Paul Dobrowsky Innovative Technology Services

Similar documents
AN EXAMPLE OF A STANDARD ARC FLASH PPE LABELING STRATEGY

2015 NFPA 70E. SESHA 2015 ARIZONA MINI CONFERENCE December 10, 2015 Intel Corporation

NFPA-70E. Electrical Safety in the Workplace. Standard for Edition

AN EXAMPLE OF A STANDARD ARC FLASH PPE LABELING STRATEGY

Arc Flash and NFPA 70E

STANDARDIZING ARC FLASH PPE LABELS

Electrical Arc Hazards

Arc Flash Analysis and Documentation SOP

NATIONAL ELECTRIC SAFETY CODE 2012 EDITION

SECTION OVERCURRENT PROTECTIVE DEVICE COORDINATION STUDY

A Guide to Establish an Arc Flash Safety Program for Electric Utilities

DC ARC FLASH. THE IMPLICATIONS OF NFPA 70E 2012 ON BATTERY MAINTENANCE

First Draft Language

Electrical Measurement Safety. Sponsored By:

Key factors to maintaining arc flash safety

Steve Kovach District Sales Engineer

ADDENDUM NO. 2 PROJECT: COURTLAND PUMP STATION CONTRACT: IFB NO COM.00030

Electrical Severity Measurement Tool Revision 4

Arc Flash Analysis Training

SECTION SHORT CIRCUIT, COMPONENT PROTECTION, FLASH HAZARD AND SELECTIVE COORDINATION STUDY

Arc Flash Mitigation An Overview. Gus Nasrallah, P.E. Electroswitch May 30, 2013

Selection of PPE Practical experience of different arc assessment methods and their comparison

Arc Flash Hazard Standards:

Arc Flash Calculation Methods

2018 Consultant s Handbook Division 26 Electrical ARC Flash Hazard Analysis

Electrical Safety Policy Health and Safety FCX-HS03 Release 07/2018 Version 1

This section applies to the requirements for the performance of power system studies by both the Design Engineer and the Contractor.

PREFACE ********************************************************** IT IS NOT INTENDED THAT THESE STANDARDS BE COPIED AND USED AS A SPECIFICATION!

Education & Training

UNIFIED FACILITIES GUIDE SPECIFICATIONS

Arc Flash Hazard and Mitigation 2 nd Workshop on Power Converters for Particle Accelerators June 14 16, 2010

APPLYING LOW-VOLTAGE CIRCUIT BREAKERS TO LIMIT ARC FLASH ENERGY

{40C54206-A3BA D8-8D8CF }

ARC FLASH & PPE UPDATE. Michael Olivo, P.E. Aaron Ramirez, E.I.T.

SECTION PANELBOARDS

Selective Coordination for Emergency and Legally-Required Standby Power Distribution Systems

2014 NEC Changes Part 1

MECKLENBURG COUNTY. Land Use and Environmental Service Agency Code Enforcement 9/8/10 ELECTRICAL CONSISTENCY MEETING. Code Consistency Questions

LOCKOUT / TAGOUT PROGRAM

ARC FLASH PPE GUIDELINES FOR INDUSTRIAL POWER SYSTEMS

NORTHWEST FLORIDA STATE COLLEGE MONUMENT SIGNS WITH LED DISPLAYS

Electrical Overcurrent Studies

CHAPTER ELECTRIC AND MAGNETIC FIELDS

2017 ELECTRICAL SAFETY SERVICES. Arc Flash Electrical Maintenance Lockout/Tagout And More

THREE PHASE PAD MOUNTED DISTRIBUTION TRANSFORMER ARC FLASH TESTING JUNE 23, 2009 FERRAZ SHAWMUT HIGH POWER LABORATORY NEWBURYPORT, MA

Arc Hazard Assessment for DC Applications in the Transit Industry

DEP 2008 ELECTRIC AND MAGNETIC FIELDS CHAPTER ELECTRIC AND MAGNETIC FIELDS

NOTICE ER Roland Flood Pumping Station Arc Flash Study

How does an Arc occur?

B. Manufacturers: Square-D, G.E. or Westinghosue.

Design Approaches for Hospital Distribution Systems With Considerations for Future Expansion, Operator Safety, and Cost

NSA, Double layered system: Two Layers of Style IC UQ60 (XCYE) 9.0 oz/yd² 305 g/m² Woven, 88% Cotton 12% Nylon, Navy, January, 2011

How does an Arc occur?

Cause, Effect & Mitigation Strategies

SECTION POWER SYSTEMS STUDIES

The NOVA Recloser shall be designed and tested in accordance with the following standards as applicable:

SEI Certification Program Manual

NEC P14 First Draft Ballot (A2016)

PHASE ROTATION METER. Operating and Instruction Manual. a n d A C C E S S O R I E S

Suggested Statement/Substantiation for The PoE Task Group PIs

Electrical testing safety Part 1: Preparing for absence of voltage testing

Section 6: System Grounding Bill Brown, P.E., Square D Engineering Services

Upgrading Your Electrical Distribution System To Resistance Grounding

Webinar: An Effective Arc Flash Safety Program

Application Note (Revision NEW) Original Instructions. EMI Control in Electronic Governing Systems

PRODUCTIVELY SAFER LOCK-OUT TAG-OUT PROCEDURE

RMEL Safety Conference

WAVEFORM CORRECTOR (WAVEFORM CORRECTORS) REPLACES SURGE PROTECTION DEVICES (SPD) PREVIOUSLY KNOWN AS (TVSS)

Section 16621A - AUTOMATIC TRANSFER SWITCH. Part 1 General

SWITCHING SAFETY & RELIABILITY CONFERENCE

ENGINEERING COMMITTEE Interface Practices Subcommittee AMERICAN NATIONAL STANDARD ANSI/SCTE

REDUCING ARC FLASH HAZARD BY REMOTE SWITCHING

Customer Requirements RF Antenna Installations

EFCOG BEST PRACTICE # 211. Best Practice Title: Managing Hazards of Multiwire Branch Circuits Installed Before the 2008 NEC

Chapter 1. Applied Grounding and Bonding. Applied Grounding and Bonding 9/18/2011. Introduction. Introduction. Paul Dobrowsky Member NEC Panel 5

Arc Flash Study Principles & Procedures for below 15 kv AC Systems. Xuan Wu, Dennis Hoffman, Ronald Wellman, and Manish Thakur

The Importance of the Neutral-Grounding Resistor. Presented by: Jeff Glenney, P.Eng. and Don Selkirk, E.I.T.

Brown University Revised 2/1/2006 Facilities Design & Construction Requirements SECTION 16461C - DRY TYPE TRANSFORMERS

Capstone Turbine Corporation Nordhoff Street Chatsworth CA USA Phone: (818) Fax: (818) Web:

Short Circuit Current Calculations

TABLE OF CONTENTS. References

Australian Standard. Switchgear assemblies and ancillary equipment for alternating voltages above 1 kv AS

Single Earthed Neutral and Multi Earthed Neutral. Single Earthed Neutral and Multi Earthed Neutral: Multi Grounded Neutral System (MEN):

Article 225: Outside Branch Circuits And Feeders

CLARK COUNTY FIRE CODE AMENDMENTS

Footwear Foot Grounders Resistive Characterization (not to include static control shoes)

TAG5000 WIRELESS PHASER. Instruction Manual HD ELECTRIC COMPANY 1475 LAKESIDE DRIVE WAUKEGAN, ILLINOIS U.S.A.

DESIGN PRACTICE NOTE DESIGN/REVIEW REQUIREMENTS FOR TRACTION BONDING PLAN

SECTION CABLE TRAYS

VACUUM INTERRUPTER APPLICATION NOTES Filename: VIAN X-Rays and Vacuum Interrupters Revision: 0 PAGE 1

3Ø Short-Circuit Calculations

NEC 2014 Code Changes

SECTION DISTRIBUTION SWITCHBOARDS

Guide for Conducting a Stray Voltage Evaluation Under the MPSC Stray Voltage Rule 1

SAFETY AND HEALTH STANDARD ELECTRICAL GROUNDING Effective Date: 07/17/10 Standard: Document Number: KUCSH0039 Rev: 4

REVIEWED HES MANAGER

400Amp True RMS AC Clamp Meter + NCV

Appendix B to Working on Exposed Energized Parts

EDS LV SUPPLIES TO MOBILE PHONE BASE STATIONS MOUNTED ON TRANSMISSION TOWERS

MV ELECTRICAL TRANSMISSION DESIGN AND CONSTRUCTION STANDARD. PART 1: GENERAL 1.01 Transformer

Transcription:

Significant Changes to NFPA 70E -2009 Edition Paul Dobrowsky Innovative Technology Services 2008 IEEE PCIC 1 Repeat Presentation This has been previously presented 2008 IEEE Electrical Safety Workshop 2008 NFPA WSCE Material was originally developed prior to the 2009 NFPA 70E being available. 2008 IEEE PCIC 2 Introduction ~ 580 Proposals ~ 800 Comments The Report on Proposals (ROP) and Report on Comments (ROC) are available at NFPA.org - Codes and Standards Tab Changes in the Standard are identified using gray highlighted text, section numbers are added to top corners of pages 2008 IEEE PCIC 3 1

More Introduction In this presentation: P 70E-XX indicates a proposal number from the ROP C 70E-XX indicates a comment from the ROC TCC indicates the Technical Correlating Committee [Bracketed information is author's explanation] 2008 IEEE PCIC 4 Last of Introduction WPTG indicates comments submitted by the Word and Phrase Task Group. It was established to deal with terms such as exposed, energized, live parts, where equipment is interacted with, working on, working near, where an electrical hazard exists, and related terms P 70E-244 2008 IEEE PCIC 5 90.2 (A) Covered [was 90.1(A)] This standard addresses electrical safety requirements for employee workplaces that are necessary for the practical safeguarding of employees during activities such as the installation, operation, maintenance, and demolition of electric conductors, electrical equipment, signaling and communications conductors and equipment, and raceways for the following... 2008 IEEE PCIC 6 2

90.2 (A) Continued [TCC clarifies that the document does not apply to the installation of systems, but to the electrical safety work practices that are related to an electrical system. ] C 70E-6a, C 70E-7, C 70E-13, C 70E-15 P 70E-4, 70E-8 2008 IEEE PCIC 7 90.2(B) Not Covered [was 90.1(B) [Exclusions for railways, communications utilities and electric utilities to NFPA 70E to remain. Scope to remain within the NEC scope. NEC Technical Correlating Committee (TCC) established a Task Group to study the issue.] P, 70E-7, 70E-9, 70E-10, 70E-12, 70E-13, 70E-14 C, 70E-31, 70E-65, 70E-112 2008 IEEE PCIC 8 90.2(B)(5) [was 90.1(A)(5)] (5) Installations under the exclusive control of an electric utility where such installations a. Consist of service drops or service laterals, and associated metering, or 2008 IEEE PCIC 9 3

90.2(B)(5) Continued b. Are located in legally established easements or rights-of-way designated by or recognized by public service commissions, utility commissions, or other regulatory agencies having jurisdiction for such installations, or 2008 IEEE PCIC 10 90.2(B)(5) Continued c. Are on property owned or leased by the electric utility for the purpose of communications, metering, generation, control, transformation, transmission, or distribution of electric energy. [Matches 2008 NEC Language where "by other agreements was deleted".] P 70E-7, 70E-10, C70E-31 2008 IEEE PCIC 11 Article 100 Definitions Updated definitions to match 2008 NEC C 70E-191a P 70E-59a 2008 IEEE PCIC 12 4

Article 100 Definitions "live parts" was changed to "energized electrical conductors or circuit parts" throughout the standard. C 70E-191b WPTG P 70E-1 2008 IEEE PCIC 13 Article 100 Definitions Arc Flash Hazard. A dangerous condition associated with the possible release of energy caused by an electric arc. 2008 IEEE PCIC 14 Arc Flash Hazard Continued FPN No. 1: A flash hazard may exist when energized electrical conductors or circuit parts are exposed or when they are within equipment in a guarded or enclosed condition, provided a person is interacting with the equipment in such a manner that could cause an electric arc. Under normal operating conditions, enclosed energized equipment that has been properly installed and maintained is not likely to pose a flash hazard. 2008 IEEE PCIC 15 5

Arc Flash Hazard Continued FPN No. 2: See Table 130.7(C)(9) for examples of activities that could pose a flash hazard. FPN No. 3: See 130.3 for flash hazard analysis information. C 70E-207 WPTG P 70E-244 2008 IEEE PCIC 16 Article 100 Definitions Arc Rating. Value attributed to materials that describes their performance to exposure to an electrical arc discharge. The arc rating is expressed in cal/cm2 and is derived from the determined value of the arc thermal performance value (ATPV) or energy of breakopen threshold (EBT). C 70E-192 P 70E-16 2008 IEEE PCIC 17 Article 100 Definitions New Balaclava (Sock Hood). An arc-rated FR hood that protects the neck and head except for facial area of the eyes and nose. P 70E-50 2008 IEEE PCIC 18 6

Article 100 Definitions Boundary, Arc Flash Protection. When an arc flash hazard exists, an approach limit at a distance from a prospective arc source within which a person could receive a second degree burn if an electrical arc flash were to occur. C 70E-212 WPTG P 70E-36 2008 IEEE PCIC 19 Article 100 Definitions New Switchgear, Arc-Resistant Switchgear, Metal-Clad. Metal-Enclosed Power Switchgear. C 70E-230 P 70E-50a 2008 IEEE PCIC 20 Article 100 Definitions Deleted Working Near (Live Parts) Any activity inside a Limited Approach Boundary [LAB only applies to shock hazard, - use within LAB or within FPB or both, or other electrical hazards in the standard.] C 70E-232 WPTG P 70E-244 2008 IEEE PCIC 21 7

Article 100 Definitions Working On (live parts energized electrical conductors or circuit parts). Coming in contact with live energized electrical conductors or circuit parts with the hands, feet, or other body parts, with tools, probes, or with test equipment, regardless of the personal protective equipment a person is wearing. C 70E-241 P 70E-244, 70E-58 2008 IEEE PCIC 22 110.1 Scope. Chapter one covers electrical safety-related work practices and procedures for employees who are exposed to an electrical hazard in workplaces covered in the scope of this standard... C 70E-258 P 70E-63 2008 NFPA WSCE Motion 2008 IEEE PCIC 23 110.5 Relationships With Contractors (Outside service personnel, etc.) (A) Host Employer Responsibilities (B) Contract Employer Responsibilities. C 70E-273 P 70E-67 2008 IEEE PCIC 24 8

110.6(C) Emergency Procedures. Employees working on or near exposed energized electrical conductors or circuit parts exposed to shock hazards shall be trained in methods of release of victims from contact with exposed energized electrical conductors or circuit parts. C 70E-294 WPTG, 70E-288 P 70E-244, 70E 78 2008 IEEE PCIC 25 110.6(C) Added a new last sentence: Training of employees in approved methods of resuscitation, including cardiopulmonary resuscitation, shall be certified by the employer annually. P 70E-249 C 70E-281, etc. 2008 IEEE PCIC 26 110.6(D)(1)(d) Tasks that are performed less often than once per year shall require retraining before the performance of the work practices involved. P 70E-82 2008 IEEE PCIC 27 9

110.6(D)(1)(e) Employees shall be trained to select an appropriate voltage-detector and shall demonstrate how to use a device to verify the absence of voltage, including interpreting indications provided by the device. The training shall include information that enables the employee to understand all limitations of each specific voltage-detector that may be used. P 70E-74 C 70E-282 2008 IEEE PCIC 28 110.6(D)(3) Retraining. New An employee shall receive additional training (or retraining) under any of the following conditions: (a) If the supervision or annual inspections indicate that the employee is not complying with the safety-related work practices 2008 IEEE PCIC 29 110.6(D)(3) Continued (b) If new technology, new types of equipment, or changes in procedures necessitate the use of safety-related work practices that are different from those which the employee would normally use, or (c) If he or she must employ safety related work practices that are not normally used during his or her regular job duties". C 70E-299 P 70E-80 2008 IEEE PCIC 30 10

110.6 (E) Training Documentation The employer shall document that each employee has received the training required by paragraph 11 0.6(D) of this section. This documentation shall be made when the employee demonstrates proficiency in the work practices involved and shall be maintained for the duration of the employee s employment. The documentation shall contain each employee s name and dates of training. 2008 IEEE PCIC 31 110.6 (E) Continued FPN: Employment records that indicate that an employee has received the required training are an acceptable means of meeting this requirement. P 70E-73 2008 IEEE PCIC 32 110.7 Electrical Safety Program. (A) General. The employer shall implement and document an overall electrical safety program that directs activity appropriate for the voltage, energy level, and circuit conditions. P 70E-92 2008 IEEE PCIC 33 11

110.7(B) Awareness and Self-Discipline.... The program shall be developed to provide the required self-discipline for employees who occasionally must perform work on or near exposed energized electrical conductors and circuit parts that may involve electrical hazards.... C 70E-322 WTPG P 70E-93 2008 IEEE PCIC 34 110.7(F) Hazard/Risk Evaluation Procedure Added an additional last sentence. The procedure shall identify the hazard/risk process that shall be used by employees to evaluate tasks before work is started. P 70E-95 2008 IEEE PCIC 35 110.7(F) FPN The hazard/risk evaluation procedure may include identifying when a second person could be required and the training and equipment that person should have. C 70E-432 P 70E-193 2008 IEEE PCIC 36 12

110.7 (H) Electrical Safety Auditing. [New] An electrical safety program shall require auditing of the work being performed of an identified frequency to help assure that the principles and procedures of electrical safety program are being followed. All electrical safety procedures shall be reviewed and revised, based upon the auditing findings, of frequency determined by the employer based on the complexity of the procedures and the type of work being covered. C 70E-328 P 70E-100 2008 IEEE PCIC 37 110.8 Working On or Near Electrical Conductors or Circuit Parts While Exposed to Electrical Hazards C 70E-334 WPTG P 70E-101 2008 IEEE PCIC 38 110.8(A) Safety-related work practices shall be used to safeguard employees from injury while they are working on or near exposed to electrical hazards from electrical conductors or circuit parts that are or can become energized.... C 70E-341 WPTG, 70E-343 P 70E-101, 70E-60 2008 IEEE PCIC 39 13

110.8(B)(2) When working on energized electrical conductors or circuit parts that if live parts are not placed in an electrically safe work condition (i.e., for the reasons of increased or additional hazards or infeasibility per 130.1), work to be performed shall be considered energized electrical work and shall be performed by written permit only. C 70E-363 P 70E-108 2008 IEEE PCIC 40 110.9(A)(1) [New] FPN: See ANSI/ISA-61010-1 (82.02.01)/UL 61010-1Safety Requirements for Electrical Equipment for Measurement, Control, and Laboratory Use Part 1: General Requirements for rating and design requirements for voltage measurement and test instruments intended for use on electrical systems 1000V and below. C 70E-367 P 70E-114, 70E-115 2008 IEEE PCIC 41 120.2(F)(1)(b) 120 Establishing an Electrically Safe Work Condition (1) Planning (b) Exposed Persons. The plan shall identify persons who might be exposed to an electrical hazard and the personal protective equipment required during the execution of the job or task. 2008 IEEE PCIC 42 14

120.2(F)(2)(f)(1) (2)Elements of Control (f)(1) What voltage detector will be used, the required personal protective equipment, and who will use it to verify proper operation of the voltage detector before and after use. P 70E-160 2008 IEEE PCIC 43 Article 130 Work ing On or Near Live Parts Involving Electrical Hazards C 70E-397 WPTG P 70E-166 2008 IEEE PCIC 44 New last sentence. 130.1(B)(3) If the purpose of crossing the Limited Approach Boundary is only for visual inspection and the Restricted Approach boundary will not be crossed, then an energized electrical work permit shall not be required. C 70E-412 P 70E-181 2008 IEEE PCIC 45 15

Table 130.2(C) Exposed Movable Conductor Table Note 2 A condition in which the distance between a conductor and a person is not under the control of the person. The term is normally applied to overhead line conductors supported by poles. C 70E-203 P 70E-3 2008 IEEE PCIC 46 130.3 New Last Sentence and exception The Flash Hazard Analysis shall be updated when a major modification or renovation takes place. It shall be reviewed periodically, not to exceed five years to account for changes in the electrical distribution system that could affect the results of the analysis. 2008 IEEE PCIC 47 130.3 Exception [New] Exception No. 1 An arc flash hazard analysis shall not be required where all of the following conditions exist: (1) Circuit is rated 240 V or less Circuit supplied by one transformer Supply transformer is rated less than 125 kva C 70E-444 2008 IEEE PCIC 48 16

130.3 Continued Exception No. 2 The requirements of Sections 130.7(C)(9); 130.7(C)(10), and 30.7(C)(11) shall be permitted to be used in lieu of a detailed incident energy analysis. C 70E-440 P 70E-203 2008 IEEE PCIC 49 130.3 FPN [New] FPN No. 1: Improper or inadequate maintenance can result in increased opening time of the overcurrent protective device, thus increasing the incident energy. P 70E-204 C 70E-451 2008 IEEE PCIC 50 130.3(A) Changed the 4 foot Flash Protection Boundary to be based on 2 cycle clearing time and 50kA fault current, or 100kA cycles. (1667 ampere seconds) [Existing is 6 cycles and 50kA, or 300 ka cycles.] P 70E-218 2008 IEEE PCIC 51 17

130.3(A) Equations for calculating the Flash Protection Boundary have been relocated to Annex D. A FPN has been added directing the user to Annex D. P 70E-208 2008 IEEE PCIC 52 130.3(B) The language is to modified so that when work is performed within the Flash Protection Boundary, one of two methods are to be used for selecting protective clothing and other PPE. --1) Incident Energy Analysis --2) Hazard Risk Categories (Tables) P 70E-226 C 70E-486, 70E-488 2008 IEEE PCIC 53 130.3(C) [New] Equipment Labeling. Equipment shall be field marked with a label containing the available incident energy or required level of PPE. P 70E-237,, 70E-300 C 70E-494, 70E-497 2008 IEEE PCIC 54 18

130.6(A) [New] (3) Changes in Scope. Employees shall be instructed to be alert for changes in the job or task that may lead the person outside of the electrically safe work condition or expose the person to additional hazards that were not part of the original plan. C 70E-516 P 70E-243 2008 IEEE PCIC 55 130.7(C)(1) New Last Sentence All parts of the body inside the Arc Flash Protection Boundary shall be protected. P 70E-261 C 70E-533 2008 IEEE PCIC 56 130.7(C)(5) The exception that permitted nonmelting flammable clothing to be used up to a 2 cal/cm2 level has been deleted. P 70E-274 C 70E-542 2008 IEEE PCIC 57 19

130.7(C)(6)(c) & Table 130.7(C)(6)(c) Specific use and testing details were added for rubber insulating equipment. The Table provides testing intervals for rubber goods. C 70E-543a P 70E-282 2008 IEEE PCIC 58 130.7(C)(9) FPN No. 1 Added information that helps explain the background behind the tables development. based on Task Groups collective experience estimated exposure levels reduction of HRC No. due to low risk closed doors don't provide enough protection to eliminate PPE in all cases full committee consensus P 70E-351 C 70E-573, 70E-574 2008 IEEE PCIC 59 Table 130.7(C)(9) Added the words or other equipment to Panelboards Rated 240 V and below in the table. [This expands the application of the table to other types of equipment not specifically included] P 70E-341 2008 IEEE PCIC 60 20

Table 130.7(C)(9) Hazard Risk Categories for work on equipment that is fed directly by a branch circuit of panelboards, switchboards, and motor control centers were added. P 70E-307 2008 IEEE PCIC 61 Table 130.7(C)(9) Hazard risk Categories for infrared thermography and other non-contact inspections were added to the table. P 70E-329 2008 IEEE PCIC 62 Table 130.7(C)(9) Modified the table to TIA 70E-04-01 This TIA was included after the index in the second printing of the 2004 edition. It reduces the short circuit values and clearing times for some of the table notes. P 70E-348 2008 IEEE PCIC 63 21

Table 130.7(C)(9) Notes 3 and 6 have been deleted. [The notes permitted an automatic reduction of one hazard/risk category for lower short circuit currents.] P 70E-349 C 70E-571 2008 IEEE PCIC 64 Table 130.7(C)(10) Usability of the table was improved by providing the Hazard Risk Categories in one column and the required items to be used in a second column. P 70E-403 2008 IEEE PCIC 65 Table 130.7(C)(10) The provision for using natural or non-melting clothing for increasing the "rating" of PPE or as a substitute for PPE has been deleted. C 70E-593, 70E-602 P 70E-389, 70E-381 2008 IEEE PCIC 66 22

Table 130.7(C)(10) Hearing Protection requirement was aded to HRC's 0 and 1. [Substantiation provided indicated that several incidents with energy levels that would fall into the HRC 0 or HRC 1 PPE range have peak sound levels exceeding the OSHA impulse limit of 140dB] C 70E-609 P 70E-391 2008 IEEE PCIC 67 Table 130.7(C)(10) Requires the use of leather gloves for Hazard Risk Category 1 tasks. [For arc effects, not electrical shock] P 70E-384 2008 IEEE PCIC 68 Table 130.7(C)(10) Note 3 4. Regular weight (minimum 12 oz/yd2 fabric weight), untreated, denim cotton blue jeans are acceptable in lieu of FR pants. The FR shirt and pants used for Hazard/ Risk Category 1 shall have a minimum arc rating of 4. C 70E-614 P 70E-382 2008 IEEE PCIC 69 23

Table 130.7(C)(10) Added a requirement to use either face shield or flash hood for hazard risk category 1 with a minimum arc rating of 4. P 70E-399 2008 IEEE PCIC 70 Table 130.7(C)(10) Modifies the table so that the arc rating is the primary focus for meeting the requirements. Using a garment or system of garments is acceptable. P 70E-389 2008 IEEE PCIC 71 Table 130.7(C)(9) The 2* designation means that a flash suit hood or alternatively a face shield used in combination with a balaclava (sock hood) is required for this task See Note 10 P 70E-356 2008 IEEE PCIC 72 24

Table 130.7(C)(11) The committee concluded that the system arc rating should be based on FR clothing only and not on non-fr underlayers. Nonflame resistant underlayers cannot be used to achieve the desired system arc rating. C 70E-621 P 70E-419 2008 IEEE PCIC 73 130.7(C)(11) Clarifies that that Table 130.7(C)(11) is to be used only after the hazard risk category is determined by using Table 130.7(C)(9)(a). [The tables are to be used as a package, and are not to be used individually as part of a hazard analysis method] P 70E-425 C 70E-620 2008 IEEE PCIC 74 130.7(C)(15) [New] Ex. No 2 Where the work to be performed inside the Flash Protection Boundary exposes the worker to multiple hazards, such as airborne contaminants, under special permission by the authority having jurisdiction and where it can be shown that the level of protection is adequate to address the arc flash hazard, non-fr Personnel Protective Equipment shall be permitted. P 70E-440 2008 IEEE PCIC 75 25

130.7(E) Alerting Techniques (4) Look-Alike Equipment. Where work performed on equipment that is deenergized and placed in an electrically safe condition exists in a work area with other energized equipment that is similar in size, shape, and construction one of the altering methods in 130.7(E)(1), (2) or (3) shall be employed to prevent the employee from entering look-alike equipment. 70E-629 P 70E-448 2008 IEEE PCIC 76 205.3 [New] General Maintenance Requirements. Overcurrent protective devices shall be maintained in accordance with the manufacturers' instructions or industry consensus standards. C 70E-636 P 70E-130 2008 IEEE PCIC 77 210.5 FPN [New] Failure to properly maintain protective devices can have an adverse effect on the flash hazard analysis incident energy values. P 70E-455 C 70E-646 2008 IEEE PCIC 78 26

Article 320. Batteries and Battery Rooms 320.1 Scope. The requirements of this article shall apply to the safety requirements related to installations of stationary storage batteries and battery rooms with a stored capacity exceeding 1 kwh or a floating nominal voltage that exceeds 115 50 volts but does not exceed 650 volts. C 70E-664, 70E-665 P 70E-471, 70E-472 2008 IEEE PCIC 79 New Article Article 350 Safety-Related Work Requirements: Research and Development Laboratories. 350.1 The requirements of this article shall apply to the electrical installations in those areas, with custom or special electrical equipment, designated by the facility management for research and development (R&D) as laboratories. 2008 IEEE PCIC 80 Article 350 Continued 350.2 Definitions 350.3 Applications of Other Articles. 350.5 Specific Measures and Controls for Personnel Safety. 350.6 Listing Requirements C 70E-718 P 70E-519 2008 IEEE PCIC 81 27

Chapter 4 Deleted Chapter 4 of NFPA 70E [Historically Chapter 4 contained extracted material from the NEC] C 70E-719 P 70E-520 2008 IEEE PCIC 82 Annex O Safety Related Design Requirements [New] X.1 Introduction. [Facility owner, manager of employer responsibilities for hazard analysis during design.] X.2 General Design Considerations. C 70E-763 P 70E-545 2008 IEEE PCIC 83 Any Parting Thoughts Electrical Safety Be part of it 2008 IEEE PCIC 84 28

?? Questions?? 2008 IEEE PCIC 85 29