Estimation of Re-striking Transient Over voltages in a 132KV Gas insulated Substation

Similar documents
Estimation of Re-striking Transient Overvoltages in a 3-Phase 132KV Gas insulated Substation

Calculation of Transients at Different Distances in a Single Phase 220KV Gas insulated Substation

Calculation of Transient Overvoltages by using EMTP software in a 2-Phase 132KV GIS

Modeling and Analysis of a 3-Phase 132kv Gas Insulated Substation

GIS Disconnector Switching Operation VFTO Study

VFTO STUDIES DUO TO THE SWITCHING OPERATION IN GIS 132KV SUBSTATION AND EFFECTIVE FACTORS IN REDUCING THESE OVER VOLTAGES

Tab 2 Voltage Stresses Switching Transients

SUPPRESSION METHODS FOR VERY FAST TRANSIENT OVER- VOLTAGES ON EQUIPMENT OF GIS

Research Article Survey of Induced Voltage and Current Phenomena in GIS Substation

A Simple Simulation Model for Analyzing Very Fast Transient Overvoltage in Gas Insulated Switchgear

The various factors influencing the VFTO levels in 500kV and. 750kV GIS have been discussed by developing the simulink models which

Effect of High Frequency Cable Attenuation on Lightning-Induced Overvoltages at Transformers

Power Frequency Withstand Voltage On-site testing of 400 kv GIS

Modelling of Sf6 Circuit Breaker Arc Quenching Phenomena In Pscad

Research Article A Simplified High Frequency Model of Interleaved Transformer Winding

Effect of Shielded Distribution Cables on Lightning-Induced Overvoltages in a Distribution System

Although shunt capacitors

A Special Ferro-resonance Phenomena on 3-phase 66kV VT-generation of 20Hz zero sequence continuous voltage

Generation of Sub-nanosecond Pulses

CHAPTER 2. v-t CHARACTERISTICS FOR STANDARD IMPULSE VOLTAGES

DIFFERENCE BETWEEN SWITCHING OF MOTORS & GENERATORS WITH VACUUM TECHNOLOGY

High voltage engineering

10. DISTURBANCE VOLTAGE WITHSTAND CAPABILITY

ANALYSIS OF VERY FAST TRANSIENT OVER VOLTAGES IN GAS INSULATED SUBSTATION

Electric Stresses on Surge Arrester Insulation under Standard and

FGJTCFWP"KPUVKVWVG"QH"VGEJPQNQI[" FGRCTVOGPV"QH"GNGEVTKECN"GPIKPGGTKPI" VGG"246"JKIJ"XQNVCIG"GPIKPGGTKPI

A Study on Ferroresonance Mitigation Techniques for Power Transformer

Electromagnetic Disturbances of the Secondary Circuits in Gas Insulated Substation due to Disconnector Switching

Chapter 1. Overvoltage Surges and their Effects

Switching Induced Transients:

Analysis of MOV Surge Arrester Models by using Alternative Transient Program ATP/EMTP

UNIT 4 PRINCIPLES OF CIRCUIT BREAKERS SVCET

AORC Technical meeting 2014

GIS Instrument Transformers: EMC Conformity Tests for a Reliable Operation in an Upgraded Substation

TECHNICAL REPORT. Insulation co-ordination

EE 1402 HIGH VOLTAGE ENGINEERING

ROEVER ENGINEERING COLLEGE ELAMBALUR, PERAMBALUR DEPARTMENT OF ELECTRICAL & ELECTRONICS ENGINEERING

Analysis of Very Fast Transient over Voltages of Transformer in Gas Insulated Substation (GIS) using Wavelet Technique

The University of New South Wales. School of Electrical Engineering and Telecommunications. High Voltage Systems ELEC9712. Appendix Partial Discharge

DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING QUESTION BANK SUBJECT CODE & NAME : EE 1402 HIGH VOLTAGE ENGINEERING UNIT I

Sources of transient electromagnetic disturbance in medium voltage switchgear

Adi Mulawarman, P.E Xcel Energy Minneapolis, MN. Pratap G. Mysore, P.E Pratap Consulting Services, LLC Plymouth, MN

Lightning performance of a HV/MV substation

Investigation into Transient SFO, FFO, VFTO Overvoltage Characteristics for Typical Gas Insulated Substations

DEPARTMENT OF EEE QUESTION BANK

Prevention of transformers damage in HPP with double generating units connected to GIS via HV cables

Ferroresonance Experience in UK: Simulations and Measurements

Abstract. 1 Introduction

POWER SYSTEM TRANSIENTS - Switching Overvoltages in Power Systems - Juan A. Martinez-Velasco, Jacinto Martin-Arnedo

INTERNATIONAL JOURNAL OF ENGINEERING SCIENCES & RESEARCH TECHNOLOGY. Approach for Fault Detection in GIS.

Power Quality and Reliablity Centre

FERRORESONANCE SIMULATION STUDIES USING EMTP

Capacitive Voltage Substations Ferroresonance Prevention Using Power Electronic Devices

Investigation of Inter-turn Fault in Transformer Winding under Impulse Excitation

Coherence and time-frequency analysis of impulse voltage and current measurements

CONTENTS. 1. Introduction Generating Stations 9 40

Effect of Shielded Distribution Cable on Very Fast Transients

Lightning transient analysis in wind turbine blades

Switching and Fault Transient Analysis of 765 kv Transmission Systems

Condition Assessment of High Voltage Insulation in Power System Equipment. R.E. James and Q. Su. The Institution of Engineering and Technology

A TECHNICAL REVIEW ON CAPACITOR BANK SWITCHING WITH VACUUM CIRCUIT BREAKERS

Delayed Current Zero Crossing Phenomena during Switching of Shunt-Compensated Lines

Simulation Model of Partial Discharge in Power Equipment

In power system, transients have bad impact on its

A MODEL TO SIMULATE EM SWITCHING TRANSIENTS IN ELECTRIC POWER DISTRIBUTION SUBSTATIONS

ANALYSIS OF A FLASHOVER OPERATION ON TWO 138KV TRANSMISSION LINES

International Journal of Advance Research in Engineering, Science & Technology

2. Current interruption transients

Relay Protection of EHV Shunt Reactors Based on the Traveling Wave Principle

DC current interruption tests with HV mechanical DC circuit breaker

Alternative Coupling Method for Immunity Testing of Power Grid Protection Equipment

PREVENTING FLASHOVER NEAR A SUBSTATION BY INSTALLING LINE SURGE ARRESTERS

A3-308 HIGH SPEED GROUNDING SWITCH FOR EXTRA-HIGH VOLTAGE LINES

How to Conduct the Lightning Impulse Withstand Test of. Three Gorges Right Bank Substation 550kV GIS

THE PROPAGATION OF PARTIAL DISCHARGE PULSES IN A HIGH VOLTAGE CABLE

HIGH VOLTAGE ENGINEERING(FEEE6402) LECTURER-24

Simulation of characteristics of impulse voltage generator for testing of equipment using MATLAB Simulink

When surge arres t ers are installed close to a power transformer, overvoltage TRANSFORMER IN GRID ABSTRACT KEYWORDS

Basics of Partial Discharge. Prepared for 2015 Phenix RSM Meeting January 2015

Neutral Reactor Optimization in order to Reduce Arc Extinction Time during Three-Phase Tripping

Transmission Line Transient Overvoltages (Travelling Waves on Power Systems)

Effects of Phase-Shifting Transformers, and Synchronous Condensers on Breaker Transient Recovery Voltages

Prediction of Transient Transfer Functions at Cable-Transformer Interfaces

ANALYSIS OF VOLTAGE TRANSIENTS IN A MEDIUM VOLTAGE SYSTEM

Simulation Study of Voltage Surge Distribution in a Transformer Winding

A Guide to the DC Decay of Fault Current and X/R Ratios

IJSRD - International Journal for Scientific Research & Development Vol. 2, Issue 04, 2014 ISSN (online):

Lumped Network Model of a Resistive Type High T c fault current limiter for transient investigations

Over-voltage Trigger Device for Marx Generators

ANALYSIS OF FAULTS INTERRUPTED BY GENERATOR

Comparison of switching surges and basic lightning impulse surges at transformer in MV cable grids

SAFETY ASPECTS AND NOVEL TECHNICAL SOLUTIONS FOR EARTH FAULT MANAGEMENT IN MV ELECTRICITY DISTRIBUTION NETWORKS

Lightning overvoltage and protection of power substations

Weidong Zhang, May.9, 2016 Development of Pre-Insertion Resistor for an 800kV GIS Circuit Breaker. ABB Group May 11, 2016 Slide 1

Surge Protection for Ladle Melt Furnaces

SWITCHING OVERVOLTAGES IN A 400-KV CABLE SYSTEM

Testing 320 kv HVDC XLPE Cable System

Advancements in online partial discharge monitoring and assessment of MV through EHV Substation assets

VOLTAGE OSCILLATION TRANSIENTS CAUSED BY CAPACITOR BANKING ENERGIZING FOR POWER FACTOR CORRECTION IN THE POWER SYSTEM

Fatima Michael college of Engineering and Technology

Transcription:

Estimation of Re-striking Transient Over voltages in a 132KV Gas insulated Substation M. Kondalu1, P.S. Subramanyam2 Electrical & Electronics Engineering, JNT University. Hyderabad. 1 Kondalu_m@yahoo.com 2 subramanyamps@gmail.com Joginpally B.R. Engineering College, Moinabad, Hyderabad Abstract: --This paper presents the most significant results of a Very fast transient Overvoltages generated due to switching operations have been analyzed and presented. Since the contact speed of dis-connector switches is low, re-striking occurs many times before the current interruption is completed.each re-striking generates transient overvoltage with level of magnitude. These transient have travelling wave behaviour, they travel to the external systems through enclosures, bushings, cable joints etc.. and cause damage to the outside equipment. They can lead secondary break downs in GIS and may give rise to electromagnetic interference. The Earth faults give rise to TEV which can interfere with the operation and control of secondary equipment in a 3-phase 132kv GIS. Thus it is important to develop a suitable MATLAB7.8 models for estimation of these overvoltages. Keywords Gas Insulated Substation (GIS), very fast Transient overvoltages, 3phase faults, MATLAB 7.8 software and Control circuitry I. INTRODUCTION For accurate analysis of transients, it is essential to find the VFTO s and circuit parameters. Due to the travelling nature of the transients the modelling of GIS makes use of electrical equivalent circuits composed by lumped elements and especially by distributed parameter lines, surge impedances and travelling times. The simulation depends on the quality of the model of each individual GIS component. In order to achieve reasonable results in GIS structures highly accurate models for each internal equipment and also for components connected to the GIS are necessary. The dis-connector spark itself has to be taken into account by transient resistance according to the Toepler s equation and subsequent arc resistance of a few ohms. The wave shape of the over voltage surge due to dis-connector switch is affected by all GIS elements. Accordingly, the simulation of transients in GIS assumes an establishment of the models for the Bus, Bushing, Elbow, Transformers, Surge Arresters, Breakers, Spacers, dis-connectors, and Enclosures and so on. A GIS system comprising of an Input Cable, Spacer, Dis-connector Switch, Bus bar of 10mts length and load has been considered for modelling into electrical network and analysis. The Fast Transient Over voltage waveform generated during Closing and Opening operation of Dis-connector Switch and 3-phase faults has been considered for calculations. Spacers are simulated by lumped Capacitance. The Inductance of the bus duct is calculated from the diameters of Conductor and Enclosure. Capacitances are calculated on the basis of actual diameters of inner and outer cylinders of central conductor and outer enclosure. Cone Insulators used for supporting inner conductor against outer enclosure are assumed to be disk type for approximate calculation of spacer capacitance. The busduct can be modelled as a series of Pi-network or as sequence parameters. However in this model, it is considered as distributed Pi-network. The Schematic Diagram of a Typical Gas Insulated System (GIS) is shown in below figure 3. Frequency nature, the VFTO imposed on the transformers connected directly to the GIS would not be distributed evenly on all transformer windings. Some windings, e.g. the first few turns connecting to the 132kV GIS, would be subject to a higher magnitude of overvoltage, posing a potential risk of insulation breakdown of the transformers[9][10]. Page 757

II. MODELLING OF 132KV GAS INSULATED SUBSTATION During the current operation of dis-connector switch in a GIS, re-strikes(pre-strikes) occur because of low speed of the dis-connector switch moving contact, hence Very fast Transient Over voltage are developed. These VFTO s are caused by switching operations and 3-phase fault When a dis-connector switch is opened on a floating section of switchgear, trapped charge may be left on the floating section. In the opening operation of dis-connector switch, transients are produced and the magnitude of these transients and rise times depends on the circuits parameters. When there is a fault occurs, there is a short circuit in the system. Transients are also produced due to the faults in the system. Due to this VFTO s are caused by switching operation can also lead to secondary breakdown with in GIS. Re-striking surges generated by the dis-connector switches at GIS generally possess extremely high frequencies ranging from several hundred KHz to several MHz. For the development of equivalent circuit low voltage step response measurements of the main GIS components have been made. Using MATLAB 7.8 of the equivalent models is developed. During opening of Dis- connector switch (DS), transients are produced due to internal oscillations. The magnitude of transients and rise times depends on the circuit parameters like inductance, Capacitance and connected Load. Assuming that some trapped charge is left is left during operating operation; transients can be calculated during closing operation of DS. Fast transient over voltages generated during Dis-connector Switch operation are a sequence of voltage of voltage steps created by voltage collapse across the gas at re-striking specific over voltage shape is formed by multiple reflections and refractions. Operation of Dis-connector Switch (DS) can be shown by using the fig 1 Where L1 = Inductance of Source C1 = Capacitance of Source C2 = Capacitance of GIS Open part U1 = Power Frequency Voltage U2 = Power GIS Voltage The more frequent service situation of the isolator is its use to connect or dis-connect unloaded parts of the installation as is shown in fig 1 for example apart of the of the GIS is disconnected by an isolator from an overhead supply line. Where by the self-capacitance C2 of this part of circuit can be upto several nf, depending on its length. First re-strike across the gap occurs when voltage across the gap exceeds the breakdown voltage. The occurrence of re-strikes is described with the following Fig 2 The voltage across the gap is the difference between U1 and U2, if it is assumed that the breakdown voltage UB of the gap increases with increasing separation and therefore with time as shown in fig 2.Then the curve U2 can be constructed as follows. At the instant of mechanical contact separation, U1 and U2 have the same value, the voltage U2 continues to retain this value, while U1 changes with power frequency, the voltage (U2-U1) Across the gap of the isolator also changes. As soon as, (U2-U1) exceeds the dielectric strength UB of the gap, a breakdown and thus first re-strike occurs. Both electrodes are there by electrically connected by conducting spark, whereby GIS section with initial voltage U2 is very rapidly charged to instantaneous value of U1. The transient current flowing through the spark then interrupts as soon as the GIS have been charged to U1 and spark extinguishes. The voltage U2 now remains constant with time, while the voltage U1.on the side of supply keeps changing. This continues until the second re- strike occurs with an increased breakdown voltage UB as a consequence of larger separation. Hence U2 follows U1, until finally at the end of the switching process the gap no longer can be broken down. Transients are also produced due to faults in the system. When there is a fault, there will be short circuit in the system. Due to this, oscillations occur due to presence of inductance and capacitance on both sides of the fault section causing transients. Dis-connector Switch (DS) operation typically involves slow moving contacts which results in numerous discharges during operation.for example, a floating section of switchgear between a disconnect switch and an open breaker (load side may be disconnected from an energized Gas insulated system (supply side). For capacitive currents below 1 amp, are-strike occurs every time the voltage between the connects exceeds the dielectric strength of the gaseous medium between them. Each re-strike generates a spark, which equalizes the potentials between the switch contacts. Following spark extinction, the supply and load side potentials will deviate according to the AC supply voltage variation and the discharge characteristics of the load side respectively. Another spark will result when the voltage across the electrode gap dependent breakdown voltage UB and the potential difference of the load and supply side U. Page 758

Each Dis-connector Switch (DS) operation generates a large number of ignitions between the moving contacts. The number of ignitions depends on the speed of the contacts. The largest and steepest surge voltages are generated only by those breakdowns at the largest contact gap. Therefore, only by those breakdowns (10-50) need be considered for dielectric purpose. A. Calculation of variable arc resistance The Variable arc resistance is calculated using the formula: ( ) Where, = Toepler s constant = 0.005 volt.sec/mt for SF6 under uniform field conditions L = spark length in meters = Initial charge or charge at the instant of breakdown T = spark collapse time in sec. Fig. 1 Electric Circuit for explaining re-strikes Fig 2 Voltage of the open ended GIS side of the Isolator Page 759

Fig. 3 Schematic diagram of a typical Gas Insulated Substation Fig. 4. 132kv GIS MATLAB implemented circuit when CB in Re-Striking Condition The value of time varying spark resistance R(t) is calculated until it reaches a value of 1 to 3 ohms. The integral in the denominator sums up the absolute value of current i through the resistance R(t) over the time beginning at breakdown inception. Thus, it corresponds to the charge conducted through the spark channel up to time t. The busduct can be modelled as a series of Pi-network or as sequence parameters. However in this model, it is considered as distributed Pi-network. The Schematic Diagram of a Typical Gas Insulated System (GIS) is shown in below figure 3. Assuming that some trapped charge is left on the floating section of switchgear during opening operation of disconnector switch, a voltage of certain value is considered during MATLAB The apparatus as disconnected with an earthing switch, three disc type Spencer s, a load bus bar above to 10mts long width three post type spacers and a 132kv gas bushing containing stress capacitor.. III. 3-PHASE EQUIVALENT CIRCUIT FOR 132KV GIS SYSTEM FOR 10MTS LENGTH The bus duct is dividing into three sections of length 1mts, 4mts, 5mts from load side. The GIS bushing is represented by a capacitance of 125pf. The resistance of 1 ohm spark channel is connected in series with circuit breaker. MATLAB Circuit for 10 mts. length in a 3-phase 132kv GIS shown in the fig. 4. Due to trapped charge some voltage remains on the floating section which can create severe conditions because the first restrike can occur at the peak of power frequency voltage giving a voltage of 2.0 p.u. On re-strike the voltage on each side will Page 760

collapse initially zero and hence creating two 1.0pu voltage steps of opposite polarities. In this, it is assumed that restriking is created at 1.0 p.u. respectively on either side of disconnector switch (DS). The transients due to closing of the circuit breaker are calculated and maximum voltage obtained with a rise time. This method implemented on MATLAB 7.8. the voltage before and after circuit breaker is taken to be 1.0 pu and -1.0pu as the most enormous condition but depending on the time of closing of circuit breaker the magnitude of the voltage on the load side changes. For different values of voltages on the load side the magnitudes and rise time of the voltage wave are calculated keeping source side voltages as constant as 1.0p.u the values are tabulated in table I. Similarly by changing the magnitudes of the voltage on the source side, keeping voltage on load side constant at 1.0p.u. Then the transient due to variation of voltage on source side obtained. The values are tabulated in Table II. TABLE I TRANSIENT DUE TO VARIATION OF RE-STRIKE VOLTAGE ON LODE SIDE S.no Load side Voltage (p.u) Magnitude of the voltage (p.u) Rise Time (Nanos) 1-1.0 2.45 10 2-0.9 2.39 13 3-0.8 2.19 12 4-0.7 2.15 10 5-0.6 2.03 12 6-0.5 1.96 11 7-0.4 1.82 10 8-0.3 1.77 13 9-0.2 1.53 12 10-0.1 1.45 9 7 0.4 1.79 9 8 0.3 1.71 12 9 0.2 1.42 11 10 0.1 1.39 9 IV. RESULTS AND DISCUSSION The phenomenon that occurs during the DS closing into a capacitive load is very nearly the reserve of processes that occur during its opening. Here, the first restrike occurs due to the residual voltage left behind by a previous opening on the load side. Circuit breaker or load break switch closing or openings also generate VFTO in the case of re-strikes but the number of such VFTO is much lower than those generated by DS operation. The various transient voltage and current at different positions in a 3 phase 132kv GIS for the first switching operation presented in results. Assumed that there is a second re-strike another switch is connected in parallel to the circuit breaker for simulation in MATLAB modeling. Transients are calculated by closing this switch when voltage difference across the contacts of the circuit breaker reaches maximum value. During Re-strike operation (source & Load) the voltage through the resistance of the circuit breaker is shown in fig.5 and fig.6. From the graph it was found the maximum current is 25A at a rise time of 13ns. TABLE II TRANSIENTS DUE TO VARIATION OF RE-STRIKE VOLTAGE ON SOURCE SIDE S.no Source side Voltage (p.u) Magnitude of the voltage (p.u) Rise Time (nanos) 1 1.0 2.43 9 2 0.9 2.37 10 3 0.8 2.17 11 4 0.7 2.11 10 5 0.6 2.01 9 6 0.5 1.91 10 Fig. 5 Transient voltage waveform during Re-strike for 10mts from source side in a 3-phase 132kv GIS Page 761

Fig 6Transient voltage waveform during Re-strike for 10mts from Load side in a 3-phase 132kv GIS Fig.8 Current waveform during Re-strike for 10mts from Load side in a 3-phase 132kv GIS TABLE III THE ANALYSIS VALUES ARE TABULATED AS FOLLOWS: Mode of operation During closing operation During opening operation During second restrike Magnitude of voltage(p.u) Rise time (Nano sec) 2.46 69 1.22 56 2.45 112 Fig 7 Current waveform during Re-strike for 10mts from source side in a 3-phase 132kv GIS To introduce the current chopping, the circuit breaker is opened remains. Hence to calculate transients due to opening operation the CB is opened at 12ns. The transients are obtained and show in fig.7. The transient calculated due to re-strike gives the peak voltage of 2.45p.u at a rise time of 112ns show in fig.8. V. CONCLUSION A model is Developed for the prediction of the VFTO phenomena in the circuit of voltage and current transformers in GIS. The main advantage of such model is to enable the transient analysis of GIS.A spark collapse time was correctly simulated by the variable resistor. By this spark collapse time, resistance of the VFTO is extended, and the component caused by short surge impedance discontinuities such as spacers, disconnectors and short bus branches were damped. A GIS system comprising of spacers, bus bar and disconnectors has been considered for modeling into electric network. The inductance of the bus bar is calculated from Page 762

diameters of conductors and enclosure using standard formulae. Cone insulators used for supporting inner conductor against outer enclosure are assumed to be disk type for approximate calculation of spacer capacitance is calculated using formulae for concentric cylinders. The entire bus length is modeled as distributed pi-network. The peak magnitude of fast transient currents generated during switching event changes from one position to another in a 132kv GIS for a particular switching operation. These transients over voltages are reduced by connecting suitable resistor in an equivalent circuit during closing and opening operation. VI. REFERENCES [1] Boggs SA., Chu F.Y. and Pujimotor N. (IYXZ), 'Disconnect Switch Induced Transients and Trapped Charge in GIs', EEE Trans. PAS, Vol. PAS-101, No.IO, pp3593-3601. [2] MohanaRao M., Naidu M.S. (199% 'Estimation of Fast Transient Overvoltages in the case of Disconnnector operation in a GIS', 3d workshop & conference on EHV Technology, IISC Bangalore. [3] J.B. Kim,M.S. Kim,K.S.Park, W.P.Son.,.D.S. Kim, G.S. Kil. Development of monitoring and diagnostic system for SF6 gas insulated switchgear. IEEE Conference Record of the 2002 IEEE International Symposium on Electrical Insulation. Boston, Massachusetts, UnitedStates, pp.453-456, 2002. [4] M.kondalu, G.Sreekanthreddy, Dr. P.S. subramanyam, Estimation Transientover voltages in gas insulated bus duct from 220kv gas insulated substation, International journal of Computer applications, (0975-8887) volume 20-no.8 april 2011. [5] M.kondalu, G.Sreekanthreddy, Dr. P.S. subramanyam, Analysis and Calculation of very fast transient over voltages in 220kv gas insulated substationiinternational Journal of Engineering &techsciencevol 2(4) 2011 [6] Li Liu-ling, Hu Pan-feng, Qiu Yu-chang, Analysis of Very Fast Transient Overvoltage Calculation Affected by Different Transformer WindingModels, Journal of Xi an Jiaotong University, 2005 ( 10 ) Vol.39 No.10:1160-1164. [7] Yang Linghui, Zhang Jiamin, Research on transient overvoltage during Operation of 500kV GIS disconnecting switch, East China Electric Power, Jan.2004, Vol.32 No.1:37-41 [8] Shibuya Y, Fujita S, Shimomura T. Effects of very fast transient over- Voltages on Transformer [J].IEE Proceedings, Part C,1999,146(4): 459 464. [9] G. Ecklin, D. Schlicht, and A. Plessel. Over voltages in GIS caused by the Operation of isolators in Surges in High Voltage Networks. K.Ragaller, Ed. New York City: Plenum Press, 1980. [10] H. Hiesinger,RWitzmann. Very fast Transient Breakdown at a needle Shaped Protrusion, IX Int. Conf. on Gas Dis. and Their Appli. Sep 1988. Page 763