lama M:ZSO 2SA 30oM 11ov m

Similar documents
NATIONAL RULES FOR ELECTRICAL INSTALLATIONS. Fourth Edition. Extracts from Amendment No.1: June 2011

FIB / FIC. r with Overcurrent Protection (RCBO) Doepke. » effi cient. » reliable. » fl exible. » future-oriented

Residual current circuit breakers (RCCBs)

CURRENT FUTURE REGULATIONS PROPOSALS

Module Title: Electrical Installation II Laboratory Sheet:

Residual Current Operated Circuit-Breakers (RCCBs)

17TH EDITION BS TH EDITION BS7671 HOW THIS AFFECTS YOU. A BITESIZE LOOK at RCDs and parts of the 18th edition DPC. wylexreasons.co.

Residual Current Operated Circuit-Breakers (RCCBs)

7 o/c4 - To meet the requirements of BS 7671, all fault current protective devices without back-up protection on the supply side must be capable of:

Residual Current-operated Circuit Breakers (RCCBs) F 360 and F 370 Range

2394 EXAM PAPER. 1. State THREE circumstances that would require a periodic inspection and test to be carried out on an installation

7P Series - Surge Protection Device (SPD) Features 7P P P

Chapter 6. WIRING SYSTEMS Safe Electrical Design

Les Hampson Cert Ed FSCTE, Chairman CAI Technical Committee

Product Classroom. Introduction. Grounding Systems. TN system. Title. Grounding System Introduction. Date October, 2016.

Chapter 1. Applied Grounding and Bonding. Applied Grounding and Bonding 9/18/2011. Introduction. Introduction. Paul Dobrowsky Member NEC Panel 5

Btdin RCD Add-on modules 63A for MCBs 1,5 modules per pole

Automatic disconnection of lighting circuits from dimming equipment

INSTRUCTION MANUAL DIGITAL PSC-LOOP TESTER MODEL 4118A KYORITSU ELECTRICAL INSTRUMENTS WORKS,LTD.

ET 51 - Electrician Theory Examination Marking Schedule

Protection components

J7M-AM/-BM. Motor--protective circuit--breaker system. J7M -BM System IEC 947, EN IEC 947, EN 60947

Add-on modules DX 3 63A for MCBs DX 3 1,5 modules per pole

FINAL - ET 60 - Electrician Theory Examination Marking Schedule

ELECTRICIAN S THEORY EXAMINATION 17 November 2012 QUESTION AND ANSWER BOOKLET

MultiMeter-Pocket CAT III 1000 V

Current Module, 3-channel, MDRC SM/S , GH Q R0111

technical information

FINAL - IT 30 ELECTRICAL INSPECTOR EXAMINATION ANSWER SCHEDULE. Question 1 Marks Reference Marking notes. (2 marks) EA 2

Chapter F Protection against electric shocks

1. general. 1.1 electric shock. 1.2 direct and indirect contact. electric shock. indirect contact. direct contact

ECM3 EARTH CONTINUITY RELAY

Options to Improve the MEN System into the 21 st Century

Chapter F Protection against electric shocks

Distribution systems and protection against indirect contact and earth fault

C&G Level 3 Award in the Periodic Inspection, Testing and Certification of Electrical Installations. Earth Fault Loop Impedance Tests

TS RES - OUTSTANDING ISSUES

Section 6: System Grounding Bill Brown, P.E., Square D Engineering Services

Spänningsstabilisatorer Voltage Stabilisers. General information

HAWK5000 Operators Manual

returned to your distributor for attention. 14. Do not operate the function switch while the instrument is connected to a circuit.

MDW-45 Converter RS RS-422/485

Page 13-2 Page Page 13-7

ELECTRICIAN S THEORY EXAMINATION 19 November 2016 QUESTION AND ANSWER BOOKLET

NOTE: This paper relates to a closed book exam & therefore candidates should attempt this exam paper with no study-notes or text books.

Safety Warnings Features Specifications Instrument Layout Operation Preparation AC Current Measurement How to Use Peak Hold Function How to Use The

Tech Talk (12) Down to Earth: A Discussion of the General Requirements for the Earthing of Control and Instrumentation Systems

Protective earthing, protective conductor and automatic disconnection in case of a fault (Fault protection)

Protection and control VIP300. Technical manual

ER 87 Electrician Regulations Answer Schedule. Question 1 Marks Reference Marking notes. (1 mark) ESR 27(2) (2 marks) ESR 74A(1AA)

NT & NQ CLASS II TRANSFORMERS FOR SIGNALLING SYSTEMS. A Balfour Beatty and Alstom Company

Btdin RCD Add-on Modules 32A - 63A for M.C.Bs 1 module per pole

MV network design & devices selection EXERCISE BOOK

Choice of earth leakage protection devices

ELECTRICIAN S THEORY EXAMINATION 20 November 2010 QUESTION AND ANSWER BOOKLET

MODEL 3810/2 Line Impedance Stabilization Network

200ADM-P. Current Injection System with Phase Shift A 3.000s 2.000A 50.00Hz 0.0. Features

TN, TT & IT Earthing Arrangements

10/2 Product overview. 10/3 4AC3 0, 4AC3 1 bell transformers. 10/5 4AC AC3 6 transformers for permanent loads. 10/8 4AC2 4 power supply units

... avoid using constructionstyle generators that have master GFCIs.

C&G Level 3 Award in the Periodic Inspection, Testing and Certification of Electrical Installations

27/04/2015

(1,5 modules per pole)

MinorWorks/Single Circuit Electrical Certificate

Safety Warnings Features Specifications Instrument Layout Operation Preparation AC Current Measurement How to Use Peak Hold Function How to Use The

CHAPTER 2 ELECTRICAL POWER SYSTEM OVERCURRENTS

CHAPTER 15 GROUNDING REQUIREMENTS FOR ELECTRICAL EQUIPMENT

Instantaneous Overcurrent Relay

AMENDMENT NO. 1 SEPTEMBER IS (Part 1) : 2001/IEC (1991) SURGE ARRESTORS

The KT 64 incorporates Anti Trip Technology (ATT) which electronically bypasses RCDs when performing loop impedance tests. This saves time and money

FINAL - ER 70 Electrician Regulations Answer Schedule. Question 1 Marks Reference Marking notes

Btdin RCD Add-on Modules 32A - 63A for M.C.Bs 1 module per pole

CA60 ma Current Clamp

TT W Wireless receiver Inline Switch

Content. Monitoring relay pluggable. 1-phase current monitoring relay phase direct-current voltage monitoring relay... 5.

O W N E R S M A N U A L. Po w e r A m p l i f i e r s

ENGINEERING STANDARD FOR INSTRUMENTS ELECTRICAL POWER SUPPLY AND DISTRIBUTION SYSTEMS FIRST EDITION MAY 2013

Why the IT system is often the best choice for power supply systems of all types

Grounding and Lightning arrestors

TEST REPORT DIN V VDE V :2006 Automatic disconnecting device


Power Supply Device (KLTE-430D) Installation & Operation Manual

G SAFETY WARNINGS. LT300 High current loop tester. User guide

power Knowledge The Hager Guide to current thinking on the regulations, protection and control of Klik lighting circuits.

Earth leakage protection Response time of medium-sensitivity residual current devices

Bringing power to life. THE RCD HANDBOOK. BEAMA GUIDE TO THE SELECTION AND APPLICATION OF RESIDUAL CURRENT DEVICES (RCDs)

LZS-A500-3 POWER SUPPLY Installation, Operation, and Maintenance Manual. IM-LZSA500-3 January 2008 Revision H

120/240 Watt AC-DC Front End with PFC W Series Convert Select 120 Convert Select 240

ET 40 - Electrician Theory Examination Marking Schedule

Harmonic Filters for Single Phase Equipment

MEGGER CM300 MK II, CM400 MK II & CM500

INSTRUCTION MANUAL MULTI-FUNCTION TESTER KEW 6016

Suppliers' Information Note. BT Metallic Path Facility. Interface Description

Performance Specification For Tactile Equipment for use at Pedestrian Crossings

Protection components

7PG21 Solkor R/Rf Pilot Wire Current Differential Protection Answers for energy

Phase and neutral overcurrent protection

INSTALLATION WARNING: BEFORE COMMENCING INSTALLATION ISOLATE YOUR MAINS ELECTRIC SUPPLY

This article is designed to give you an insight into generators that can be used with your caravan or motorhome.

Series OLH10KD 10kW HIGH VOLTAGE POWER SUPPLIES

Transcription:

Sentry Technical by Honeywell www.mkelectric.co.uk Standards and approvals All Sentry RCDs are designed to fully comply with the requirements of 8S EN 61008: 1995.1EC 1008:1990 They all feature positive contact status indication in accordance with the 17th Edition lee Wiring Regulations (537.2.2.1 and 537.3.2.2). -... IIA ~ RCD ~ RCD lama M:ZSO 2SA 30oM 11ov m ljo/@;s Technical specification Electrical Rated making and breaking capadty /m: 16-40A = SOOA 63-80A = 800A IOOA = IOOOA Type AC Rated short-circuit current I inc: 16A - 40A = 1 O,OOOA (63A fuse) 63A - BOA = IO,OOOA (100Afuse) IOOA = IO,OOOA (12SA fuse) Rated residual short-circuit current {IL\m: 16 I OOA = IO,OOOA Rated voltages: 2 pole devices, 11 OV and 230V 4 pole devices, 230V to 440V Operating voltages: 2 pole devices. 11 OV - 1 OOV to 2 50V 230V 1 OOV to 2 50V 4 pole devices, 185V - 440V Tripping Time: 1 x IL\n.:300ms 5 x IL\n.:40ms Time delay version 1 x IL\n 150 500ms 5 x IM SO 150ms Physical Ambient operating temperature: - 25c to + 400C IP rating: Front face alter installation of enclosure IP40 Terminal capacity: Solid standard 1 x 1.5 50mm' Flexible with female. 1 x 1.5. 35mm' Tightening torque: 3Nm - - - - Description The Sentry range of RCDs offers a comprehensive selection of devices designed to meet most residential. commercial and light industrial requirements. The ra nge includes two and four pole, a.c., d. c. fau lt current sensitive and time delayed models and a selection of current ratings from 16 to 1 OOA is available in a variety of tripping sensitivities. When in the OFF position a contact gap of 4mm is present, enabling Sentry RCDs to be used as isolating switches where appropriate. Positive indication of the opening of the contacts is only given when contact status indicator shows green. The operating dolly may be locked in either the ON or OFF position without affecting the ability of the trip mechanism to operate, i.e. the RCD is 'trip free'. It is not possible to hold the contacts closed when a fault condition exists. All Sentry RCDs incorporate a filtering device to provide protection against transient surges in the supply to the unit, thus reducing the occurrence of unwanted tripping. Features M eet BS EN and lee Wiring Regulation requirements Extensive range to suit all specifications Protect against unwanted tripping Positive contact status indication Suitable for most residential, commercial and light industrial applications Offer a high degree of protection against electrocution in accidental shock hazard situations Two module, double pole units ava ilable up to 100A Indication of earth fault. via central dolly position Max. installation altitude: 2000 metres

by Honoyw911 Sentry Techn ical technical hotline +44 (0)1268 563720 Rating specification Double pole, 2 module Rating 16A, 110V lorna 16A, 110V 16A, 230V lorna 16A, 230V 32A, llov 32A, 230V 40A, 230V 63A, 230V 63A, 230V looma 63A, 230V 300mA 80A, 230V 30m A 80A, llov 30m A 80A, 230V 300mA 80A, 230V looma looa, 230V looa, 230V looa, 230V Tripping current looma 300mA Double pole, pulsating d.c., fault current sensitive, 2 module 16A, 230V 16A, 230V 32A. 230V 40A, 230V 63A, 230V lorna Time delayed, 2 module 80A, 230V 1 OOmA looa. 230V looma Four pole, 4 module 2SA, 230/400V 40A. 230/400V 40A, 230/400V looma 63A, 230/400V 63A, 230/400V looma 63A. 230/400V 300m A Four pole, pulsating d.c., fault current sensitive, 4 module 40A, 230/400V list No. 6016s 6416s 6316s S716s 6032s 6730s 5740s 5760s 6160s 5860s 5780s 6080s 5880s 6180s 7700s 6600s 7800s 6216s 6716s 6630s 5640s 5660s 6980s 6400s 6425s 6440s 6240s 6463s 6363s 6263s 6640s Installation Sentry RCDs must never be used as the sole method of basic protection, but are invaluable in providing supplementary protection in high risk environments where damage may occur. Application The choice of the most suitable RCD for a particular application should take into account the following considerations: 1. Sensitivity 1 OmA RCDs offer a high degree of protect ion against electrocution in an accidental shock hazard situation. They are of particular value in a high risk area where resistances external to the body are likely to restrict the earth fault current flowing through the body to less than and where 11 OV supply is being used. RCDs offer a high degree of protection in an accidental shock hazard situation and are by far the most popular sensitivity used in the United Kingdom. In a shock situation, the current flowing through the human body at 240V 50Hz could be between 80 and 240mA, depending on the resistance of the body in question. To ensure that there are no harmful physiological effects in such a situation, it is necessary for t he RCD to operate within 300mS at and 40mS at 150mA. As the Sentry RCD typically operates well below these times, it clearly more than satisfies this requi rement. 1 OOmA RCDs may, in some circumstances, provide protection against electrocution in an accidental shock hazard situation. However, it is important to note that there is a likelihood that the earth fau lt current may be below the sensitivity of the RCD. This becomes increasingly likely if additional resistances to that of the human body are in t he current path. 300mA RCDs provide protection against the risk of fire only. They do not provide protection against electrocution in an accidental shock hazard situation. A typical application would be lighting circuits where it is deemed that the risk of electric shock is small. It is important to note that a current of less than 500mA flowing in a high resistance path is sufficient to bring metallic parts to incandescence and, potentially, initiate a fire. 2. Requirements of the lee Wiring Regulations BS 7671 RCDs may be used to provide additional protection against both fault protection and basic protection. Fault Protection Defined as protection against electric shock under single fault conditions. Effective earthing in conjunction with automatic disconnection should always be employed to protect against the effects of fault protection. The provision of a low resistance path back to the supply from the fault should ensure that the overcurrent device operates before damage occurs. This is the earth fau lt loop impedance. In circumstances where the earth fault loop impedance in the circuit is too high to ensure operation of the overcurrent device, then the lee Wiring Regu lations allow the installation of an RCD. To comply with the Regulations, the earth loop impedance of the circuit (in ohms), multiplied by the rated tripping current of the RCD (in amperes) must not produce a va lue greater than 50. With this in mind, the maximum values of earth loop impedance permissible when installing an MK Sentry RCD are as follows: 50 50 Z (max) = -- = -- = 1666 ohms ' lon 0.03 Rated Tripping Current of RCD Maximum Permissible Earth Fault loop Impedance 10mA 5000 ohms 1666 ohms 100mA 500 ohms 300mA 166 ohms RCD's are fu rther specified for fault protection on TT systems (Regulation 411.5.2, 411.5.3 apply)

Sentry Technical by Honeywell www.mkelectric.co.uk Application (continued) Direct Cont act Defined as "contact of persons or livestock with live parts". The Regulations recognise four main means of providing protection against direct contact which include enclosures and the use of extra low voltage systems. However, the use of RCDs is specified by the Regulations in the following instances: A socket outlet rated at 32A or less which may reasonably be expected to supply portable equipment for use outdoors shall be protected by an RCD having the characteristics specified in Regulation 412-06-02. (Regulation 471-16-01 applies.) Where socket outlets are used to supply caravans on caravan sites, then they must be protected by an RCD having the characteristics specified in Regulation 412-06-02. Regulation 412-06-02 stipulates among other things that where supplementary protection is provided by residual current devices, their rated residual operating current must not exceed and that they must trip within 40ms at 5 times rated operating current. Although RCDs must never be used as the sole method of direct contact protection, they are invaluable in providing supplementary protection in high risk environments where damage may occur. Typical applications include situations where equipment may be used outside or fed by trailing sockets, equipment accessible to children or equipment used in wet areas. For these reasons RCDs are commonly found in schools, hospitals and residentia l installations. 3. Types of fault current In an installation different types of fault current can occur. MK offer RCDs to suit these conditions. Sentry Type AC RCDs are suitable for situations where there are residual sinusoidal alternating currents, whether applied suddenly or rising slowly. This is the most commonly used type of RCD in the UK. Sentry Type A RCDs (i.e. pulsating d.c. fault current sensitive) are suitable for situations where there are residual sinusoidal alternating currents, whether suddenly applied or slowly rising. These situations can occur with the use of semiconductor devices in modern electrical and electronic equipment. such as computers, printers, plotters, televisions, video cassette recorders and hi-fi equipment, is growing. Such devices may resu lt in the normal sinusoidal a.c. waveform generated by the mains electrical supply being 'modified'. for example, the waveform may be rectified or, as in asymmetric phase control devices, the waveform may be chopped. The resulting waveforms are said to contain a pulsating d.c. component as illustrated below. Norma l a _c. waveform Pulsating d_c. waveform Half wave rectified t t - - Pulsating d_c. wavefo rm Typical asymmetrical phase control t

by Honoyw911 Sentry Technical technical hotline +44 (0)1268 563720 Application (continued) Pulsating d.c. fault current sensitive RCDs Should a waveform containing a pulsating d. c. component develop an earth fault, then it is possible that it may not be detected by an "a. c. only" sensitive RCD. For this reason, the Sentry range contains RCDs designed to be sensitive to pulsating d.c. fault currents thus maintaining the intended degree of protection. Type B RCDs are suitable for situations where there are residual sinusoidal alternating currents, residual pulsating direct currents and smooth d.c. and a.c. residual current of various frequencies, w hich would not trip Type AC or A RCDs. These situations can occur in 50Hz a.c. installations with electronic equipment, e.g. frequency converters, UPS installations, power supply unit or high-frequency power converters. The following symbols are used on the front plate of the device to indicate the type of RCD. I'"'-' I - type AC RCD. ~~~ - type A RCD. 1~11 -- - 1 -type B RCD. 4. Temperature All Sentry RCDs are suitable for use in the temperature range -2sc to + 40 C. This is indicated on the RCD by the symbol $. 5. Time Delayed RCDs UJ Type S (or selective) When two or more Sentry RCDs are installed in series with one another, measures must be taken to ensure that they discriminate properly. In event of an earth fault, only the RCD immediately upstream from the fault should operate. RCDs do not discriminate on rated tripping current alone, i.e. a 1 OOmA rated RCD situated upstream from a rated RCD, will not offer inherent discrimination. In order to ensure that discrimination is achieved, a Sentry Time Delayed RCD should be used. The inbuilt time delay period ensures that the downstream RCD opens the circuit before the upstream RCD starts to operate. The maximum tripping time of a Sentry Time Delayed RCD is SOOms. Please refer to the current edition of the Wiring Regulations BS 7671 for guidance on the use of these products. 6. 3 phase, 3 wire systems Sentry 4 pole RCDs may be used to provide earth fault protection on 3 phase. 3 wire systems. as the current balance mechanism does not require a neutral to be connected in order to operate effectively.

Sentry Technical by Honeywell www.mkelectric.co.uk Operation The RCD provides an indication of an earth fault and contact status as detailed below. The operating dolly provides the following indication: = Switched ON + = Switched OFF due to Earth Fault or test button operation 0 = Switched OFF The contact status is shown through the window. Red = contact closed Green = contact open (RCD is switched off) In the event of an Earth Fault in the installation or the operation of the test button. the dolly w ill move to the central position(+ ) and the contact status indicator shows green. To re-connect the supply the dolly must be reset by moving to the off position before switching on. ~ RCD ~ RCD ~ RCO 77001 100A 3JmA 77001 100A 3JmA 7700t 100A 3JmA ON ZJIN"' ZJ1Nt9 200VI5l I ~~ ~f ~ ~f OFF 0 '. PUSH egj TO TEST PUSH egj TO TEST PUSH egj TO TEST RESET + ~ ~~ Testing If an RCD is installed for additional protection against indirect contact, it is a requirement of the lee Regulations that the effectiveness of the RCD be verified. This must be achieved by a test simulating an appropriate fault condition and be independent of any test facility incorporated in the RCD. The test currents to be applied are as follows: Test current Condition 0.5 x I I:J. n RCD must not trip 1.0 x I I:J. n RCD must trip within 300mS 5.0 x II:J. n RCD must trip w ithin 40mS Where l t:j. n is the RCD's rated tripping current in accordance with wiring regulations and product standard BS EN 61006. For time delay RCD 1.0 x I I:J. n RCD must trip between 130-500mS.

by Honoyw911 Sentry Technical technical hotline +44 (0)1268 563720 Dimensions (mm) 85 69Max 35.6 60 I @ @ ~ =- - 0 L ~ J 0 m ~ Gil - - lu I 6 44 16 45.. 69Max 72 60 ~ I 85 @ 0 @ 0 @ 0 @ ~ - ~ : _ ~ :. ~...: _,.,... 0 '- "" @ @ @ @ r [31 w ~ - - 6 44 16 45