2V165 Transformer Parallel Control Relay

Similar documents
1M122A Transformer Parallel Control System

2P48 Potential Selecting Relay

2C73 Setting Guide. High Impedance Differential Relay. Advanced Protection Devices. relay monitoring systems pty ltd

2V164-S User Guide. Voltage Regulating & Control Relay. Advanced Protection Devices. relay monitoring systems pty ltd. User Guide.

Advanced Protection Devices

Reyrolle Protection Devices. 7PG21 Solkor R/Rf Pilot Wire Current Differential Protection. Answers for energy

ERV-M ELECTRONIC FAN SPEED CONTROLLER. Mounting and operating instructions

High-set undervoltage stage with definitetime. or inverse definite minimum time (IDMT) characteristic. Low-set undervoltage stage with definitetime

Data Acquisition Modules/ Distributed IO Modules

NPRG860 & NPRG870 perform synchronization and paralleling of generators with electrical network. NPRG860 features a speed adjustment function.

NPRG860 NPRG870 REGULATION. Automatic Synchronizer for Generator

Fault indicator. Application. SPEF 3A2 C 1MRS MBG Issued: April 1999 Status: Updated Version: B/ Data subject to change without notice

User's Manual: Series 450T AC Current Input (External Sensor), AC-Powered Transmitters

PRODUCT / TEST MANUAL 2V162K4 VOLTAGE REGULATOR RELAY

EVDP610 IXDP610 Digital PWM Controller IC Evaluation Board

Automation for a Changing World. Delta Power Meter DPM Series VARITEL

IF30. User's manual. Description. Table of contents IF30

The wireless alternative to expensive cabling...

VFSC9 ELECTRONIC SPEED CONTROLLER. Mounting and operating instructions

User's Manual: Series 350T AC Current Input (External Sensor), DC-Powered Transmitters

2V68-S User Guide. CT Supervision And Shorting Relay. User Guide

K-Factor Scaler F5140 and Programming Kit F5141 Installation & Operating Instructions

PRODUCT/TEST MANUAL 2V162K12 VOLTAGE REGULATOR RELAY

Modbus communication module for TCX2: AEX-MOD

83 SERIES. 83 Series - Modular timers A. Features

T 1000 PLUS Secondary Injection Relay Test Set

Delta Power Meter DPM Series

Agilent Technologies 8114A 100 V/2 A Programmable Pulse Generator

T 1000 PLUS. Secondary Injection Relay Test Set. Designed for testing relays and transducers

MultiNet. Instruction Manual. Digital Energy Multilin. Serial to Ethernet Converter. Manual P/N: A2 Copyright 2009 GE Multilin

IRT Eurocard. Type AG-738. Stereo Audio Phase / Failure Detector

T 1000 PLUS. Secondary Injection Relay Test Set. Designed for testing relays and transducers

TD 1000 PLUS. Secondary Injection Relay Test Set. Designed for testing relays and transducers

DIGITAL SYNCHRONIZING UNIT KS3.2 SERVICE MANUAL. 144 x 144 x 77 mm C E R T I F I E D

www. ElectricalPartManuals. com Transformer Differential Relay MD32T Transformer Differential Relay

T/3000 T/3000. Substation Maintenance and Commissioning Test Equipment

EMC Test Report. Report Number: M030826

83 Series - Modular timers 16 A. Features

SECTION LOW VOLTAGE ACTIVE HARMONIC FILTER SYSTEM NEMA 1 ENCLOSED

Hamdy Faramawy Senior Application Specialist ABB Sweden

02/11/2015

02/11/2015

Kotron Sentinel Model 804 RF Level Transmitter

POWER TRANSDUCERS ACTIVE AND REACTIVE SERIES: T-W WATT T-V VAR

CROSS Chassis from 160 A to 450 A

PROMUX Distributed MODBUS I/O Modules Catalog and Design Guide

ZZxD-Nx-xR Series. Wireless Modbus I/O B&B ELECTRONICS PRODUCT INFORMATION

NT240 TIMER. PROGRAMMABLE TIMER INSTRUCTIONS MANUAL V20x G TIMER OUTPUTS INTRODUCTION SPECIFICATIONS AUXILIARY SUPPLY OUTPUT INSTALLATION TIMER INPUTS

ma/bcd Converter Model MFC-201 ma/bcd The MFC-201 ma/bcd Converter is a device designed to convert a DC current signal into BCD (8421) signals.

SINEAX I 503 / SINEAX U 504 Transducer for AC current or AC voltage

MODEL DDS8par 48-bit Binary Parallel Controlled Synthesizer

Fixed Series Compensation

DANFYSIK A/S - DK-4040 JYLLINGE - DENMARK

AMU-214 Auxiliary Monitor Unit Operations Manual

6RZ. > <8ms and <30ms performance versions > Single and dual element versions > Draw out case > Flush panel or rack mount > Made in Australia

Uni-Mux XQL Multi-Channel Data Acquisition Module

USING RS-232 to RS-485 CONVERTERS (With RS-232, RS-422 and RS-485 devices)

Kotron Sentinel Model 804 RF Level Transmitter

1S24. Arc Fault Monitoring System. Arc fault protection to provide high speed detection and clearance of arcing faults.

PRODUCT TEST MANUAL 2SY110K28 SYNCHRONISM CHECK RELAY

1 INTRODUCTION ORDER CODE / INFORMATION

8902/RE and 8902/RR Resolver Speed Feedback Options

Kotron Sentinel Models 822, 832 and 842 RF Point Level Switches

MultiNet Serial to Ethernet Converter

USER MANUAL. MODEL 457B Seven Port Active Twinax Star Hub. SALES OFFICE (301) TECHNICAL SUPPORT (301)

Programmable K-Factor Scaler B and Programming Software Kit B

Zlinx Wireless I/O. Peer-to-Peer and Modbus I/O PRODUCT INFORMATION B&B ELECTRONICS

Position Indicator model MFC-300/IP. Technical Manual. Licht

+5V Multiprotocol, Software-Selectable Cable Terminator

Selection guide. Communication accessories. Communication accessory selection guide. Characteristics

User Manual. Data Acquisition Modules/ Distributed IO Modules

SPECIAL SPECIFICATION 6574 Low Power Wireless Modem

MiCOM P120, P121, P122 and P123 Universal Overcurrent Relays

Technical Manual TRANSDUCER AMPLIFIER TYPE DR7AC. Doc. Ref CD2402K

SYNCHRONISING AND VOLTAGE SELECTION

Current Loop Interface Module M 2025D

7PG21 Solkor R/Rf Pilot Wire Current Differential Protection Answers for energy

Application and Commissioning Manual for Numerical Over Current Protection Relays Type MIT 121/131 CONTENTS PAGE APPLICATION 2-4 INSTALLATION 5-11

02/11/2015

DRTS-6. DRTS-6 has been designed to test: DRTS-6. Advanced Protection Relay Test Set and Measurement System

OVEN INDUSTRIES, INC. Model 5C7-362

2520 Pulsed Laser Diode Test System

N. TEST TEST DESCRIPTION

7PG21 Solkor R/Rf Pilot Wire Current Differential Protection Energy Management

PROMUX Distributed MODBUS I/O Modules Catalog and Design Guide

SYNCHRONISM RELAY SYNCRO-96. (Code ) INSTRUCTION MANUAL ( M / 99A ) (c) CIRCUTOR S.A.

The Allen-Bradley Servo Interface Module (Cat. No SF1) when used with the Micro Controller (Cat. No UC1) can control single axis

PLC-K506 Series FEATURES DESCRIPTION FEATURES

XP2-R Power and reverse power relay. (January 2006) Manual XP2-R (Revision New)

TECHNICAL MANUAL. SERIES AP5202 DC Strain Gage In-Line Amplifier ISO 9001/AS9100

Installation and Operating Instructions Quadratic Integra 1530 Digital Metering Systems

Electronic AC Load ZSAC Series. 400 W up to 21,000 W 260 V up to 440 V 3 A up to 100 A. Rev. 3.03

Installation / Monitoring Technique

Multi-voltage Multi-function. BE: Off-delay with control signal BE: Off-delay with control signal CE: On- and off-delay with control signal

PowerFlex 400 AC Drive Guide Specification

Measuring Transducer MT4xx series Programmable AC Current Transducer MT418

N. TEST TEST DESCRIPTION

Single Channel Loop Detector

nd30 EXAMPlE OF APPliCATiON MEASUREMENT AND ViSUAliZATiON OF POWER NETWORk PARAMETERS Ethernet www/ ftp Modbus TCP Modbus RS-485

XP2-R Power and Reverse Power Relay

Transcription:

Technical ulletin 2V165 Transformer Parallel ontrol Relay Features SYSTEM FETURES Large back lit display panel System status LED indicators Simple menu setting procedure Wide auxiliary supply range with fail alarm contact Self diagnosis & fail alarm Size 4M draw out case Made in ustralia ONTROL MONITORING Tap change out of step alarm Pre-configured parallel control schemes refer 1M1 technical bulletin DT DISPLY Tap position indicator input for up to four (4) transformer tap changers Reference tap position indicator output Transformer In Step status OMMUNITION Non platform specific P programming software Optically isolated communication ports MODUS RTU compatible network protocol Operation The 2V165 relay is built on the Micro MTRIX digital platform. The standard Micro MTRIX human machine interface (HMI) is combined with fully solid-state voltage sensing & measuring circuitry to provide high accuracy, simple set up & flexible operation. Self-monitoring is carried out by hardware & software watchdogs. The TPI inputs, output relays & opto isolated status inputs form the essential barriers against high voltage line transients while a switchmode auxiliary supply provides a wide operating range. n RS232 programming port is provided for ease of establishing relay settings using a P. pplication 2V165 depicted in a 4M56 case Made in ustralia The 2V165 Series relays are designed to monitor & control the tap changers of up to four (4) transformers connected on a common bus & operating in the master slave control configuration. Master follower parallel control schemes traditionally use auxiliary switches on the tap changers to determine out of step errors. While this is a reliable & proven technique there are two significant drawbacks: 1. Wiring complexity between the tap changer auxiliary switches 2. Requirement for matched tap changers The first issue is overcome by replacing each tap changer auxiliary switch with a TPI transducer (2V200), which sends a frequency signal proportional to the tap position. This requires only two wires for each tap changer & is simply wired back to the 2V165. The second issue is overcome with a user specified tap position logic table in the 2V165 to allow non-matched tap changers to operate together. The tap position of each transformer is monitored as well as the raise / lower commands initiated by the selected master voltage regulating relay. The 2V165 responds by sending the appropriate raise / lower commands to each tap changer in accordance with the tap position logic table. If any tap changer moves outside the limits established in the tap position logic table, an out of step alarm contact will pick up & all further tap change commands inhibited. ny or all of the transformers may be taken off the parallel scheme & operated independently. This is signaled to the 2V165 via status inputs, which inhibit any tap change commands or alarm outputs relating to that transformer. status input is provided to automatically step all tap changers to a programmed position within the tap position logic table. RMS 2V165 Relays have many in built features to simplify the interface with OLT's to provide a reliable, effective & simple to operate voltage control system. Refer to the 1M1 & 1M1 technical bulletins for pre-configured system solutions. Due to RMS continuous product improvement policy this information is subject to change without notice. 2V165/Issue E - 17/11/08-14

ontrol Functions TPI INPUTS Four (4) TPI inputs are provided to accept a 1 to 5K HZ frequency coded signals from the RMS manufactured 2V200 TPI transducers. The 2V165 is programmed with the number of taps & direction for each transformer. table is established by the user for the correct tap positions relative to a reference position. e.g. Reference Tap 1 Tap 2 Tap 3 Tap 4 Tap 5 Tap n Transformer 1 1 2 3 4 5 n1 Transformer 2 1 2 3 4 5 n2 Transformer 3 1 1 2 2 3 n3 Transformer 4 20 19 18 17 16 n1 Pre-defined tap position logic table If the tap of any transformer steps outside the pre-defined band the out of step contact will pick up. user specified time delay (1-30s in 0.5s steps), is provided to allow for differences in tap changer operate times. It should be noted that this table is only required when tap changers are not matched. The tap position logic table template on this page should be completed & supplied with the 2V165 ordering code where unmatched tap changers are to be used. The 2V165 will then be supplied pre-programmed with the specified configuration. TP RISE / LOWER INITITE INPUTS Two (2) separate status inputs are provided to detect tap raise & tap lower initiate signals from the master voltage regulating relay. These are used to allow the 2V165 to check that tap position changes only occur in synchronization with tap raise / lower commands. n input control signal of 1s minimum duration is required. TP RISE / LOWER INITITE OUTPUTS When a tap raise or lower input is detected the 2V165 sends specific tap change output commands to each transformer such that the positions in the pre-defined tap position logic table are observed. continuous contact output is provided which is reset when the corresponding tap position indicator changes position. must be wired to provide an increase in system volts. must be wired to provide a reduction in system volts. OUT OF STEP LRM When a tap raise or lower command is output, an out of step alarm timer is initiated. If all tap changers have not moved to the specified tap within the user specified time delay (1-30s in 1s steps), the alarm contact will close & a message identifying the problem tap changer displayed. TP HNGE FEEDK OUTPUT ONTT This contact is closed when a tap raise / lower command pulse is received from the 2V164 VR & is reset when all transformers have successfully moved to the next position in the tap position logic table. This contact is wired back to the 2V164 tap change feedback status input to pause the interval timer from starting until all transformers have completed the tap change sequence. LL TRNSFORMERS OFF GROUP OUTPUT ONTT When all transformers are set to OFF GROUP via the ON GROUP status inputs, this N/O contact is closed. This function is useful to automatically inhibit the local VR to avoid tap change fail & voltage level alarms. IN GROUP STTUS INPUTS status input is provided for each transformer to signal if the transformer is operating as part of the parallel group. This is indicated by an LED on the front panel with the text ON GROUP. & lower commands will be inhibited for transformers not ON GROUP & its tap position not used to initiate an out of step alarm. UTO HOME When a transformer is put back ON GROUP it will automatically home to the Reference Tap Position to match the other transformers ON GROUP. user specified time delay (10-300s in 5s steps), is provided to allow for the tap changer to reach the specified target position during which period the Out of Step alarm is inhibited. GO TO SPEIFIED TP status input is provided which may be initiated to drive all ON GROUP transformer tap changes to a user specified reference tap position. n initiate pulse of 1s minimum is required. OPERTIONL INDITORS LEDs indicate the following conditions. Transformer 1 ON GROUP Transformer 2 ON GROUP Transformer 3 ON GROUP Transformer 4 ON GROUP Tap change in progress Out of step alarm Healthy Service DT DISPLY During normal operation the front panel LD provides the following information: The tap position of each transformer Transformer out of step status TPI NLOGUE OUTPUT single tap position indicator analogue output signal is provided for interface to an RTU. The analogue output is linked to the reference tap position (= transformer 1 tap position if matched tap changers are used). Output: 4 to 20m ompliance voltage: 5V Maximum burden: 250 Ohms ccuracy: +/-3% nalogue output: Tap 1 4m Tap N 20m Where N = maximum selected tap setting TP POSITION LOGI TLE TEMPLTE Table 1 T1 T2 T3 T4 (Only required when tap changers are not matched) Reference Tap Position 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 23 24 25 26 27 28 29 30 omplete this table with the desired relative transformer tap positions & submit with the ordering code for factory programming. Increased transformer voltage output is to the right. i.e. an increase in the reference tap position will result in an increase in system voltage. Due to RMS continuous product improvement policy this information is subject to change without notice. 2V165/Issue E - 17/11/08-24

Technical Data RELY FIL LRM /O alarm contact is maintained in the energized state when all of the following conditions are met: The auxiliary supply is applied The internal 24V D rail is within acceptable limits The PU hardware watchdog maintains a pulsing output PU software watchdog records suspect events to an assert register and if necessary performs a soft restart. OUTPUT ONTT RTINGS Make & carry 30 or D (Limits L/R=40ms & 300V max.) for 0.2s 20 or D (Limits L/R=40ms & 300V max.) for 0.5s 5 or D continuously reak (Limits 5 & 300V max.) 1,250V resistive 250V at 0.4PF inductive 75W D resistive 30W D inductive L/R = 40ms 50W D inductive L/R = 10ms INSULTION WITHSTND IE60255-5 2KV RMS & 1.2/50 5KV impulse between: all input terminals & frame all output terminals & frame all input & output terminals each input group each output group HIGH FREQUENY DISTURNE IE60255--1 2.5KV 1MHz common mode 1.0KV 1MHz differential mode ELETROSTTI DISHRGE EN61000-4-2:1995 8KV Level 3 RDIO FREQUENY INTERFERENE EN61000-4-3:1995 10V/m Level 3 FST TRNSIENT DISTURNE EN61000-4-4:1995 4KV Level 4 OPERTING TEMPERTURE RNGE -5 to +55 degrees elsius ambient operating temperature range. ESSORIES SUPPLIED WITH EH SYSTEM 1 x M4 self threading mounting screw kit P/N 290-406-151 2 x M4 terminal screw kit (28 per kit) P/N 290-407-153 1 x Product Test Manual P TO µmtrix SERIL LE One cable supplied with each order. P/N 290-406-151 PROGRMMING PORT SERIL LE OMMUNITIONS Two (2) communications ports are available. Programming port The programming port is accessible from the front panel of the relay via an RS232 physical link & P configuration program supplied with the relay. The µmtrixwin configuration program is designed to operate with all relays from the Micro MTRIX range & with all installed firmware version. Network port The network port is intended for applications where permanent connection to a master control system is required. n optically isolated RS232 or RS485 physical layer is provided for this function. The RS485 connection is intended for applications where multiple µmtrix relays are to be connected on a common communications bus. The RS232 connection is intended for interface to an RS232 to optic fiber converter in environments subject to extreme electrical interference. The network port may be used for a permanent link to a modem, remote P, data concentrator or SD system. The standard communications protocol is MODUS RTU. hanging the Network port from RS485 to RS232 µmtrix relays are shipped with the rear network port terminals configured as RS485. This configuration may be changed in the field to RS232 if required by withdrawing the relay module from the case & changing the three configuration links as depicted. Due to RMS continuous product improvement policy this information is subject to change without notice. 2V165/Issue E - 17/11/08-34

Ordering Information Generate the required ordering code as follows: e.g. 2V165 2V165 1 2 3 4 5 1 UXILIRY SUPPLY RNGE 20-70V D 40-300V D / 40-275V 2 DIGITL INPUT OPERTING VOLTGE GROUP 1 24-80V /D 75-150V /D 150-300V /D 3 DIGITL INPUT OPERTING VOLTGE GROUP 2 24-80V /D 75-150V /D 150-300V /D 4 DIGITL INPUT OPERTING VOLTGE GROUP 3 24-80V /D 75-150V /D 150-300V /D 5 TPI NLOGUE OUTPUTS Not required Required 4 to 20m TP POSITION LOGI TLE FIRMWRE Not required Matched tap changers Non matched tap changers omplete the table on page 2 2V165 wiring diagram - Relay shown in de-energised condition 1 OMMUNITIONS (RS 232 SD option) D9 RS232 P Programming port Transformer 1 IN GROUP Status input group 1 Transformer 2 IN GROUP Vx 3 5 7 9 7 25 27 23 30 34 32 Power supply / PU fail alarm Transformer 1 Network port 24 26 28 SEND REEIVE GROUND Transformer 3 IN GROUP Status input group 2 11 13 15 36 40 38 Transformer 2 OMMUNITIONS (RS 485 SD option) D9 RS232 P Programming port Transformer 4 IN GROUP input command Status input group 3 input command Go to specified tap 13 16 18 20 42 46 44 48 52 50 19 Transformer 3 Transformer 4 Network port IS links J19 J18 24 26 28 SHIELD RS485 Shielded twisted pair cable (Up to 1Km) 120 Ohm To other umtrix relays (Up to 32 units) Fit external terminating resistor to end of US relay only Fit internal IS jumper links for single relay connection only Transformer 1 tap position indicator input Transformer 2 tap position indicator input Transformer 3 tap position indicator input Transformer 4 tap position indicator input 35 37 39 41 43 45 47 49 21 17 10 8 14 12 53 55 2 Out of step alarm Tap hange feedback ll OFF LINE Tap position output Due to RMS continuous product improvement policy this information is subject to change without notice. 2V165/Issue E - 17/11/08-44

ustralian ontent Unless otherwise stated the product(s) quoted are manufactured by RMS at our production facility in Melbourne ustralia. pproximately 60% of our sales volume is derived from equipment manufactured in house with a local content close to 90%. Imported components such as semi-conductors are sourced from local suppliers & preference is given for reasonable stock holding to support our build requirements. Quality ssurance RMS holds NSI (NT ertification Services International), registration number 6869 for the certification of a quality assurance system to S/NZS ISO9001-2000. Quality plans for all products involve 100% inspection and testing carried out before despatch. Further details on specific test plans, quality policy & procedures may be found in section 4 of the RMS product catalogue. Product Packaging Protection relays are supplied in secure individual packing cardboard boxes with moulded styrene inserts suitable for recycling. Each product & packing box is labeled with the product part number, customer name & order details. Design References The products & components produced by RMS are based on many years of field experience since Relays Pty Ltd was formed in 1955. large population of equipment is in service throughout ustralia, New Zealand, South frica & South East sia attesting to this fact. Specific product & customer reference sites may be provided on application. Product Warranty ll utility grade protection & auxiliary relay products, unless otherwise stated, are warranted for a period of 24 months from shipment for materials & labour on a return to factory basis. Repair of products damaged through poor application or circumstances outside the product ratings will be carried out at the customer s expense. Standard onditions of Sale Unless otherwise agreed RMS Standard Terms & onditions (QF 907) shall apply to all sales. These are available on request or from our web site. Relay Monitoring Systems Pty Ltd 6 nzed ourt, Mulgrave, Victoria 3170, USTRLI Tel: 61 3 9561 0266 Fax: 61 3 9561 0277 Email: rms@rmspl.com.au Web: www.rmspl.com.au 2008 Relay Monitoring Systems Pty Ltd Due to RMS continuous product improvement policy this information is subject to change without notice.