Application of a thyristor-controlled series reactor to reduce arc furnace flicker

Similar documents
Static Synchronous Compensator (STATCOM) for the improvement of the Electrical System performance with Non Linear load 1

CHAPTER 4 POWER QUALITY AND VAR COMPENSATION IN DISTRIBUTION SYSTEMS

Stability Enhancement for Transmission Lines using Static Synchronous Series Compensator

INVESTIGATION OF HARMONIC DETECTION TECHNIQUES FOR SHUNT ACTIVE POWER FILTER

Investigation of D-Statcom Operation in Electric Distribution System

Journal of Electrical and Electronic Engineering

Power Quality enhancement of a distribution line with DSTATCOM

PUBLICATIONS OF PROBLEMS & APPLICATION IN ENGINEERING RESEARCH - PAPER CSEA2012 ISSN: ; e-issn:

Multi-Pulse Voltage Source Converter Statcom For Voltage Flicker Mitigation

Increasing Dynamic Stability of the Network Using Unified Power Flow Controller (UPFC)

Analysis and modeling of thyristor controlled series capacitor for the reduction of voltage sag Manisha Chadar

A Review on Simulation and Implementation of Thyristor controlled reactor and Shunt Hybrid Power Filter

Chapter -3 ANALYSIS OF HVDC SYSTEM MODEL. Basically the HVDC transmission consists in the basic case of two

The Impact of Connecting Distributed Generation to the Distribution System E. V. Mgaya, Z. Müller

CHAPTER 5 POWER QUALITY IMPROVEMENT BY USING POWER ACTIVE FILTERS

Improving the Transient and Dynamic stability of the Network by Unified Power Flow Controller (UPFC)

Transient stability improvement by using shunt FACT device (STATCOM) with Reference Voltage Compensation (RVC) control scheme

Address for Correspondence

2020 P a g e. Figure.2: Line diagram of series active power filter.

SHUNT ACTIVE POWER FILTER

SIMULATION OF D-Q CONTROL SYSTEM FOR A UNIFIED POWER FLOW CONTROLLER

Power Quality Improvement of Distribution Network for Non-Linear Loads using Inductive Active Filtering Method Suresh Reddy D 1 Chidananda G Yajaman 2

I. INTRODUCTION IJSRST Volume 3 Issue 2 Print ISSN: Online ISSN: X

CHAPTER 6 UNIT VECTOR GENERATION FOR DETECTING VOLTAGE ANGLE

Harmonics Elimination Using Shunt Active Filter

II. RESEARCH METHODOLOGY

POWER QUALITY ENHANCEMENT IN ARC FURNACE ENVIRONMENT Nupur Laxman Mali,

Impact of Thyristor Controlled Series Capacitor on Voltage Profile of Transmission Lines using PSAT

IJSRD - International Journal for Scientific Research & Development Vol. 3, Issue 03, 2015 ISSN (online):

ECE 422/522 Power System Operations & Planning/Power Systems Analysis II 5 - Reactive Power and Voltage Control

Long lasting transients in power filter circuits

Literature Review for Shunt Active Power Filters

I. INTRODUCTION. Keywords:- FACTS, TCSC, TCPAR,UPFC,ORPD

LARGE-SCALE WIND POWER INTEGRATION, VOLTAGE STABILITY LIMITS AND MODAL ANALYSIS

Digital Simulation of Thyristor Controlled Interphase Power Control Technology (TC- IPC) to limit the fault currents

INSTANTANEOUS POWER CONTROL OF D-STATCOM FOR ENHANCEMENT OF THE STEADY-STATE PERFORMANCE

ELEMENTS OF FACTS CONTROLLERS

Modeling of Statcom. P.M. Sarma and Dr. S.V. Jaya Ram Kumar. Department of Electrical & Electronics Engineering GRIET, Hyderabad, India

Analysis of Single and Multi Resonance Point in Reactance Characteristics of TCSC Device

The unified power quality conditioner: the integration of series and shunt-active filters

Improvement of Power System Distribution Quality Due to Using Dc-Converter Loads and Electric Arc Furnaces. H.A. Khalik, M. A. Aziz, and E. Farouk.

Power Conditioning Equipment for Improvement of Power Quality in Distribution Systems M. Weinhold R. Zurowski T. Mangold L. Voss

University of Jordan School of Engineering Electrical Engineering Department. EE 219 Electrical Circuits Lab

CHAPTER 3 COMBINED MULTIPULSE MULTILEVEL INVERTER BASED STATCOM

Harmonics Reduction in a Wind Energy Conversion System with a Permanent Magnet Synchronous Generator

SIMULATION OF STATCOM FOR VOLTAGE QUALITY IMPROVEMENT IN POWER SYSTEM

Chapter 10: Compensation of Power Transmission Systems

Voltage and Current Waveforms Enhancement using Harmonic Filters

Application of SVCs to Satisfy Reactive Power Needs of Power Systems

Assessment of Saturable Reactor Replacement Options

Analysis of Power System Oscillation Damping & Voltage Stability Improvement Using SSSC in A Multimachine System

OPTIMAL DESIGN OF A SINGLE TUNED PASSIVE FILTER TO MITIGATE HARMONICS IN POWER FREQUENCY

Line Impedance Estimation Using SCADA Data

METHOD TO DETERMINE CONTRIBUTION OF THE CUSTOMER AND THE POWER SYSTEM TO THE HARMONIC DISTURBANCE

Transients under energizing multiple power filter circuits

Lab 1. Objectives. Single Line Diagram. Methodology. Observations. Jon Jawnsy Yu 26 October 2009

Hours / 100 Marks Seat No.

ATYPICAL high-power gate-turn-off (GTO) currentsource

A Static Synchronous Compensator for Reactive Power Compensation under Distorted Mains Voltage Conditions

Design of SVPWM Based Inverter for Mitigation of Harmonics in Power System

Power Quality Analysis of Non- Linear Loads for Industrial Power System

SRI VIDYA COLLEGE OF ENGG AND TECH

Power System Stability Enhancement Using Static Synchronous Series Compensator (SSSC)

Control Of Shunt Active Filter Based On Instantaneous Power Theory

Design and Simulation of Passive Filter

Understanding the Design and Control of VSC-Based HVDC System with Shunt Passive Filters

Improving Passive Filter Compensation Performance With Active Techniques

How Full-Converter Wind Turbine Generators Satisfy Interconnection Requirements

CHAPTER 4 HARMONICS AND POWER FACTOR

ASPECTS OF REAL-TIME DIGITAL SIMULATIONS OF ELECTRICAL NETWORKS

Delayed Current Zero Crossing Phenomena during Switching of Shunt-Compensated Lines

Analysis of Advanced Techniques to Eliminate Harmonics in AC Drives

Voltage-Current and Harmonic Characteristic Analysis of Different FC-TCR Based SVC

Optimum dimensioning of a flicker compensator in three-phase electric-arc furnaces supply systems

Arvind Pahade and Nitin Saxena Department of Electrical Engineering, Jabalpur Engineering College, Jabalpur, (MP), India

Improving the Power Factor Correction in the Presence of Harmonics by Reducing the Effect of Resonance and Harmonics

Var Control. Adding a transformer and transformer voltage regulation. engineers loadflow program. The control system engineers loadflow.

MODELLING & SIMULATION OF ACTIVE SHUNT FILTER FOR COMPENSATION OF SYSTEM HARMONICS

Brief Study on TSCS, SSSC, SVC Facts Device

COMPARATIVE PERFORMANCE OF SMART WIRES SMARTVALVE WITH EHV SERIES CAPACITOR: IMPLICATIONS FOR SUB-SYNCHRONOUS RESONANCE (SSR)

Analysis of Effect on Transient Stability of Interconnected Power System by Introduction of HVDC Link.

2. Current interruption transients

[Mahagaonkar*, 4.(8): August, 2015] ISSN: (I2OR), Publication Impact Factor: 3.785

Implementation of SRF based Multilevel Shunt Active Filter for Harmonic Control

Improve Power Factor and Reduce the Harmonics Distortion of the System

Considerations for the Application of Thyristor Controlled Series Capacitors to Radial Power Distribution Circuits

Implementing Re-Active Power Compensation Technique in Long Transmission System (750 Km) By Using Shunt Facts Control Device with Mat Lab Simlink Tool

Harmonics and Their Impact on Power Quality. Wayne Walcott Application Engineering Manager June, 2017

WILEY CONTROL OF POWER INVERTERS IN RENEWABLE ENERGY AND SMART GRID INTEGRATION. Qing-Chang Zhong. Tomas Hornik IEEE PRESS

FGJTCFWP"KPUVKVWVG"QH"VGEJPQNQI[" FGRCTVOGPV"QH"GNGEVTKECN"GPIKPGGTKPI" VGG"246"JKIJ"XQNVCIG"GPIKPGGTKPI

IMPORTANCE OF VSC IN HVDC

A Fuzzy Controlled PWM Current Source Inverter for Wind Energy Conversion System

Field Programmable Gate Array-Based Pulse-Width Modulation for Single Phase Active Power Filter

INVESTIGATION INTO THE HARMONIC BEHAVIOUR OF MULTIPULSE CONVERTER SYSTEMS IN AN ALUMINIUM SMELTER

Voltage Source Converter Modelling

Current Rebuilding Concept Applied to Boost CCM for PF Correction

ISSN: ISO 9001:2008 Certified International Journal of Engineering Science and Innovative Technology (IJESIT) Volume 2, Issue 3, May 2013

HARMONIC distortion complicates the computation of. The Optimal Passive Filters to Minimize Voltage Harmonic Distortion at a Load Bus

shunt (parallel series

Course ELEC Introduction to electric power and energy systems. Additional exercises with answers December reactive power compensation

Transcription:

ELEKTROTEHNIŠKI VESTNIK 78(3): 112-117, 2011 ENGLISH EDITION Application of a thyristor-controlled series reactor to reduce arc furnace flicker Ljubiša Spasojević, Boštjan Blažič, Igor Papič University of Ljubljana, Faculty of Electrical Engineering, Tržaška 25, Ljubljana E-pošta: ljubisa.spasojevic@fe.uni-lj.si Abstract. This paper presents the basic principles of a thyristor-controlled series reactor for the reduction of arc furnace flicker which negatively impacts a transmission network. The developed models of a transmission network and an arc furnace with a sinusoidal variation of arc length were used for simulations and calculations. The concept of flicker compensation using a thyristor-controlled series reactor is presented with simulation examples. These simulations showed that the integration of a thyristor-controlled series reactor can successfully reduce flicker levels in the transmission network. Keywords: power quality, flicker, arc furnace, thyristor-controlled reactor 1 INTRODUCTION Electricity is a commodity like any other product and it must satisfy quality standards. It is necessary to maintain a certain level of voltage quality in a network to ensure the proper operation of connected equipment. The system operator and users of the system are responsible for the voltage quality. Each network user (a consumer or producer of electricity) must limit the negative impact of their own equipment on network voltage quality (due to the injection of higher harmonics, consumption of reactive power, flicker, unsymmetrical load ) to a pre-agreed level. A violation of power quality involves a violation of basic steady-state voltage parameters and a deformation of waveforms. Arc furnaces are one of the main sources of flicker in transmission networks. 2 SIMULATION MODEL AND THE OPERATING PRINCIPLE OF A THYRISTOR-CONTROLLED SERIES REACTOR A thyristor-controlled series reactor improves the stability of the high voltage arc of an arc furnace and reduces flicker. The stabilises the arc by dynamically controlling the series reactor installed between the transformer and the arc furnace. The controlled reactor acts as a dynamic spring [1, 2]. The technology takes advantage of the rapid switching of thyristors and advanced predictive computer controls. Figure 1 shows a single line scheme of an arc furnace installation with a thyristor-controlled series reactor connected to a high voltage grid. The basic operating principle is based on diverting the current from the series reactor (L 1 ) to the parallel reactor (L 2 ). The parallel reactor has a smaller inductive resistance and is switched in and out of the electrical circuit to control the furnace current. The series reactor has a large fixed inductive resistance and is connected on the line side. When the senses an overcurrent, the thyristor switch opens and current flows through path P 1. The fast insertion of reactor L 1 limits the overcurrent swing. High voltage grid I f P 1 Reactor L 1 L c R 1 110 / 35 kv R c L f R f 110 kv P 2 35 / 0.4 kv Arc Thyristor switches Figure 1. Single-line scheme of the plant network used in the simulations S k R 2 L 2 SPLC Received 17 February 2011 Accepted 14 March 2011

APPLICATION OF A THYRISTOR-CONTROLLED SERIES REACTOR TO REDUCE ARC FURNACE FLICKER 113 When the senses stable arcing, the switch closes, connecting the furnace through reactor L 2 to the main substation transformer for high power operation as shown by path P 2 [1, 2, 3]. Figure 1 shows part of the plant network which is used in the simulations. The network model involves a high-voltage network equivalent, a 110/35 kv transformer substation, a 35/0.4 kv furnace transformer, reactors, thyristor switches and impedance of the cable between the substation and furnace transformer. The values of these parameters are shown in Table 1. S k represents the short-circuit power at the 110 kv connection point. Short circuit voltages (u k ) for different tap positions of the furnace transformer are shown in Table 2. An equivalent model of the plant network was designed using PSCAD software [5, 6]. High voltage level U grid [kv] 110 Short circuit power S k'' [MVA] 3750 Short circuitvoltage u k_110/35 [%] 7.69 Reactor inductance L 1[H] 0.02 Cable inductance L c [H] 0.0002 Furnace cable inductance L f [H] 0.00035 Parallel inductance L 2[H] 0.001 Parallel resistance R 2[Ω] 0.015 Reactor resistance R [Ω] 0.3 Cable resistance R c [Ω] 0.062 Furnace cable resistance R f [Ω] 0.00035 Table 1. Values of the parameters of the model shown in Figure 1 Tap position Voltage on low voltage level of transformer [V] u k [%] 7 343.1 4.19 8 363.3 3.96 9 383.2 3.75 10 4.038 3.54 11 425.1 3.33 12 444.9 3.14 13 464.6 2.94 14 481.7 2.78 15 500 2.61 Table 2. Values of u k for different tap positions of the furnace transformer 2.1 Description of the arc furnace model A nonlinear model of the arc furnace and flicker meter are designed in the simulation programme. The nonlinear voltage-current (V-I) characteristics of the arc furnace can be described by the following equation (1) [5, 6]: = = + (1) where U a and I a are the voltage and current of the arc, U at is the minimum arc voltage to which the voltage drops when the current increases and C and D are constants which determine the difference between increasing and decreasing current paths of the V-I characteristic [5]. To simulate variation in the arc length, a stochastic or a deterministic approach can be used. The stochastic approach provides random variations of the arc length, which is closer to reality, but the mathematical treatment in this case is more complex and requires long simulation times. Under the deterministic approach, the arc length varies by a sine function at the corresponding selected frequency. This approach does not fully describe the operation of the electric arc furnace but allows a much easier simulation with shorter simulation times and without additional statistical treatment of the results. The deterministic model provides higher flicker levels at a certain operating point of the arc furnace compared to the stochastic model. For this reason, the deterministic variation of the arc length was chosen in our simulations. The following formula describes the deterministic variation of the arc length: = sin (2) where D 1 is determined by the amplitude of the sine curve and l 0 is constant. When the length of the arc equals l 0, the furnace model does not produce harmonics. Since human eyes are most sensitive to flicker at voltage fluctuations at around 8.8 Hz, the frequency 9 Hz for the frequency ω of arc fluctuations in (2) was selected [5, 6]. 2.2 Description of the control algorithm The control algorithm is based on the continuous monitoring of the reactive current of the furnace. The block diagram of the control algorithm is shown in Figure 2. The current between the network and the furnace is measured. The reactive, i.e.q-component, of the current is proportional to the reactive power of the furnace. Since higher order harmonics are present, the q-component of the current is not a constant value. Using a Fast Fourier Transform (FFT), the control algorithm extracts the low-frequency variations of the reactive current which are the source of flicker. The 50 Hz FFT filters harmonic components out of the reactive current component and the 9 Hz FFT removes the fundamental frequency reactive current component. The outputs of these two filters are subtracted. Block Table 1 converts the difference of these two signals into reactance X. When the value is minimal the output signal of the block table 1 is equal to 6.28 Ω which is the maximum value of both reactances. When the value is maximal, the output signal of block Table 1 equals 0.30 Ω which is the minimum value of both reactances. Next, this reactance value is converted to susceptance B.

114 SPASOJEVIĆ, BLAŽIČ, PAPIČ Susceptance B represents the equivalent susceptance of both reactors, as shown in Figure 2b. If L1 If L2 3 f / d q Igd fft (9 Hz) d c X 1 X B lo ck Table 1 B B L 1 B L 2 If L3 Ig q fft (5 0 Hz) dc a) B 2 R 2 L 2 pu B lock Table 2 α α c α 1 I 2 B I l1 b) I 1 R 1 L 1 B 1 Figure 3. Waveforms of the active and reactive power of a furnace without a thyristor-controlled reactor (P fur, Q fur ), tap position 13 Figure 2. Block diagram of the control algorithm The value of susceptance B 1 is constant and equals 0.159 S, while the value of susceptance B 2 is controlled with the thyristors firing angle. Resistances R 1 and R 2 are relatively small and are not considered in the control scheme. Angle α is a nonlinear function of susceptance B 2 and is obtained from block Table 2 [5]. Because of the phase displacement between the 35 kv voltage and the current through thyristors there is also a correction angle α c. Finally, α 1 represents the angle value for thyristors triggering. The correction angle value equals 53. This control algorithm can be used for the selected frequency of arc length variation. 3 SIMULATION OF OPERATION In the experimental part of this work, three simulations were performed. With the first simulation the operation of the furnace without a reactor was shown. In the second simulation a thyristor-controlled series reactor with coarse regulation was used. The third simulation was performed with a thyristor-controlled series reactor with full regulation. The results obtained from the simulations are compared at the end. The data obtained from simulation of the arc furnace operation without compensation are used as reference values. 3.1 Simulation without a reactor A simulation of the furnace operation without a reactor, i.e. operation of the furnace directly connected to a high voltage grid, was carried out. Waveforms of the signals are shown in Figures 3 and 4. Numeric values of the active and reactive power and flicker levels are listed in Table 3. High- and low-frequency oscillations of voltage, current, active and reactive power are also evident from Figures 3 and 4. As no series reactor is used, the values of active and reactive power of the furnace are equal to the values of the active and reactive power of the network. The flicker level on the 110 kv voltage level equals 1.03. Figure 4. Waveforms of the voltage at the 35 kv level and current of the network without a thyristor-controlled reactor, tap position 13 A simulation at different tap positions of the furnace transformer was performed. The results for different tap positions of the furnace transformer are shown in Table 3. In order to compare the results, all the simulations must be performed at the same operating point of the furnace. Tap position 15 14 13 Pst_35kV 9.51 8.91 8.36 Pst_110kV 1.21 1.15 1.10 Pfur [MW] 31.15 29.74 28.28 Qfur [MVAr] 40.71 37.37 34.20 Table 3. Numeric values of parameters for different tap positions of a furnace transformer without a thyristorcontrolled reactor (mean values of P and Q) 3.2 Simulation with coarse regulation In this simulation of the furnace operation a thyristorcontrolled reactor was included, but the control algorithm only worked in two conditions (on with α=90, and off with α=180 ), and hence the term coarse regulation. In the on condition of the control algorithm, a maximum value of current across the thyristors is reached. In the off condition, the control algorithm does not trigger the thyristors. The control

APPLICATION OF A THYRISTOR-CONTROLLED SERIES REACTOR TO REDUCE ARC FURNACE FLICKER 115 algorithm was switched on 5 seconds after the simulation started. During the first 5 seconds, the series operates as a damping reactor. Figure 5 shows the waveforms of the active and reactive power. Significant oscillations of the active and reactive power are present. This is a consequence of the coarse regulation. The selected tap position of the furnace transformer was 16. Figure 7. Waveforms of the voltage at the 35 kv level and network current with coarse regulation, before and after starting the control algorithm; tap position 16 Figure 5. Waveforms of the active and reactive power of the furnace (P fur, Q fur ) and active and reactive power of the network (P grid, Q grid ) with coarse regulation before and after the start of the control algorithm; tap position 16 The control algorithm in this simulation is based on continuous monitoring of the value of an error signal. The reference value for comparison is 0. When the control algorithm of the senses an error signal bigger than the reference value, the switch opens and current flows through inductance L 1. When the senses an error signal less than the reference value, the switch closes and connects the furnace to the network through L 2 which is parallel to inductance L 1. As a result, there is a large and continuous oscillation of active and reactive power. The flicker at the 35 kv and 110 kv levels can be seen in Figure 6. It should be noted that the flicker meter model in PSCAD does not calculate flicker in the first 2 seconds of the simulation. In Figure 7 the amplitudes of the voltage and current on the 35 kv level before and after starting the control algorithm are shown. Table 4 shows the mean values of the furnace parameters used in this simulation and obtained flicker values. Tap 16 Pst_35kV 4.79 Pst_110kV 0.56 Pfur [MW] 28.99 Qfur [MVAr] 34.80 Pgrid [MW] 29.24 Qgrid [MVAr] 39.62 Table 4. Numeric values of furnace parameters with coarse regulation, tap position 16 (mean values of P and Q) 3.3 Simulation with full regulation A simulation of the furnace with a thyristor-controlled reactor with full regulation was performed. The value of angle α varies between 90 and 180 [7]. Because of the phase displacement between the voltage and current through the thyristors, the maximum current through the thyristor is reached at α=90. At α=90 the current of the furnace through the thyristor is maximal, while at α=180 the current of the furnace through the thyristor is zero. In the first 5 seconds of the simulation the control algorithm did not operate. During this time, the operates as a damping reactor. After 5 seconds, the control algorithm starts calculating angle α. In Figures 8, 9 and 10 waveforms of the active and reactive power, current and flicker before and after the start of the control algorithm are shown. Figure 6. Flicker waveforms at the 110kV and 35kV levels with coarse regulation of the ; before and after starting the control algorithm

116 SPASOJEVIĆ, BLAŽIČ, PAPIČ Figure 8. Waveforms of the active and reactive power of the furnace (P fur, Q fur ) and the active and reactive power of the network (P grid, Q grid ), before and after the start of the control algorithm, tap position 16 U (kv) I (ka) Figure 9. Waveforms of the voltage at the 35 kv level and current of grid before and after the start of the control algorithm, tap position 16 4 ANALYSIS OF THE SIMULATION RESULTS The fluctuations of reactive power from the grid in Figure 8 are lower after the start of the control algorithm, whereas the fluctuations of active power are higher. Since the periodically bypasses inductance L 1, connecting the furnace to the network also through inductance L 2 as a result, there is increased reactive energy consumption. In order to see all of the advantages of a thyristorcontrolled reactor application, a comparison with some other flicker reduction process must be made. For this reason, in the first 5 seconds the was operating with disabled thyristors. During this time, the operates as a damping reactor. The numeric values for both types of operation are listed in Table 6 where also the values for operation without the series are given. A significant reduction of flicker levels can be noticed after the start of the control algorithm operation. Because of the inductance the reactive power losses are larger than those without the reactor. Active power losses also exist, but they are much smaller. Table 6 shows that the operating point of the furnace with a thyristor-controlled reactor, i.e. P = 27.29 MW and Q = 30.82 MVAr, is close to the values of the operating point of the furnace without a thyristorcontrolled reactor at the 13 th tap position. Tap Position 16 16 13 Period First 5 seconds After 5 seconds Without a Pst_35kV 7.11 1.83 8.36 Pst_110kV 0.92 0.16 1.10 Pfur [MW] 23.31 27.29 28.28 Qfur [MVAr] 23.16 30.82 34.20 Pgrid [MW] 23.80 27.55 28.28 Qgrid [MVAr] 33.37 37.80 34.20 Table 6. Numeric values of furnace parameters in the first 5 seconds, after 5 seconds of simulation with a and without a (mean values of P and Q) Figure 10. Flicker level at the 110 kv and 35 kv levels before and after the start of the control algorithm, tap position 16 The simulation was performed at the 16th tap position of the transformer. Numeric values of this simulation are shown in Table 5. Tap Position 16 Pst_35kV 1.83 Pst_110kV 0.16 Pfur 27.29 Qfur 30.82 Pgrid 27.55 Qgrid 37.80 Table 5. Numeric values of parameters for the 16th tap position of a transformer with a thyristor-controlled reactor (mean values of P and Q) Regulation Tap Position Without Coarse regulation With a 13 16 16 Pst_35kV 8.36 4.79 1.83 Pst_110kV 1.10 0.56 0.16 Pfur [MW] 28.28 28.99 27.29 Qfur [MVAr] 34.20 34.80 30.82 Table 7. Numeric values of furnace parameters without, with coarse regulation and with full regulation According to the active power of the furnace it can be seen that the operating point of the furnace with coarse regulation is close to the operating point of the furnace without a thyristor-controlled reactor at the 13 th tap position, as shown in Table 7.

APPLICATION OF A THYRISTOR-CONTROLLED SERIES REACTOR TO REDUCE ARC FURNACE FLICKER 117 The data from Table 7are graphically presented in Figure11. For a similar level of active furnace power the flicker level is smaller when using the thyristorcontrolled reactor. The flicker level with the thyristorcontrolled reactor is approximately 7 times smaller than the flicker level without a thyristor-controlled reactor. It may be concluded that using a thyristor-controlled reactor at the source of flicker significantly reduces flicker levels in the high voltage network. Flicker level 1,2 1 0,8 0,6 0,4 0,2 0 28.28 MW 28.99 MW 27.29 MW Figure 11. Graphic representation of the flicker level for approximately the same active furnace power 5 CONCLUSION The paper shows that using a thyristor-controlled series reactor is an effective method for reducing flicker levels in a network. The comparison of a thyristor-controlled reactor with compensation using passive inductors showed that the thyristor-controlled reactor has advantages. It reduces the fluctuations of reactive power and enables the furnace s stable operation. The limitations onthe furnace s maximum power are also smaller than the limitations with passive compensation (for the same tap position). While the use of a thyristorcontrolled reactor is more expensive, it is also a more efficient solution for flicker problems. ACKNOWLEDGMENT without coarse with Operation part financed by the European Union, European Social Fund. Operation implemented in the framework of the Operational Programme for Human Resources Development for the Period 2007-2013, Priority axis 1: Promoting entrepreneurship and adaptability, Main type of activity 1.1.: Experts and researchers for competitive enterprises. [2] T. Gerritsen, T. Ma, M. Sedighy, J. Janez, F. Stober, N.Voermann, J. R. Frias, SPLC A Power Supply for Smelting Furnaces, Santo Domingo, Dominican Republic. [3] United State Patent, patent no. US 6.603.795 B2, Date of patent 05.08.2003 [4] www.pscad.com [5] I. Papič, Analiza vpliva obratovanja porabnikov na ZGK železarna Ravne in ZGK železarna Štore na kakovost napetosti v prenosnem omrežju, Ljubljana, February 2005, pp. 75-96 [6] I. Papič, B. Blažič, Kompenzacija flikerja s statičnim kompenzatorjem, 7. Konferenca slovenskih elektroenergetikov, stran, Velenje, 2005. Ljubiša Spasojević received a BSc degree in electrical engineering from the University of Novi Sad, Serbia, in 2008. He is currently a researcher at the Faculty of Electrical Engineering, Ljubljana. His research interests include power quality in large industrial networks. Boštjan Blažič received BSc, MSc and PhD degrees, all in electrical engineering, from the University of Ljubljana, Slovenia, in 2000, 2003 and 2005, respectively. He is presently an assistant at the Faculty of Electrical Engineering, Ljubljana. His research interests encompass power quality, distributed generation, mathematical analysis and control of power converters. Igor Papič received BSc, MSc and PhD degrees, all in electrical engineering, from the University of Ljubljana, Slovenia, in 1992, 1995 and 1998, respectively. From 1994 to 1996 he was employed by the Siemens Power Transmission and Distribution Group in Erlangen, Germany. He is currently a professor at the Faculty of Electrical Engineering in Ljubljana. In 2001 he was a visiting professor at the University of Manitoba in Winnipeg, Canada. His research interests include power conditioners, FACTS devices, power quality and active distribution networks. LITERATURE [1] J. Mulcahy, T. L. Ma, The SPLC A New Technology for Arc Stabilization and Flicker Reduction on AC Electric Arc Furnaces, Toronto, Ontario, Canada IEEE Guide for Application of Shunt Power Capacitors, IEEE Standard 1036-1992, 1992.