REHAU PROFILA BENCH TRUNKING INSTALLATION GUIDELINES. Building Solutions Automotive Industry

Similar documents
REHAU PROFILA BENCH TRUNKING A CABLE MANAGEMENT SYSTEM WITH MULTIPLE ALTERNATIVES. Construction Automotive Industry

REHAU CABLE TRUNKING SOLUTIONS. For all your data trunking requirements

RAUTOOL ASSEMBLY TOOLS FOR REHAU EVERLOC TM COMPRESSION SLEEVES PARTS LIST /1

Pinnacle Technical. Bench and Shelf Trunking. cable management perimeter and distribution. Features.

Norwich Technical. Trunking PERIMETER AND DISTRIBUTION. Description CABLE MANAGEMENT. Colour: White only. Material: PVCu. mkelectric.co.

Powerlink Plus Technical

Ega Industrial Technical

CABLE MANAGEMENT. Technical Information

Marshall Tufflex. Cable Management. Steel Trunking Systems

150mm to 200mm. With box in comp 2 2 = 1535mm² total area 2 = 691mm² 45% space factor. C. & C. Marshall Ltd.

PINNACLE RANGE INTRODUCTION PERIMETER AND DISTRIBUTION FEATURES & BENEFITS CABLE MANAGEMENT

Prestige 2Com Technical

Warwick PVC Perimeter Trunking Systems

Risk Assessment & Safe Working Practice

Trunking Guide. Colour List... W White M Magnolia B Black. shape & size (wxh) colours available

PRESTIGE 3D COMPACT RANGE INTRODUCTION PERIMETER AND DISTRIBUTION FEATURES & BENEFITS CABLE MANAGEMENT

Trunking. light grey in U23X. Industrial Catalogue

DLP-S Trunking LIMOGES Cedex. Phone : Fax :

Cablelink Plus Flush Technical

Cable Cover Guide. Color List... W White B Black P Premium Wood (stainable Floor Trim only) shape & size (wxh) colors available

Installation Instructions - Model V4JSD 1

Raised Floor system LIMOGES Cedex. Phone : Fax :

Section 1. Kitchen installation. Base cabinets

DUALCASE VERSATILE ALUMINIUM SIGN SYSTEM

POWER, VOICE AND DATA ACCESSORIES FOR TRUNKING

Cable Management Solutions with DLP TM

The Festival Assembly Instructions

Ega Mini Trunking, Communication & Red Alert Trunking

Side Light Frame Pack Assembly Instructions

Opus Base Unit Assembly

Installation Guide for PermaSnap Plus Coping

Side Light Frame Pack Assembly Instructions

Sauna & Steam. Traditional Sauna Installation Instruction Manual

Trunkingxxxxxx. aluminium colour U23X. Industrial Catalogue

Installation for Full Size Polaris Ranger Crew Doors

INSTRUCTIONS. Taurus (BM) Unit Assembly

PRESTIGE 3D ANTIBAC BLUE

Commercial Wine & Liquor Display. Double Displays

THANK YOU FOR PURCHASING FROM HERITAGE PATIOS

Topo Freestanding Applications - Private Office

900 SERIES WALL PANELS

Assembly Instructions & General Overview

Cable Tray Kit: - Cable Tray - Cable Tray Cover - Power Block Support (x2) Top Support Kit: (x2) - 2 Top Supports. Quantities are per bench

Innovative Cable Management. Supplied by

RISER & LATERAL SYSTEM

INSTALLATION INSTRUCTIONS FOR PLASCORE NARROW STILE DOORS

POP PLUS / SPIDER SET-UP INSTRUCTIONS

Safety Glasses Safety Gloves Ladders Measuring Tape Spirit Level String Line. Tin-Snips Rivet Gun Caulking Gun Silicone Socket Set

Installation guide. Step-by-step instructions

ODYSSEY TRUNKING CURVED PROFILE

Installing flat panels on the MPL15 wall mount

Shetland Stalls Installation Instructions

Flush Floor system LIMOGES Cedex. Phone : Fax :

OXYGEN INSTALLATION. Revision date

GROWING BETTER THROUGH DESIGN. 6ft Lean-To LEAN-TO. Assembly Instructions 04/02

Jabiru Installation instructions

Tradewinds Amplify Display System Instructions

Busbar and Modular Wiring Systems

INSTALLATION INSTRUCTIONS DANUBE ACRYLIC NEO ANGLE

Assembly Instructions Please keep for future reference Inspire 40

Range height adjustable assembly

PATIO INSTALLATION MANUAL

If you discover that material is missing or defective, contact our customer service department immediately:

Merloni Elettrodomestici. Technical Fitting Manual FRIDGE. Language Issue/Edition Page GB /

INSTALLATION GUIDE FOR METAL LABORATORY CASEWORK

INSTALLATION INSTRUCTIONS FOR PLASCORE F5075 FRAME WALL

General Prisoner Transport Install Instructions PT-2-INST

MARSHALL-TUFFLEX CAT 6 COMPLIANT TRUNKING SYSTEMS

Laminate goes Wall. Installation documentation for wall panelling with gekko-system and Extravagant from CLASSEN.

commercial & industrial cable management solutions

Assembly Instructions

PFW 6875 Installation Guide Installationsanleitung, Guía de Instalacíon, Guida de Installazione, Guide d Installation, Installatie gids

AIR MASTER SYSTEMS INSTALLATION GUIDE TABLE OF CONTENTS

ESA-300 Full Breakout

for Rigid Sun Lite Planning the layout

Assembly Instructions

Installation Guide. Evolve bi-fold. 8. Door restrictor- optional p9. 1. Before you start p2. 9. Adjustment. 2. Measuring and surveying p2

TrendWall Floor-To-Ceiling Panels Installation Instruction

ASS 70.HI Lift/Sliding and Sliding Doors Installation Guide

Answer Power Beam and Boundary Screen

aluminium profile system

TONNEAU INSTALLATION INSTRUCTION

This instruction manual is an in-depth look and explanation of how to assemble and install the Murphy Bed properly and efficiently.

VYTEX PREMIUM SLIDING GLASS DOOR. Table of Contents. Precautions and Safety 2. Tools Required...3. Inspect and Prepare Door...4

MX8 SERIES 6-1/4 HANDRAIL W/ VINYL HANDGRIP

TS-20KD-1010 LOW PROFILE CARGO SCALE INSTALLATION GUIDE

Low Headroom Rear Mount TorqueMaster

Installation and Assembly: Flat Video Wall Mount For 40" to 65" Flat Panel Displays

PANATRIM AND UNITRIM.

PVC U PERIMETER TRUNKING SYSTEMS

compile system INSTALLATION GUIDE Updated January 2019

CURVED TO PERFECTION. Range of upvc Three Compartment Trunking

7 X 10 X 6 SHELTER 7 X 16 X 6 SHELTER 12 X 10 X 6 SHELTER 12 X 16 X 6 SHELTER

INSTALLATION INSTRUCTIONS

CI/SfB. Marshall-Tufflex. (62) In6. Twin165 Trunking

User Instructions Multiline Otter Scoreboard Caddy Assembly

Y1160A EIA Rack Sliding Shelf Installation Note

INSTALLATION INSTRUCTIONS Aluminum Railing System

PowerLock. Installation Instructions. Attention Dealers: Please give this owners manual to the customer when the product is delivered.

Hospital Grade Welded Ceiling System

Transcription:

REHAU PROFILA BENCH TRUNKING INSTALLATION GUIDELINES www.rehau.co.uk Building Solutions Automotive Industry

PROFILA BENCH TRUNKING CONTENTS PAGE 1. Generalities.... 03 2. Fixing the Base.... 03 2.1 Adjacent lengths of PROFILA Bench Trunking.... 03 3. Protective Foil.... 04 4. Dividers...... 04 5. Main Lid...... 04 6. Accessory Boxes.... 04 7. Endcaps (Single & Twin).... 04 8. Internal and External Covers.... 05 9. Flat Angles & Tee Pieces.... 05 10. Security Rivets.... 05 11. Typical Installation Layouts... 06 11.1 Installation on Worktops and against Walls... 06 11.2 Instalation on Island Location... 06 11.3 PODS... 06 11.4 Post Columns... 06 12. Classification... 07 13. Cable Capacity... 07

REHAU BENCH TRUNKING INSTALLATION GUIDELINES Cabling inside this trunking must only be installed and maintained by a competent person in accordance with BS7671 (UK Wiring Regulations) PROFILA Bench Trunking is a cable management system intended for distribution of low voltage power and communication circuits on worktops. 2. Fixing the Base Base must be fixed to worktop and back wall (if available) 25mm from the ends as shown below. 1. Generalities PROFILA Bench Trunking is a cable management system based on an asymmetric triangular shaped profile for protecting low voltage electrical and data installations. Due to its asymmetric design the system can be installed in two different configurations: Fig 3: Fixing distances Fig 1: High configuration Fig 2: Low configuration Fixing pints between end cuts can be done alternating along the grooved channels as shown below. We recommend using No. 8 round head screws and washers. High configuration - Default configuration for all fabricated accessories, recommended in most applications Low configuration - It requires special internal and external corners PROFILA Bench Trunking can be used in continuous extrusion lengths or as individually assembled POD units. Internal and external corners come in high configuration as standard. Low configuration corners must be ordered specifiying this requirement. Fig 4: Interval distances If worktop and wall are not perpendicular (90 angle), fix base only to worktop.

2.1. Fixing Adjacent Lengths of PROFILA Bench Trunking Adjacent lengths of base must be aligned and joined together by using 3 off metallic dowel pins (Art.265921). Some pins are supplied with the main profile; additional pins are available separately. Insert 3 off dowel pins in one section of trunking as shown: 3 Protective Foil PROFILA Bench Trunking profiles come with a protective tape to prevent damage during transport and installation. This protective layer must not be removed before completion of installation. 4 Dividers Dividers provide circuit segregation. PROFILA Bench Trunking can be further subdivided in two or three compartments by attaching additional PVC dividers onto the built-in DIN 35 rail as follows: Fig 5: Joining adjacent lengths of bench trunking Bring the two profiles together without leaving any gaps: Fig 9: Divider options 5 Main Lid The main lid provides access and protection to circuits inside trunking. PROFILA Bench Trunking uses a common lid with the REHAU perimeter trunking systems COMPACT Data (140 X 50) and PROFILA Data (180x65). To fit, align clip features on lid and base and apply pressure. To remove, peel the cover away from the base. 6 Accessory Boxes Fig 6: Adjacent profile lengths To install lids, leave a 13mm (+/-2) gap ensuring that the joint line on the base is right in the middle of the gap. Finally, place joint cover ensuring it overlaps lids on both sides. The accessory box allows installation of standard BS1363 electrical accessories and data outlets. It comes in single and double gang configuration. Adjustable single socket box: Art. 202415 Adjustable double socket box: Art. 202425 Adjustable socket boxes are common to all REHAU data trunking ranges and the internal depth can be set between 38 and 48mm within the PROFILA Bench Trunking range. Socket boxes clip directly onto the base and should be fitted prior to main lid as the later will overlap built-in lugs on the boxes. Fig 7: Main lid gap Fig 8. Joint cover installed Fig 10: Bench trunking with adjustable accessory boxes

7 Endcaps (Single and Twin) Minimum column size using fabricated corners: Provide side protection to circuits and accessories. Fig 14: Minimum column dimensions Fig 11: Fixing endcaps To fit, align pegs on endcaps with receptacle features on base and push fit until the internal face of the endcap makes contact with the end side of the base. Standard internal and external corners come in high configuration as default; if low configuration is required this must be informed at the time of ordering. 9 Flat Angle and Tee Pieces These accessories are non-standard and the following information must be provided when ordering - Type of configuration: (High or low) - Up or down accessory - Left or right handed accessory 10 Security Rivets Nylon push-rivets (Art. 289585) provide additional security for fixing endcaps and joint covers. Fig 12: Correct fitting of single endcaps If possible, inspect the back of the trunking making sure there are no gaps between the endcap and the base. 8 Internal and External Corners Corners provide change of direction horizontally at 90 angles. Internal and external corners are fabricated using sections of PROFILA Bench Trunking profile cut at 45 angle and welded. The installation of these articles must be done in a similar way to adjacent lengths using dowel pins and joint covers as explained in section 1.2. Fig 15: Security rivets To fix, drill a 3.0mm hole through the accessories and base or main lid to accommodate the rivet shaft. Finally, push plunger until head is flush against the accessory surface. Fig 13: Fabricated corners Fig 16: Security rivets installed For endcaps, drill holes towards the inside of the accessory (not in the middle) ensuring base and/or lids are engaged by rivet shaft. 3

11.3 PODS Stand alone units in 4 different configurations: Fig 17: Joint cover with security rivets For join covers, drill holes offset towards either side of the accessory (not in the middle) ensuring base and/or lids are engaged by rivet shaft 11 Typical Installation Layouts PROFILA Bench Trunking base has internal grooves that can be used as guides for drilling fixing holes. 11.1 Installation on Worktops and Against Wall In order to maximise the useful working area it is recommended to use PROFILA Bench Trunking on high configuration. Standard internal and external corners are set for this configuration and are not suitable if the trunking is installed in low configuration (with the longest side horizontally). Special corners must be ordered to suit the low configuration. - Single POD with 1 gang box - Single POD with 2 gang box - Twin POD with 2 off 1 gang box - Twin POD with 2 off 2 gang Fig 20: POD unit box POD units do not include frontplates. PODS come with one endcap loose to allow wiring and installation of electrical accessories and also to allow drilling of the manin base to pass cables through. After wiring is completed and the POD is secured to the worksop, the endcap must be securely fitted. 11.4 Posts Columns Vertical cable management solutions and in areas with high density of sockets (Power and data). Two default options are available: - 8 sockets (For use on top of working surfaces) - 24 sockets (For use in combination with raised access floor systems) Fig 21: Vertical solutions Fig 18: Recommended orientation over worktops 11.2 Installation on Island Location Specific advice for fixing these units must be requested in advance to REHAU Single or Twin (back to back with twin endcap) Fig 19: Twin configuration 4

12 Classification According to BSEN 50085-1 (2005): - Non-flame propagating - With electrical insulating characteristics - With high protection outside and inside - Cable Trunking System (CTS) for impact 5J - Minimum installation and application temperature: -5 C - Maximum application temperature: 60 C Other classification - Protection against the ingress of solid objects according to BS EN 60592:1992 IP4X - Total maximum current capacity of circuits inside Profila Bench Trunking 120A @ 230V 13 Cable Capacity - Cross section area Fig 22: Cross section areas - Number of Cables Conductor CSA (mm 2 ) Full compartment (1) POWER Compartment With socket Box (2) Bottom compartment (4) Cable outside diameter (mm) Compartment Full compartment (1) DATA With socket box (2) 1.5 266 113 28 6 81 34 15 2.5 181 77 20 7 59 25 12 4.0 138 58 16 8 45 19 9 6.0 108 46 12 9 36 15 6 Tab 1: Cable capacity bench trunking This product is Design Registered. Top compartment (3) 5

UK & IRELAND SALES OFFICES London, REHAU Ltd, The Building Centre, 25 Store Street, London WC1E 7BT Slough, Units 5 J & K, Langley Business Centre, Station Road, Langley, Slough SL3 8DS Phone: 01753 588500 Fax: 01753 588501 Manchester, Brinell Drive, Irlam, Manchester M44 5BL Phone: 0161 777 7400 Fax: 0161 777 7401 Glasgow, Phoenix House, Phoenix Crescent, Strathclyde Business Park, Bellshill, North Lanarkshire ML4 3NJ Phone: 01698 503700 Fax: 01698 503701 Dublin, 9 St. Johns Court, Business Park, Swords Road, Santry, Dublin 9 Phone: 00353 (0)1 8165020 Fax: 00353 (0)1 8165021 www.rehau.co.uk E39.680EN/JOP/08.10