Regional Technical Seminar SHORT CIRCUIT FORCES

Similar documents
Regional Technical Seminar SHORT CIRCUIT FORCES

Transformer Winding Design. The Design and Performance of Circular Disc, Helical and Layer Windings for Power Transformer Applications

CHAPTER 2 ELECTROMAGNETIC FORCE AND DEFORMATION

Western Mining Electric Association San Antonio TX Layer vs. Disk Windings Discussion NOVEMBER 15, SPX Transformer Solutions, Inc.

Electrical Design Process

Transformer Technology Seminar What to consider at Design Reviews

PES & IAS NY Chapter And NY LMAG June 23 rd, 2015

CHAPTER 3 SHORT CIRCUIT WITHSTAND CAPABILITY OF POWER TRANSFORMERS

Regional Technical Seminar TAP CHANGERS

Transformer Technology Seminar Winding Selection

SPECIFICATION FOR STEP UP TRANSFORMER 0.415/11Kv and (630KVA & 1000KVA)

TRANSFORMER TECHNOLOGY GPT

POWER TRANSFORMER SPECIFICATION, DESIGN, QUALITY CONTROL AND TESTING 18 MARCH 2009

(2) New Standard IEEE P (3) Core : (4) Windings :

Transformer Design: Economics & Reliability

DATA SHEET FOR LIGHTING TRANSFORMER APPD. BY VDV PROJECT NO

save energy, it is precious SYNERGY transformers Mfg. of all types of Distribution / Power & Furnace Transformers

HOW TO SAFE GUARD THE TRANSFORMER..???

Understanding and Extracting Valuable Information from Basic and Advanced Power Transformer Testing Techniques

86 chapter 2 Transformers

TIGHTENING TORQUE ON WOODEN CORE CLAMP (Nm) (STEEL FASTENER) 1 M M M M M

Group F : Sl. No. - 1) 33/0.403 KV, 100 KVA Station Transformer GUARANTEED & OTHER TECHNICAL PARTICULARS. Table : A

Short-Circuit Current Calculations

S C Strength of Winding Exits and Leads : A critical area for Failure Prevention in Power Transformers

CONSULTANT PROCEDURES & DESIGN GUIDELINES Liquid-Filled Utility Transformers UNIVERSITY OF MISSOURI

Phase Shifting Transformers. Presented by

PROBLEMS on Transformers

KNOW MORE ABOUT THE TRANSFORMERS. Glossary Transformers

WESTERN UNDERGROUND COMMITTEE GUIDE 2.6 (2.6/00/0868)

S. C. Electric Cooperative s Specification for a Single-Phase, Single Bushing Overhead Distribution Transformer (Revised 10/2013)

SOUTHERN ELECTRICITY SUPPLY COMPANY OF ODISHA LIMITED (SOUTHCO UTILITY)

Transformer Factory Testing

PCS Working Group on General Requirements C

ANALYSIS OF OPERATION MODE AND PERFORMANCE INDICATORS OF A TRANSFORMER WHEN CONTROLLING ITS VOLTAGE WITH AN ALTERNATING MAGNETIC FLUX

DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING QUESTION BANK SUBJECT CODE & NAME : EE 1402 HIGH VOLTAGE ENGINEERING UNIT I

Hendrix Tap, Tie & Ground Wire

Effects of Harmonic Distortion I

MV ELECTRICAL TRANSMISSION DESIGN AND CONSTRUCTION STANDARD. PART 1: GENERAL 1.01 Transformer

Power Transformers Basics

TRANSFORMERS PART A. 2. What is the turns ratio and transformer ratio of transformer? Turns ratio = N2/ N1 Transformer = E2/E1 = I1/ I2 =K

GOVERNMENT COLLEGE OF ENGINEERING, BARGUR

Pomona, CA May 24 & 25, LTC Applications - Location, Series & Preventative Auto Transformers

Regional Technical Seminar

Understanding the Value of Electrical Testing for Power Transformers. Charles Sweetser - OMICRON

Assessment of Winding Deformation in Power Transformer using SFRA and Numerical Techniques Ashwini Bhujangrao Gaikwad

UNIVERSITY OF MISSOURI Liquid-Filled Utility Transformers 2016 Q1

Prolific Systems & Technologies Pvt. Ltd. CORE DETAILS. CENTRE Figure - II L-2 X Y Wt-2

Transformers handling and transport

Understanding the Value of Electrical Testing for Power Transformers. Charles Sweetser, OMICRON electronics Corp. USA

Protecting power transformers from common adverse conditions

CONTENTS. 1. Introduction Generating Stations 9 40

Shunt Reactors. Global Top Energy, Machinery & Plant Solution Provider

3Ø Short-Circuit Calculations

APPENDIX 4 TYPICAL LAYOUT, VALUES AND CONSTANTS

Training Fees 3,300$ per participant including Materials/Handouts, Tea/Coffee Refreshments & International Buffet Lunch.

Electrical Description

Copper Core & Coil Transformer

and cured to reduce hot spots and seal out moisture. The assembly shall be installed on vibration-absorbing pads.

51-SDMS-04 SPECIFICATIONS FOR. DISTRIBUTION TRANSFORMERS UP TO 36 kv WITH ALUMINUM WINDINGS FOR DUAL SECONDARY 400/230 V AND 230/133 V

Short Circuit Current Calculations

GREEN TRAFO PRODUCTS SHR - THREE-PHASE SHUNT REACTOR

TABLE OF CONTENT

MEDIUM VOLTAGE PRODUCT. PARAMETERS GUIDE How to specify the indoor instrument transformers correctly

Power transformers for Network, Rectifiers, Furnace

Transformer Protection

Curve accuracy (enough data points to be statistically significant): See Attachment B.

Siemens Transformer Technology Seminar Insulation & Thermal Design

A Review Comprehension: Guideline for Testing of HV, EHV and UHV Substation Equipment

Liquid-Filled Transformers

Technical Information Requirement for MV Transformers and Transformer for Internal Power Supply for SUNNY CENTRAL

2C73 Setting Guide. High Impedance Differential Relay. Advanced Protection Devices. relay monitoring systems pty ltd

148 Electric Machines

AGN 034 Alternator Reactance

ROEVER ENGINEERING COLLEGE ELAMBALUR, PERAMBALUR DEPARTMENT OF ELECTRICAL & ELECTRONICS ENGINEERING

ANALYSIS OF TRANSIENT ACTIONS INFLUENCE IN POWER TRANSFORMER

Analysis of Major Changes to Arrester Standards IEC STEVE BREWER

Technical Information Requirement for MV Transformers and Transformer for Internal Power Supply for SUNNY CENTRAL

Discipline Electrical Testing Issue Date Certificate Number T-2837 Valid Until Last Amended on - Page 1 of 6 LOCATION 1

CONDITIONS FOR A TENTATIVE APROVAL FOR CONNECTION OF TRANSFORMERS

Cork Institute of Technology. Autumn 2008 Electrical Energy Systems (Time: 3 Hours)

Evaluating the Response of Surge Arresters

Comparison of CAN/CSA C88.1, IEEE C /01 & IEC 60137

INTERPRETATION METHODOLOGY TO IDENTIFY FAULT LOCATION IN A POWER TRANSFORMER

ANALYSIS OF TRANSIENT ACTIONS INFLUENCE IN POWER

Three-phase short-circuit current (Isc) calculation at any point within a LV installation using impedance method

COMPANY PROFILE... 1 QUALITY CERTIFICATES... 2 APPLICATIONS... 3

TesTIng of Power. Transformers are the largest, most. feature. By brandon dupuis

Optimization of power transformers based on operative service conditions for improved performance

Course 11 Distribution Transformer Applications Instructor: David R. Smith, PE Due: April 24, 2017 (EV), April 25, 2017 (LC)

Loss prophet. Predicting stray losses in power transformers and optimization of tank shielding using FEM

Comparison of Leakage Impedances of Two Single-phase Transformers

Schedule of Accreditation issued by United Kingdom Accreditation Service 2 Pine Trees, Chertsey Lane, Staines-upon-Thames, TW18 3HR, UK

شركة كهرباء محافظة القدس المساهمة المحدودة JERUSALEM DISTRICT ELECTRICITY CO. LTD.

MESP TECHNICAL SPECIFICATION FOR AN ESSENTIAL SERVICES SUPPLY STEP UP TRANSFORMER

3-phase short-circuit current (Isc) at any point within a LV installation

Tougher than any challenge. Transformers for highcurrent. industrial applications. siemens.com/transformers

ELECTRICAL NETWORKS SPECIFICATION TECHNICAL SPECIFICATION FOR A 230V/110V AND 400V/110V TRANSFORMER

POWER TRANSFORMERS CATALOGUE

Back to the Basics Current Transformer (CT) Testing

Transcription:

Regional Technical Seminar SHORT CIRCUIT FORCES

Short Circuit Forces Wallace Exum Electrical Design Engineer wallace.exum@spx.com

Agenda 1. What is Short Circuit 2. Types of Faults 3. How to Calculate Short Circuit Current 4. Relationship between Current, Magnetic Field and Forces 5. Short Circuit Failure Modes 6. Non-standard Requirements 7. Types of Transformer Applications with Special Fault Duty SPX Transformer Solutions, Inc. August 31, 2018 3

What is Short Circuit SPX Transformer Solutions, Inc.

Normal Transformer Operation Normal Circuit An AC source supplies power to a given load (i.e. a city). A complete circuit has a source, with power entering a load and returning to the source. Amount of current that flows is directly related to the load on the transformer. 1000 amps 1000 amps SPX Transformer Solutions, Inc. June 20 th, 2018 5

12500 amps What is a Fault? System Fault An un-intended electrical connection made between two energized components having different voltage potentials. Results in some (or all) of the current bypassing the intended load. Currents are typically very high due to low fault impedance SPX Transformer Solutions, Inc. June 20 th, 2018 6

Types of Faults SPX Transformer Solutions, Inc.

Types of Faults Basic Types of Faults in Power Systems Line-to-Ground (Most Common) One or more conductors make electrical contact with ground Example: Wildlife or Lightning. A lightning strike causes a flashover. The stroke between the line and ground causes ionization of the air (a low impedance path to ground). SPX Transformer Solutions, Inc. August 31, 2018 8

Types of Faults Basic Types of Faults in Power Systems Line-to-Line Two different phases come into direct or indirect contact with each other Example: A bird with a large wingspan touches two conductors simultaneously SPX Transformer Solutions, Inc. August 31, 2018 9

Types of Faults Basic Types of Faults in Power Systems Double Line-to-ground Three Phase (least common) Similar to Line-to-Line but when all three phases make contact with each other Example: A falling tree on a transmission line SPX Transformer Solutions, Inc. August 31, 2018 10

Types of Faults IEEE Standards for Transformers and Short Circuit: C57.12.00-2015 Section 7 Liquid-immersed transformers shall be designed and constructed to withstand the mechanical and thermal stresses produced by external short circuits under the conditions specified in 7.1.3, 7.1.4, and 7.1.5. The external short circuits shall include three-phase, single line-toground, double line-to-ground, and line-to-line faults on any one set of terminals at a time. Duration of faults shall be limited to 2 seconds unless otherwise specified by the user Transformer components such as leads, bushings, LTCs, de-energized tap changers, and current transformers that carry current continuously shall comply with all the requirements of 7.1.3 and 7.1.4. However, when not explicitly specified, LTCs are not required to change taps successfully under short circuit conditions. The temperature of the winding conductor (copper) during short circuit shall not exceed 250C C57.12.90-2015 Section 12 Impedance variation shall not exceed 2% for transformers <= 30MVA (ONAN) Impedance variation shall not exceed 1% for transformers > 30MVA (ONAN) Transformers shall be designed to withstand all types of faults SPX Transformer Solutions, Inc. August 31, 2018 11

Types of Faults IEEE Standards for Transformers and Short Circuit: IEEE Standard C57.109 Sample I 2 * t curve for a Category IV transformer. Category IV transformer > 10,000 KVA single-phase > 30,000 KVA three-phase SPX Transformer Solutions, Inc. August 31, 2018 12

How to Calculate Short Circuit Current SPX Transformer Solutions, Inc.

How to Calculate Short Circuit Current C57.12.00 Section 7 defines both symmetrical and asymmetrical current Symmetrical Current Asymmetrical Current Isc symmetrical SC Current (A, rms) Ir rated current (A, rms) Zt transformer impedance for same voltage tap and MVA as rated current (Ir) Zs system impedance in per unit on the same MVA base for rated current (Ir) Make sure Ir and Zt are on the same MVA base SPX Transformer Solutions, Inc. August 31, 2018 14

How to Calculate Short Circuit Current EXAMPLE: Assume we have a 30MVA transformer with a 69kV primary and a rated secondary current of 1000 amps. The tested load losses are 72 kw, and the tested impedance is 8.0%. Find Isc and Isc(pk,asym). Symmetrical Current with Zs Symmetrical Current without Zs 1000 0.08 + Z s Z s = MVA T MVA S = 30 9800 = 0.31% 1000 0.08 + 0.0031 = 12,034 A 1000 0.08 + 0 = 12,500A Difference is almost 500A or 4% Note: Zs is derived from C57.12.00-2015 Table 14 if not specified from customer. SPX Transformer Solutions, Inc. August 31, 2018 10

How to Calculate Short Circuit Current EXAMPLE: Assume we have a 30MVA transformer with a 69kV primary and a rated secondary current of 1000 amps. The tested load losses are 72 kw, and the tested impedance is 8.0%. Find Isc and Isc(pk,asym). Asymmetrical Current without Zs I SC pk asym = 2.702 12,500 I SC pk asym = 33,775 A Note: Forces are proportional to current-squared. Therefore the forces from this example will be (33,775 amps / 1000 amps) 2 = (33.775) 2 = 1140 x normal forces 1. Find %R Load Loss (kw) %R = 100x KVA T 2. Find X/R X R = Z T %R = 8% 0.24% = 33.33 = 100x72 30,000 = 0.24% K = 1 + e tan 1 33.33 + π 2 1 33.33 sin(tan 1 (33.33)) 2 K = 2.702 SC Current is much greater than normal load current SPX Transformer Solutions, Inc. August 31, 2018 11

How to Calculate Short Circuit Current EXAMPLE: Assume we have a 30MVA transformer with a 69kV primary and a rated secondary current of 1000 amps. The tested load losses are 72 kw, and the tested impedance is 8.0%. Find Isc and Isc(pk,asym). C57.12.00-2015 Table 13 K = 1 + e tan 1 33.33 + π 2 1 33.33 sin(tan 1 (33.33)) 2 K = 2.702 Peak factor can be calculated or more easily looked up in table SPX Transformer Solutions, Inc. August 31, 2018 12

How to Calculate Short Circuit Current COMPARISON EXAMPLE: Assume we have a 30MVA transformer with a 69kV primary and a rated secondary current of 1000 amps. What is the symmetrical current considering only the transformer impedance of 8%. What is it at 6% Symmetrical Current, 8% Zt Symmetrical Current, 6% Zt 1000 0.08 + 0 = 12,500A 1000 0.06 + 0 = 16,667A SPX Transformer Solutions, Inc. August 31, 2018 18

How to Calculate Short Circuit Current Impedance Consequences Standard Impedances are tabulated in C57.12.10-2010 Section 4.6.1 Standard Impedances are classified by HV BIL and whether or not the unit has an LTC Standard Impedances are tabulated for the self-cooled (ONAN) rating SPX Transformer Solutions, Inc. August 31, 2018 19

Relationship Between Current, Magnetic Field and Force SPX Transformer Solutions, Inc.

Relationship Between Current, Magnetic Field and Force Resulting Magnetic Field Direction (CW) Current Flow Derived from Maxwell s MMF Law SPX Transformer Solutions, Inc. August 31, 2018 21

Relationship Between Current, Magnetic Field and Force Effect of Many Turns Fields at inner/outer edges add together. One uniform magnetic path results Magnetic field (B) intensifies with # turns (N) or the current (I). B NI F (NI) 2 Forces are proportional to the amount of current, squared SPX Transformer Solutions, Inc. August 31, 2018 22

Relationship Between Current, Magnetic Field and Force Left hand rule Resulting Magnetic Field Direction (CW) F Resulting Force Direction F - Force B Flux I - Current Current Flow (I) Leakage Magnetic Field (B) Remember TIM and the FBI SPX Transformer Solutions, Inc. August 31, 2018 23

Relationship Between Current, Magnetic Field and Force Weaker Magnetic Field Weaker Magnetic Field Arrows represent FORCE and its relative magnitude & direction Max LV COIL Strongest Magnetic Field HV COIL SPX Transformer Solutions, Inc. Min Magnetic Field Radial Distance August 31, 2018 24

Relationship Between Current, Magnetic Field and Force A net magnetic force also results between two coils (i.e. HV to LV), because the two coils are essentially two huge electro-magnets that repel each other. Repulsive Force Directions Between Magnets or Coils Summative force between these coils could be millions of pounds The inner coil experiences net inward radial crushing compressive forces The outer coil experiences net outward radial expanding type forces SPX Transformer Solutions, Inc. August 31, 2018 25

Relationship Between Current, Magnetic Field and Force INDICATES FORCE DIRECTION Mag field leaks out radially whenever there is an axial spreading out of turns in a coil. The larger the axial spread of turns, the more radial the field becomes Axial Location of DETC Taps Finite Element Analysis of Leakage Field Between Coils SPX Transformer Solutions, Inc. August 31, 2018 26

Short Circuit Failure Modes Photo Courtesy of A-Line E.D.S SPX Transformer Solutions, Inc.

Short Circuit Failure Modes Axial Radial Combined Beam Bending Beam Bending Spiraling Keyspacer Compression Buckling Telescoping Conductor Tilting Hoop Facture of Axial Support SPX Transformer Solutions, Inc. August 31, 2018 28

Short Circuit Failure Modes Ribs Cooling duct Radial spacers Paper insulated conductor SPX Transformer Solutions, Inc. August 31, 2018 29

Short Circuit Failure Modes Due to Axial Forces Axial Beam Bending & Keyspacer Compression Photo Courtesy of A-Line E.D.S SPX Transformer Solutions, Inc. August 31, 2018 30

Short Circuit Failure Modes Due to Axial Forces Conductor Tilting SPX Transformer Solutions, Inc. August 31, 2018 31

Short Circuit Failure Modes Due to Axial Forces Fracture of Axial Support Photo Courtesy of A-Line E.D.S SPX Transformer Solutions, Inc. August 31, 2018 32

Short Circuit Failure Modes Axial Forces - Design Criteria Fracture of Axial Support Coil Supports Limited on deflection and flexural strength Verticals/ Flitch-plates are designed to some % of yield strength Active-Part is pre-stressed (clamped) Keyspacer Compression Stress must be no more than 11,600 PSI (80 mpa) for Paper Covered Conductor (Much less than facture limit) Stress must be no more than 17,400 PSI (120 mpa) for Paperless Conductor (such as netting CTC) Axial Beam Bending Stress must be no more than some % of yield strength Conductor Tilting Stress must be no more than some % critical tilting limit SPX Transformer Solutions, Inc. August 31, 2018 33

Short Circuit Failure Modes Due to Radial Forces Beam Bending SPX Transformer Solutions, Inc. August 31, 2018 34

Short Circuit Failure Modes Due to Radial Forces Buckling Photo Courtesy of A-Line E.D.S SPX Transformer Solutions, Inc. August 31, 2018 35

Short Circuit Failure Modes Due to Radial Forces Hoop SPX Transformer Solutions, Inc. August 31, 2018 36

Short Circuit Failure Modes Radial Forces - Design Criteria Radial Beam Bending and Hoop Stress must be no more than some % of yield strength Buckling Designed for Free and Forced Buckling Stress must be no more than some % of critical buckling limit Critical buckling limit depends on the slenderness ratio of the winding and the yield strength of the conductor SPX Transformer Solutions, Inc. August 31, 2018 37

Short Circuit Failure Modes Due to Combined Forces Spiraling Telescoping Photo Courtesy of A-Line E.D.S SPX Transformer Solutions, Inc. August 31, 2018 38

Winding Temperature During a Short Circuit Calculated on basis that all heat is stored (heats up too quickly to radiate heat to equilibrium) Insulation Temperature not to exceed 250 C for copper 200 C for EC grade aluminum Copper or Aluminum Method defined on IEEE C57.12.00-2000 section 7.4. Insulated Conductor SPX Transformer Solutions, Inc. June 20 th, 2018 39

Winding Temperature During a Short Circuit Approximate method: Tf = (SΔk)2 t Km + TOR + Ta Tf = final winding temperature at end of a short circuit ( C) TOR = maximum top liquid temperature rise over ambient temperature ( C) Ta = ambient temperature ( C) SΔk = winding current density at symmetrical short circuit current (W/dm 2 ) t = short circuit duration (s). Km = 156 for copper / 73 for EC grade aluminum SPX Transformer Solutions, Inc. June 20 th, 2018 40

Non-Standard Requirements SPX Transformer Solutions, Inc.

Non-Standard Requirements Short Circuit Current shall only be limited by the transformer impedance. Windings shall be designed for infinite bus condition (no system impedance). Any pre-fault operating voltage greater than 1.0 per unit rated voltage Any customer specified asymmetrical peak factor (Ex: 2.762) Any customer specified minimum offset of the winding s electrical centers Any customer specified buckling limits Example: Stress must be less than 35% of yield strength for Magwire Customer specifies CTC for all windings subjected to compressive forces References to IEC 60076-5 Annex A Fault duration longer than 2 seconds Special fault duty (C57.12.00-2015 Section 7.1.5.5) Specific lead support requirements (max span, material, density, etc.) SPX Transformer Solutions, Inc. August 31, 2018 42

Non-Standard Requirements - EXAMPLE EXAMPLE IS A TWO WINDING NON-LTC TRANSFORMER (DYN1). 12/16/20MVA 69KV 26.4KV 8.0% IZ FOUR CASES 0.25% OF WINDING OFFSET, 0% OVERVOLTAGE 0.50% OF WINDING OFFSET, 0% OVERVOLTAGE 0.50% OF WINDING OFFSET, 5% OVERVOLTAGE 0.50% OF WINDING OFFSET, 10% OVERVOLTAGE SPX Transformer Solutions, Inc. August 31, 2018 43

Non-Standard Requirements - EXAMPLE STRESS (PSI) FOR THE FOUR DIFFERENT CASES Low Voltage (Inner Winding) Radial Axial Beam Beam Keyspacer Hoop Buckling Bending Bending Compression Conductor Tilting 0.25% Wdg Offset, 0% Overvoltage 5437 5437 12311 12886 6935 1555 0.50% Wdg Offset, 0% Overvoltage 5435 5435 12307 12962 7439 1667 0.50% Wdg Offset, 5% Overvoltage 5993 5993 13569 14291 8201 1838 0.50% Wdg Offset, 10% Overvoltage 6577 6577 14892 15684 9000.6 2018 SPX Transformer Solutions, Inc. August 31, 2018 44

Non-Standard Requirements - EXAMPLE STRESS (PSI) FOR THE FOUR DIFFERENT CASES High Voltage (Outer Winding) Radial Axial Beam Beam Keyspacer Conductor Hoop Buckling Bending Bending Compression Tilting 0.25% Wdg Offset, 0% Overvoltage 5073 0 0 6348 2906 631 0.50% Wdg Offset, 0% Overvoltage 5071 0 0 6428 3098 673 0.50% Wdg Offset, 5% Overvoltage 5591 0 0 7087 3416 742 0.50% Wdg Offset, 10% Overvoltage 6136 0 0 7778 3749 814 SPX Transformer Solutions, Inc. August 31, 2018 45

Non-Standard Requirements - EXAMPLE PERCENT INCREASE FOR THE FOUR DIFFERENT CASES Low Voltage (Inner Winding) Radial Axial Beam Beam Keyspacer Hoop Buckling Bending Bending Compression Conductor Tilting 0.25% Wdg Offset, 0% Overvoltage - - - - - - 0.50% Wdg Offset, 0% Overvoltage -0.04% -0.04% -0.03% 0.59% 7.27% 7.20% 0.50% Wdg Offset, 5% Overvoltage 10.23% 10.23% 10.22% 10.90% 18.26% 18.20% 0.50% Wdg Offset, 10% Overvoltage 20.97% 20.97% 20.96% 21.71% 29.79% 29.77% SPX Transformer Solutions, Inc. August 31, 2018 46

Non-Standard Requirements - EXAMPLE PERCENT INCREASE FOR THE FOUR DIFFERENT CASES High Voltage (Outer Winding) Radial Axial Beam Beam Keyspacer Conductor Hoop Buckling Bending Bending Compression Tilting 0.25% Wdg Offset, 0% Overvoltage - - - - - - 0.50% Wdg Offset, 0% Overvoltage -0.04% - - 1.26% 6.61% 6.66% 0.50% Wdg Offset, 5% Overvoltage 10.21% - - 11.64% 17.55% 17.59% 0.50% Wdg Offset, 10% Overvoltage 20.95% - - 22.53% 29.01% 29.00% SPX Transformer Solutions, Inc. August 31, 2018 47

Non-Standard Requirements - EXAMPLE Changing the offset of electrical centers of the windings primarily affects the axial forces Changing the pre-fault overvoltage condition increases the Peak Factor (K) by that same percentage thereby increasing the peak current. Both axial and radial forces are affected. 5% Overvoltage will increase the short circuit forces by about 10% 10% Overvoltage will increase the short circuit forces by about 21% SPX Transformer Solutions, Inc. August 31, 2018 48

Questions SPX Transformer Solutions, Inc.