SINGLE-PHASE VSV SWITCH

Similar documents
SINGLE-PHASE VSV SWITCH

Distribution/Substation Transformer

Section L5: PRE-ENERGIZATION TEST PROCEDURES FOR LOAD-ONLY ENTITIES AND TRANSMISSION-ONLY ENTITIES

POWER DELEGATOR SERIES 7200A POWER DISTRIBUTION UNIT WITH POWER CONDITIONING GENERAL SPECIFICATIONS

MV ELECTRICAL TRANSMISSION DESIGN AND CONSTRUCTION STANDARD. PART 1: GENERAL 1.01 Transformer

Brown University Revised 2/1/2006 Facilities Design & Construction Requirements SECTION 16461C - DRY TYPE TRANSFORMERS

WESTERN UNDERGROUND COMMITTEE GUIDE 2.6 (2.6/00/0868)

DSM Dynamic Shunt

Michigan State University Construction Standards SWITCHBOARDS, PANELBOARDS, AND CONTROL CENTERS PAGE

Circuit Breakers. Excerpt from Master Catalogue. Circuit Breakers. Specifically For You

Hexa Multi Module 366HMM. Introduction. Design Specifications. Key Features

Capstone Turbine Corporation Nordhoff Street Chatsworth CA USA Phone: (818) Fax: (818) Web:

3.0 CHARACTERISTICS. Type CKO Overcurrent Relay. switch, which allows the operation indicator target to drop.

American Electrical Institute

Standard Pole Mount Parabolic Antenna Mounting Instructions 3 ft. (90cm) & 4 ft. (120cm)

MGM Transformer. Vacuum Pressure Impregnated (VPI) Dry-Type Substation Transformer Specification Guide

Specialty Switches. Inertia Engineering & Machine Works, Inc Hardaway Road, Stockton CA 95215

MECKLENBURG COUNTY. Land Use and Environmental Service Agency Code Enforcement 9/8/10 ELECTRICAL CONSISTENCY MEETING. Code Consistency Questions

MVR Molded Vacuum Reclosers. Instruction Manual

INSTRUCTION MANUAL. Type SWF. Sine Wave Filters 690 Volts, 50Hz

The Variable Threshold Neutral Isolator (VTNI)

7. INSPECTION AND TEST PROCEDURES

Howard Smart Transformer Specification Guide

SINGLE PHASE BUCK & BOOST TRANSFORMERS INSTRUCTION MANUAL

The Isolator/Surge Protector (ISP)

The NOVA Recloser shall be designed and tested in accordance with the following standards as applicable:

The Isolator/Surge Protector (ISP)

Article 250 Grounding & Bonding

SPECIFICATION FOR HORIZONTAL AIRFLOW OUTDOOR RESISTIVE LOAD BANK

High Frequency Sinewave Guardian TM Filter

Power Processor - Series 700F 10KVA to 150KVA

a) Determine the smallest, standard-sized circuit breaker that should be used to protect this branch circuit.

Model 935A Current Source Operation Manual

SECTION 16483D ADJUSTABLE FREQUENCY DRIVE - MICRODRIVE (MVX <10-HP)

Table K. Input/Output Ratings & External Wiring Requirements for the Powerware /80 Rating 50/60 Hz. kva kw VOLTS VOLTS / /220

PIRANHA 3 (3-phase, Power Conditioning Voltage Regulator)

SPECIAL SPECIFICATION 6419 Fiber Optic Video Transceiver with Data

Digital Lighting Systems, Inc. PD804-DMX. Eight Channel DMX Pack. (includes information for PD804-DMX-S) USER'S MANUAL. PD804-DMX-UM Rev.

INSTALLATION, OPERATION AND MAINTENANCE GUIDE

SUGGESTED SPECIFICATION for Series 300 Automatic Transfer Switches

INTELLIMETER REGISTER

P. O. BOX 269 HIGHLAND, ILLINOIS, U.S.A PHONE FAX

CONTINUING EDUC ATION

SPECIAL SPECIFICATION 6609 Fiber Optic Color Video and Data Transmission Equipment

1995 Metric CSJ SPECIAL SPECIFICATION ITEM Multimode Video Fiber Optic Transmission Equipment

Dual Reversing Module

High Frequency SineWave Guardian TM Filter

3Ø Short-Circuit Calculations

Pole Mount Installation Guide

OPERATING MANUAL SERIES R B F BRUSHLESS RACK SYSTEM

Short Circuit Current Calculations

Substation Preventive Maintenance

CP /240-MC4 User Manual

S&C Series 2000 Circuit-Switchers Outdoor Transmission (69 kv through 230 kv)

TOSHIBA International Corp

Low Voltage Power Factor Correction Equipment Specifications Automatic, Automatic Detuned, Automatic Tuned

Short-Circuit Current Calculations

OPERATING MANUAL SERIES R B F 400 VAC BRUSHLESS RACK SYSTEM

INSTALLATION AND MAINTENANCE MANUAL FOR GROUND MONITOR GM-250 COPYRIGHT 1983 AMERICAN MINE RESEARCH, INC.

B. Manufacturers: Square-D, G.E. or Westinghosue.

The Importance of the Neutral-Grounding Resistor. Presented by: Jeff Glenney, P.Eng. and Don Selkirk, E.I.T.

TWR-ISM-002-I Radar Hardware User's Manual

BE1-87G VARIABLE PERCENTAGE DIFFERENTIAL RELAY

SECTION PANELBOARDS

ASX SERIES PACIFIC OPERATION MANUAL AC POWER SOURCE POWER SOURCE

SECTION COMMUNICATIONS ELECTRICAL POWER DISTRIBUTION

Specifications. S&C Circuit-Switcher Mark V Outdoor Transmission (34.5 kv through 345 kv) Conditions of Sale SPECIAL TO THIS PRODUCT:

LX Series Part-Sensing Light Screen

3/29/2012 MAIN TOPICS DISCUSSED ELECTRICAL SYSTEMS AND ELECTRIC ENERGY MANAGEMENT SECTION K ELECTRIC RATES POWER COMPUTATION FORMULAS.

Rev /13 SSRMAN-1B SERIES USERS MANUAL SSR INTELLIGENT BURST FIRING CONTROL COPYRIGHT 2013 NUWAVE TECHNOLOGIES, INC.

SECTION DISTRIBUTION SWITCHBOARDS

KNOW MORE ABOUT THE TRANSFORMERS. Glossary Transformers

SPECIFICATION FOR STEP UP TRANSFORMER 0.415/11Kv and (630KVA & 1000KVA)

SECTION CABLE TRAYS FOR COMMUNICATIONS SYSTEMS

VALVTECHNOLOGIES, INC. INSTALLATION, OPERATIONS & MAINTENANCE MANUAL STEAM CHOKE VALVES

User's Manual: Series 450T AC Current Input (External Sensor), AC-Powered Transmitters

Grounding Recommendations for On Site Power Systems

Equipment Rack Grounding. Technical Note

Article 225: Outside Branch Circuits And Feeders

UNIVERSITY OF MISSOURI Liquid-Filled Utility Transformers 2016 Q1

micro DOUBLE TEN SWITCH

Instructions for Installation. S&C ELECTRIC COMPANY Specialists in Electric Power Switching and Protection TABLE OF CONTENTS INTRODUCTION INSTALLATION

Digital Lighting Systems, Inc.

Class 300 Equipment CBS 305, 320 Current Boost Systems FEATURES. DESCRIPTION Page 2. SPECIFICATIONS Pages 2 through 4.

PERFORMANCE SPECIFICATION SHEET RELAY, ELECTROMAGNETIC PERMANENT MAGNET DRIVE, 25 AMPERES, SPDT, HERMETICALLY SEALED

UBC Technical Guidelines Section Edition Medium-Voltage Transformers Page 1 of 5

INSTRUCTION MANUAL. March 11, 2003, Revision 3

WAVEFORM CORRECTOR (WAVEFORM CORRECTORS) REPLACES SURGE PROTECTION DEVICES (SPD) PREVIOUSLY KNOWN AS (TVSS)

IC800SSD Hardware Manual Pub 348R5. for models. A publication of

EASTERN ILLINI ELECTRIC COOPERATIVE Application for Operation of Member-Owned Generation

PRE COMMISSIONING TESTS ON EQUIPMENT AT 33/11 KV SUB STATIONS. IR Values are to be read on the megger by meggering the Power transformer

Datawave Magnetic Synthesizer

ELECTRIC GROUNDING AND WIRING REQUIREMENTS BOOTHS-METAL

200 Watt Passive Shunt Module

MULTI-BEAM LS10 Light Screen System

Topic 6 Quiz, February 2017 Impedance and Fault Current Calculations For Radial Systems TLC ONLY!!!!! DUE DATE FOR TLC- February 14, 2017

OPTIMIZING MAINS IMPEDANCE: REAL WORLD EXAMPLES by Judith M. Russell Consulting Electrical Engineer PowerLines

INSPECTION 1. Take the cover off the relay, taking care to not shake or jar the relay or other relays around it.

Solenoid Data Book 1425 Lake Avenue Woodstock, IL Phone: (815) Toll Free: Sales Fax: (815)

KILOVAC EV200 Series Contactor With 1 Form X (SPST-NO) Contacts Rated 500+ Amps, Vdc

Transcription:

May 2006 Supercedes: March 2006 SINGLE-PHASE VSV SWITCH INSTALLATION AND OPERATING MANUAL Table of Content: Page I. General...2 II. Specifications...2 III. Installation...2 IV. Maintenance...4 V. VSV Power Input/Design Requirements...4 VI. Appendix A (VSV Switch before November 2001)...7 4000 East 116 th Street λ Cleveland, Ohio 44105-4398 USA λ 216-271-6600 λ FAX 216-341-3615 http://www.joslynhivoltage.com

Page 2 of 8 I. GENERAL The Type VSV (VerSaVac) Switch was redesigned in November 2001 with a Low Energy (LE) operating mechanism. This instruction manual outlines the positive impact of this change in the Specification and Power Input/Design Requirements Sections. All VSVs received under this redesign will be clearly identified with a LE stamped/printed on the nameplate. This manual also maintains the necessary power input requirement details for all VSV received from Joslyn before November 2001 in the Appendix A Section. The VSV continues to be completely factory adjusted and sealed. A cable connector assembly for interconnection wiring to the switch is supplied. Accessories such as a junction box or an electronic switch control can be supplied as optional items. Equipment Included with Each Switch Single Phase VSV Eyebolt Type Terminals Hardware provision to connect ground Cable Assembly Manual Trip Lever Junction Box Capacitor Controls Zero Voltage Closing Control (Special VSV switch part number required) Extra auxiliary contacts Animal Protectors Undervoltage Trip Controls Optional Accessories (Ordered Separately) II. SPECIFICATIONS Control Voltage: 120 Vac VSV: 80 Vac* to 127 Vac 240 Vac VSV: 160 Vac* to 252 Vac Inrush Current: 120 Vac VSV: 12 Amps per switch for a maximum of 1.5 cycles 240 Vac VSV: 12 Amps per switch for a maximum of 1.5 cycles Open and Close Operating Time: 11 milliseconds Recommended Control Pulse Time: 100 milliseconds * Minimum voltage that must be maintained at the pins of the switch control cable connector during the operating inrush current transient. III. INSTALLATION A. Inspection: 1. Uncrate and visually inspect for shipping damage or missing items. 2. If any damage occurred, immediately file a claim with the shipping carrier and then contact you local Joslyn Hi- Voltage Representative. 3. The VSV is shipped from the factory in the CLOSED position to eliminate any potential damage to the vacuum contact due to possible excessive vibration during the shipping process. The VSV MUST always be in the CLOSED position whenever the switch is being transported to prevent the possibility of contact damage.

Page 3 of 8 B. Mount the VSV: The mounting bracket on the VSV is designed to be directly bolted to a wooden utility pole using 5/8 diameter mounting hardware (not provided). Mounting hardware shall be compatible with the galvanized coating of the VSV bracket such that it does not reduce the corrosion resistance level of the coating or the mounting hardware. Refer to the specific switch outline drawing for further mounting and dimensional details. The VSV shall be mounted in a manner such that it does not reduce the required insulation levels of the VSV or any other nearby device. C. Connecting to the VSV 1. Grounding: A ½-13UNC galvanized steel bolt, nut, flat and lockwasher are provided for grounding. The User is responsible for solidly grounding the mechanism housing to all applicable standards to ensure proper and safe operations. 2. High Power Connections: Eyebolt Type Terminal are provided for #8 Solid to 2/0 copper cable connections. Maximum Torque on Terminal Stud is 216 in-lbs. I M P O R T A N T The Versavac switch is not designed for rigid bus connections that can exert high forces. If rigid bud is used, flexible connection joints must be used to prevent any bus forces applied to the Versavac terminals. When tightening the terminals to the 216 in-lbs., the proper work practice of holding the connector bolt and then tightening the connector nut must be utilized to eliminate any induced rotational or twisting torque on the terminal. Excessive rotational torque or stress on the switches' stationary terminals could result in damage of the terminal connection integrity. The actual connection of the high voltage cables are required to be orientated to avoid close proximity of the switch module to assure proper interrupting performance. The high voltage cables should be orientated to maintain a minimum distance of 12 from the side of the interrupter housing. Figure 1 is provided to demonstrate proper installation details. Interrupter Housing Correct Correct Incorrect Figure 1: Cable Connections D. Mounting Control Cabinets or Junction boxes A control cabinet or junction box is not a standard accessory. User should consult manufacturer of controls or junction boxes for installation recommendations of such devices. If a control or junction box is purchase as an optional accessory, refer to the provided wiring and interconnection drawings for specific installation details.

Page 4 of 8 E. Operational Checks After setting up the VSV and control, operate the VSV from the control cabinet to close and open observing the position indicator for agreement with control indication if applicable. If the manual trip lever is supplied, close the VSV and strike the trip handle observing that the switch has opened. F. High Potential Testing High potential testing is used to check the integrity of the vacuum inside the vacuum interrupter. Loss of vacuum results in complete breakdown across open vacuum contacts at voltages below 30kV RMS. Only AC high potential testing is meaningful. DC testing cannot be used. With the VSV in the open position, apply 30kV RMS across each individual contact for 15 seconds. To avoid possible generation of x-rays, do not apply more than 30kV RMS. During the high potential testing, self-extinguishing, momentary breakdowns lasting only a few seconds may occur. These "breakdowns" are not significant but can result in false indication of vacuum loss if the test set utilizes a highspeed overload relay or breaker. During normal operation with the VSV in service, loss of vacuum or a defective interrupter may be indicated by excessive AM radio noise with the VSV open, or by measuring a difference in surface temperatures (a differential of more than 5 o C temperature rise above normal ambient) between switches on the same capacitor bank. A vacuum interrupter that has experienced a loss of vacuum will typically have an increased contact resistance. A module which has a higher than normal resistance will operate at a higher temperature than other VSVs. G. Resistance Testing: With the VSV in the closed position, measure the resistance across the VSV terminals. Resistance values should be less than 200 micro-ohms. Resistance measurements should be made at a current of 10 Amperes. IV. MAINTENANCE No maintenance of the VSV is required. V. VSV Power Input/Design Requirements New Standard Low Energy VSV Switch VSV switches shipped from Joslyn after November 2001 have been redesigned to operate at a minimum voltage of 80 volts. This is 22 volts lower than the previous 102 volt minimum requirement. For the 240 Vac VSVs, the minimum operating voltage is now 160 volts. Recommended voltages for normal duty must be above these values to insure proper operation with expected power system variations. The new Type VSV switch can be easily identified by a LE stamped/printed on the nameplate Consistent with this redesign, acceptable voltage drop from the control power transformer to the VSV switches during the inrush current flow of 12 amps RMS per switch pole (36 amps total for 3 poles) has been increased to 10%. This is twice the acceptable value contained in the National Electrical Code (NEC). This 10% voltage drop requires a maximum circuit resistance of 0.333 ohms at a nominal voltage of 120 volts. For a 240 volt VSV, 12 amps RMS per switch pole (36 amps total for 3 poles) the maximum allowable circuit resistance is 0.667 ohms. The inrush current level exists for approximately 24 ms (1.5 cycles).

Page 5 of 8 Also, readily available control power transformers with standard impedance can now be utilized in all installations. The need to locate and purchase new special impedance transformers has been eliminated. Low Energy VSV Installation Example (120 VAC Application) (See Table 1 for Wire Resistance) Calculation of the voltage drop must include the supply and return paths for the power to the switches. The voltage drop calculation must include the run from the transformer to the controller, controller to junction box, the junction box to each pole and any small gauge wire within the controller. This small gauge wire introduces a large drop even though the length of wire is not long. 1.) In Figure 2 the power transformer is 100 feet from the junction box or the capacitor controller. Since #8 AWG is run between the transformer and the junction box or the controller there is a total of 200 feet (hot and neutral) of #8 AWG wire. Using Table 1, this run has a resistance of.1256 ohms and a voltage drop of 4.52 volts (36 X.1256). 100 feet #8 AWG Power Transformer Control Power "Hot" Lead VSV Switch Junction Box VSV switches 8 foot 16 AWG cable Control Power Neutral Lead Cap Control Power Lead Close or Open Lead to VSV 30 feet #14 AWG Capacitor Controller Figure 2: VSV LE Example Installation 2.) The capacitor controller has 2 feet total of #18 AWG internal wiring. The resistance of this run is.0128 ohms which has a voltage drop of 0.46 volts. 3.) The VSV junction box is 30 feet from the capacitor controller. The total run is 60 feet of #14 AWG, which includes the return path, gives a circuit resistance of 0.1515 ohms and a voltage drop of 5.45 volts. 4.) The individual cable for each pole from the junction box to the VSV Switch is 8 foot, 16 AWG cable and has a total resistance of 0.06406 ohms and a voltage drop of 0.77 volts (12 x 0.06406 = 0.77V) 5.) The total voltage drop of the cabling is 4.52 + 0.46 + 5.45 + 0.77 volts for a total drop of 11.2 volts, which is acceptable, because it is less than 12.0 volts at 120 Vac, or the 10% acceptable voltage drop limit. FORMULA FOR VOLTAGE DROP FT x Resistance (from Table 1) = Wire Resistance x Switch Current = Voltage Drop Transformer to Junction Box: 200 feet of 8 AWG = 200 x (0.000628) 0.1256 Ohms x 36 amps = 4.52 Volts Controller Internal Wiring: 2 feet of 18 AWG = 2 x (0.006374) 0.0128 Ohms x 36 amps = 0.46 Volts Controller to Junction Box: 60 feet of 14 AWG = 60 x (0.002525) 0.1515 Ohms x 36 amps = 5.45 Volts Junction Box to Switch: 16 feet of 16 AWG = 16 x (0.004020) 0.06406 Ohms x 12 amps = 0.77 Volts Total Voltage Drop = 11.2 Volts

Page 6 of 8 Since the current flow to the switches is transient, the control power transformer does not have to be continuously rated for 36 amps at 120 VAC or 60 amps at 240 VAC. The transformer does need to have the capability to supply the momentary current requirement without an excessive voltage drop. Table 1 - Wire Resistance Reference AWG OHMS/FT AWG OHMS/FT #2.0001563 #12.001588 #4.0002485 #14.002525 #6.0003951 #16.004004 #8.0006282 #18.006374 #10.0009989 MANUAL REVISION NOTES Date Page Scope May 2006 2 Add note special Versavac switch part number required for ZVC 3 Add IMPORTANT note regarding rigid bus connections March 2006 3, 4, 7, 8 Added a clearance reference of 12 in second bullet of Item C point 2. In-rush rating for 240 VAC VerSaVac corrected from 60A to 36A. Corrected to 240 VAC resistance from 0.4 to.667 ohms in 2 nd paragraph of Section V. Revised 2 nd paragraph of Section VI (Appendix A) for clarification. March 2002 2 & 4 In-rush rating for 240 VAC VerSaVac corrected from 20A to 12A. November 2001 Rework Manual VerSaVac II LE version.

Page 7 of 8 Application Details for VSV Switches before November 2001 only VI. APPENDIX A This information/example is supplied only as a reference for VSV switches previously purchased and/or received before November 2001 and are currently in-service. The details outlined below are consistent with the February 2000 revision of this Instruction Manual,. VSV switches produced between January 1, 2000 and November 1, 2001 were improved to require a minimum operating voltage of only 102 volts (Prior to January 1, 2000, the minimum voltage requirement was 107V). For the 240 volt VSVs, the minimum operating voltage was also reduced to 204 volts. Recommended voltages for normal duty must be above these values to insure proper operation with expected power system variations. Consistent with the National Electrical Code (NEC), the cabling from the control power transformer to the VSV switches must be sized to allow no more than a 5% drop during the inrush current flow of 12 amps RMS per switch pole (36 amps total for 3 poles). This 5% voltage drop requires a maximum circuit resistance of 0.166 ohms at a nominal voltage of 120 volts. For a 240 volt VSV, 20 amps RMS per switch pole (60 amps total for 3 poles) the maximum allowable circuit resistance is 0.200ohms. The inrush current level exists for approximately 24 ms (1.5 cycles). In addition to the requirement of no more than a 5% voltage drop, the voltage at the cable connector pins of the switches must be at least 102 volts [204 volts for 240 volt VSV switch] during the switch operating current transient. Note: 102V and 204V are design calculation values, and can only be accurately measured with an oscilloscope and when the solenoids are energized at peak voltage to determine worst case. Example Installation Calculation (120 VAC Application) (See Table 1 for Wire Resistance) Calculation of the voltage drop must include the supply and return paths for the power to the switches. The voltage drop calculation must include the run from the transformer to the controller, controller to junction box, the junction box to each pole and any small gauge wire within the controller. This small gauge wire introduces a large drop even though the length of wire is not long. 1.) In Figure 2 the power transformer is 100 feet from the junction box or the capacitor controller. Since #4 AWG is run between the transformer and the junction box or the controller there is a total of 200 feet (hot and neutral) of #4 AWG wire. Using Table 3, this run has a resistance of.0497 ohms and a voltage drop of 1.79 volts (36 X.0497). Power Transformer 100 feet #4 AWG Control Power "Hot" Control Power Cap Control Power Lead VSV Switch Junction Box Close or Open Lead to VSV VSV switches 8 foot #16 AWG cable 30 feet #10 AWG Capacitor Controller Figure 3: Example Installation 2.) The capacitor controller has 2 feet total of #18 AWG internal wiring. The resistance of this run is.0128 ohms which has a voltage drop of 0.46 volts.

Page 8 of 8 3.) The VSV junction box is 30 feet from the capacitor controller. The total run is 60 feet of #10 AWG, which includes the return path, gives a circuit resistance of.06 ohms and a voltage drop of 2.16 volts. 4.) The individual cable for each pole from the junction box to the VSV Switch is 8 foot, 16 AWG cable and has a total resistance of 0.06406 ohms and a voltage drop of 0.77 volts (12 x 0.06406 = 0.77V) 5.) The total voltage drop of the cabling is 1.79 + 0.46 + 2.16 + 0.77 volts for a total drop of 5.2 volts, which is acceptable, because it is less than 6.0 volts at 120 Vac, or the 5% acceptable voltage drop limit. FORMULA FOR VOLTAGE DROP FT x Resistance (from Table 1) = Wire Resistance x Switch Current = Voltage Drop Transformer to Junction Box: 200 feet of 4 AWG = 200 x (0.0002485) 0.0497 Ohms x 36 amps = 1.79 Volts Controller Internal Wiring: 2 feet of 18 AWG = 2 x (0.006374) 0.0128 Ohms x 36 amps = 0.46 Volts Controller to Junction Box: 60 feet of 10 AWG = 60 x (0.0009989) 0.060 Ohms x 36 amps = 2.16 Volts Junction Box to Switch: 16 feet of 16 AWG = 16 x (0.004020) 0.06406 Ohms x 12 amps = 0.77 Volts Total Voltage Drop = 5.18 Volts Since the current flow to the switches is transient, the control power transformer does not have to be continuously rated for 36 amps at 120 VAC or 60 amps at 240 VAC. The transformer does need to have the capability to supply the momentary current requirement without excessive voltage drop. The kva rating of the transformer is not sufficient information to determine the voltage drop during the momentary current requirements of the switches. The percent impedance rating of the transformer, along with the kva nameplate, gives a good indication of this capability. It is important, however, to verify that for the 1.5 cycle operating current that excessive voltage drop does not occur. Table 2 lists various kva sizes of transformers and the maximum percent impedance allowable for proper operation. Table 3 is a listing of transformers that have been utilized in VSV installations at 120 VAC. Table 3 is not intended to be a comprehensive list but is intended as a list of qualified transformers for users who do not wish to verify the percent impedance requirements of the control power transformer utilized. Table 2: Maximum Transformer Impedance ** kva Rating Maximum % Impedance (120VAC) Maximum % Impedance (240VAC) 0.5 kva 0.5% 1.0% 1.0 kva 1.2% 2.4% 3.0 kva 2.5% 5.0% Table 3: 120 VAC Transformers and Suppliers ** Manufacturer Phone Number Type Eastern Electric (602) 252-2326 CBT.5 kva or 1kVA Mid Central (608) 835-3513 SS-72-120SP, SP indicates cap switch Instrument Transformer, Inc. (ITI) (727) 442-0414 PT5-110-722F, CPT5-95-5 ** NOTE: Tables 2 and 3 only apply to VSV switches received before November 2001.