Installation/operation instructions. Insulation monitor type SIM-Q/SIM-Q LF D (UK) Measuring range 1...0Mohm or 10...

Similar documents
DEIF A/S. Insulation monitor. Type SIM-Q

DEIF A/S. Insulation monitor. Type SIM-Q/SIM-Q LF

TCM-2 Thyristor Control Module DATA SHEET

Installation and start up instructions. Detection of vector shift. Detection of over- and underfrequency. Generator disconnection on mains failure

Installation and start up instructions. Synchroniser type FAS-115DG uni-line H (UK) Synchronisation of generator to busbar

Installation and start up instructions. Paralleling relay type HAS-111DG uni-line G (UK) Synchronisation of generator to busbar

Installation and start up instructions. Synchroniser type FAS-113DG uni-line F (UK) Synchronisation of generator to busbar

DATA SHEET. Voltmeters and Ammeters,

DATA SHEET Differential current relays, RMC-131D ANSI code 87

DEIF A/S. TAS-311DG Selectable AC transducer J (UK) Installation and start up instructions

Function. Adjustment. Extra functions included. Modes. Housing

Installation Instructions and Reference Handbook. Installation instructions

1. General Instructions 2 2. Safety 2 3. Lamp Starting Test Instrument LSTI 5 3

DEIF A/S. Application note. Generators parallel with mains Multi-line 2 version 2. Application description. Power import control. Power export control

VCE VET INTEGRATED TECHNOLOGIES

DIGITAL MULTIMETER CONTENTS DIGITAL MULTIMETER CONTENTS

RMV-122D, RMV-132D ANSI

DVM98. True RMS Digital Multimeter. 1 Safety information. 1.1 Preliminary. 1.2 During use

Automatic synchronising relay

XR1 Rotor Earth Fault Relay. (May 2007) Manual XR1 (Revision New)

ISOMETER IRDH575. Approvals

DATA SHEET Reverse power relays, RMP-121D ANSI code 32

User s Manual. MiniTec TM Series. Model MN26 (Model MN26T includes temperature probe) Mini Autoranging MultiMeter

Angle position transmitter Type RT-2 Marine bridge instrumentation C (UK) Measuring output: DC current signal 0..20mA or 4..

DATA SHEET. Switchboard instruments,

XR1 Rotor Earth Fault Relay. Manual XR1 (Revision C)

DC Circuits, Ohm's Law and Multimeters Physics 246

270 manual.qxd 5/9/2005 3:04 PM Page 1. Digital Clamp-on Meter Instruction Manual

DEIF A/S. Application Notes. MDR-2 test procedures. Test of current measurement. Test of differential current measurement.

Dipl.-Ing. W. Bender GmbH & Co. KG Londorfer Str Grünberg Tel.: Fax:

OPERATOR S INSTRUCTION MANUAL

BENCH METER Model>9803. Wavecom Instruments

Phase and neutral overcurrent protection

DVM645BI BENCH MULTIMETER TAFELMULTIMETER MULTIMETRE DE TABLE BANCO MULTÍMETRO TISCHMULTIMETER. User Manual. Gebruikershandleiding

ISOSCAN EDS460-DG. Insulation fault locator for DC IT systems with high system leakage capacitances

MultiMeter-Pocket CAT III 1000 V

IDEAL INDUSTRIES, INC. TECHNICAL MANUAL MODEL: MODEL: Multimeter Service Information

AC/DC DIGITAL CLAMP METER OPERATION MANUAL

Design and Technology

AC/DC Power Supply Series APPLICATION NOTE

RAGU 81D DIGITAL MULTIMETER OPERATION MANUAL

OPERATOR S INSTRUCTION MANUAL M-2625 AUTO RANGING DIGITAL MULTIMETER

DATA SHEET Selectable AC transducer TAS-311DG

MODEL: D03128 CLAMP METER

DIGIT & POINTER MULTIMETER

2000 A DCA/ACA CLAMP + DMM,

DEIF A/S. Application Notes. Basic Gen-set Controller. Single generator set. Automatic mains failure. Parallel with mains (grid)

MS2109A AC/DC Clamp Meter. User Manual. Contents

Model ST Instruction Manual. True RMS Autoranging Digital Multimeter. reedinstruments. www. com

isolr275 / AGH-LR Digital Ground Fault Monitor / Ground Detector For Low-Resistance Ungrounded (Floating) AC/DC Systems

The future of installation testing is here. The Fluke 1650 Series Multifunction Testers

AC/DC Power Supply Series APPLICATION NOTE

CM-IWM.11 Insulation monitoring relay

Power supply CP-E 24/2.5

AC/DC CLAMP METER USER S MANUAL

DLVP A OPERATOR S MANUAL

Power supply CP-E 24/20.0

DATA SHEET. CIO multi-inputs. CAN bus-based I/O module

User Guide. Digital AC/DC Clamp Meter Model 38394

DIGITAL MULTIMETER INSTRUCTION MANUAL

Earth fault protection for isolated neutral systems with frequency converters

USER'S MANUAL DMR-6700

R/C SMD Tweezers Multimeter Model RC200

User s Guide. Digital AC/DC Clamp Meter Model 38394

(240 ) Measurement of DC currents and DC voltages. Size (mm): Q48 Q144 Q72 Q144 Q48 Q144

Instruction Manual for Digital Grounding Resistance Meter. Table of Contents

MM V 10A ENGLISH. INSTRUCTION MANUAL Auto-Ranging DATA HOLD AUDIBLE CONTINUITY MIN / MAX TEMPERATURE DIODE TEST CAPACITANCE

DIGITAL MULTIMETER. MODEL CDM-50 Part No OPERATING INSTRUCTIONS

2.7. IT system floor-standing distribution cabinet Series -IPS-F/EDS

Model DIGITAL MULTIMETER

T6+ Analog I/O Section. Installation booklet for part numbers: 5/4-80A-115 5/4-90A-115 5/4-80A /4-90A-1224

Instruction Manual for Digital Grounding Resistance Meter

AC/DC Power Supply Series APPLICATION NOTE

AC/DC. Monitoring Technique. VARIMETER IMD Insulation monitor RN 5897/300

Pen-type DIGITAL MULTITESTER

ELECTRICAL POWER TRANSMISSION TRAINER

Power supply CP-E 12/10.0 Primary switch mode power supply Data sheet

OWNER S MANUAL HH0308C. AUTO-RANGING DC/True RMS AC DIGITAL MULTIMETER

Autoranging Multimeter Extech EX503

DIGITAL CLAMP METER Use s Manual

MM700. True RMS ENGLISH. INSTRUCTION MANUAL Auto-Ranging. Measurement Technology

DIGITAL MULTIMETER OPERATING INSTRUCTIONS MODEL CDM-35. Part No

Protection relays and controllers. Types TRANSAL DC-2TF, ACV-3TF, ACI-3TF, PFC-2TF TRANSAL DC-2TB, AVC- 3TB, ACI-3TB, PFC-2TB

200Amp AC Clamp Meter + NCV Model MA250

770E DIGITAL MULTIMETER OPERATOR S MANUAL

Multifunction AC/DC Voltage Tester

3B SCIENTIFIC PHYSICS

8000 SERIES PRECISION MULTIMETER VERIFICATION AND ADJUSTMENT GUIDE

MEGGER BMM2000 Series Insulation Multimeters User Guide

ET 61 - Electrician Theory Examination Marking Schedule

User's Guide Mini Multimeter with Non-Contact Voltage Detector (NCV) Model EX330

IDEAL INDUSTRIES, INC. TECHNICAL MANUAL MODEL:

Digital Clamp Meter Model: &

MS8268 HANDHELD DIGITAL MULTIMETER OPERATOR S INSTRUCTION MANUAL

Power supply CP-E 48/5.0 Primary switch mode power supply Data sheet

User s Guide. MultiView Series Digital MultiMeters Models: MV110 MV120 MV130

OPERATING INSTRUCTIONS

SET Installation and Operating Instructions. Level switch for two sensors

CONTENTS. SAFETY PRECAUTIONS: Before use, read the following safety precautions

400Amp True RMS AC/DC Clamp Meter Model EX613

Transcription:

Installation/operation instructions Insulation monitor type SIM-Q/SIM-Q LF Monitoring of insulation resistance on an AC network Working voltage up to 690V AC, withstands up to 1000V DC Measuring range 1...0Mohm or 10...0Mohm Working frequency down to 5Hz (SIM-Q LF) DEIF A/S Alarm on exceeding the adjusted set point 3 functions: Monitoring, fault finding, test AC and DC auxiliary voltage DEIF A/S Tel.: (+45) 9614 9614 Frisenborgvej 33, DK-7800 Skive Fax: (+45) 9614 9615 Denmark E-mail: deif@deif.com

Generally Description The SIM-Q is intended for insulation monitoring on a single-phase or a 3-phase IT power system with or without neutral. The special characteristic of an IT power system is the fact that no live conductor is connected directly to earth. The SIM-Q is connected to the power system by connecting the terminal marked P to one of the phases (or the neutral). The PE input is then connected to the safety cable. To be able to monitor any kind of insulation failure, all accessible conductive building structures must be connected to the cable marked PE (protective earth). Installation Connection If a test function is desirable, an arrangement based on a resistor and a push-button can be mounted as illustrated on the drawings below. The value of the resistor can be any value from 0Ω to the max. allowed insulation value. The SIM-Q can be supplied from the IT system under supervision, but it can also be supplied from another source, e.g. a 24V DC source, see the label for supply information. The following functions can be selected by means of the switch available from the front of the SIM-Q: Monitoring, fault finding and test. L1 L2 L3 N PE L N PE 22k/ 220k 22k/ 220k TEST TEST 1 3 2 PE P X4 X3 X2 X1 1 3 2 PE P X4 X3 X2 X1 With the switch in monitoring mode, the SIM-Q will run a fast measuring mode the first 15 seconds after a power-up. This mode can be used to perform a switchboard test. When a known resistor is connected for testing, the aux. supply is disconnected and reconnected at the same time (not shown in the illustration). The response time for measuring the known resistor will be approx. 6 seconds. The 2 red LEDs will be illuminated, but the relay contact will not be activated. After 15 seconds the SIM-Q automatically changes to normal monitoring mode. As an alternative the test can be carried out in fault finding mode. The response time will be 1 second, and if the set point is exceeded the relay output will be activated. If the switch is moved to position Test, an internal function test of the SIM-Q is carried out. The reading on the scale during the test is 0 ohm, and the relay output is activated. Page 2 of 9 Tel.: (+45) 9614 9614 Fax: (+45) 9614 9615 E-mail: deif@deif.com

Connection of AC auxiliary supply Installation/operation instructions SIM-Q/SIM-Q LF Type: 80...152V AC Type: 176...288V AC Type: 320...576V AC X 1, X 2: 100V AC ±20% X 1, X 2: 220V AC ±20% X 1, X 2: 400V AC ±20% X 1, X 3: 110V AC ±20% X 1, X 3: 230V AC ±20% X 1, X 3: 450V AC ±20% X 1, X 4: 127V AC ±20% X 1, X 4: 240V AC ±20% X 1, X 4: 480V AC ±20% Label for AC version Connection of DC auxiliary supply Type: 24V DC X 1 - X 2 + Label for DC version Dimensions Page 3 of 9

Configuration of the relay function The relay contact can be configured to either a normally energised contact (NE) or a normally de-energised contact (ND). ND function is recommended, if the SIM-Q is supplied from the IT system under supervision, because a disconnection of the supply will not result in an alarm. Figure 1 below shows the location of the switch S1 on the PCB for selection of either ND or NE relay function. The PCB is located under the lid. 50μF 1M ND S1 500μF 10M NE Example: Max. 50μF leakage capacitor is selected 1MΩ is selected as measuring range ND is selected as relay function Note: On SIM-Q LF S1 must always be in the 500μF position! Figure 1 IMPORTANT - Use electrostatic discharge protection! Sufficient care must be taken to protect the PCB against static discharges during the configuration. Once the unit is installed and connected, these precautions are no longer necessary. Configuration of the max. leakage capacitor (stray earth capacitance) The leakage capacitor is normally a phenomenon based on the cables in the power system. When the cables are mounted close to the metal structure, e.g. the hull of the ship, a capacitive coupling is unavoidable. The size of the capacitor can be measured using insulation test equipment based on a known frequency and a known test voltage. If only the cables contribute to the leakage capacitor, the capacitor will be small - less than 1μF. On the other hand, the leakage capacitor can be very big, if the loads connected to the power system are based on frequency converters cooling containers Page 4 of 9 Tel.: (+45) 9614 9614 Fax: (+45) 9614 9615 E-mail: deif@deif.com

1114020xxxA Installation/operation instructions SIM-Q/SIM-Q LF and other electronics equipment. The reason is that all these loads normally have decoupling capacitors mounted on the power port, and these decoupling capacitors are normally connected to the ground and then also connected to the protective earth (PE). Regarding measurement of the total leakage capacitor, please see the appendix. Configuration of the measuring range The SIM-Q can be configured for measuring range 1 0MΩ with 22kΩ on the scale centre or for 10 0MΩ with 220kΩ on the scale centre. Figure 1 shows the position of the switch for selection of either 1MΩ or 10MΩ measuring range. Please notice that a change of measuring range also involves a change of scale. Change of scale can be done by following the instructions below. Figure 2 Interrupt signal/supply to the terminals before exchanging the scale Push the scale cover towards the rear edge Remove the scale by means of a screwdriver or the like Insert new scale and press gently till it snaps into place Push the scale cover back again, after this the unit is ready for mounting Adjustment of the set point The requested alarm limit value is set on an ohm scale on the rear of the instrument, see Figure 3. Range "x10" is marked: The scale values on the ohm scale are multiplied by 10. Typical setting: Insulation resistance corresponding to lower limit of the section marked with red on the instrument scale. Figure 3 Page 5 of 9

If precise alarm settings are wanted, a known resistor corresponding to the red section on the instrument scale is connected between P and PE. Then adjust the potentiometer until alarm is transmitted. For fast response, set the switch on the front in the fault finding position. Operation Indicators The SIM-Q is equipped with 3 LED indicators, one green LED and 2 red LEDs. Only the green indicator marked SUPERVISION is lit when the unit is connected to auxiliary supply and no insulation error is detected. If the SIM-Q detects a change in the insulation measurement, the SUPERVISION LED starts flashing with a fast rate. If the insulation error detected is fluctuating, the internal integration time is automatically extended, which is indicated by a slower flash rate. As long as the SUPERVISION LED is flashing, the latest measured value is kept and indicated on the instrument until a new value is found, then the reading on the instrument is updated. Please notice that if the insulation is fluctuating, the green LED will flash most of the time, but updates will be performed within 450 seconds (setting 50μF) or 2400 seconds (setting 500μF) as a maximum. The 2 red LED indicators marked +FAULT and -FAULT are illuminated, if an insulation error below the set point is detected. If a DC voltage (component) occurs on the system together with an insulation error, the +FAULT or the -FAULT LED is illuminated, indicating the polarity of the DC voltage. This function will indicate where to look for the insulation error. In case only one red LED is illuminated, the fault is to be found in a load with a built-in rectifier, e.g. a frequency converter. If a DC voltage is detected, but the alarm limit value is not yet reached, the +FAULT or the -FAULT LED will flash to indicate that there is a DC component higher than 50V DC between the power system and earth (PE), but no insulation error below the alarm limit value yet. Figure 4 below illustrates a situation where a DC can occur between the P and the PE input of the SIM-Q. Figure 4 Page 6 of 9 Tel.: (+45) 9614 9614 Fax: (+45) 9614 9615 E-mail: deif@deif.com

Installation/operation instructions SIM-Q/SIM-Q LF The capacitor marked C illustrates the leakage capacitor. The diodes marked 1 and 2 illustrate the rectifier in the load. If the situation is as illustrated at diode marked 2, the +FAULT LED is illuminated. If the situation is as illustrated at diode marked 1, the -FAULT LED is illuminated. Response time responsetime 50uF responsetime 500uF sekunder 500 450 400 350 300 250 200 150 100 50 0 0 10 20 30 40 50 60 70 SIM-Q 80 90 kohm 100 200 500 1000 10000 sekunder 3000 2500 2000 1500 1000 500 0 10 20 30 40 SIM-Q/SIM-Q LF 50 70 kohm 100 500 1000 10000 The above curves illustrate the response time with an actual leakage capacitor of 50μF and 500μF. If the leakage capacitor is less than 50/500μF, the response time will then be reduced in time accordingly. Note: If the insulation error is fluctuating, the above response times will be prolonged, however, no longer than the above max. values (450 seconds/2400 seconds). If there is a leakage capacitor in the system, the SIM-Q will indicate an insulation error for the first 15 seconds after a power-up. If the set point is exceeded, the 2 red LEDs will be lit, but the relay output is inhibited for the first 15 seconds after power-up. If the installation contains frequency converters working down below 20Hz, the SIM-Q LF should be used instead, providing reliable measurements down to 5Hz. Fuses: Recommended fuse for aux. supply X2, X3, X4 max. 2A. Warning: If the installation is to be tested by means of a high-voltage "MEGGER", the measuring leads to the SIM-Q at terminal "p" must be disconnected before testing is carried out. Omitting this may result in damage to the SIM-Q, if the test voltage is higher than 1000V AC/DC. Besides the insulation test will be affected by the built-in DC voltage generator impedance (approx. 250kΩ). Technical specifications Please see the data sheet, document no. 4921230020. Page 7 of 9

Appendix Measuring of the leakage capacitance in a connected network using a voltmeter and amp meter (SL = PE) Single phase: CE = A/(V x 2 x phi x f). Phi is 3.14 and f is the frequency in Hz. 3 phases: CE = A/(V x 3 x 2 x phi x f). Example for a 3-phase system: The amp is measured to 30A and the voltage is measured to 400V: CE = 30A/400V x 3 x 2 x 3.14 x 50Hz = 137μF per phase, total CE is 3 x 137μF = 411μF. For a 4-wire network the CE total = CE x 4. Page 8 of 9 Tel.: (+45) 9614 9614 Fax: (+45) 9614 9615 E-mail: deif@deif.com

Installation/operation instructions SIM-Q/SIM-Q LF Measuring of the leakage capacitance in a disconnected network using an ma meter, a voltmeter and an AC source with a known frequency CE total = ma/(v x 2 x phi x f). Phi = 3.14 and f is the frequency in Hz. Example where the ma is measured to 100mA and the voltage from the AC source is measured to 50V AC: CE total = 0.1A/50V x 2 x 3.14 x 50) = 6.3μF. Using the fault finding function of the SIM-Q to estimate the size of the leakage capacitor Please notice that this method can only be used in cases where no insulation error is present. Set the switch in fault finding position. Discharge the leakage capacitor by short-circuiting P and PE by means of a low impedance load, e.g. a bulb suitable for the AC voltage level on the system. Open the short circuit between P and PE. Then measure the time (t) that elapses until the instrument indicates approx. 0.5 (0.05) Mohm on the scale. Using the formula C = t/0.3, the approx. leakage capacitor in μf (microfarad) can be calculated. Example: t = 10 seconds, C = 33μF. Errors and changes excepted Page 9 of 9