Power factor improvement in three-phase networks with unbalanced inductive loads using the Roederstein ESTAmat RPR power factor controller

Similar documents
Analysis the electrical parameters of a highfrequency coreless induction furnace

The influence of home nonlinear electric equipment operating modes on power quality

Simulation Results of a Shunt Active Power Filter with Control Based on p-q Theory

Thyristorised Automatic Power Factor

Introduction to Rectifiers and their Performance Parameters

Case Study Survey of Harmonic Pollution Generated by Railway Systems and Filtering Solutions

Analysis of Harmonic Distortion in Non-linear Loads

ARE HARMONICS STILL A PROBLEM IN DATA CENTERS? by Mohammad Al Rawashdeh, Lead Consultant, Data Center Engineering Services

Study for the electric arc of alternative current at the single phase welding machine using the Matlab/Simulink environment

We are IntechOpen, the world s leading publisher of Open Access books Built by scientists, for scientists. International authors and editors

p. 1 p. 6 p. 22 p. 46 p. 58

POWER FACTOR CORRECTION. HARMONIC FILTERING. MEDIUM AND HIGH VOLTAGE SOLUTIONS.

Electric Power Quality Monitoring and Analysis at a Tri-generation Plant under Development

HARMONICS CAUSES AND EFFECTS

Simulation Results on the Currents Harmonics Mitigation on the Railway Station Line Feed

Functioning Analysis of a High Frequency Electro Thermal Installation with Electromagnetic Induction Using PSCAD-EMTDC Tool

CHAPTER 5 POWER QUALITY IMPROVEMENT BY USING POWER ACTIVE FILTERS

22.0 Harmonics in Industrial Power Systems

What does Power Factor mean?

Understanding Harmonics

Harmonics and Their Impact on Power Quality. Wayne Walcott Application Engineering Manager June, 2017

McGill Power Sales & Engineering, INC.

Intelligent traffic control system using PLC

Active Harmonic Filter (AF3)

ELECTROMAGNETIC POLLUTION PRODUCED BY THE INDUSTRIAL FREQUENCY CRUCIBLE INDUCTION FURNACES IN THE POWER SUPPLY NETWORK

APQline Active Harmonic Filters. N52 W13670 NORTHPARK DR. MENOMONEE FALLS, WI P. (262) F. (262)

Peteris Spels, ABB Inc., WMEA, November 18, 2011 HARMONICS. ABB Group December 14, 2011 Slide 1

Three Phase PFC and Harmonic Mitigation Using Buck Boost Converter Topology

ISSN Vol.03,Issue.07, August-2015, Pages:

Improving Passive Filter Compensation Performance With Active Techniques

EXPERIMENTAL STUDY OF THE POWER FACTOR COMPENSATION CONVERTER

Electrical Motor Power Measurement & Analysis

Generator Advanced Concepts

CHAPTER 4 HARMONICS AND POWER FACTOR

Emicon Engineering Consultants L.L.C.

1. Introduction to Power Quality

Production power on a budget: How to generate clean reliable power, Part 2 By Guy Holt

R. W. Erickson. Department of Electrical, Computer, and Energy Engineering University of Colorado, Boulder

Available online at ScienceDirect. Procedia Technology 21 (2015 ) SMART GRID Technologies, August 6-8, 2015

Using dspace in the Shunt Static Compensators Control

Investigation of Passive Filter for LED Lamp

Synchronous Reference Frame Theory For Nonlinear Loads using Mat-lab Simulink

DESIGN AND ANALYSIS OF ELIMINATION OF HARMONICS USING WIND ENERGY CONVERSION SYSTEMS

Technical News. Part 2: Harmonics. The link between harmonics and power factor. Industrial Electrical and Automation Products, Systems and Solutions

WILEY CONTROL OF POWER INVERTERS IN RENEWABLE ENERGY AND SMART GRID INTEGRATION. Qing-Chang Zhong. Tomas Hornik IEEE PRESS

ABB DRIVES Technical guide No. 6 Guide to harmonics with AC drives

How Harmonics have led to 6 Power Factor Misconceptions

PRUDENT PRACTICES TO IMPROVE POWER FACTOR AND REDUCE POWER LOSS.

Power Quality Analysis in Power System with Non Linear Load

Three phase six-switch PWM buck rectifier with power factor improvement

SHUNT ACTIVE POWER FILTER

The Occurrence of Faults in Permanent Magnet Synchronous Motor Drives and its Effects on the Power Supply Quality

Power Factor and Power Factor Correction

How adjustable speed drives affect power distribution

DSP-BASED CURRENT SHARING OF AVERAGE CURRENT CONTROLLED TWO-CELL INTERLEAVED BOOST POWER FACTOR CORRECTION CONVERTER

Harmonic distortion from induction furnace loads in a steel production plant

Tuningintobetter power quality

World Academy of Science, Engineering and Technology International Journal of Electrical and Computer Engineering Vol:7, No:6, 2013

Multimeter 500CVD21 RTU500 series

Power Quality Notes 3-2 (MT)

Laboratory no. 3 FLUORESCENT LAMPS FITTINGS

A Single Phase Power Factor Correction Using Programmable Interface Circuit

Power Quality Analysis: A Study on Off-Line UPS Based System

Harmonics Reduction using 4-Leg Shunt Active Power Filters

Power Factor & Harmonics

APPLICATIONS. AFQ Active Multi-Function Filter. AFQ solves thousands of problems in countless types of installations, in particular the following:

Grid codes and wind farm interconnections CNY Engineering Expo. Syracuse, NY November 13, 2017

Fundamentals of Power Quality

EMC Aspects of Power Quality

HYBRID STATCOM SOLUTIONS IN RENEWABLE SYSTEMS

Sinusoidal Current Control based Shunt Active Power Filter for Current Harmonics Reduction

Influence of Switching Elements on Harmonics and Power Factor Improvement

SERIES ACTIVE power filters have proved to be an interesting

Harmonic Distortions Analyzer for Power Rectifiers

Wideband resistive voltage divider for a standard wattmeter

Compensation of Reactive Power Case Study

Analysis and modeling of thyristor controlled series capacitor for the reduction of voltage sag Manisha Chadar

Modeling of Conduction EMI Noise and Technology for Noise Reduction

ENERGY SAVINGS THROUGH POWER CONDITIONING WITH THE PowerGUARD SYSTEM

ISSN: X Impact factor: (Volume 3, Issue 6) Available online at Modeling and Analysis of Transformer

Power Quality, Earthing And Bonding Oct $4,250 Dubai, UAE. In any of the 5 star hotels. The exact venue will be informed once finalized.

Improve Power Factor and Reduce the Harmonics Distortion of the System

PQ-Box 100 Network Analyzer for Low-, Medium- and High-Voltage Networks

Single Phase Bridgeless SEPIC Converter with High Power Factor

Power Quality improvement of a three phase four wire system using UPQC

HARMONIC contamination, due to the increment of nonlinear

P2 Power Solutions Pvt. Ltd. P2 Power Magnetics. Quality Power within your Reach. An ISO 9001:2008 Company

International Journal of Advance Engineering and Research Development ANALYSIS AND MITIGATION OF HARMONICS IN MEDICAL FIELD

Harmonics Elimination Using Shunt Active Filter

Understanding Input Harmonics and Techniques to Mitigate Them

Power Factor Correction of Inductive Loads using PLC

STATCOM with FLC and Pi Controller for a Three-Phase SEIG Feeding Single-Phase Loads

ISSN: ISO 9001:2008 Certified International Journal of Engineering and Innovative Technology (IJEIT) Volume 5, Issue 11, May 2016

Australian Journal of Basic and Applied Sciences. Simulation and Analysis of Closed loop Control of Multilevel Inverter fed AC Drives

E S C R I P T I V E B U L L E T I N .,.,.,. Bulletin DB-106. October, Square D Company Power System Studies ---1 I SQU ARED COMPANY --

ANALYSIS OF EFFECTS OF VECTOR CONTROL ON TOTAL CURRENT HARMONIC DISTORTION OF ADJUSTABLE SPEED AC DRIVE

FAULT AND STABILITY ANALYSIS OF A POWER SYSTEM NETWORK BY MATLAB SIMULINK

Power Quality Analysers

ANALYSIS OF VOLTAGE TRANSIENTS IN A MEDIUM VOLTAGE SYSTEM

Improving the Power Factor Correction in the Presence of Harmonics by Reducing the Effect of Resonance and Harmonics

Transcription:

IOP Conference Series: Materials Science and Engineering PAPER OPEN ACCESS Power factor improvement in three-phase networks with unbalanced inductive loads using the Roederstein ESTAmat RPR power factor controller To cite this article: C M Dini et al 018 IOP Conf. Ser.: Mater. Sci. Eng. 94 01051 Related content - New Technologies for Smart Grid Operation: Improvement of service reliability and optimization of energy delivery (asset management) S T Mak - Influence of load type on power factor and harmonic composition of three-phase rectifier current N V Nikolayzin, E V Vstavskaya, V I Konstantinov et al. - Three-phase Inverter Based on STC8A8K Controller Xiuhua Wang View the article online for updates and enhancements. This content was downloaded from IP address 148.51.3.83 on 11/09/018 at 19:4

Power factor improvement in three-phase networks with unbalanced inductive loads using the Roederstein ESTAmat RPR power factor controller C M Diniș, C D Cunțan, R O S Rob and G N Popa Politehnica University of Timisoara, Department of Electrical Engineering and Industrial Informatics, 5 Revolution Street, Hunedoara, 33118, Romania E-mail: corina.dinis@fih.upt.ro Abstract. The paper presents the analysis of a power factor with capacitors banks, without series coils, used for improving power factor for a three-phase and single-phase inductive loads. In the experimental measurements, to improve the power factor, the Roederstein ESTAmat RPR power factor controller can command up to twelve capacitors banks, while experimenting using only six capacitors banks. Six delta capacitors banks with approximately equal reactive powers were used for experimentation. The experimental measurements were carried out with a three-phase power quality analyser which worked in three cases: a case without a controller with all capacitors banks permanently parallel connected with network, and two other cases with power factor controller (one with setting power factor at 0.9 and the other one at 1). When performing experiments with the power factor controller, a current transformer was used to measure the current on one phase (at a more charged or less loaded phase). 1. Introduction The paper presents the analysis of a power factor improvement in three-phase network with unbalanced inductive loads using capacitors banks, without series coils. Power factor (PF) is an important power engineering parameter. PF measured must be greater than neutral PF (0.9 for low voltage, and 0.95 for medium and high voltages). An artificial solution to increase the PF is to connect capacitors banks (CBs) in parallel with electric loads, which create capacitive reactive power (opposite with inductive reactive electric power), so, the overall reactive power decreases. CBs can be connected on the low or medium voltage. Capacitors values must be calculated and chosen to improve PF [1-4]. Increasing of the PF in industry can be achieved by natural means (e.g. choosing the right electric motors and transformers, reducing free running time, achieving high quality repairs of electrical equipment, changes of induction motors with synchronous motors) and/or by artificial means (using of synchronous compensators, static VAR compensators, CBs controlled by power factor controller - PFC). The use of CBs is a common solution to improve PF in low voltage electrical installations [3-6]. To improving of PF in the low voltage substation, CBs connection can be done manually or automatically (e.g. with a PFC). To improve PF with CBs (for a single large power electric motor or for a group of electric motors), the effect of nonlinearity becomes significant and current waveforms deviate more from sine shape [4-11]. Electric waveforms (current or voltage) can be decomposed into fundamental (frequency 50 Content from this work may be used under the terms of the Creative Commons Attribution 3.0 licence. Any further distribution of this work must maintain attribution to the author(s) and the title of the work, journal citation and DOI. Published under licence by Ltd 1

Hz) and harmonics, through Fast Fourier transform. Passive, active, or hybrid filters, can be used with CBs to improve power quality of the grid [6], [7], [9]. Experimental measurements were performed on the network with three-phase inductive loads (two three-phase induction motors) and, also single-phase inductive loads (low-pressure mercury lamps and high-pressure mercury lamp with inductive ballast) that are connected on the same phase [4], [5], [11], [1]. It is observed that the PFC controls the power factor close to the set value, for the phase on which the phase shift is measured, and on other phases, the power factor is not adjusted properly. Operation limitations of the three-phase controller that measures the power factor on a single phase will be evaluated. It is also noted that the improvement of the power factor will increase the deformation of the phase currents.. Power quality and harmonics effects The main disruptive phenomena of the power quality are: frequency variations; long-term interruptions; transient over-voltages; harmonic and inter-harmonic; slow variations in the effective voltage value; voltage shocks, short-term interruptions; voltage fluctuations/flicker; unbalances of the three-phase voltage system. In an ideal energy system (perfectly clean), the voltage and current curves are perfectly sinusoidal. In practice, non-sinusoidal currents occur if the load is non-linear in relation to the applied voltage [13-15]..1. Some indicators of power quality The power quality analyser CA 8334B can computes up to 50 harmonics rank [16], [17]. The RMS values of voltage and currents are: 1 1 N N j 0 V ( V ) (1) RMS i 1 1 N N j 0 ji I ( I ) () RMS i where i is L1, L or L3. Total harmonic distortion of voltages and currents: Crest factor voltage and current can be compute with: V I ji 50 ( Vni ) n THD i V1 100 (3) 50 ( Ini ) n THD i I 1 100 (4)

N 1 n 0 max Vpp i, Vpm i V CF i (5) 1 V ni N N 1 n 0 Positive voltage and negative voltage are given by relations: The unbalance voltage and currents are calculated with: Power factor (including harmonics) is given by: max I pp i, I pm i I CF i (6) 1 I ni N V1 av a V3 V (7) 3 V1 a V av3 V (8) 3 V V unb 100 (9) V I I unb 100 (10) I P PF (11) S 3. Power factor improving with capacitor banks The role of capacitor banks is to provide the reactive power required for inductive loads. The goal of the capacitor banks are: decreasing of the phase current; increasing the voltage level for electric loads; reduction of the active and reactive power losses; improving the power factor of the source; reduction total consumption at power source. Compensation of reactive power with capacitors banks also has the following advantages: - the installations are static, have no wear parts, so there is no need for expensive improvement or surveillance; - it has a relatively low gauge and can be located at any point; - the active power losses are relatively low (-6 W/kVAr). 4. Power factor improving in electrical networks with power factor controllers In the experimental installation, a 1-steps ESTAmat RPR power factor controller (from VISHAY, Germany) and three phase power quality are used (Figures 1, 4, 5, 6) [1], [17]. 3

Figure 1. Electrical setup with ESTAmat RPR controller - K1...K6 - power relays, RI 13 type; - CT current transformer, with transformation ratio 15A/5A connect on the phase L1. Inductive three-phase loads used in experiments are two induction motors: - Motor 1 (M1): power: 0.75 kw; current:.1 A; efficiency: 0.7; power factor: 0.76; rotation: 1350 rpm; shaft diameter: 19 mm Figure ; - Motor (M): power: 0.5 kw; current: 0,85 A; efficiency: 0,6; power factor: 0,7; rotation: 1350 rot/min; shaft diameter: 14 mm Figure 3. Figure. Induction motor M1 Figure 3. Induction motor M Figure 4. Power switch S1 Figure 5. Power quality analyser CA 8334 B Figure 6. ESTAmat RPR controller 4

Single-phase inductive loads are lamps: H1 Hg fluorescent lamp with magnetic ballast, x 0 W; H Hg high pressure lamps, 15 W; H3 Hg fluorescent lamp with magnetic ballast, x 0 W. In experiments, where used six capacitor banks, in delta connection (Figure 7, two capacitor banks in one box). The electrical parameters for capacitor banks, delta connection, are: - Capacitors bank 1, B1: C1=3x3.78µF/400V, Qb1=571 VAr; - Capacitors bank, B: C=3x4µF/400V, Qb=616 VAr; - Capacitors bank 3, B3: C3=3x3.71µF/400V, Qb3=560 VAr; - Capacitors bank 4, B4: C4=3x3.9µF/400V, Qb4=588 VAr; - Capacitors bank 5, B5: C5=3x4.1µF/400V, Qb5=6 VAr; - Capacitors bank 6, B6: C6=3x3.6µF/400V, Qb6=54 VAr. Figure 7. Capacitors banks used in experiments 5. Experimental measurements In the following experiments with the current transformer, the current was measured on phase L1. The current transformer connected to the PFC input. The single-phase loads were connected between L1 and null, at experiments 1, and 3. At experiments 1 and the single phase consumers were connected between L1 and null, and at experiment 3 between L and null. 5.1. Experiment 1, power factor controller with DPF set=1 The stages at experiments 1 are shown in Table 1. Table 1. Stages at first experiment DPF set = 1 Measuring stages DPF (-) 1. Motor M1 connected 0.1 i. Capacitors banks B1, B connected 3. Motor M connected 0.64 i 4. Lamp H1 connected 0.6 i 5. Capacitors bank B3 connected 0.6 i 6. Lamp H3 connected 0.91 i 7. Lamp H connected 0.48 i 8. B4, B5, B6 connected 0.98 c 5

9. Motor M1 disconnected 0.58 i 10. Capacitors banks B1, B disconnected 1 11. Lamps H1, H3 disconnected 0.64 i 1. B3 disconnected 0.9 i 13. B4 disconnected 0.94 c 14. Motor M disconnected 0.88 c 15. Lamp H lamp disconnected 0.06 c 16. Capacitors bank B5 disconnected - 17. B6 disconnected - M and H1 were connected, and then PFC connected capacitors banks B1 and B, DPF = 0.6 (Figures 8-11). Figure 8. Fresnel diagram at connection of M1 Figure 9. Fresnel diagram at connection of M1, M and lamp H1 Figure 10. Phases currents and the null current Figure 11. Fresnel diagram An then, after a period of time, PFC was connected capacitors bank B3 (Figures 1, 13). 6

Figure 1. Fresnel diagram when was connected M Figure 13. Voltage and current on phase L1 After a while were connected all electrical loads (M1, M, H1, H, H3), and the power factor controller was connected all capacitors banks: DPF = 0.98 capacitive (Figures 14, 15). Figure 14. Fresnel diagram for currents Figure 15. Phases currents and the null current M1 was disconnected and, after a short time, B1 and B were disconnected by PFC, DPF=1 (Figures 16-18). Figure 16. Voltage and current on phase L1 7

Figure 17. Fresnel diagram for currents Figure 18. Fresnel diagram for currents H1 and H3 were disconnected and, after a short time, B3 and B4 were disconnected by PFC, DPF m = 0.63 inductive. 5.. Experiment, power factor controller with DPF set =0.9 The stages at experiments are shown in Table. Table. Stages at second experiment DPF set = 0.9 Measuring stages DPF (-) 1. Motor M1 connected 0.1 i. Capacitors bank B1 connected 0.9 i 3. Capacitors bank B connected 0.79 i 4. Motor M connected 0.63 i 5. Lamp H1 connected 0.59 i 6. Capacitors bank B connected 0.99 i 7. Lamp H3 connected 0.9 i 8. Lamp H connected 0.47 i 9. Capacitors banks B4, B5 connected 0.9 i 10. Motor M1 disconnected 0.74 i 11. Capacitors banks B1, B disconnected 0.9 i 1. Lamps H1, H3 disconnected 0.86 i 13. Capacitors bank B3 disconnected 0.95 i 14. Motor M disconnected 0.8 i 15. Capacitors bank B4 disconnected 0.9 i 16. Lamp H is connected - 17. Capacitors bank B5 disconnected - M1 and M were connected, and in a short time B1 and B were connected, DPF m = 0.63 inductive (Figures 19, 0). 8

Figure 19. Phases currents and the null current Figure 0. Fresnel diagram for currents H1 was connected and after a short period of time, B3 was connected by PFC, DPF m = 0.99 inductive (Figures 1-3). Figure 1. Phases currents and the null current Figure. Fresnel diagram for currents Figure 3. Harmonic spectra for currents Then H3 and H were connected, and, after a short period of time, B4 and B5 were connected by PFC, DPF m = 0.9 inductive (Figures 4-6). 9

Figure 4. Phases currents and the null current Figure 5. Fresnel diagram for currents Figure 6. Harmonic spectra for currents H1 was connected and then, immediate, B3 was connected by PFC, DPF m = 0.99 inductive (Figures 7, 8). Figure 7. Voltage and current on phase L1 Figure 8. Voltage and current on phase L And then, H3 and H were connected, and then immediate B4 and B5 were connected by PFC, DPF m =0.9 inductive. It was disconnected M1 and then B1 and B were disconnected by PFC, DPF m =0.9 inductive. H1 and H3 were disconnected, B3 was disconnected by PFC, and DPF m =0.95 inductive. 10

M was disconnected and B4 was disconnected by PFC, DPF m =0.9. Finally, H was disconnected and B5 was disconnected by PFC. Figure 9. Voltage and current on phase L3 Figure 30. Phases currents and the null current 5.3. Experiment 3, power factor controller with DPF set =0.9 At experiment 3, all single-phase loads were connected at phase L, and the current was measure by current transformer on phase L1. The stages at experiments 3 are shown in Table 3. Table 3. Stages at third experiment, DPF set = 0.9 Measuring stages DPF (-) 1. Motor M1 connected 0.1 i. Capacitors bank B1 connected 0.9 i 3. Capacitors bank B connected 0.77 i 4. Motor M connected 0.61 i 5. Lamp H1 connected 0.6 i 6. Lamp H3 connected 0.6 7. Lamp H connected 0.61 i 8. Motor M1 disconnected 0.4 c 9. Capacitors bank B1 disconnected 10. Lamps H1, H3 disconnected Low current 11. Motor M disconnected 0.11 c 1. Capacitors bank B disconnected - 13. Lamp H disconnected - Initially, before introducing three phase and single phase consumers DPF m = 0.1 inductive (Figures 31, 3). Then M1 and M were connected, and in short time B1 and B were connected by PFC, DPF m = 0.61 inductive (Figures 33-35). Then the H1, H3 and H lamps are connected, but the PFC will no longer connect any CB, because the single phase consumers were connected to L phase and not to the current measuring phase, and DPF m = 0.61 inductive (Figures 36-38 ). After disconnecting the motor M1, shortly after is disconnected the B1 by PFC, and after the motor M is disconnected the B is disconnected by PFC and DPF m = 0.11 (Figure 39). Also, the H1 and H3 lamps were disconnected from the second phase (L). 11

Figure 31. Voltage and current on phase L1 Figure 3. Phases currents and the null current Figure 33. Phases currents and the null current Figure 34. Harmonic spectra for currents Figure 35. Fresnel diagram for currents It can be seen from this experiment that if the single phase consumers do not mount on the same phase as the current measure (with CT), they do not influence the insertion of the capacitors banks by the power factor controller, nor will the power factor reach the value set on the regulator, only a much lower value. 1

Figure 36. Phases currents and the null current Figure 37. Fresnel diagram for currents Figure 38. Harmonic spectra for currents Figure 39. Voltage and current on phase L 5.4. Experiment 4, capacitors banks permanently connected in the network The all capacitors banks (CB1-CB6) are connected in the network and the PFC doesn t use. Stages at experiments 4 are shown in Table 4. Three-phase and single-phase consumers were connected and disconnected in the same order as the other experiments. After disconnecting the motors and lamps H1 and H3, an inductive DPF m = 0.37 is obtained (Figures 40, 41). Table 4. Stages at fourth experiment, without controller Measuring stages DPF (-) 1. Motor M1 connected. Motor M connected 3. Lamp H1 connected 4. Lamp H3 connect 5. Lamp H connect 6. Motor M1 disconnect 0.35 i 7. Lamps H1, H3 disconnected 0.9 i 8. Motor M disconnected 0.37 i 9. Lamp H disconnected - 13

Figure 40. Phases currents and the null current Figure 41. Fresnel diagram for currents Some aspects from experiments are shown in Figure 4. Figure 4. Photos from experiments As a result of the four experiments, it is noted that the six used capacitors banks only go into operation if the DPF is set to 1. If the DPF is set to 0.9, only five (from six) capacitors banks are used. If the single phase consumers are not mounted on the same phase on which the current is measured, the ESTAmat RPR controller does not take these into account when adjusting the DPF and fails to adjust the DPF to the set value. For this case (Experiment 3), only two capacitors banks from the six existing ones are used. It is also noted that the insertion of capacitors banks by the controller in the circuit to improve the DPF leads to a significant increase in current deformation (increase THD currents) and increase, also, unbalance. 14

6. Conclusions By using a power factor correction installation, there is provided: high power factor in the consumer supply network, thus maximum energy saving; low reactive energy costs; high efficiency of network connected electrical equipment and high power transfer capacity through cables. The results of the power factor improvement with the power factor controller are as follows: eliminates penalties; reduce load in transformer and equipment; reduces losses in transformers, cables and other equipment, and helps stabilize system voltage by increasing the apparent power available. The power factor controller continuously measures the current and voltage, only one phase (e.g. L1). The current transformer is mounted on one phase, usually the most loaded, without taking into account the charging of the other phases. Very often, sub-compensation or over-compensation, with negative effects in the electricity network, occurs, on the other phases of the low-voltage electrical network. Most controllers take into account the capacitor operating temperature and the resonance, but do not check at the same time the harmonic distortion of voltage and current on each phase. There is an increase in the deforming regime with undesirable effects on the electrical network. Additional losses due to harmonic current circulation, reduced electrical machine efficiency, additional charge of capacitors banks, power cables heating, additional charging of null current, additional stresses of insulators. Usually, currents from the power station are unbalance (there are a lot of single-phase consumers) and are strongly deformed (the total harmonic distortion for current may be 5-35 %). The currents have the following higher harmonics: 5 th rank (<5%), 3 rd rank (<0%) and 7 th (<1%), with amplitudes higher than the other harmonics, 9-40 (<10 %). References [1] Jankovskis J, Stepins D and Pikulins D 010 Efficiency of PFC Operating in Spread Spectrum Mode for EMI Reduction, Electronics and Electrical Engineering 7(103) 13-16 [] Garcia O, Cobos J A, Prieto R, Alou P and Uceda J 003 Single Phase Power Factor Correction: a Survey, IEEE Transactions on Power Electronics 18(3) 749-755 [3] Popa G N, Paliciuc C and Diniș C M 013 On the Use of a Low Voltage Power Factor Controller in Deforming Regime, The 4th International Symposium on Electrical and Electronics Engineering IEEE-ISEEE, Galați, Romania, October 11-13, pp 1-6 [4] Diniș C M, Popa G N and Iagăr A 016 On the Use of Low Voltage Power Factor Controller in Textile Industry, International Conference on Applied and Theoretical Electricity ICATE 016, Craiova, Romania, 6-8 October, pp 1-6 [5] Iagăr A, Popa G N and Diniș C M 017 Power Quality from Theory to Experimentations, Politehnica Publishing House, Timişoara, Romania (in Romanian) [6] Dell Aquila A, Marinelli M, Giuseppe V and Yanchetta P 004 New Power-Quality Assessment Criteria for Supply Systems Under Unbalanced and Nonsinusoidal Conditions, IEEE Transactions on Power Delivery 19(3) 184-190 [7] *** 011 Capacitors and Reactors for Power Factor Correction, Manual, Electronicon Kondensatoren, Gera Gmbh, Germany [8] Meyer D 004 Switchgear for Power Factor Correction Systems, Guide, Moller, Germany, pp 1-6 [9] Ceraolo M and Poli D 014 Fundamentals of Electric Power Engineering: From Electromagnetics to Power Systems, Wiley-IEEE Press [10] Baggini A 008 Handbook of Power Quality, Ed. John Wiley & Sons Ltd., New York, USA [11] Albert H, Gheorghe Ș, Golovanov N, Elefterescu L and Porumb R 013 Power Quality. Contributions. Results. Perspectives, AGIR Publishing House, Bucureşti, Romania (in Romanian) [1] Fărcaș C, Petreuș D and Palaghiță N 003 Power Factor Improving in Modern Supplies, Risoprint Press, Cluj-Napoca, Romania (in Romanian) 15

[13] Arrillaga J and Watson N R 003 Power System Harmonics, John Wiley&Sons, Ltd., West Sussex, Anglia [14] Gobbi A 009 Understanding Power Factor and Input Current Harmonics in Switched Mode Power Supplies, TDI Power, pp 1-1 [15] *** 001 Power Quality Application Guide, Copper Development Association, U.K. [16] *** 007 Three Phase Power Quality Analyzer CA 8334B, User s Guide, Chauvin-Arnoux, France [17] *** 010 Power Factor Correction and Harmonic Filtering in Electric Plants, Technical Applications Papers no.8, ABB, Bergamo, Italy 16