STUDY OF CIRCULATING CURRENT PHENOMENA IN MULTIPLE PARALLEL INVERTERS OPERATING IN MICROGRID

Similar documents
Modular Grid Connected Photovoltaic System with New Multilevel Inverter

Current Control Strategy for Parallel Operation of Inverters Based On Micro grids M.Bavithra 1, Belwin J. Brearley 2

Lecture 19 - Single-phase square-wave inverter

Cross-Circulating Current Suppression Method for Parallel Three-Phase Two-Level Inverters

Research on Parallel Interleaved Inverters with Discontinuous Space-Vector Modulation *

Simulation of Three Phase Cascaded H Bridge Inverter for Power Conditioning Using Solar Photovoltaic System

Published in: Proceedings of 2016 IEEE 8th International Power Electronics and Motion Control Conference, IPEMC-ECCE Asia 2016

IJSRD - International Journal for Scientific Research & Development Vol. 4, Issue 01, 2016 ISSN (online):

Selective Harmonic Elimination Using Three Phase Shunt Active Power Filter

Simulation of Single Phase Grid Connected Photo Voltaic System Based On PWM Control Of Switched Boost Inverter For DC Nanogrid Applications

A Fuel Cell Fed Single Stage Boost Inverter with Unique Impedance Network

Modelling and Simulation of High Step up Dc-Dc Converter for Micro Grid Application

Study & Comparison of Various Topologies of Dynamic Voltage Restorer & Its type: a Review

Pulse width modulated (PWM) inverters are mostly used power electronic circuits in

Sepic Topology Based High Step-Up Step down Soft Switching Bidirectional DC-DC Converter for Energy Storage Applications

Simulation and Analysis of a Multilevel Converter Topology for Solar PV Based Grid Connected Inverter

A Modified Apod Pulse Width Modulation Technique of Multilevel Cascaded Inverter Design

PV PANEL WITH CIDBI (COUPLED INDUCTANCE DOUBLE BOOST TOPOLOGY) DC-AC INVERTER

FFT Analysis of THD in Distribution System with Grid Connected RES

Control of Power Converters for Distributed Generation

Modeling of Single Stage Grid-Connected Buck-Boost Inverter for Domestic Applications Maruthi Banakar 1 Mrs. Ramya N 2

Power Quality Improvement in Hybrid Power Generation for Distribution System Using PWM Technique

Upgrading Power Quality of a Distributed Generation Power System

SINGLE PHASE MULTI STRING FIVE LEVEL INVERTER FOR DISTRIBUTED ENERGY SOURCES

13. DC to AC Converters

Design and Implementation of Quasi-Z-Source Inverter for Off-grid Photovoltaic Systems

An Interleaved High Step-Up Boost Converter With Voltage Multiplier Module for Renewable Energy System

Photovoltaic Grid-Connected System Based On Cascaded Quasi-Z-Source Network

MODELLING & SIMULATION OF ACTIVE SHUNT FILTER FOR COMPENSATION OF SYSTEM HARMONICS

Design of Three Phase PWM Voltage Source Inverter for Induction Heater

Design of Single-Stage Transformer less Grid Connected Photovoltaic System

UNIFIED POWER QUALITY CONDITIONER IN DISTRIBUTION SYSTEM FOR ENHANCING POWER QUALITY

Z-SOURCE INVERTER BASED DVR FOR VOLTAGE SAG/SWELL MITIGATION

Hybrid Modulation Technique for Cascaded Multilevel Inverter for High Power and High Quality Applications in Renewable Energy Systems

ELG4139: DC to AC Converters

COMPENSATION OF VOLTAGE SAG USING LEVEL SHIFTED CARRIER PULSE WIDTH MODULATED ASYMMETRIC CASCADED MLI BASED DVR SYSTEM G.Boobalan 1 and N.

Design and Implementation of Closed Loop LCL-T Resonant DC-to- DC Converter Using Low Cost Embedded Controller

Voltage Support and Reactive Power Control in Micro-grid using DG

SIMULATION AND EVALUATION OF A PHASE SYNCHRONOUS INVERTER FOR MICRO-GRID SYSTEM

Power Quality improvement of a three phase four wire system using UPQC

Generalized Multilevel Current-Source PWM Inverter with No-Isolated Switching Devices

A Single Phase Multistring Seven Level Inverter for Grid Connected PV System

AEIJST - July Vol 3 - Issue 7 ISSN A Review of Modular Multilevel Converter based STATCOM Topology

Online Dynamic Topology Type PV Grid - Connected Inverter for Efficiency Expansion

CAPACITOR VOLTAGE BALANCING IN SINGLE PHASE SEVEN-LEVEL PWM INVERTER

Simulation of Five Level Cascaded H-Bridge Multilevel Inverter with and without OTT Filter

DESIGN OF SINGLE-STAGE BUCK BOOT CONVERTER FOR INVERTER APPLICATIONS

INTERNATIONAL JOURNAL OF PURE AND APPLIED RESEARCH IN ENGINEERING AND TECHNOLOGY

Hybrid Anti-Islanding Algorithm for Utility Interconnection of Distributed Generation

University of Kurdistan. Adaptive virtual impedance scheme for selective compensation of voltage unbalance and harmonics in microgrids

Multilevel Current Source Inverter Based on Inductor Cell Topology

A New Control Strategy for Three- Phase Inverter Applied To Induction Motor of Micro Grid

Performance comparison of Quasi-Z-Source inverter with conventional Z-source inverter

CHAPTER 5 MODIFIED SINUSOIDAL PULSE WIDTH MODULATION (SPWM) TECHNIQUE BASED CONTROLLER

Using modified modulation and double frequency ripple suppression control reduce the capacitance in a single phase PV quasi-z-source inverter

Improving Passive Filter Compensation Performance With Active Techniques

A Three Phase Power Conversion Based on Single Phase and PV System Using Cockcraft-Walton Voltage

UPQC with Islanding and Grid Connection for Microgrid Applications

Fuel cell power system connection. Dynamics and Control of Distributed Power Systems. DC storage. DC/DC boost converter (1)

Stability of Voltage using Different Control strategies In Isolated Self Excited Induction Generator for Variable Speed Applications

Analysis of Harmonic Reduction for Synchronized Phase-shifted Parallel PWM Inverters with Current Sharing Reactors

An Efficient Cascade H-Bridge Multilevel Inverter for Power Applications

IJESRT. (I2OR), Publication Impact Factor: (ISRA), Impact Factor: Student, SV University, Tirupati, India.

Three Phase PFC and Harmonic Mitigation Using Buck Boost Converter Topology

An Isolated DC-AC Converter Module Integrating Renewable Energy Source and Energy Storage for Cascaded Inverter

A Switched Boost Inverter Fed Three Phase Induction Motor Drive

Grid Tied Solar Panel Interfacing using 2( Level Inverter with Single Carrier Sinusoidal Modulation; where N is the number of H-bridges

ANALYSIS OF PWM STRATEGIES FOR Z-SOURCE CASCADED MULTILEVEL INVERTER FOR PHOTOVOLTAIC APPLICATIONS

MODELING AND SIMULATION OF MICRO GRID SYSTEM BASED ON RENEWABLE POWER GENERATION UNITS BY USING FIVE LEVEL CASCADED H-BRIDGE CONVERTER

Cascaded H-Bridge Five Level Inverter for Harmonics Mitigation and Reactive Power Control

A Novel Cascaded Multilevel Inverter Using A Single DC Source

Impacts of P-f & Q-V Droop Control on MicroGrids Transient Stability

ANALYSIS AND IMPLEMENTATION OF FPGA CONTROL OF ASYMMETRIC MULTILEVEL INVERTER FOR FUEL CELL APPLICATIONS

Multilevel Inverter Based Statcom For Power System Load Balancing System

Harmonics analysis of Sinusoidal PWM and Third harmonic injection PWM controlled Voltage source inverter

Available online at ScienceDirect. Procedia Technology 21 (2015 ) SMART GRID Technologies, August 6-8, 2015

Simulation and Comparison of DVR and DSTATCOM Used For Voltage Sag Mitigation at Distribution Side

POWER QUALITY IMPROVEMENT BY USING ACTIVE POWER FILTERS

Chapter 2 Shunt Active Power Filter

PUBLICATIONS OF PROBLEMS & APPLICATION IN ENGINEERING RESEARCH - PAPER CSEA2012 ISSN: ; e-issn:

Design of Hybrid Active Filter for Power Quality Improvement of Electrical Distribution System Using Fuzzy Logic Controller

Novelty Technique for Power factor Improvement by a Single phase Rectifier

A Voltage Controlled DSTATCOM using Hybrid Renewable Energy DC Link VSI for Power Quality Improvement

A Comparative Study of Different Topologies of Multilevel Inverters

Inverter topologies for photovoltaic modules with p-sim software

DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING St. JOHNS COLLEGE OF ENGINEERING & TECHNOLOGY YERRAKOTA, YEMMIGANUR, KURNOOL, (A.P.

Power Quality Improvement of Distribution Network for Non-Linear Loads using Inductive Active Filtering Method Suresh Reddy D 1 Chidananda G Yajaman 2

Active Power Factor Correction for AC-DC Converter with PWM Inverter for UPS System

Modelling of Five-Level Inverter for Renewable Power Source

Modeling & Simulation of Micro Grid Distribution System to reduce Harmonics Using Active Power Filters and PI controllers

A DYNAMIC VOLTAGE RESTORER (DVR) BASED MITIGATION SCHEME FOR VOLTAGE SAG AND SWELL

PF and THD Measurement for Power Electronic Converter

Enhancement of Fault Current and Overvoltage by Active Type superconducting fault current limiter (SFCL) in Renewable Distributed Generation (DG)

Design of Single Phase Pure Sine Wave Inverter for Photovoltaic Application

Lecture Note. DC-AC PWM Inverters. Prepared by Dr. Oday A Ahmed Website:

Modeling and Analyses of Cascaded H-Bridge Multilevel Converter for Micro Grid Application

A NOVEL APPROACH TO ENHANCE THE POWER QUALITY USING CMLI BASED CUSTOM POWER DEVICES

Lecture 6 ECEN 4517/5517

Modified Multilevel Inverter Topology for Driving a Single Phase Induction Motor

A SPWM CONTROLLED THREE-PHASE UPS FOR NONLINEAR LOADS

Transcription:

STUDY OF CIRCULATING CURRENT PHENOMENA IN MULTIPLE PARALLEL INVERTERS OPERATING IN MICROGRID 1 RUPALI P. NALAWADE, 2 PRASAD M. JOSHI 1 Student, 2 Professor, Department of electrical engineering, Government college of engineering, Karad, India E-mail; 1 rupali.177@gmail.com, 2 dr.pmjoshi@gmail.com Abstract Now a days, renewable energy is used as an alternative way of generating clean energy. Increasing use of green energy benefits the global environment and hence makes it a global concern. Literature review indicates that, microgrid (MG) can offer a power system with features like increased reliability, flexibility, cost effective and efficient energy. The parallel operation of small inverters gives modularity to the system and provides extra reliability and redundancy. This paper deals with study of circulating current phenomena in parallel inverters. Accurate power sharing means minimization of the circulating current among the modules. However the issues related to synchronization of parallel inverters, power sharing amongst the inverting units and minimization of circulating currents still remains an important topic for research. Index Terms Inverters, Parallel Inverters, Circulating Current. I. INTRODUCTION Microgrid can be simply defined as the combination of distributed generation (DG), electrical energy storage and loads. A microgrid is a small-scale power grid that can operate independently or in conjunction with the area s main electrical grid. Microgrids can be intended as back-up power or to support the main power grid during periods of heavy demand hence reducing costs and enhancing reliability. The generators used in microgrid may be fuel cells, PV array, wind turbine or any other alternative power sources. The main function of microgrid is to provide stable operation during faults and various network disturbances[1]. Parallel operation of inverters is more useful for improved reliability and easy redundancy operation. Parallel operation of inverter system is very sensitive. When voltage source inverters are connected in parallel, small deviation in the output voltage of each module can generate crosscurrent or circulating current which affects the reliability and reduce the power efficiency. So it becomes necessary to study the parallel operation of inverter and phenomena of circulating current[2]. The paper is divided in four sections including the introduction, the second section describes structure, topology and configuration of inverter, the third section discusses the phenomena of circulating current and the fourth section deals with Control strategies for minimization of circulating current. II. INVERTER A. Structure of inverter Inverter is a DC to AC converter used to convert a DC input voltage into a symmetrical AC output voltage of desired magnitude and frequency as shown in fig.1. The wave shape of AC output voltage of inverter should be sinusoidal. However practical inverters give output voltage that are non-sinusoidal and contains some harmonics. Inverters used in low and medium power application normally give square wave output. In high power applications sinusoidal waveform is required, so inverters are carefully designed to give sinusoidal output with low distortion. Fig.1 DC to AC converter The DC voltage input to the inverter is provided by battery, fuel cell, solar cell or any other DC voltage source. The switching device used in inverter includes BJTs, MOSFETs, IGBTs and GTOs. The selection of particular switching device depends upon power handling capacity, switching frequency and the cost. Using this devices covert Dc voltage to Ac voltage. An inverter having DC voltage source as an input is called the voltage source inverter(vsi). There are three types of VSI 1. Square wave inverter- This is the basic type of inverter. Its output is alternating square wave. In this inverter AC output is produced from a DC input supply by closing and opening switches in correct sequence. The output voltage V0 is +Vdc, -Vdc or zero depending on switch position(ref.fig2). This output wave content is more harmonic. 9

generator(carrier signal) and sinusoidal signal(control signal). Fig.2 Square wave inverter 2. Modified sine wave inverter- Modified sine wave inverters output waveforms is similar to the square waveform. In modified sine wave inverter there are three voltage levels in the output high, low and zero with dead zone between high and low pulses. Modified sine wave inverter output waveform is more accurate as compare to square wave inverter. B. Inverter Topology Various topologies are used for inverter design. Two common topologies are push-pull and H-bridge topology. Push-pull topology is suitable for production of square wave and modified square wave and H-bridge is useful for producing modified square wave and sine wave outputs. 1. Push-pull topology- Fig.5. shows the basic design of push-pull topology. It consist of battery as a input DC source, Transformer and transistor switches. Fig.5 Push-Pull topology Fig.3 Modified sine wave inverter 3. Pulse width modulated inverter- Pulse width modulated (PWM) is single phase full bridge inverter as shown in fig.4 This PWM inverter uses constant DC voltage source as a input. Therefore magnitude and frequency of output voltage needs to be controlled. This control is achieved by PWM signal for inverter switches to obtain AC output voltage close to pure sine wave. When top transistor switch closes current flows from negative terminal of battery through the transformer primary side to the battery positive. This induces a voltage in the secondary side of transformer(ref.fig.5a). After some time top switches open and bottom switches are closed allowing current to flow in the opposite direction. Only one switch at a time is closed. Output of this topology is square waveform. Fig.5a Fig.4 Pulse width modulated inverter Basically an inverter is a combination of switches and PWM which generates a signal to turn these switches on and off. PWM consist triangular wave 2. H-bridge topology- This topology is similar to push-pull topology. The main advantage of this topology is simple design and require only primary winding of transformer. The design of this topology shown in fig.6.this topology consist of four transistor and transformer primary side connected between the middle of bridge. The transistors are switched on and off in a specific pattern same as push-pull topology. Two opposite corners of the bridge are closed, allowing current to 10

flow from the battery negative through the transformer primary side to the positive terminal of the battery. This current induces a current flow in the secondary side of transformer. or more parallel modules fails, output power is not interrupted. 4. Lower cost- Low component and manufacturing cost. 5. Field expandable- Parallel inverter system can be easily expandate to increase output power and redundancy by adding more modules[3]. Fig.6 H-bridge topology C. Configuration of parallel Inverter system The parallel configuration of voltage source inverters is applied to share the load power, to obtain redundancy, to improve the reliability and to make the power expansion flexible. High power inverters dissipate large amount of heat and handle large current, these two factors result in low reliability and high cost. Solution for this problem is to design low power inverter modules and use them in parallel to achieve high power and reliability. Fig.7 A system of parallel inverter modules The outputs of all inverter modules connected together forms the system output. Hence the outputs of the inverter modules are directly connected together and each module is capable of delivering same amount of power. Ideally all modules should provide same amount of current to the load. The load current shared equally to all inverter modules. D. Advantages of parallel inverter system over single inverter system 1. Improved heat dissipation- Each module generates a fraction of the total heat which can be dissipated very easily. 2. Improved current handling- Each module switches a portion of the total current. 3. Higher reliability- Each module handles a lower current and dissipates less heat which improves module reliability. In parallel inverter system any one E. Design of parallel inverters When parallel inverter system is designed some points are required or for achieve this objective parallel inverter system is designed. These are 1. Balanced load shearing- All inverter modules designed should have same maximum power rating, so as all modules shear equal load current. Unequal output current causes more stress on some modules which reduce reliability of system and increased module failure. Suppose two inverters are connected in parallel then current imbalance signals,i imb1 and I imb2 are generated by power distribution block. Each current imbalance signal is the difference between current, which the module is providing and current which module delivered to the load. If N no of inverter modules connected in parallel then each module deliver 1/N of the total load current. Therefore, I imb1 calculated as I imb1 =I out1 -(1/N)I load I imb1 =I out1 -(1/N)(I out1 +I out2 + +I outn ) For balanced load shearing I out1 =I out2 =.I outn =(1/N)I load 2. Maximize redundancy- If any one of the inverter module fails should not cause any disturbance in power delivered to the load. When an inverter module fails, the remaining inverter modules contribute a higher current to compensate for the failed inverter modules. For example if any one of the module fails I ref short to ground. In this case reference current for all modules become zero and system output voltage drops to Zero. Therefore single module failure causes total system failure. To overcome this problem isolation of I ref current is required. For this use of voltage buffer is recommended to isolate I ref that goes to each module. Therefore when reference current I ref1 of one module fails the other reference current I ref2 and I refn remains undisturbed. 3. Fault protection- While designing the parallel inverter system one more challenge is to protect the system against module failure. for example a module 11

fails when its output is shorted to ground. This type of failure disturbs the output voltage and damage the other modules. We need to protect each module by adding both output current limiting circuit and fault protection circuit. The fault protection circuit of faulty module detects a short circuit and isolates the output of that module from the rest of system. The current limiting circuit is required to protect module from failing due to the initial high current while the fault protection circuit detect short circuit. 4. Module synchronization- All inverter module connected in parallel should have the same output voltage, frequency and phase. If the output voltage of modules are not equal a current flow from the module with the higher voltage to the lower voltage that current is known as crosscurrent or circulating current. 5. Minimize module interdependence- Inverter modules should be independent from one another. Faulty module will not disturb the other module in independent system[4]. III.CIRCULATING CURRENT PHENOMENA All inverter module connected in parallel should have the same output voltage, frequency and phase. If the output voltage of modules are not equal a current flow from the module with the higher voltage to the lower voltage that current is known as crosscurrent or circulating current. Circulating current reduce the power efficiency, cause the output overload and can result in module failures. Circulating current is of two types. 1. Low frequency circulating current- Low frequency circulating current generates when the parallel inverter modules are slightly out of phase or have different voltage amplitude. This circulating current causes inverter modules to operate ineffectively and can result in module or system failure. 2. High frequency circulating current- When two or more PWM inverters are connected in parallel with insufficient output filters then high frequency circulating current is produced (Ref.Fig8). In this each inverter generate different PWM waveform which causes different output voltage at each inverter. This voltage generated at the frequency of the PWM switching oscillator creates circulating current. Fig.8 Parallel connection of two inverters 12 Z1 and Z2 are the current shearing inductor, Zh is the load impedance,v1 and V2 are the output voltages.i 1 and i 2 is the load current. The circulating current is defined as, From equation 6 we conclude that circulating current depends upon on current shearing impedances and difference in the output voltages of parallel inverter. Phase difference and amplitude difference produce circulating current[5]. Fig.9 Circulating current flow between the parallel Inverters IV.CONTROL STRATEGIES FOR MINIMIZATION OF CIRCULATING CURRENT When two or more inverters are connected in parallel circulating current is produced. For minimizing this circulating current various control strategies are describes in literature. These are as follows. 1. Droop control method- The control technique which does not require any interconnecting wires among inverter modules is called droop control method. In conventional droop control method, load shearing is achieved by changing(drooping)

the voltage and frequency of the inverter. Frequency and voltage droop control system work well for linear loads[6]. 2. Master-slave control method- In this control technique, one inverter act as a master while the rest of the inverters in the system are slaves to this main inverter. Master inverter operates in Voltage controlled mode to control the output voltage of other slave inverters which operate in a current controlled mode. This method uses current controlled inverters in parallel with one voltage source inverter (master). This technique is useful when large numbers of inverters are connected in parallel. 3. Instantaneous current sharing control- In this centralized control technique all inverters share information about the current shared among them. There are different categories to drive references for current like average current sharing, maximum current sharing and rotating reference current sharing. This control system is considered as multiple input multiple output (MIMO) system as it gives and receives information from more than one inverter. There are several schemes to meet the requirement of accurate current sharing. One of them is to equally divide the load among all inverters in a system to detect an unbalanced current. It needs to regulate voltage and frequency to minimize active and reactive components of this detected current[6]. 4. Parallelism control- This control strategy based on principle of droop control and distributed control. Distributed control in the sense all the inverters connected in parallel has a common reference bus but they need not exchange information between them. Parallelism control employs the feedback of the inductor current of its own VSI for controlling the parallel operation. The proposed strategy is based on a single reference voltage (Vref ) for all VSIs, thus the output voltages of all inverters have only small deviations, which are caused by parametric variations in the control and power components of the inverters. Therefore, the parallelism control has the function of equalizing these small deviations to ensure power sharing among the inverters. The proposed control for the parallel operation of VSIs based on the feedback of the inductor current differs from the current control loop in multiloop control[7]. CONCLUSION One of the modes of producing a cost effective energy is to develop the power system with features like increased reliability, flexibility, cost effective and efficient energy. These features can be obtained by connecting the inverters in parallel and by implementing strategies to minimize the circulating currents. Hence it becomes necessary to study the issues related to synchronization of parallel inverters, power sharing amongst the inverting units and minimization of circulating currents. In this paper an overview of parallel operation of inverters is presented. The circulating current phenomena is discussed. Different control strategies for minimization of circulating current are enumerated. Accurate power sharing among the inverter modules provides improved reliability and easy redundancy in the operation, which can be achieved by minimization of the circulating current among the modules. Various strategies like Droop control method, Master-slave control method, Instantaneous current sharing control and Parallelism control method can be implemented to generate an inverter which will provide a cost effective energy. Thus studding the Circulating Current Phenomena in Multiple Parallel Inverters Operating in Microgrid can provide the solution to the increasing cost effective energy demands. The future work is do fabricate the laboratory model for parallel operation of inverter and apply different control strategies to minimize the circulating current. REFERENCES Fig.10 Control scheme of the VSIs connected in parallel [1] San-Yi Lee, Wen-Chih Yang, Operating strategies for stabilizing the operation of micro grid with various Distributed Generation Sources International Journal of Emerging Technology and Advanced Engineering, Volume 3, Issue 9, September 2013 [2] Telles b. Lazzarin, Guilherme A.T. Bauer, Ivo Barbi A control strategy by instantaneous average values for Parallel operation of single phase voltage source inverters Based in the inductor current feedback, Member, IEEE transaction on Industrial Electronics, vol. 59, NO. 1, Nov2009 [3] Takao Kawabata, Shigenori Higashino, Member, IEEE Parallel Operation of Voltage Source Inverters, IEEE 13

Transactions on Industry Applications, vol. 24. No. 2. March/April 1988 [4] A.Johnsy1PG student [PED], Dept of EEE, College of Engineering, Chennai, Tamilnadu, India1, Analysis of a Control Strategy for Parallel Operation of Single Phase Voltage Source Inverters IJAREEIE, Journal, Vol. 3, Special Issue 2, April 2014 [5] Hui Cai, Rongxiang Zhao, and Huan Yang, Student Member, IEEE Study on Ideal Operation Status of Parallel Inverters IEEE Transactions on Power Electronics, Vol. 23, no. 6, November 2008 [6] Josep M. Guerrero, Senior Member, IEEE, Juan C. Vásquez, José Matas, Miguel Castilla, and Luis García de Vicuña, Control Strategy for Flexible Microgrid Based on Parallel Line-Interactive UPS Systems IEEE Transactions on Industrial Electronics, Vol. 56, no. 3, March 2009 [7] Telles B. Lazzarin, Member, IEEE, Guilherme A. T. Bauer, and Ivo Barbi, Fellow, IEEE, A Control Strategy for Parallel Operation of Single-Phase Voltage Source Inverters: Analysis,Design and Experimental Results IEEE Transactions on Industrial Electronics, Vol. 60, no. 6, June 2013. 14