On-Load Tap Changer Type M

Similar documents
ON LOAD TAP CHANGERS RSV 5.3 TECHNICAL DATA

ON LOAD TAP CHANGERS RS 6.3 / RS 6 TECHNICAL DATA

ON LOAD TAP CHANGERS RS 9.3 / RS 9 TECHNICAL DATA

On-load tap-changer VACUTAP VRC and VRE

On-load tap-changer VACUTAP VRD, VRF, VRG

VACUTAP VVS COMPACT ON-LOAD TAP-CHANGER FOR GRID APPLICATIONS.

TECHNICAL DATA TYPE CV & SV OIL-IMMERSED ON-LOAD TAP CHANGER

TECHNICAL DATA TYPE CMD OIL-IMMERSED ON-LOAD TAP CHANGER

TECHNICAL DATA TYPE SHZV VACUUM ON-LOAD TAP CHANGER FOR OIL-IMMERSED TRANSFORMER

1ZSC AAJ en, Rev. 1. Vacuum on-load tap-changers, type VUBB Technical guide

TAP CHANGER SELECTING MANUAL TECHNICAL DATA

Pomona, CA May 24 & 25, LTC Applications - Location, Series & Preventative Auto Transformers

VACUTAP VR On-Load Tap-Changer for Regulating Transformers

OUTDOOR VOLTAGE TRANSFORMERS (Indoor units available) Description:

1ZSE en, Rev. 6. On-load tap-changers, type UBB Technical guide

24 th International Conference on Electricity Distribution Glasgow, June Paper 0881 ABSTRACT STATE OF THE ART INTRODUCTION ECOTAP VPD

DATA SHEET FOR LIGHTING TRANSFORMER APPD. BY VDV PROJECT NO

Discipline Electrical Testing Issue Date Certificate Number T-2837 Valid Until Last Amended on - Page 1 of 6 LOCATION 1

save energy, it is precious SYNERGY transformers Mfg. of all types of Distribution / Power & Furnace Transformers

Load Tap Changers for Power Transformers

KNOW MORE ABOUT THE TRANSFORMERS. Glossary Transformers

Schedule of Accreditation issued by United Kingdom Accreditation Service 2 Pine Trees, Chertsey Lane, Staines-upon-Thames, TW18 3HR, UK

Technical Questionnaire 9.101/6 Transformer Test System. Personal Data. Application. Test of. Delivery scope

Training Fees 3,300$ per participant including Materials/Handouts, Tea/Coffee Refreshments & International Buffet Lunch.

CONSULTANT PROCEDURES & DESIGN GUIDELINES Liquid-Filled Utility Transformers UNIVERSITY OF MISSOURI

Introduction. Centrado leading-edge transformer. Introduction

Three-Phase Transformer Test Systems

UNIVERSITY OF MISSOURI Liquid-Filled Utility Transformers 2016 Q1

36kV VOLTAGE TRANSFORMERS (OUTDOOR TYPE)

SPECIFICATION No SS-88/5 630 kva, 30 / 0.4 kv THREE-PHASE TRANSFORMERS WITH ON-LOAD TAP CHANGER

VACUTAP VR THE ALL-AROUND ON-LOAD TAP-CHANGER. TRANSFORMER CONTROL

شركة كهرباء محافظة القدس المساهمة المحدودة JERUSALEM DISTRICT ELECTRICITY CO. LTD.

INTERNATIONAL STANDARD

SOUTHERN ELECTRICITY SUPPLY COMPANY OF ODISHA LIMITED (SOUTHCO UTILITY)

Substation Preventive Maintenance

Technical guide. Type VRLTC load tap changer

MR PUBLICATION. On-Load Tap-Changers for Power Transformers A Technical Digest

About us. Vision. To lead our field in innovation, quality and customer service.

Electrical Description

1ZSC AAW en, Rev. 2. On-load tap-changers, type UC Technical guide

Regional Technical Seminar

Technical guide. Type VRLTC load tap changer

Phase Shifting Transformers. Presented by

TECHNICAL DESCRIPTION TD-77A/3 170 KV COMPACT GAS INSULATED INTEGRATED SUBSTATION MODULES

HOW TO SAFE GUARD THE TRANSFORMER..???

ELECTRICAL NETWORKS SPECIFICATION TECHNICAL SPECIFICATION FOR A 230V/110V AND 400V/110V TRANSFORMER

MV ELECTRICAL TRANSMISSION DESIGN AND CONSTRUCTION STANDARD. PART 1: GENERAL 1.01 Transformer

SECTION VI TECHNICAL SCHEDULES

Brown University Revised 2/1/2006 Facilities Design & Construction Requirements SECTION 16461C - DRY TYPE TRANSFORMERS

DMRC ELECTRICAL STANDARDS & DESIGN WING (DESDW)

Comparison of CAN/CSA C88.1, IEEE C /01 & IEC 60137

On-load tap-changers, type UC and VUC Technical guide

TRANSFORMERS FOR GIS APPLICATIONS VOLTAGE VOLTAGE TRANSFORMERS FOR GIS APPLICATIONS

FDM Medium Voltage Controller

SECTION TRANSFORMERS

TECHNICAL DESCRIPTION ND-387. THREE-PHASE TRANSFORMERS, 150 / 21kV, 40/50MVA AND 20/25 MVA, Dyn1

Hands-On Transformer Testing and Maintenance

1ZSE en, Rev. 9. On-load tap-changers, type UC and VUC Technical guide

A Review Comprehension: Guideline for Testing of HV, EHV and UHV Substation Equipment

Onsite Mobile AC High Voltage Test System

S. C. Electric Cooperative s Specification for a Single-Phase, Single Bushing Overhead Distribution Transformer (Revised 10/2013)

Group F : Sl. No. - 1) 33/0.403 KV, 100 KVA Station Transformer GUARANTEED & OTHER TECHNICAL PARTICULARS. Table : A

nical catalogue Tech

Transformer Protection

AC Resonant Test Systems Tank Type Up to 150 kv

CEYLON ELECTRICITY BOARD SRI LANKA. Procurement of Plant

SPECIFICATION FOR STEP UP TRANSFORMER 0.415/11Kv and (630KVA & 1000KVA)

3. COMBINED TRANSFORMERS Oil-paper insulation

Innovative Test Techniques and Diagnostic Measurements to Improve the Performance and Reliability of Power System Transformers

7. INSPECTION AND TEST PROCEDURES

Prolific Systems & Technologies Pvt. Ltd. CORE DETAILS. CENTRE Figure - II L-2 X Y Wt-2

Shunt Reactor Switching

INTERPLANT STANDARD - STEEL INDUSTRY CODE OF PRACTICE FOR TESTING & COMMISSIONING OF TRANSFORMERS AND RELATED SWITCHGEARS

Industrial Electrician Level 3

PRESENTATION ON IS 1180 (Part 1): 2014 DISTRIBUTION TRANSFORMERS SHYAM KUMAR SCIENTIST B ELECTROTECHNICAL BUREAU OF INDIAN STANDARDS

Shunt Reactors. Global Top Energy, Machinery & Plant Solution Provider

TECHNICAL SPECIFICATION FOR POWER TRANSFORMER

Secondary Arresters. Figure 1. Type L secondary surge arrester rated 175 Vac, 125 Vdc.

CAST RESIN DRY TRANSFORMER

SGMF(T) series. Onsite Mobile AC High Voltage Test System. Applications:

TRANSFORMER TECHNOLOGY GPT

BUCK-BOOST TRANSFORMERS

PUBLIC POWER CORPORATION ENGINEERING & CONSTRUCTION OF TRANSMISSION PROJECTS DEPARTMENT

Tap Changer Condition Assessment Using Dynamic Resistance Measurement

POWER FACTOR CORRECTION. HARMONIC FILTERING. MEDIUM AND HIGH VOLTAGE SOLUTIONS.

HIGH VOLTAGE ENGINEERING(FEEE6402) LECTURER-24

Description & Applications Questions & Answers Selection Charts Single Phase Selection Charts Three Phase...

شركة الوقت للكهرباء والمقاوالت ذ.م.م.

Advanced Test Equipment Rentals ATEC (2832) CP RC. Resonance circuit for GIS testing

ABB Power Technologies

Diagnostic testing of cast resin transformers

Liquid-Filled Transformers

Type 297, High-Voltage Mica Capacitors Corona-free Mica Coupling Capacitors for Medium-Voltage PDA s

TMC Transformers TMC

ProLine P Precise Temperature Measurement at High Voltage Potentials up to 6.6 kv

Keywords: Power Transformer, On-load Tap Changer, AVR, Low Voltage Variation, Change Positions, OLTC Control.

PRODUCT PORTFOLIO TEST AND MEASURING SYSTEMS

Arild Furnes,ATPA OGP/Petrobras workshop, Dry type transformers-ideal for FPSO - Transformers for electrical and drive systems

CONDITIONS FOR A TENTATIVE APROVAL FOR CONNECTION OF TRANSFORMERS

R Distribution Transformers. Mineral Oil-Immersed, Self-Cooled, 60 Hertz Voltages and Connections. Reference Data

Transcription:

On-Load Tap Changer Type M OLTC type model M III 500 Y, U m = 123 Kv, 500A, ± 9 steps The type M On Load tap changers are used to vary the ratio of oil-immersed transformers under load.in general they are designed for network transformer as well as industrial transformer applications. The tap changer comprises of a diverter switch and a tap selector in a single column design and represent the most recent state of technology. The tap changer offers both transformer manufacturer and user a great number of essential advantages. On-Load tap changer Type M Versatility Three pole design for neutral application at 350 A, 500 A and 600 A ratings for three phase wye- connected windings. Three pole fully insulted design, at 350 A and 600A ratings for the three phase delta or auto connected windings. Single pole design at 350 A, 500A, 600A, 800A, 1200A, 1500A and 1800A ratings for auto connected windings or single phase transformers. Available up to 34 steps and 35 positions Insulation to ground and tap selector size can be selected independently of one another. Convenient for bell type tank installation Additional devices for potential tie-in of tap winding during change over selector (tie-in resistor, tie-in contact). Optional extras, especially for the application in industrial transformers. Compactness High speed transition resistor type diverter switch with arc extinction at the first current zero. Diverter switch uses snap action mechanics by energy accumulator mounted directly on the diverter switch. Minimum possible tap selector dimensions because five available sizes ensures matched impulse voltage withstand ability. Radial dimensions of the tap selector are reduced by special shaping of all parts on high potential, distances between tap selector bars determined by actual voltage stress. Optimised integration of the change over selector in to fine selector contact circle. 2

The Diverter switch Unit This unit comprises of the spring operated energy accumulator, the diverter switch itself and the transition resistors. For inspection, the unit has to be withdrawn from the oil compartment through the head. The Tap Selector The tap selector comprises of the gearing, the column with take off rings, the contact bridges with the corresponding drive tubes and segments, and the upper and lower cage rings. The tap selector may also include a change over selector. 3

4

Technical Data The technical data of type M have been verified in type tests according to International Standard IEC 214 (1989). Moreover, they meet all corresponding National Standards. Detailed information and comprehensive data for selectig a type M for a particular application are contained in our Sepcific Drawings. Tap Changer model MIII 350 Y M III 500 Y M III 600Y M I 351 M I 501 M I 601 M I 802 M I 1200 M I 1500 M I 1800 M III 350D M III 600 D Number of poles and application 3 (neutral) 3 (neutral) 3 (neutral) 1 1 1 1 1 1 1 3 3 Max. rated through-current (A) 350 500 600 350 500 600 800 1200 1500 1800 350 600 Short circuit strength (ka) thermic (3 sec.) 6 8 8 6 8 8 16 24 24 24 6 8 dynamic (peak) 15 20 20 15 20 20 40 60 60 60 15 20 Max. rated step voltage (V) 3300 3300 3300 3300 3300 3300 3300 3300 3300 3300 3300 3300 Max. rated switching capacity (kva) 1000 1400 1500 1000 1400 1500 2000 3100 3500 4200 1000 1500 Rated frequency (Hz) 50...60 Operating positions without change-over selector : max. 18 with change-over selector : max. 35 Insulation to ground Highest voltage fro equipment Um (kv) 72.5 123 170 245 300 72.5 123 Rated lighting impulse withstand voltage (kv.1.2/50) 350 550 750 950 1050 350 550 Rated power-frequency withstand voltage (kv, 50 Hz, 1min.) 140 230 325 395 460 140 230 Tap Selector 3 different tap slector sizes (B, C, D) available according to the require- U m /tap selector size ments by voltage stress on the tap winding. Lightning impulse withstand voltage 72.5/B, 123/C (in kv, 1.2/50 across regulating range : B = 265, C = 350, D = 490 Diverter switch oil pressure-proof up to 0.3 bar compartment pressure difference (test pressure 0.6 bar) Oil suction pipe Standard equipment Oil displacement approx. 195...265 litres (595 litres) 1 1 applies to M III 350 D, M III 600 D Oil filling quantity approx. 125...190 litres (400 liters) 1 Weight approx. 240...285 kg (540 kg) 1 Drying procedure Drive mechanism vacuum-drying up to max. 110 o C vapor-phase drying upto max.125 o C Motor drive unit MA2, protective housing in outdoor design, motor data : 415 V, 3-ph, 1.0 Hp, 50 Hz, step by step operation with local and remote control, mechanical and electrical position limitation, facility for remote position indication, hand crank operation for emergency and adjustment purpose. EMR/GEN/M/0010 5