International Conference on Power Systems Transients (IPST 2009)

Distance Protection of Cross-Bonded Transmission Cable-Systems

Switching Restrikes in HVAC Cable Lines and Hybrid HVAC Cable/OHL Lines

Measurements for validation of high voltage underground cable modelling

Resonances in Collection Grids of Offshore Wind Farms

Analysis and simulation of switching surge generation when disconnecting a combined 400 kv cable/overhead line with shunt reactor

System grounding of wind farm medium voltage cable grids

Measurements of the Distorted No-load Current of a 60/20 kv, 6 MVA Power Transformer Søgaard, Kim; Bak, Claus Leth; Wiechowski, Wojciech Tomasz

Aalborg Universitet. Linderum Electricity Quality - Measurements and Analysis Silva, Filipe Miguel Faria da; Bak, Claus Leth. Publication date: 2013

Aalborg Universitet. Ground Loop Impedance of Long EHV Cable Lines Ohno, Teruo; Bak, Claus Leth; Sørensen, Thomas K.

Published in: Proceedings of the 2016 IEEE International Conference on Power Electronics, Drives and Energy Systems (PEDES)

Solving Customer Power Quality Problems Due to Voltage Magnification

EVALUATION OF DIFFERENT SOLUTIONS OF FAULTED PHASE EARTHING TECHNIQUE FOR AN EARTH FAULT CURRENT LIMITATION

Lightning transient analysis in wind turbine blades

In power system, transients have bad impact on its

Frequency Domain Analysis of Capacitor Transient Overvoltages

Aalborg Universitet. EHV/HV Underground Cable Systems for Power Transmission Bak, Claus Leth. Publication date: 2015

Published in: IECON 2016: The 42nd Annual Conference of IEEE Industrial Electronics Society

2. Current interruption transients

A Study on Ferroresonance Mitigation Techniques for Power Transformer

Ferroresonance Experience in UK: Simulations and Measurements

Delayed Current Zero Crossing Phenomena during Switching of Shunt-Compensated Lines

Transformer energisation after network blackout

Power System Studies

ANALYSIS OF VOLTAGE TRANSIENTS IN A MEDIUM VOLTAGE SYSTEM

Published in: Proceedings of the 37th Annual Conference of IEEE Industrial Electronics Society, IECON 2011

Chapter -3 ANALYSIS OF HVDC SYSTEM MODEL. Basically the HVDC transmission consists in the basic case of two

Novel Electrically Small Spherical Electric Dipole Antenna

Considerations for the Application of Thyristor Controlled Series Capacitors to Radial Power Distribution Circuits

Long lasting transients in power filter circuits

Harmonic filter design for electrified railways

Application of Reactive Compensation equipment in industrial systems under aspects of harmonics and switching transients: A study of real case

FERRORESONANCE SIMULATION STUDIES USING EMTP

Published in: Proceedings of the IEEE International Power Electronics and Application Conference and Exposition (IEEE PEAC'14)

High voltage engineering

Earth Fault Protection

Neutral Reactor Optimization in order to Reduce Arc Extinction Time during Three-Phase Tripping

A Special Ferro-resonance Phenomena on 3-phase 66kV VT-generation of 20Hz zero sequence continuous voltage

Tab 2 Voltage Stresses Switching Transients

Exercise 1: Series RLC Circuits

OCCURRENCE OF DELAYED CURRENT ZERO CROSSING DUE TO LINE REACTIVE OVERCOMPENSATION LT CAMPINAS FERNAO DIAS 500 kv.

Pre-insertion Resistor of Switching Shunt Capacitor Banks

Transient Analysis and Mitigation of Capacitor Bank Switching on a Standalone Wind Farm

Simulation and Analysis of Ferroresonance in Power System

Aalborg Universitet. Published in: th European Conference on Antennas and Propagation (EuCAP) Publication date: 2017

FGJTCFWP"KPUVKVWVG"QH"VGEJPQNQI[" FGRCTVOGPV"QH"GNGEVTKECN"GPIKPGGTKPI" VGG"246"JKIJ"XQNVCIG"GPIKPGGTKPI

Ferroresonance Conditions Associated With a 13 kv Voltage Regulator During Back-feed Conditions

POWER FACTOR CORRECTION. HARMONIC FILTERING. MEDIUM AND HIGH VOLTAGE SOLUTIONS.

SWITCHING OVERVOLTAGES IN A 400-KV CABLE SYSTEM

Although shunt capacitors

Modeling of long High Voltage AC Underground Cables

A Guide to the DC Decay of Fault Current and X/R Ratios

HYBRID STATCOM SOLUTIONS IN RENEWABLE SYSTEMS

Harmonic control devices

UNDERSTANDING SUB-HARMONICS

The current distribution on the feeding probe in an air filled rectangular microstrip antenna

Power system impacts of decreasing resonance frequencies

Published in: Proceedings of the 16th Conference on Power Electronics and Applications, EPE 14-ECCE Europe

Do Capacitor Switching Transients Still Cause Problems?

Capacitive Voltage Substations Ferroresonance Prevention Using Power Electronic Devices

Analysis of a 405 km transmission line with series compensation

Analysis and design of lumped element Marchand baluns

Harmonic resonances due to transmission-system cables

CAPACITORS are commonly found in distribution

10. DISTURBANCE VOLTAGE WITHSTAND CAPABILITY

Power Quality enhancement of a distribution line with DSTATCOM

Directional Sensing for Online PD Monitoring of MV Cables Wagenaars, P.; van der Wielen, P.C.J.M.; Wouters, P.A.A.F.; Steennis, E.F.

Aalborg Universitet. Publication date: Document Version Accepted author manuscript, peer reviewed version

LCR Parallel Circuits

Switching and Fault Transient Analysis of 765 kv Transmission Systems

Design and Simulation of Passive Filter

Transmission Line Transient Overvoltages (Travelling Waves on Power Systems)

CHAPTER 5 POWER QUALITY IMPROVEMENT BY USING POWER ACTIVE FILTERS

Distribution Transformer Random Transient Suppression using Diode Bridge T-type LC Reactor

Evaluation of coupling between dc and ac transmission lines on the same right-of-way: Parametric analysis and mitigation methods

Published in: Proceedings of the th European Conference on Power Electronics and Applications (EPE'15-ECCE Europe)

ABSTRACT 1 INTRODUCTION

ASPECTS OF REAL-TIME DIGITAL SIMULATIONS OF ELECTRICAL NETWORKS

Exercise 2: Parallel RLC Circuits

Dynamic Study on the 400 kv 60 km Kyndbyværket Asnæsværket Line Ohno, Teruo

TECHNICAL BULLETIN 004a Ferroresonance

Some aspects regarding harmonic s distortions propagation in large medium voltage distribution system

A Thyristor Controlled Three Winding Transformer as a Static Var Compensator

Stability Enhancement for Transmission Lines using Static Synchronous Series Compensator

SIMULATION OF D-STATCOM AND DVR IN POWER SYSTEMS

AORC Technical meeting 2014

Harmonic Design Considerations for Wind Farms

Aalborg Universitet. MEMS Tunable Antennas to Address LTE 600 MHz-bands Barrio, Samantha Caporal Del; Morris, Art; Pedersen, Gert F.

Harmonic control devices. ECE 528 Understanding Power Quality

Overvoltage Phenomena in Offshore Wind Farms Following Blocking of the HVDC Converter

Oscillators. An oscillator may be described as a source of alternating voltage. It is different than amplifier.

Enhancement of Power Quality in Distribution System Using D-Statcom for Different Faults

Power Quality and Reliablity Centre

University of Jordan School of Engineering Electrical Engineering Department. EE 219 Electrical Circuits Lab

Improving Passive Filter Compensation Performance With Active Techniques

CHAPTER 4 POWER QUALITY AND VAR COMPENSATION IN DISTRIBUTION SYSTEMS

Decreasing the commutation failure frequency in HVDC transmission systems

An induced emf is the negative of a changing magnetic field. Similarly, a self-induced emf would be found by

Assessment of 42 Km, 150 kv AC submarine cable at the Horns Rev 2 HVAC wind farm

Design Strategy for Optimum Rating Selection of Interline D-STATCOM

Transcription:

Aalborg Universitet Study of High Voltage AC Underground Cable Systems Silva, Filipe Miguel Faria da; Bak, Claus Leth; Wiechowski, Wojciech T. Published in: Proceedings of the Danish PhD Seminar on Detailed Modelling and Validation of Electrical Components and Systems 21 Publication date: 21 Document Version Publisher's PDF, also known as Version of record Link to publication from Aalborg University Citation for published version (APA): da Silva, F. M. F., Bak, C. L., & Wiechowski, W. T. (21). Study of High Voltage AC Underground Cable Systems. In Proceedings of the Danish PhD Seminar on Detailed Modelling and Validation of Electrical Components and Systems 21 (pp. 1-15). Energinet.dk. General rights Copyright and moral rights for the publications made accessible in the public portal are retained by the authors and/or other copyright owners and it is a condition of accessing publications that users recognise and abide by the legal requirements associated with these rights.? Users may download and print one copy of any publication from the public portal for the purpose of private study or research.? You may not further distribute the material or use it for any profit-making activity or commercial gain? You may freely distribute the URL identifying the publication in the public portal? Take down policy If you believe that this document breaches copyright please contact us at vbn@aub.aau.dk providing details, and we will remove access to the work immediately and investigate your claim. Downloaded from vbn.aau.dk on: september 14, 218

Study of High Voltage AC Underground Cable Systems F. Faria da Silva, Claus L. Bak, Wojciech T. Wiechowski ABSTRACT igh-voltage cables are starting to be more often used to H transmit electric energy at high-voltage levels, introducing in the electric grid phenomena that are uncommon when using Overhead Lines. Under the phenomena worthy of special attention are those related with the cable energisation and deenergisation. Examples are switching overvoltage, zeromissing phenomenon, energisation of cables in parallel, series resonance and disconnection overvoltage, all described and explained in this paper. This paper starts by describing the main objectives of this PhD project, followed by a description of the different phenomena, illustrated by simulations based on real cable/system parameters. I. INTRODUCTION On the 4 th of November 28, Denmark Government decided that in order to reduce the visual pollution caused by Overhead Lines (OHL), all the transmission lines with a voltage level equal and below 15 kv must be undergrounded gradually within the next 2 years. Additionally, all new 4 kv lines will be built as cable lines (with some exceptions) [1][2]. This massive use of HV cables will force to some changes in the philosophies used until now for the planning, analysis and operation of electrical power systems. This PhD project intends to study the main problems affecting systems using a large number of HV cables and present the respective solutions. The PhD project should also provide guidelines to be used in the migration from an OHL based grid to a cable grid. II. PROBLEM DEFINITION Cables have electric characteristics distinct from OHL, being the most notable the higher capacitance of the first ones, This work is supported by Energinet.dk. F.F.S. is a PhD student at the Institute of Energy Technology, Aalborg University, 922 Aalborg, Denmark (e-mail: fms@energinet.dk, phone no. +45 99 4 92 8). C. L. B. is with the Institute of Energy Technology, Aalborg University, 922 Aalborg, Denmark (e-mail: clb@iet.aau.dk). W. T. W. is a Senior System Analyst at the Planning Department of Energinet.dk (e-mail: wwi@energinet.dk) Paper submitted to the PhD Seminar on Detailed Modelling and Validation of Electrical Components and Systems 21 in Fredericia, Denmark, February 8th, 21 what results in a larger production of reactive power by the line and reduction of transmitted active power. Other consequences are an increase of power losses and a raise of the voltage in the receiving end. To compensate the generated reactive power are usually installed shunt reactors, which due to their inductive characteristic raise other problems to the system, being the more notably ones resonances. In the analysis of a cable system especial attention must be given to the transients, as the connection/disconnection of a cable is a complex electromagnetic phenomenon that may originate overvoltage in the energised cable, and strongly affect the rest of the grid. Harmonics are also a relevant issue in cable systems. As cables have a large capacitance than OHL, the resonance frequencies will be at lower frequencies than in OHL based grids, and thus more likely to be a problem for the grid. III. OBJECTIVES The main objectives of this PhD project are: To identify the main problems on system with large amounts of HVAC cables; Study countermeasures for these problems; Do a full-scale test of a 1 km, 15 kv cable; Study of harmonic in a large HV cable system; Provide guidelines/suggestions for the planning of future electrical systems at 4kV, 15kV and 132kV levels; IV. PHENOMENA DESCRIPTION A. Energisation of a single cable The energisation of a cable may origin a transitory overvoltage, which amplitude depends of the moment in which the cable is connected. If the circuit breaker is closed when the voltage at its terminals is zero the overvoltage is minimum, ideally zero, but if the connection is made for a peak voltage, the overvoltage is maximum. The reason for this difference is the charging of the cable's capacitance and the energy oscillation between the cable's capacitance and inductance. To better understand this phenomenon it will be explained using a simple LC series circuit, as the one shown in Fig. 1, whose simulation's plot is shown in Fig. 2. 1

Fig. 1. LC Circuit Voltage [kv] 3 2 1-1 -2 Vin I_CB -3.15.11.115.12.125.13.135 Time [s] Fig. 2. Voltages and current (current not at scale) for Fig. 1 circuit when connected at peak voltage. (Blue: Vin, Green: Vc, Red: I_CB) L Vc C the inductor is connected for zero voltage, in order to maintain its continuity the current will have a DC component with amplitude equal to the amplitude of the AC component. If the inductor is connected for a peak voltage no DC component is present [4]. If there is no resistance in the system, the DC component is not damped and it will be maintained infinitely. In reality there is always some resistance and the DC component disappears after some time. Fig. 3 shows an inductor in series with a resistor, both of them in parallel with a capacitor. The resistance is 1 times smaller than the inductor reactance, which is equal to the capacitor reactance. Fig. 4 shows a simulation of Fig. 3. The circuit breaker closes when the voltage is crossing zero, and therefore the DC component in the inductor is maximum. The inductive and capacitive AC components cancel out (IL and IC have equal amplitude and are in phase opposition) and the current I1 contains only the decaying DC component In this system, initially both capacitor and inductor have no energy, but as the voltage in the capacitor (Vc) has to be continuous, when the circuit breaker closes for a voltage value that not zero, the capacitor has to be charged through the inductor, initiating a transient with the system natural frequency. After a very short moment the voltage in the capacitor is equal to the source voltage, but when this moment is reached the current in the inductor is at a peak value (see Fig. 2) and by energy conservation it can not become zero immediately. Thus the voltage in the capacitor continues to increase becoming larger than the source voltage while the current decreases to zero, when the current makes to zero Vc reaches a peak value and the capacitor starts to discharge [3]. As the system has no resistance this transient is not damped, and the oscillatory behaviour continues with one difference. Due to the fact that source is sinusoidal, for each transient cycle at system natural frequency, Vc will match the source voltage at different points, and thus the amplitude of Vc is different for each cycle, as the reference voltage for the capacitor terminals, is constantly changing. Other phenomenon associated with cables' energisation is the appearance of a decaying DC current at the connection moment, what may lead to zero-missing phenomenon. An easy way of understanding zero-missing phenomenon is by analysing an inductor in parallel with a capacitor of equal impedance. In this situation the currents in the capacitor and inductor have equal amplitude and are in phase opposition. The current in the inductor can also have a DC component, whose value depends on the voltage at moment of connection. In an inductor there is a 9º phase difference between the current and the voltage at its terminals. Thus, if the voltage is zero the current should be maximum and vice-versa. The current in an inductor is continuous and zero before the connection, so it must also be zero after the connection regardless the voltage at moment of connection. Therefore, if Fig. 3. Equivalent scheme of an inductor in series with a resistor, both in parallel with a capacitor Fig. 4. Current in the inductor (IL), in the capacitor (IC) and the sum (I1=IL+IC) The behaviour of a system consisting of a shunt reactor and a cable is not very different from the one depicted in Fig. 3. The shunt reactor can be modelled as an inductor in series with a resistor, and the cable is mainly a capacitive shunt element [5]. The two situations explained before are shown in Fig. 5 and Fig. 6. In Fig. 5 it is shown the current through the circuit breaker and the voltage at the cable's end for a circuit breaker closing a zero voltage, thus there is maximum initial DC component, but no switching overvoltage. Whereas in Fig. 6 are shown the current and the voltage for a circuit breaker closing at peak voltage, resulting in a maximum switching overvoltage (1.75 pu), but no initial DC component. 11

inrush current. This shift of the "capacitor's" charge from one cable to the other is shown in Fig. 7. When the circuit breaker is closed the energy stored in the cable already energized is transferred to the cable being energized, as indicated by the arrows in Fig. 7. The inrush currents will not be as high as the ones obtained when energizing capacitor banks in parallel, due to the cables' resistance and inductance, which limits the transient and damps it faster. Fig. 5. Current in the circuit breaker and voltage on the end of the cable for a situation of maximum DC component Fig. 7. Cable's energisation equivalent circuit To demonstrate this phenomenon the energisation of two equal 4km, 72.5kV cables, whose datasheet can be consulted in [8], will be simulated as represented in Fig. 8. The cables are connected in parallel, and in order to reduce the grid influence its short-circuit power is low (a.4367ω resistance and a 31.416Ω reactance), this way there is a larger interaction between the two cables and a smaller one with the grid. Fig. 6. Current in the circuit breaker and voltage on the end of the cable for a situation of maximum switching overvoltage B. Energisation of cables in parallel Electrically, cables are mainly capacitive elements, so the energisation of a cable, when connected to an already energised one, can be seen as being similar to the energisation of capacitor banks in parallel. When energising a capacitor bank that is in parallel with an already energised capacitor bank there will be an inrush current whose amplitude depends of the voltage in the connection moment, and can go up to 1pu [6] or even 2pu [7]. A cable can be modeled as series of RLC circuits like is shown in Fig. 7. As the cable's inductance and resistance are very small the series of "capacitors" on the two cables will be almost in parallel. When in parallel, capacitors should have the same voltage, so part of the charge on the "capacitors" of the energized cable will transfer almost immediately for the "capacitors" of the cable being connected, originating an Fig. 8. Energisation of a cable in parallel with an already energized cable (t 2>>t 1) The simulation results are presented in Fig. 9 and Fig. 1. Fig. 9 shows the current on the sending end for the energisation of cable A at t 1, with cable B not connected to the busbar. This situation is similar to the energisation of a single cable and it was explained in the previous sub-section. The current maximum value is around 7A. At t 2, after cable A have reached steady-state conditions, cable B is energized. The currents in both cables during the energisation of cable B are shown in Fig. 1. As can be noticed during the first.3ms the currents are 12

almost symmetrical, meaning that the current being injected in cable B is coming from cable A. It should be observed that when energising a cable in parallel with an already energised cable, the frequency and the currents reach higher peak values that for the energisation of a single cable, the current's amplitude is 1kA when for energisation of a single cable it did not pass the 7A, an increase of 43%. takes a long time to completely damp the voltage in the cable. Current [A] 8 6 4 2-2 -4-6.2.4.6.8.1 Time [s] Fig. 9. Current on Cable A sending end during the energisation its energisation Current [A] 15 1 5-5 -1-15.5.55.51.515.52.525.53 Time [s] Fig. 1. Currents on the sending ends of Cable A and Cable B during the energisation of Cable B (Blue: Cable A; Red: Cable B) C. Deenergisation of a single cable When a cable is disconnected the energy stored in the cable has to be damped, what due to the low cable resistance can take several seconds. When there is a shunt reactor connected directly to the cable, the stored energy will oscillate between the cable and the shunt reactor, with a resonance frequency that can be approximately calculated by (1), where L sh is the shunt reactor inductance and C cable is the cable capacitance. This equation does not consider the cable's inductance, which is small when compared with the shunt reactor inductance. f r 1 (1) 2 L C sh cable Fig. 11. Voltage in the end of the cable during its deenergisation. a) Zoom of the disconnection moment b) First 5s of the cable's deenergisation In this situation no overvoltage is expected, but this happens because mutual inductances between the shunt reactor phases were not considered. When the cable is disconnected the three phases are disconnected in different moments, being normally a time difference of 3.333 ms between the disconnection of each phase, if shunt reactor's mutual inductance is considered the system will be unbalanced and overvoltage is expected [9]. When the three phases are connected there is a phase difference of 12º between the three currents (see Fig. 12.a), but after the first phase be disconnected, that phase starts to oscillate at resonance frequency while the other two continue to do it at 5Hz, thus the phase difference is no longer 12º. Because of mutual inductance the voltage in each phase depends of the current in the other two phases, as the system is no longer balance the voltage will become larger in one or two phases while it becomes smaller in the remaining phase(s). The situation with larger overvoltages is the one shown in Fig. 12.b, where the voltage due to self and mutual inductances are aligned generating a maximum voltage. This can be verified in Fig. 11 where it is shown the voltage during the cable deenergisation. The shunt reactor compensates 46% of the cable's reactive power, thus using (1) a resonance frequency of approximately 34Hz is expected, and this is the value obtained in the simulation. It can also be noticed in Fig. 11.b that due the low system's resistance it Fig. 12. a) Currents and voltage in phase A when the cable is connected; b) Currents and voltage in phase A, for a possible disconnection The simulations done previously are repeated but considering a mutual inductance of -.4H between the phases 13

of the shunt reactors. The system resonance frequency is 34.25Hz, and the phases are disconnected by the following order A->C->B. In Fig. 13 are shown the voltages after the cable disconnection. VAB VA VAC Fig. 13. Vectorial representation of the voltages after all the three phases be disconnected From Fig. 13 is expected a higher voltage in phase C than in the other two, and this can be verified in Fig. 14 where are shown the simulation plots. Notice that while in the first phase to be disconnected (Phase A) there is no overvoltage in the second (Phase C) the voltage goes up to 1.16pu. In the analyzed case the mutual inductances were all equal, but in reality they are most likely to be different, unbalancing even more the system. It is also noticed in the figures a low frequency component, this happens because after the disconnection of the last phase, each of the phases resonate at slightly different frequencies, and so due to mutual coupling a modulated low-frequency decaying voltage appears [9]. connected for zero voltage, and no overvoltage is expected. The simulation plots are present in Fig. 15. When there is no transformer the behaviour is the expected one and there is only a slight overvoltage (Fig. 15.a). But when a transformer is used, and the system cable plus transformer is energized the voltage goes up to 2pu in one of the phases, and higher than 1.7pu in the other two phases (Fig. 15.b). The overvoltage takes several cycles to be damped and is presented in the system for more than 1s, in the simulation the transformer saturation was not activated. The system frequency spectrum is shown in Fig. 16, being the minimum impedance, i.e. the series resonance point, for a frequency of approximate 8Hz. Fig. 15. Voltage in the cable's receiving end during its energization: a) without transformer b) with transformer 4 Impedance [Ohm] 3 2 1 Fig. 14. Voltage in the end of the cable. a) 2nd phase to be disconnected b) 1st phase to be disconnected D. Series Resonance between cable and transformer The inductance of a transformer can create a series resonance circuit with the capacitance of a cable. This situation is characterized by low impedance for the harmonic currents at the resonance frequency, what may result in high current distortion and overvoltage if the cable is long enough. The reason for this phenomenon to be more relevant when using underground cables than OHL is because the capacitance is higher on the first ones, and thus the resonance frequency lower. To simulate this phenomenon is used a 18km cable, connected to a transformer, which is connected to an ideal voltage source. The system is energised two times, with and without the transformer, in both times the three phases are 14 25 5 75 1 125 15 Frequency [Hz] Fig. 16. Frequency Spectrum During the cable/transformer energisation there is an energy exchange between the system's inductance and capacitance at system resonance frequency. The main voltage harmonic continues to be the fundamental, but the high current that appear at the resonance frequency originates voltages with the same frequency, which when added to the fundamental distort the voltage and create the temporary overvoltage presented on Fig. 15.b. The simulation was made without transformer saturation, if it saturates other harmonic currents would be injected in the system what may increase the overvoltage a little more.

V. CONCLUSIONS Several non-desirable phenomena are associated with HV underground cables transients. These transients may reduce the lifetime or even damages cables and remaining network equipment. Thus they must be attended when planning and operating the electric grid. This paper presents several of those phenomena, showing how overvoltages and inrush currents can appear in systems based on HVAC cables. The phenomena were presented for simple systems, consisting in no more than two cables, shunt reactor and transformer. A real grid is much more complex, and thus in reality these phenomena may be even more dangerous for the network. Therefore, countermeasures and mitigation methods have to be study under the risk of in the future having instead constant fails and damages in the grid. VI. REFERENCES [1] Energinet.dk, "Kabelhandlingsplan 132-15 kv", 29, (in Danish) [2] ELINFRASTRUKTURUDVALGET, " Technical report on the future expansion and undergrounding of the electricity transmission grid", Appil 29 [3] Alan Greenwood, "Electric Transients in Power Systems", John Wiley & Sons, 1st Edition, 1971 [4] J. F. Borges da Silva, "Electrotecnia Teórica - 1ª Parte", 2nd edition, AEIST, 1995 (in Portuguese) [5] J. H. R. Enslin, Yi Hu, R. A. Wakefield, "System Considerations and Impacts of AC Cable Networks on Weak High Voltage Transmission Networks", Transmission and Distribution Conference and Exhibition, 25/26 IEEE PES, May 26 [6] IEEE Guide for the Protection of Shunt Capacitor Banks, IEEE Standard C37.99-2, 2 [7] C. D. Tsirekis, N. D. Hatziargyriou, "Control of Shunt Capacitors and Shunt Reactors Energization Transients", IPST 23 [8] 6-5kV High voltage Underground Power Cables: XLPE Insulated Cables, Nexans [9] Claus L. Bak, Wojciech Wiechowski, Kim Søgaard, Søren D. Mikkelsen, "Analysis and simulation of switching surge generation when disconnecting a combined 4kV cable/overhead line with shunt reactor", IPST 21 15