Bulletin B1243: RIBTW24B-BCAI RIBMNW24B-BCAI

Similar documents
CCE Image may differ from the actual product By Martin Labbé, eng., Jasmin Goupil & Louis Perreault

BAS Integration Manual

ISO 9001 CERTIFIED. 607 NW 27th Ave Ocala, FL Phone: (352) or Fax: (352) OPERATION MANUAL

ECB-103 BACnet B-ASC 10-Point Programmable Controllers

SRC-110 Series Zone Controllers with Modbus RTU

SRC-110 Series Zone Controllers. BACnet MS/TP. Product sheet CT2.143 SRC-110-BAC

Microprocessor Control Board Set Up Procedures (OR PLC)

H7625A, H7635A, H7626A, H7636A Series 2000 Humidity/Temperature Sensors

H7625A, H7635A, H7626A, H7636A Series 2000 Humidity/Temperature Sensors

Modbus Integration Integration for Modbus Functionality for VT8300 Series

Electro Controls. Input-Output Modules WattsIndustries.co.uk

ELECTRONIC THERMOSTAT: T920

Modbus communication module for TCX2: AEX-MOD

Spa Control Troubleshooting Guide

SmartFan Multi SD. Speed Control for DC Fans CONTROL RESOURCES INCORPORATED. The driving force of motor control & electronics cooling.

VersaPoint I/O Module

Peak Current. Continuous Current. See Part Numbering Information on last page of datasheet for additional ordering options.

Relay (R1) 003. Balancing Valve. Slab Pump (P1) Max. 4 pipe diameters apart. Injection Pump (P2) 150 No 24V only. Power. Off.

Ocean Controls KT-5221 Modbus IO Module

269 Troubleshooting Guide 11/4/98 1

TECHNICAL PRODUCT DATASHEET

Application Solutions for: Analog (Input /

Viconics VT76x7 Series Rooftop Unit Controllers Engineering Guide Specification

MINI 048 / JUN 2003 PAGE 1. Temperature I/O Module HE500OCS048 / HE500OCS078 HE500RCS078

IMC-316P Hardware Manual for model IMC-316P-X-D

Brushed DC Motor Control. Module with CAN (MDL-BDC24)

Jaguar Motor Controller (Stellaris Brushed DC Motor Control Module with CAN)

SC30-SM2 Series Signal Conditioners

ADAM-4022T Serial Base Dual Loops PID Controller User s Manual

MULTISTACK The Modular Water Chiller

Analog Servo Drive 30A20AC

Digital Proportional Amplifier. Type: RT-VSPA2-50. Series: 3X. Table of contents. Features. RD13763/11.07 Replaces:

S1 Programming Chart Program Description S1 Switch Positions. Constant ON High/Low Track, WR

USB BACNET COMMUNICATION OPTION MANUAL

Product overview. Features. Product specifications. Order codes. 1kΩ Resistance Output Module

Electronic Amplifier Model VT 3017 and VT 3018 (Series 3X) for the control of proportional directional valves, without positional feedback

5570M Series Intercom Installation and Operation Guide

K-FACTOR SCALER B & B

TA-Slider 160 KNX R24 Protocol Implementation

AxCent Servo Drive A50A100

B850 Boiler House Energy Monitor

Rev /13 SSRMAN-1B SERIES USERS MANUAL SSR INTELLIGENT BURST FIRING CONTROL COPYRIGHT 2013 NUWAVE TECHNOLOGIES, INC.

6.6 Analog input module SM 331; AI 8 x 13 Bit; (6ES7331-1KF02-0AB0)

Anacon Power & Controls

DO NOT USE UNIT POWER

SilverMax Datasheet. QuickSilver Controls, Inc. NEMA 23 Servomotors.

TD_485 Transceiver Modules Application Guide 2017

BACnet Protocol Implementation Conformance Statement

MODEL 421 Over/Under Motor Load Monitor

K-Factor Scaler F5140 and Programming Kit F5141 Installation & Operating Instructions

ELECTRONIC THERMOSTAT: T951

RWD44U Controller. Installation and Commissioning Guide Document No October 5, Function. Application

Wireless Analog Output Modules

VT8300 Series Installation Guide 24 Vac Low Voltage

Analog Servo Drive 30A8

Anacon Power & Controls Relay Assembly Specialists An Anacon Electronic Sales, Inc. Company

8V General information. 2 Order data 8V

B850 Boiler House Energy Monitor

Electronic amplifier for the control of proportional valves without position control Model VT 3006, Series 3X H/A 4240/94 VT X

354B SERIES SHAWNEE II High Speed Predetermining

IB6 Series Solid-State Isolation Relay

This product is for use in a dry, indoor environment only. This product is not to be installed near water, liquid, or flammable materials.

8V General information. 2 Order data 8V

RWD68U Controller. Installation and Commissioning Guide Document No October 1, Function. Application

TECHNICAL DATASHEET #TDAX Universal Input, Single Output Valve Controller CAN (SAE J1939)

INSTALLATION AND OPERATING INSTRUCTIONS

Analog Servo Drive 25A20DD

Metasys Zoning Package Commissioning

Analog Servo Drive 30A8

FX10 Standard Programmable Electronic controller for HVAC and refrigeration applications. Features and Benefits

HLC-1000 High-limit Humidity Control

Programmable K-Factor Scaler B and Programming Software Kit B

Solid-State Digital Counter H7AN

E2T0 DVP

Analog Servo Drive 20A20

Series 354. SHAWNEE II High-Speed Digital Predetermining Counter. The 354B Directly Replaces 354A. COUNTERS PRODUCT HIGHLIGHTS

AxCent Servo Drive AZBE10A4IC

BATCHMATE 1500 Batch Control Computer Technical Bulletin

PAM & SAM System User s Manual

BACnet PTEC Controller VAV with CO2 Monitoring, Parallel Fan and AOV or Floating Point Heating, Application 6682

Continental Hydraulics Installation Manual CEM-RA-A

TECO F510 Inverter. Quick Start Guide. Step 1. Supply & Motor connection

INSTRUCTION SHEET. Eaton Logic Controller ELCM TC Temperature Modules. [Applicable Temperature modules] ELCM-TC04ANNN MTN1

HARDWARE GUIDE. Digital Sensor - T1100 Series. Specifications and Operational Guide

RT-5005/5006/5007/5008

PACSystems* RX3i IC695ALG600

BACnet PTEC Controller Dual Duct 2 AVS - Constant Volume with Two Inlet Sensors and Optional Reheat, Application 6665

GE Fanuc IC695ALG600. Rx3i PacSystem

Analog Servo Drive 100A40

Owner s Manual S5 SERIES ELECTRONIC STEP CONTROLLER WITH VERNIER CONTROL

VT1536A Isolated Digital Input/Output Signal Conditioning Plug-on

DC Current Transducers

HARDWARE GUIDE. FlexIO Controller M2000 Series. Specifications and Operational Guide

PCX-9000 Series Datasheet

PROMUX Distributed MODBUS I/O Modules Catalog and Design Guide

ADJUSTABLE SPEED DRIVES. AS1 Drive

Microprocessor Step Controller/Sequencer

AxCent Servo Drive A25A100

Owner s Manual S10 SERIES ELECTRONIC STEP CONTROLLER WITH VERNIER CONTROL

TECHNICAL DATASHEET #TDAX021901

Transcription:

Bulletin B243: RIBTW24B-BC RIBMNW24B-BC Enclosed BACnet Network Relay Device RIBTW24B-BC RIBMNW24B-BC One Binary Output (2 Amp Relay SPDT + Override) Contact Ratings: 2 Amp Resistive @ 277 Vac 2 Amp Magnetic Ballast @ 277 Vac 6 Amp Electronic Ballast @ 277 Vac () Amp Tungsten @ 2 Vac () VA Pilot Duty @ 277 Vac 77 VA Pilot Duty @ 2 Vac 2 HP @ 277 Vac HP @ 2 Vac CTROL V 2 ^To select Analog IN or T3 input, use COM Relay Override is selected via DIP Sw & 2: DIP es * Relay State ** 2 Auto X Override on Override off * = Open ; = Closed ** Device must be powered for override Red LED is on when Relay is on. Connect to terminals,, COM 5M6 ENERGY MANAGEMENT EQUIPMENT RISK OF ELECTRIC SHOCK - MORE THAN E CAUTI: DISCNECT MAY BE REQUIRED TO DEENER- GIZE THE DEVICE BEFORE SERVICING. FOR SUPPLY CNECTIS USE #2AWG WIRES OR LARGER D FOR AT LEAST 75 C(67 F). 3932U Page

Two Binary Inputs (Dry Contact, Class 2) CTROL V 2 ^To select put Analog IN or T3 input, use COM Connect to terminal pair COM & or & Contact rating ~ 24 Vdc @ 2 ma Pink LED is on when respective Binary Input is closed 24 Vac/dc Power Input Connect to terminal pair 24Vac/dc Input When connecting 24Vac to both the RIB(s) and a halfwave device, damage to device can occur. Option : Use seperate transformer for each device, or an isolated 24Vdc power supply. Option 2 Add diode between devices, see diagram. 24 Vac RIBMNW24B-BC or RIBTW24B-BC 24 Vac/dc Com Half-Wave Device 24 Vac Com ^^ Option 2: Add diode on 24 Vac power (Com) interconnection between devices. Band on diode faces towards RIB(s). IN44 Page 2

BACnet Network Optional End of Line Resistor (EOL) Included. Basic Data Network Media: Twisted Pair 22-24AWG, shielded recommended Terminations: Functional Devices product installed at both ends of the network Use 2 Ω end of line resistors. All other cases Follow instructions from the device installed at the end of the network. Polarity: Network is polarity sensitive Baud Rate: 96, 92, 384, 576, 768, 52 (DIP able) CTROL V 2 ^To select Analog IN or T3 input, use COM Addressing, Baud Rate, and ID Address & Baud Rate must be set prior to power up via DIP switches. Device ID will default to 277XXX where XXX is the Address. Examples: Address - 4 Device ID - 2774 Address - 2 Device ID - 2772 Device ID can be changed via network command. Once changed, it will no longer default to 277XXX. (Each Address & Device ID must be unique.) Device Instance is changed via Object-Identifier Property of the Device Object DIP es* 8 9 Baud Rate 96 92 384 576 768 52 * = Open ; = Closed All other combinations = 96 Baud This model utilizes: BO (Relay output),, (Dry contact Binary inputs), (Analog input), AV (Set Point), AV 2 (Differential), BV (Set Point Function Enable), BV 2 (Set Point Mode), BV 3 (Set Point Function Status) Address selected via DIP Sw 7, see Bulletin B228 Page 3

One put (T2/ or -5 Vdc or - Vdc) Utilized for optional Set Point Function if enabled (see next page). CTROL V 2 ^To select THERM. SELECT Analog IN or T3 input, use COM T2/ Install THERM SELECT Jumper Install per Type Table Close Sw () Open Sw 2 () Connect to Terminals & THERM + Thermistor Specifications Thermistor Type 2 (T2) Precon K @ 77 F (25 C) PN ST-R24, Model 24, (or equivalent.) Thermistor Type 3 (T3) Precon K @ 77 F (25 C) Model 3, (or equivalent.) Thermistor not included. For both T2 and T3: MIN_PRES_VAL must be set to -36 Celcius or -32.8 Fahrenheit (real value) MAX_PRES_VAL must be set to 66.3 Celcius or 5.34 Fahrenheit (real value). Temperature Range/Resolution: -35 to C range in steps / -3 to 5 F range in.8 steps to 32 C range in. steps / 5 to 9 F range in.8 steps 32 to C range in steps / 9 to 22 F range in.8 steps Input (-5 Vdc) Uninstall THERM SELECT Jumper Install per Type Table Close Sw () Open Sw 2 () Connect to Terminals & COM Input (- Vdc) Uninstall THERM SELECT Jumper Install per Type Table Open Sw () Close Sw 2 () Connect to Terminals & COM Raw analog default settings are and 23 (real), respectively. Units default to 95 (no units). Page 4

Set Point Function RIB[*]24B-BC The Set Point Function of this product monitors the put () and controls the Binary Output (BO) based on a Set Point and Differential set by the user. The Set Point Function will continue to operate even if network communication is lost. The function has two modes, Increasing or Decreasing, which are shown in the table below. Set Point Function Mode put Binary Output Increasing < Set Point Differential @ Priority 6 Increasing > Set Point + Differential @ Priority 6 Decreasing < Set Point Differential @ Priority 6 Decreasing > Set Point + Differential @ Priority 6 Inputs Set Point Function Enable (BV) Enables or disables the set point function. Set Point Mode (BV2) Sets the set point function operation mode to either increasing or decreasing. Set Point (AV) The desired set point to be maintained. Set Point Differential (AV2) The difference above and below the set point needed to trigger a state change. put () put for the set point function. Outputs Set Point Function Status (BV3) Status feedback of the input settings for the set point function. See Set Point Function Status Conditions section. Relay (BO) Setup The set point function software running on the RIB[*]24B-BC requires multiple hardware and software settings to be configured for the logic to execute correctly. Please follow the steps outlined below to ensure proper functionality. Hardware Setup Follow steps on pg. 4 to setup hardware for desired put (T2/, -5 Vdc, - Vdc) Note: Hardware setup should be performed before powering on the device. Software Setup Follow Input steps when using a - or - analog input. Follow Thermistor Input steps when using a T2 or T3 thermistor analog input. Input. Update BACnet object s Units property to desired units. 2. Update the MIN_PRES_VAL property of to (default), and update the MAX_ PRES_VAL property of to 23 (default). 3. Read s Present Value to verify the Input is being measured and converted correctly (Present Value is a -23 value, proportional to the input voltage). 4. Update BACnet object AV s and AV2 s Units property to match the units of. 5. Update BACnet object BV2 s Present Value to select the desired set point function mode. a. = Increasing Mode b. = Decreasing Mode Note: Set Point and Differential set in Steps 6 and 7 are on a -23 scale. 6. Update BACnet object AV s Present Value to the desired set point. 7. Update BACnet object AV2 s Present Value to the desired differential. Page 5

8. Read BACnet object BV3 s Present Value to verify the Set Point Function Status. This value should be (Valid). If it is (Invalid), please verify the Set Point Function Status Conditions are satisfied see below. 9. Update BACnet object BV s Present Value to (On) to enable the set point function. Thermistor Input. Update BACnet object s Units property to either (62) Celsius or (64) Fahrenheit. 2. Based on the Units property configured in step, update the MIN_PRES_VAL and MAX_PRES_VAL properties of accordingly see For both T2 and T3 on pg. 4. 3. Read s Present Value to verify the temperature is being measured and converted correctly. 4. Update BACnet object AV s and AV2 s Units property to match the units of. 5. Update BACnet object BV2 s Present Value to select the desired set point function mode. a. = Increasing Mode (Heat) b. = Decreasing Mode (Cool) 6. Update BACnet object AV s Present Value to the desired set point. 7. Update BACnet object AV2 s Present Value to the desired differential. 8. Read BACnet object BV3 s Present Value to verify the Set Point Function Status. This value should be (Valid). If it is (Invalid), please verify the Set Point Function Status Conditions are satisfied see below. 9. Update BACnet object BV s Present Value to (On) to enable the set point function. Set Point Function Status Conditions The following conditions must be satisfied for the set point function to operate properly.. Hardware jumpers and DIP switches must be set for the type of analog input being utilized. 2. The units of and AV must be the same 3. The MIN and MAX Present Value properties of must be set to match the units 4. For a Input: a. (set point differential) > b. (set point + differential) < 23 5. For a Thermistor Input a. (set point differential) > minimum measurable temperature (dependent on units) see Measurable Temperature Range below. b. (set point + differential) < maximum measurable temperature (dependent on units) see Measurable Temperature Range below. Measurable Temperature Range Celsius with T2 or : o Minimum = -35 C o Maximum = C Fahrenheit with T2 or : o Minimum = -3 F o Maximum = 22 F Short Cycle Protection for HVAC Applications The Minimum_On_Time and Minimum_Off_Time properties of BO can be used to ensure short cycling of the relay load is not possible. Page 6