ABB flowmeter technology FSM4000 AC-excited magmeter

Similar documents
Ambient Conditions. Operating Conditions. Pressure

ADDMAS CORIOLIS MASS FLOW METER

Electro-Magnetic Flowmeters COPA-XE

Flow Technologies Overview. For internal use only / Siemens AG All Rights Reserved.

ARE HARMONICS STILL A PROBLEM IN DATA CENTERS? by Mohammad Al Rawashdeh, Lead Consultant, Data Center Engineering Services

ESA400 Electrochemical Signal Analyzer

www. otech.com.sg EFS801 ELECTROMAGNETIC FLOWMETER

SITRANS F flowmeters. SITRANS F System information MAGFLO electromagnetic flowmeters 4/9

Magnetic-inductive flow meter. PITe / UMF2. Technical Datasheet. Maintenance-free Nearly no pressure drop Robust design Easy installation and start-up

FLOMID FX Electromagnetic Flowmeter

ME scope Application Note 02 Waveform Integration & Differentiation

ABB Measurement & Analytics. FSM4000 The electromagnetic flowmeter of choice For critical applications in a wide range of industries

Overall Accuracy = ENOB (Effective Number of Bits)

This tutorial describes the principles of 24-bit recording systems and clarifies some common mis-conceptions regarding these systems.

Marketing Communications

Technology and Benefits of Programmable Linear Position Sensors (Based on Inductive Measurement)

Linear vs. PWM/ Digital Drives

FLOW SWITCH 600 Series Velocity Flow Sensor. Instruction Manual

Field IT Electro-Magnetic Flowmeters Mini-Mag with integral XE converter

Analog Devices: High Efficiency, Low Cost, Sensorless Motor Control.

OPTIFLUX 5000 Technical Datasheet

Achieving accurate measurements of large DC currents

SITRANS F flowmeters SITRANS F M. Transmitter Transmag 2 with sensor 911/E 4/77. Overview

Latest Control Technology in Inverters and Servo Systems

SITRANS F flowmeters. SITRANS F M System information MAGFLO electromagnetic flowmeters. 4/18 Siemens FI

MRI SYSTEM COMPONENTS Module One

Lauren Gresko, Elliott Williams, Elaine McVay Final Project Proposal 9. April Analog Synthesizer. Motivation

Reduce Load Capacitance in Noise-Sensitive, High-Transient Applications, through Implementation of Active Filtering

PhD Inline Vortex. Performance Specifications Accuracy. Operating Specifications

Suppression of Powerline Noise with Isolation Transformers

OPTIFLUX 5000 Technical Datasheet

Proven Measurement for A World of Applications

Digital Signal Processing. VO Embedded Systems Engineering Armin Wasicek WS 2009/10

Introduction To Temperature Controllers

NOTICE. The above identified patent application is available for licensing. Requests for information should be addressed to:

Power Quality Monitoring and Power Metering Tutorial

Photometer System Mar 8, 2009

EIS Measurement of a Very Low Impedance Lithium Ion Battery

Sonic Distance Sensors

Vibrating Wire Instrumentation

-binary sensors and actuators (such as an on/off controller) are generally more reliable and less expensive

TECHNICAL BULLETIN 004a Ferroresonance

Step vs. Servo Selecting the Best

UNIT II MEASUREMENT OF POWER & ENERGY

UNIT-3. Electronic Measurements & Instrumentation

ECET 211 Electric Machines & Controls Lecture 4-2 Motor Control Devices: Lecture 4 Motor Control Devices

Chapter 2 Analog-to-Digital Conversion...

White Paper: Electrical Ground Rules

COVENANT UNIVERSITY NIGERIA TUTORIAL KIT OMEGA SEMESTER PROGRAMME: MECHANICAL ENGINEERING

Efcon Water. Installation & User Manual Electro Magnetic Flowmeter (EMF) Efcon Water compact Electro Magnetic Flowmeter (EMF) Manual Version UK

Technical note. Impedance analysis techniques

A NOVEL METHOD OF RATIO CONTROL WITHOUT USING FLOWMETERS

Common Mode Susceptibility of Computers

4. Digital Measurement of Electrical Quantities

1. Introduction to Power Quality

Application Note (A13)

High Performance ZVS Buck Regulator Removes Barriers To Increased Power Throughput In Wide Input Range Point-Of-Load Applications

LIMITATIONS IN MAKING AUDIO BANDWIDTH MEASUREMENTS IN THE PRESENCE OF SIGNIFICANT OUT-OF-BAND NOISE

Time Matters How Power Meters Measure Fast Signals

Non-Contact AC Voltage Probe SP3000, AC Voltage Probe SP9001

Electro-hydraulic Servo Valve Systems

Enhanced Resonant Inspection Using Component Weight Compensation. Richard W. Bono and Gail R. Stultz The Modal Shop, Inc. Cincinnati, OH 45241

A DSP IMPLEMENTED DIGITAL FM MULTIPLEXING SYSTEM

Module 1: Introduction to Experimental Techniques Lecture 2: Sources of error. The Lecture Contains: Sources of Error in Measurement

OMNETICS CONNECTOR CORPORATION PART I - INTRODUCTION

Understanding PID Control

CHAPTER 3. Instrumentation Amplifier (IA) Background. 3.1 Introduction. 3.2 Instrumentation Amplifier Architecture and Configurations

D102. Damped Mechanical Oscillator

MEMS Optical Scanner "ECO SCAN" Application Notes. Ver.0

Signal Detection with EM1 Receivers

Modal damping identification of a gyroscopic rotor in active magnetic bearings

OIL AND WATER SEPARATION AT ITS BEST

Application Note (A12)

THE BENEFITS OF DSP LOCK-IN AMPLIFIERS

Electromagnetic Flow Transmitter

Isolated, Linearized Thermocouple Input 5B47 FEATURES APPLICATIONS PRODUCT OVERVIEW

Differential ph Design Overcomes Common ph Sensor Challenges

FLOMID-MX Control unit for electromagnetic flowmeters USERS MANUAL. instrumentación para fluidos. Realitzat: Revisat R+D Electrònic: Aprovat: Data:

A Practical Guide to Free Energy Devices

Section 7 - Measurement of Transient Pressure Pulses

OVERVIEW OF SVC AND STATCOM FOR INSTANTANEOUS POWER CONTROL AND POWER FACTOR IMPROVEMENT

Designers Series XIII

LZYN Triangle Series Mass Flow Meter

4/30/2012. General Class Element 3 Course Presentation. Practical Circuits. Practical Circuits. Subelement G7. 2 Exam Questions, 2 Groups

Total Consistency Measurement. Metso Microwave Consistency Transmitter

A Self-diagnostic Method for the Electrode Adhesion of an Electromagnetic Flow-meter

5. Transducers Definition and General Concept of Transducer Classification of Transducers

Filter Considerations for the IBC

Load Isolation Transformers

Oscillator/Demodulator to Fit on Flexible PCB

Preventing transformer saturation in static transfer switches A Real Time Flux Control Method

HI 2204LT Loop Powered Level Weight Transmitter OPERATION AND INSTALLATION MANUAL

User s Manual for Integrator Long Pulse ILP8 22AUG2016

A Unity Power Factor Boost Rectifier with a Predictive Capacitor Model for High Bandwidth DC Bus Voltage Control

Basic Electronics Learning by doing Prof. T.S. Natarajan Department of Physics Indian Institute of Technology, Madras

KMS101W. ManuFlo Page 1 MANU ELECTRONICS PTY LTD Flow Measurement Products. Electromagnetic Wafer Flowmeters with S100 display

USER MANUAL MODEL USFT-CS ULTRASONIC FLOW TRANSMITTER. Rev04009 USER MANUAL DEI MODEL USFT-CS

How to Select the Right Positioning Sensor Solution A WHITE PAPER

Faraday Laws of Electromagnetic Induction CLIL LESSON

Common-emitter amplifier, no feedback, with reference waveforms for comparison.

Transcription:

White paper ABB flowmeter technology FSM4000 AC-excited magmeter Innovative AC-excited magmeter benefits pulp and paper operations by Greg Livelli, ABB Measurement Products Design innovations in AC-excited magmeters offer the fast response and noise-free outputs with the zero-drift performance of pulsed DC magmeters The pulp and paper, metals, and mining industries hold some of the most aggressive and challenging applications for electromagnetic flowmeter (magmeter) measurement. Changing operating conditions, higher consistency and solid contents, and tighter process control are pushing the boundaries of magmeter performance. Conventional electromagnetic flowmeters using DC excitation have been used to measure flow in these noisy and difficult applications, but they are typically saddled with long damping times to smooth their output. This results in slow response times and ultimately waste and quality issues. Recent improvements in AC electromagnetic flowmeters can now provide these users with better performance, quicker response, and noise-free outputs not possible with DC technology. These improvements can lead to increased efficiency, improved quality, and conservation of raw materials and energy, reducing direct costs and increasing profits. The new AC magmeters can perform well in the simplest to the most extreme applications, making them a universal solution to conductive liquid flow measurement. Reviewing electromagnetic flowmeter principles The principle of operation for magnetic flowmeters is based on Michael Faraday s law of electromagnetic induction. Magnetic coils are excited by an AC or DC current creating a magnetic field within a meter body through which a conductive liquid passes. This voltage is extracted through a pair of electrodes which are installed on opposite sides of the pipe. The voltage developed is proportional to the density of the magnetic field, the length of the conductor, and the velocity of Figure 1. Conductive fluid flows through a field produced by an electromagnet, generating a voltage at the electrodes (Faraday's Law). the conductor moving through the field. There is nothing in the function of magnetic flowmeters that depends on pressure, temperature, density or viscosity because the magmeter develops its signal independent of these parameters. The volumetric flow rate through the magmeter is an easily derived function of this velocity signal and the known cross-sectional area of the meter body. The raw voltage signal (on the order of micro-volts) then goes to a transmitter for processing and conversion to a signal suitable for process control or for simple totalization. Internal noise signals accompany the raw flow velocity signal. Appropriate measures such as shielding, insulation, and capacitance neutralization can eliminate internal noise. Signals from sources external to the flow meter (such as electrically charged fluids, large particles, and electrochemical potentials at the electrode interface) also introduce unwanted electronic noise into the system. In addition, electromagnetic fields at line frequency present in virtually all installations contribute to the external noise. 1 ABB

Electronic noise does not affect AC and DC excited systems in the same way. Noise effects must be considered in the context of both zero shift and flow signals respectively. AC verses DC excitation systems Early electromagnetic flowmeters were all excited by AC. The magmeter coils were energized by line voltage (120 VAC +/- 10%) at 60 Hz line frequency. Figure 2 shows the resulting sinusoidal (sine) waveform developed by the signal electrodes of an AC magmeter. The amplitude of the waveform varies directly as the flow rate through the magmeter. The AC magmeter proved to be a significant advancement when compared to flow measurement by differential pressure techniques. It offered no obstruction to the flow and could measure flow rates over a much wider ranges. Additionally, in cases of rapidly changing flow conditions, and, most significantly, when the pipe became empty, the AC magmeter provided fast fullscale response time. It recovered quickly from a nonfull state. Figure 2. Typical sine waveform for the AC line voltage energizing the electromagnet and for the resulting signal voltage from the electrodes. But the zero flow signal of conventional AC meters tended to drift, requiring repeated recalibration. The primary weakness of conventional AC systems is this zero-shift. The phenomenon is best understood by appreciating that Faraday s Law cuts two ways. As noted, the measured voltage is proportional to the velocity of the fluid passing through a magnetic field created by excitation. It's equally true that non-moving conductors, such as electrode signal wires near the varying magnetic field, also generate voltage. Figure 3. Typical pulsed-dc waveform for exciting the electromagnets. During the off part of the cycle, any measured voltage constitutes electric noise. In conventional AC-excited magnetic flowmeters, the continuous alternating current in the presence of a stationary conductor (the fluid at zero flow rate) creates a varying non-flow induced voltage, which is electronic noise. Typically, noise created by fixed conductive electrode wires can be zeroed out by operators during start-up (or even eliminated by circuitry if the voltages are out of phase with each other). However, non-moving conductive coatings that accumulate on the electrodes during normal process conditions (after zeroing the system) often cause an apparent shift in zero in conventional AC systems. The introduction of pulsed DC electromagnetic flow meters went a long way towards solving the problem of maintaining a stable zero flow signal. Pulsed DC magmeters were originally energized by low voltage (~10 VDC) at 3¾ Hz. Instead of continuous power to the coils, the coils are both energized and deenergized during a voltage cycle. Figure 3 shows the square -like pulse waveform developed by the signal electrodes of a pulsed DC magmeter. During the off part of the cycle, any measured voltage constitutes electric noise. The measuring system can automatically and continuously compensate for this noise, greatly reducing the zero signal drift. As a result, pulsed DC magnetic flowmeters can maintain a stable signal for zero flow that is less affected by coating deposits on the signal electrodes. Dealing with process signal noise Despite this advantage, pulsed DC magnetic flowmeters have often proved unsuccessful in certain applications because of process noise, which comes in two forms: 1/f noise and electrode impingement. The 1/f noise decreases with excitation frequency. More 2 ABB

noise occurs at low frequencies, especially at 10 Hz and less. The major problem with this process noise is that the low levels of the magnetic coil excitation result in a greater chance for disruption of the flow measurement. Figure 4 shows this 1/f noise function in graphical terms. The magnitude of 1/f noise typically depends on the severity of conditions in a field installation. For example, in low consistency (0 to 3%) pulp stock flows, the 1/f Figure 4. Process noise diminishes with frequency, except for a spike at 60-Hz line voltage frequency. noise increases as stock consistency increases. Also, chemical additions upstream and near a magmeter often produce 1/f noise as a function of rapidly changing fluid conductivities, which disturb the electrode interface. The second type of process noise is a phenomenon known as electrode impingement. This is a mechanical disturbance of the electrode/electrolytic interface of the process fluid with the electrode surfaces. These disturbances cause the electrode signal to temporarily spike several times its normal magnitude. This noise is typical of heavy liquors that contain a variety of solids particles. In addition, most slurries represent a potential to display electrode impingement characteristics to various degrees. Reducing noise content The original pulsed DC magmeters operated at 3¾ Hz (waveform cycles of 3¾ times per second). This low frequency coil excitation produced excellent zero stability, but was susceptible to 1/f noise. In recent times, pulsed DC magmeter vendors have attempted to reduce the effect of 1/f noise by increasing the signal filter's low frequency cutoff value as well as by increasing the coil excitation frequency. But two problems arise. First, the signal filter can also eliminate part of the live process signal being measured, adversely affecting magmeter accuracy. Second, as coil excitation frequency increases, the square waveform begins to deform, taking on the some of the characteristics of the AC magmeter. The waveform begins to droop, becoming distorted. Because the pulsed DC magmeter measures process noise when the coils are de-energized, a droopy waveform makes it increasingly difficult for the signal converter to accurately separate process noise from process signal. For example, a 30 Hz coil drive will experience 1% droop in the square waveform when the low frequency cut-off is 0.3 Hz, and a 10% droop if the cut-off is raised to 3 Hz. Ultimately, this can lead to pulsed DC magmeter inaccuracies and non-repeatabilities. Pulsed DC noise suppression algorithms have had limited success in reducing the problems associated with mechanical disturbances. Process noise, because its magnitude is a relatively large portion of the pulsed DC magmeter s flow signal, also tends to distort the flow measurement. The historic fix is to increase the damping constant until the signal converter s analog output ceases to be erratic. Because of the resulting long response times, this fix greatly reduces the ability to control production processes by means of magmeter flow measurement. Typically, pulsed DC magmeters in these cases serve only for monitoring purposes. The AC magmeter, on the other hand, has a high signalto-noise ratio in noisy flow applications. The AC magmeter delivers more power to the magmeter coils, so the measured electrode signal is a higher voltage compared to a DC meter. Most specifications for power consumption call for pulsed DC magmeters 24 inches and smaller to consume no more that 23 VA, while AC magmeters of the same size consume no more than 50VA. The higher power requirements of the AC magmeter help to establish a measuring system that is much less susceptible to the ill effects of process noise. 3 ABB

As a result of noise issues, AC magmeters are often selected over pulsed DC magmeters on difficult, highly noisy applications. They more rapidly respond to changing flow conditions and recover more quickly from empty pipe conditions. Closing the gap Although the pulsed-dc method of magnetic field excitation predominates today, it has not replaced AC technology entirely. AC magmeters are more resistant to process generated noise created by varying fluid conductivities and slurries, making them more suitable for many demanding applications. Various innovations have reduced the functionality gap between DC and AC magnetic flowmeter, namely: - the introduction of hard electrode tips, - higher operating frequencies, - microprocessor techniques in noise reduction. But in the final analyses, conventional AC magnetic flowmeters still outperform DC designs with respect to process noise; whereas DC magnetic flowmeters are inherently better with respect to zero stability. The FSM4000 AC magmeter from ABB contains more innovations to close the gap with pulsed DC. For example, the FSM4000 operates at an optimal 70 Hz, a Figure 5. Excitation of the FSM4000 magmeter takes place at 71.43 Hz, a frequency characterized by minimum process noise. Advanced DSP techniques further enhance noise reduction. frequency in the low part of the noise spectrum. Operating at this frequency eliminates virtually all need for output signal dampening used in noisy applications. In addition, the FSM4000 eliminates zero-shift through use of a field search coil, which allows the processor to subtract electronic noise signal from the aggregate of the noise and flow signal. To accomplish this, the signal and reference values are stored after filtering, and are available in their respective results buffer at a sample rate of 4kHz. The 71.43Hz magnetic field excitation frequency is a multiple of the sampling frequency. As a result, the number of measured values per period has an integer value, producing exactly 56 samples per excitation period. In this way, exactly one period of the measured signal can be stored in the respective results buffers. To determine the measured flowrate, the ratio of the signal to reference must be known. For this purpose, the areas of the signal and reference are integrated and inserted in the ratio computation. The start signal for the calculation of the flowrate is the zero crossing of the reference- -easily determined by waiting for the change in the sign of the measured values sent. The system determines the phase shift between the signal and the reference by examining the zero crossing of the signal and reference using samples and partial samples. The phase shift constitutes the zero adjustment for the flowrate measurements, enhancing zero stability. The result is a magmeter with faster dynamic response, yielding tighter accuracies and higher signal-to-noise ratios. Digital Signal Processing Advances in digital signal processing (DSP) have made it easier for users to develop data acquisition systems (signal converters) and analysis systems. The term DSP is misleading because it is usually associated with Fast Fourier Transforms, digital filters, and spectrum analysis. DSP, however, involves processing of an analog signal in the digital domain. Real-world signals, such as voltages, pressures, and temperatures are converted to their digital equivalents for processing by the digital microprocessor. Digital Signal Processing relies more heavily on the soft 4 ABB

ware processing of signals in the digital mode rather than using analog hardware and filtering to do the job. Processing a digital signal offers more alternatives, and software is much more flexible than hardware. These benefits lead to more effective methods of separating the real signal from the process noise. Tangible advantages include: improved measurements in applications involving vibration, hydraulic noise, and temperature fluctuation. As with any electromagnetic flowmeter, unwanted frequency signals can be generated caused by hydraulic noise and line noise. DSP provides faster A/D conversions for the sensor signal, providing a greater number of sample points compared to prior technologies. Digital filters, with sharp drop-offs, eliminate signal frequencies created by hydraulic noise and line noise that are outside the targeted measurement range. Advanced filtering techniques, such as automatic filter adaptation and frequency weighting, further allow the processor to accurately extract the flow signal from a potentially noisy sensor signal. By employing the power of the DSP Converter, improvements are made to zero stability, low flow performance, and measurement accuracy over a wide range of conditions. Independant tests confirm performance The Herty Foundation (Savannah, GA) performed independent tests of the ABB FSM4000 flowmeter. The foundation ran several tests against competing electromagnetic flowmeters in the pulp and paper industry. To duplicate actual mill conditions near the short circulation piping of the headbox, the measured flow had a 3.6% consistency with and without injection of about 5% entrained air. The charts indicate flow variation for various signal dampening values. Lower dampening values improve response time. Smaller flow variations indicate steady readings with good noise rejection. The performance of the FSM4000 flowmeter (AC 70 Hz) for the entrained air case was outstanding. Herty's decision to induce entrained air at the rate of 5% adds a real-world element to the tests. Many stock streams, despite the best efforts of process system designers and pulp and paper mill operators, often contain this disruptive condition. Causes for entrained air include atmospheric washers and screens along with pump cavitation and other conditions. Figure 6. Under typical pulp and paper conditions, the ABB FSM4000 magmeter greatly outperformed competing DC- and AC-excited flowmeters. Entrained air is essentially noise to the flowmeter and constitutes a major contributor to inaccurate control. Having an excitation frequency near 70 Hz, the FSM4000 operates away from the normal background noise of 60 Hz line frequency as well as outside the area where noise is prevalent in typical DC and high signal DC electromagnetic flowmeters. This design innovation minimizes the presence of environmental noise during signal conversion. Additionally, with asynchronous synthesized coil excitation, the signal processor rejects all signals that do not fit within the expected signal envelope. This mode of operation greatly improves rejection of noise caused by trapped air and particles. 5 ABB

WP_F_FSM4000_TECHNOLOGY_05-2012 Contact: ABB Measurement Products 125 East County Line Road Warminster, PA 18974 USA Tel: +1 215 674 6000 Fax: +1 215 674 7183 www.abb.com/measurement Copyright ABB 2012 All rights reserved 6 ABB